Replacement of Existing LT Panel at Hindurao Hospital BPS.
2024_DJB_252590_8
NIT NO. 22 (2023-2024)
Open Tender
Miscellaneous Services
Item Wise
30 days
EE(EANDM)-M-5
Please refer Tender documents.
3 documents required · 3 mandatory
₹500
THROUGH DJB OFFICIAL WEBSITE IN LINK TENDER
₹15,900
Yes
6 Feb 2024
25 Jan 2024
31 Jan 2024
25 Jan 2024
31 Jan 2024
25 Jan 2024
Supply of LT Distribution panel sheet steel enclosure made out of 2mm CRCA sheet totally enclosed, powder coated free standing, floor mounted type, dust& vermin proof, outward opening, lockable doors having hidden hinges and a bolted back cover both using non-deteriorating neoprene rubber gaskets to provide IP-54 protection, each part of the fabricated panel will be strictly subjected to seven tank treatment. The various components, assemblies and sub equipment’s of the panel will be as per standard given in relevant IS. The bus bar of the panel will be shaped out of high conductivity, electrolytic conductor and shall be liberal sized in aluminum. The control wiring of the panel will be done with PVC flexible copper wires of 1.5mm cross section. Each wire will be terminating with a ferule crimped to the wire, size 1600MM x1800x375MM. Having following components of approved make.
MCCB 415V, Four pole. High breaking capacity 50KA 50Hz,200Amp with spreader and Extended Handle- Make L&T/Siemens/ Schnider/DJB Approved
MCCB 415V, TP 3phase 36KA 50Hz,100Amp with spreader and Extended Handle - Make L&T/Siemens/ Schnider/DJB Approved
MCB Single pole 6Amp. Make L&T/Siemens/ Schnider/DJB Approved
MCB Triple pole 32Amp Make L&T/Siemens/ Schnider/DJB Approved
PVC insulated copper flexible cable single core 25 sq.mm Make: Havells/Gloster/DJB Approved
Over load relay 30-50A Make: L&T/Siemens/ Schnider/DJB Approved
Amp. Meter Digital with ASS Make AE/L&T/ Schnider/DJB Approved
Volt Meter Digital with VSS Make AE/L&T/ Schnider/DJB Approved
Motor protection Relay with Thermal over load, short circuit, earth fault, Phase loss, phase unbalance, phase reversal , under current & locked rotor protection Make: L&T/Siemens/ Schnider/DJB Approved
Power contactor Three phase 200Amp. With 1NO+1NC Make L&T/Siemens/ Schnider/DJB Approved
Power contactor 220V 3phase 70Amp.With 1NO+1NC Make L&T/Siemens/ Schnider/DJB Approved
Power contactor 220V 3phase50Amp.With 1NO+1NC Make L&T/Siemens/ Schnider/DJB Approved
Star delta timer on delay Make: L&T/Siemens/ Schnider/DJB Approved
On Delay Timer Make: L&T/Siemens/ Schnider/DJB Approved
Phase Sequence Relay Make: L&T/Siemens/ Schnider/DJB Approved
Indicating lights LED type RYB & On/OFF Make : L&T /Schnider/Siemens/DJB Approved
Push Button for start (Green Colour)/Stop (Red Colour) Make : L&T /Schnider/Siemens/DJB Approved
Current Transformer200/5 Make AE /Saviour/Siemens/DJB Approved
Current Transformer100/5, Make AE /Saviour/Siemens/DJB Approved
Supply of Insulating Rubber Mats for Floor for Safety Purpose Size- 2 mtr*1 mtr*10 mm Black/Red/Blue Plain Chequered confirming to IS 5424:1969
Supply of Flexible Spiral-reinforced PVC Conduit of suitable size for 25 sq. mm single core cable.
Providing and fixing 25 mm*05 mm G.I. strip on surface or in recess for connections etc. as required
Providing & Fixing of Fire Fighting equipment Co2 type Fire Extinguishers ISI Marked Conforming to IS15683, Complete with Delivery hose horn, wheel type release valve locking arrangement, operation manual and bracket, operating Temperature -30 degree Celsius to +60 degree Celsius of 02 Kg. Make Life Guard/DJB approved
Making of all sefety arrangement i.e. Safety Belt, gum boots, helmet, Gloves etc for all work
Dismantling of old panel connections from Supply meter/ Main Switch/Change Over/Starter /Motor & shifting the same to JE Store as per Engineer in charge,where required. including all loading/unloading/freight/cartage charges of Old materials.
Installation of the panel at site by making foundation, termination of cable both incoming & out going side , including cable connections to the motors and supply mains taking cable inside Flexible Spiral-reinforced PVC Conduit. This includes cartage, loading& unloading etc.
Earthing made for LT distribution Panel with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but without charcoal/ coke and salt ) as per site requirements.
Testing and Commissioning of the all installed component in LT Panel and setting of with relevent and required IS standards and Testing of LT Panel prior to and after switching on as follow:-A. Check equipments specifications.B. Continuity and ear thing.C. MCCB mechanism and alignment.D. Meggaring of all equipments for phase to phase, neutral to body, neutral to earth and phase to earth.E. Test of all functionsF. Checking of all tightness of nuts and bolts.G. Setting of relay/delays parameters to achieve smooth functioning.H. Alignment of doors etc.I. Interlocking tests. As per the satisfaction of the engineer in charge
Gupta Brothers
Super System Engineers
Premier Engineering Company
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .