Loading…
Loading…
Tender Value
₹41.1 L
EMD Value
₹41,075
Closing Date
23 Apr 2026, 6:00 pmClosed
Similar tender results from the same govt authority in the past 3 years.
chief officer Santrampur Nagarpalika
Bid Documents for Supply, Installation, Testing, Commissioning Of 43 Kw (Ac) 54 Kw (Dc) Grid Connected Rooftop Solar Project At Mahadev Shopping Center Building Santrampur Nagarpalika under SJMMSVY 2025-26
295934
27 of 25-26
Open
Electrical Works
Mahisagar
3 documents required · 3 mandatory
₹1,770
Chief Officer Santrampur Nagarpalika Mahisagar
₹41,075
10 Apr 2026
10 Apr 2026
10 Apr 2026
23 Apr 2026
10 Apr 2026
Name of Work: Bid Documents for Supply, Installation, Testing, Commissioning Of 43 Kw (Ac) 54 Kw (Dc) Grid
Connected Rooftop Solar Project At Mahadev Shopping Center Building Santrampur Nagarpalika under SJMMSVY
SCHEDULE - "B1"
Name of Work : Supply, Installation, Testing, Commissioning Of 43 Kw (Ac) 54 Kw (Dc) Grid Connected
Rooftop Solar Project At Mahadev Shopping Center Building Santrampur Nagarpalika.
Item No. Item Total Qty. Rate Per Amount
S.I.T.C of Poly Crystline/Mono Crystline PV Module
(ALMM approved) with 72 Cells - 150 Cells or More
Frame Material : Anodized Aluminum alloy Frame
With Twin Wall Profile, Front Cover : High
Transmission Low-Iron Tempered Glass (AR Coated),
High efficency and positive power tolerance Pmax:
0/+5, Module Efficiency should be approx. 18%-
21%, Normal operating temperature 45'C, Junction
1 Box with Waterproof IP67 & MC4 Compatible and
Enclosed with Bypass diodes 100%
Electroluminescence test to ensure error free
Modules, Thw temp. co-efficient of the PV module
shall equal or better than -0.45%/degree C. Solar PV
modules of minimum fill factor 75% to be used. Unit
Production:- 4 to 5 Unit /kw /day (Actual)(1Year
Avg) With 10 year Product warranty and 25 year
Linear Power o/p
(E) Moudule Warranty.
Range: 520 - 545 watt, Maximum
Power Voltage Vmpp: 41 - 42 V, Maximum Power 55620.00 33.33 PER WATT
Current Impp: 12.5 - 13 A
S.I.T.C of Solar Inverter Gried Tied: MPPT Range: 80-
1000 V, Max efficiency: 97.5% - 98.9%, O/p
Frequency: 50/60Hz, Operating Altitude (m) ≤4000,
O/p Power Factor: ~1, O/P THDi: <3%, Operating
Tempreture Range: -25~60°C, Anti-islanding
Protection: Integrated, Input Reverse Polarity
2 Protection Integrated, Insulation Resistor Detection
Integrated, Residual Current Monitoring Unit
Integrated, Output Over Current Protection
Integrated, Output Short Circuit Protection
Integrated, Output Over Voltage Protection
Integrated, Protection Degree: IP65, User Interface
LCD & APP,Datalogger & Communication: GPRS / Wi-
Solar Inverter: 50 kW to 100 kW: Max. input
Current: 40 A, Max DC i/p Power: 66500-130500 W
& Nominal o/p Power: 50000-100000 W, Nomimal 55620.00 8.08 PER WATT
O/p Voltage: 400 V 3-Phase,Nominal O/p Current:
Supplying and Erecting Seamless Box Pipe of
suitable size for rooftop solar installations with good
stability agaist wind, Thickness 2 mm and 80 micron,
Hot Dipped Galvanized steel coils. suitable
arrangement for base plate for foundation , solar
panel mounting, the structure should be suitable for
3 carry the load of solar panel,wiring, sprinkler system
etc. with necessary foundation work/wall mount, j
bolt, anchor fastner etc. the nut bolt used for
installtion of stucture should be (SS 304)
quality.box. pipe ref. size (A) 40 x 40 x 2mm, (B)
SANTRAMPUR NAGARPALIKA, SANTRAMPUR
Supplying and Erecting Stainless Steel Nut Bolt (SS
304) for Installation of Solar PV Module, Structures,
4 and other related items with required size as
engineer in charge demands for project Size, length
upto 10 x 150 mm
DC Cable: Electron beam cross linked compound,UV,
Ozone, Temperature & Hydrolysis resistant Flame
Retardant, Low Smoke Excellent Encapsulation Very
long / Service life > 25 Standards / Material
Properties: Fire performance : IEC 60332-1-2 Smoke
5 emission : IEC 61034/ EN 50268-2 Halogen Free: EN
50267-2-1/-2, IEC 60754-2 Toxicity: EN 50305, ITC
– Index <3 Ozone Resistant : EN50396 Weathering
UV: HD 605/A1 or DIN 53367 Approvals : EN 50618;
H1Z2Z2-k with suitable sized of PVC pipe(ISI Mark)
and Clamps,Shadels,Lugs.
(A) 1 core 4 sqmm copper DC cable Colour Red
(B) 1 core 4 sqmm copper DC cable Colour Black
S.I.T.C of Distribution board from AC Side , ACDB 3-
Phase - 51 kW - 100 kW: which includes AC1 DUTY
CONTRACTOR‐200A 4P, 200A MCCB 4P(Cat III)
WITH SPREADER & SHUNT, 3 PHASE SPD, VOLTAGE
6 MONITORING RELAY, ELR WITH CBCT, PHASE
INDICATING LAMP, POWER CABLE & OTHER
ACCESSORIES. All switchgears and connection are
enclosed with IP66 Enclosure and operate the
S.I.T.C of Distributiob System DC Side, DCDB -
kW - 65 kW (12in:12out) : Input Mcb - 1000 V,
7 Amp, 1000 V DC SPD TYPE
TERMINAL/END,PLATE/END CLAMP: 4SQMM (KUT6)
FOR OUTPUT, DC CABLE With suitable size of
interconnection.
Providing and erecting XLPE(IS:7098)(I)-88 ISI
armoured cable multistrand Copper conductor for
8 1.1 KV. to be laid on wall with necessary clamps or
in existing trench / pipe at road crossing or floor of
following size of cables. (D) 3 1/2 core 70 Sq. mm (
35 Sq. mm 1/2 core)
SANTRAMPUR NAGARPALIKA, SANTRAMPUR
Supplying & erecting in earthpit of minimum bore
dia. 225mm size approved make Safe Earthing
Electrode consisting Pipe-in-Pipe Technology as per
IS 3043-1987 made of corrosion free hot dipped
G.I.Pipes having Outer pipe dia of 80 mm having
80-200 Micron galvanising, Inner pipe dia of 40 mm
having 200-250 Micron galvanising, connection
terminal dia of 14 mm with constant ohmic value
surrounded by highly conductive compound with high
charge dissipation suitable for following type of
applications with chamber and heavy duty cover
(A)(approved make OEM has to submit test
certificate including value of earth resistance of
installation duly stamped and signed by agency and
officer Incharge has to ensure the value of earthing
9 resistane mentioned in test Certificate) & having
back filling compound of (B) Inner chemical (CCM
Compound)- Resistivity:- 0.2 ohm / meter testing as
per IEC 62561-2017, Voltage drop:- < 1 volt at no
load & dry form, Sulphar content:- <2%(C) Back fill
Compound :- Earthing compound should be capable
to retain moisture for long time Necessary test
report must be submitted by Agency.[C] For
Electrical Installation covering Transformer Neutrals,
Lightning arrester Earthing, A.C.Plant & Sensitive
Computer System(like Automation, SCADA)i.e.
independent Earthing located in other than
normal soil i.e. Soft Rock, Marshy Soil etc.-
Length of Pipe : 3 Mtrs. -Back filling Compound :2
nos Bags of 25 Kg.
SITC of Vertical Air Termination Solid aluminium with
Base- 10 mm dia and 1000 mm long. Air
Termination Base tested for conditioning, Ageing
10 Test & Lightning impulse current withstand test:
kA of 10/350µs waveform in an accredited Third
party laboratory as per 6.3 & 6.4 of IEC 62561-1
2017 protocol with MAST 34mm dia 3000 mm long-
Cold Galvanized
Providing and erecting required size Copper strip for
11 earthing of H.T. OCB / ACB/ Transformer, LT panel
board, Motors etc. using copper clamp.
Providing and erecting ISI mark Medium class RIGID
PVC PIPES of following size complete to be erected
12 on/in wall or ceiling erected with necessary PVC
fittings & Junction boxes fixed with adhesive solution
& Clamps with following dia of pipes, in approved
manner as directed
SANTRAMPUR NAGARPALIKA, SANTRAMPUR
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
01-SBD Rooftop (41.07.00 Lacs).pdf
02 Santrampur Abstarct.pdf
03 Schedule B1.pdf
05.Make In List.pdf
6.Electrical work Specification.pdf
0.PQ Eligibility Criteria.pdf
Download all tender documents and submit your bid