Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹51.3 LAccepted-AOC NO 3 WD BUILDING JP AGARWALLA ROAD BHARALUMUKH KAMRUP ASSAM 781009 UDYAM AS 03 0009483 | KAMRUP METRO | ASSAM | 781009 | L1 | Accepted-AOC AOC | |
| 2 | L2₹57.1 L+₹4.6 L (8.72%)Rejected-Finance NAKARI BORIGAON SIDING JORHAT 785001 ASSAM | JORHAT | JORHAT | ASSAM | 785001 | L2 | Rejected-Finance Unsuccessful bidder | |
| 3 | L3₹59.4 L+₹6.9 L (13.1%)Rejected-Finance H M APARTMENT FLAT NO 5C SJ ROAD ATHGAON GUWAHATI 781001 ASSAM | KAMRUP METRO | ASSAM | 781001 | L3 | Rejected-Finance Unsuccessful bidder | |
| 4 | L4₹59.9 L+₹7.3 L (13.9%)Rejected-Finance 9 NAROTTAM KUNJ MADHU NAGAR AGRA CANTT 282001 | AGRA | UTTAR PRADESH | 282001 | L4 | Rejected-Finance Unsuccessful bidder | |
| 5 | L5₹61.4 L+₹8.8 L (16.8%)Rejected-Finance | L5 | Rejected-Finance Unsuccessful bidder |
Tender Value
₹55 L
EMD Value
₹1.1 L
Closing Date
23 Oct 2023, 6:00 pmClosed
CWE Tezpur
HQ CWE TEZPUR PO DEKARGAON DIST SONITPUR PIN 784501 (ASSAM)
REPAIR/MAINTENANCE OF TRANSFORMER, VCB, DO FUSE, PANEL BOARDS, EARTHING PIT PANEL, ACBS, CAPACITOR BANK AND MISC ALLIED WORKS OF HT NETWORK AT SAA UNDER GE(S) TEZPUR
2023_MES_619379_1
CWE/TEZ(S)/T-33 of 23-24
Open Tender
Electrical and Maintenance Works
Item Rate
120 days
GE(S) Tezpur
Please refer Tender documents.
8 documents required · 8 mandatory
₹1,000
GE(S) Tezpur
₹1.1 L
Yes
23 Dec 2023
18 Sept 2023
25 Oct 2023
18 Sept 2023
23 Oct 2023
9 Oct 2023
Amount
Excavation in trenches n.exc 1.5m wide and n.exc and 1.5 mtr in depth getting out in in soft/loose soil all as specified and directed by Engineer-in-charge.
All as per item No. 1 above but exceeding 1.5 mtr and not exceeding 3 mtr in depth.
Returning and filling including spreading, leveling, watering and well ramming in layer n.exc 25 CM thick in soft/loose soil all as specified and directed by Engineer-in-charge.
Removing excavated material to a distance not exc. 50 mtrs and deposting where directed at a level not exceeding 1.50mm above the starting point all as specified and directed by Engineer-in-charge.
Supply and laying natural river sand as cushioning of cables, including spreading and punning down all as per clause No 3.21 of SSR part -I complete all as specified and directed by Engineer-in-charge and directed by Engineer in charge Note : punned thickness will only be measured for payment purpose.
Supplying and laying un-reinforced precast concrete cable cover, but class HV, Type 1, flat, size 300mmx 180mm x 40mm complete all as specified and directed.
Supply,Laying ,testing, and commissioning size 3x120 sqmm cross-sectional area XLPE insulated, screened, PVC bedded, galvanised steel strip armoured heavy duty electric cable with aluminium conductor 11000 volts earthed, grade, in tranches / fixing on wall by saddel/ fixing on poll / drawn through GI pipes including taking down Old unsv UG cable complete all as specified and directed.
Supply,Laying ,testing, and commissioning size 3 x 95 sqmm cross-sectional area XLPE insulated, screened, PVC bedded, galvanised steel strip armoured heavy duty electric cable with aluminium conductor 11000 volts earthed, grade, in tranches / fixing on wall by saddel/ fixing on poll / drawn through GI pipes including taking down Old unsv UG cable complete all as specified and directed.
Supply,Laying ,testing, and commissioning size 3 x 95 sqmm cross-sectional area Aerial Bunch Cable with H4 grade Aluminium, with extruded semi conductor screen, XLPE insulation, Insulation screen Non-metallic extruded semi conducting layer, insulation screen metallic applied helically over the non metallic layer, sheath PVC type ST2, with messanger conductor of one run of ACSR of nominal dia 55 sqmm , heavy duty 11000 volts grade, fixing on poles including all its hardware accessories such as suspension hook, insulator, suspension clamp, rubber insert etc including taking down Old unsv ABC cable complete all as specified and directed.
Dismantling of Steel tubular poles / struts any size complete.
M & L in repair Steel tubulr swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts and screws as specified type 410 SP-55, 11 metres long including one primer coat , one under coat,,one finishing coat of aluminium paint, marking of pole numbers and making 03 Nos of black colour strip and 03 Nos red colour strip in alternate of 30 cm wide on equal distance from coping complete all as specified and directed.
M & L in repair angle iron Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint complete all as specified and directed.
M&L for cement concrete type D2, 1:4:8 (using 40 mm graded sto agg.) in foundations, filling and mass concrete complete all as specified.
M&L for cement concrete type C1 1:3:6 (20mm graded aggregate) in or mud stops, rounded or chamfered on edges etc all as specified and directed
M&L for cement concrete type B0, 1:2:4 (using 12.5 mm graded sto agg.) for coping above ground level of steel electric pole concrete complete all as specified.
M & L for Broken Stone or Boulders Hardcore of Gauge not exc. 63mm, deposited, spread and levelled in layers not exc. 150mm thick, watered and rammed to a True Surface, complete all as specified and directed.
S & F in repair composite polymer type pin insulator for 11 KV overhead line including all its accessories complete all as specified.
M & L in repair composite polyme Disc type insulator, ball and socket type with tension clamps and all hardware components for conductors, working pressure fit for 11000 volts complete all as specified and directed.
S & F in repair composite polymer type post insulator for 11 KV overhead line including all its accessories complete all as specified.
S & F in repair composite polymer type post insulator for 33 KV overhead line including all its accessories complete all as specified.
S & F in repair composite polymer type pin insulator for 33 KV overhead line including all its accessories complete all as specified.
M & L in repair composite polymer Disc type insulator, ball and socket type with tension clamps and all hardware components for conductors, working pressure fit for 33KV complete all as specified and directed.
M & L Composite Polymer Lightning arresters expulsion type complete with all fittings, transmission class, discharge capacity 65 kilo amp suitable for 11 KV (station class/distribution class) to fix it on the Pole with continuity conductor upto earth terminal including taking down unsv LA complete all as specified and directed.
M & L Composite Polymer Lightning arresters expulsion type complete with all fittings, transmission class, discharge capacity 65 kilo amp suitable for 33 KV (station class) to fix it on the Pole with continuity conductor upto earth terminal including taking down unsv LA complete all as specified and directed.
M & L Composite Polymer Air Break switch gang operated Triple pole, mechanically operated, mounted on insulator and steel frame, with operating mechanism worked from ground level, for current rating upto 200 amps fit for 11 KV with all accessories including taking down unsv GOD Complete all as specified and directed.
M & L Composite Polymer Air Break switch gang operated Triple pole, mechanically operated, mounted on insulator and steel frame, with operating mechanism worked from ground level, for current rating upto 200 amps fit for 33 KV with all accessories including taking down unsv GOD Complete all as specified and directed.
S & F in repair Male Contact/ moving contact blade of Air Break Switch 11 Kv complete all as specified and directed.
S & F in repair Female contact/ fixed contact Jaw of Air Break Switch 11 Kv complete all as specified and directed.
S & F in repair MS jumper Carrierof Air Break Switch 11 Kv complete all as specified and directed.
S & F in repair Back contactor Plate of Air Break Switch 11 Kv complete all as specified and directed.
M & L Composite Polymer Expulsion type Drop Out fuse single pole 11 KV , above 50 Amps upto 100 Amps including MS channel for fixing it with the pole including taking down old unsv DO fuse complete all as specified and directed.
Material and labour for painting of steel tubular pole 11 mtr long, including cross arms bracing supports etc complete by applying two coat of synthetic enamelled paint (colour will be chose by EIC) after surface preparation, marking of pole numbers and making 3 Nos of black colour strip 30 cm wide on equal distance from coping complete all as specified and as directed by Engr - in Charge.
Supply & Fix syntheic mat of size 2m x 1m x 3 mm including taking out old Unseveciable Syntheic mat all as specified and directed by Engineer-in-charge.
Supply and Fix Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with MS clamps, bolts and nuts of approved size, for 20x15cm size complete all as specified and directed.
Supply and fix Cable jointing kit for 11KV (E) grade cable for Outdoor End termination heat shrink type complete with Jointing material and acceesseries suitable for 3 core are XLPE armoured at conductor cable of size 120 to 185 sq mm all as specified including Disconnecting and cutting down the existing old unserviceable / worn out cable end joint Kit 11 KV grade indoor termination cold shrink type as directed by Engineer-in-charge.
All As per Item No - 36, but for 50 to 95 Sqmm
All as per Item No-36 , but for outdoor End Termination Aerial Bunch Cable of 50-95Sqmm
Supply and fix Cable jointing kit for 11KV (E) grade cable for Outdoor Straight through joint, heat shrink type complete with Jointing material and acceesseries suitable for 3 core are XLPE armoured at conductor cable of size 50 to 95sq mm all as specified as directed by Engineer-in-charge.
All As per Item No - 39, but for 120 to 180 Sqmm
All as Per Item No-39, but for outdoor Straight through Joint of Aerial Bunch Cable
M & L Earthing complete with GI earth plate electrode 60cmX60cmX6 mm thick buried directly in ground (earth pit not less than 2.25 mtrs deep below ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, connecting to galvanized earth strip 32 x 6 mm as earthing conductor by means of bolts, nuts, check nuts and washers of GI and all as shown in Electrical plate No.5 of SSR Part I and including testing on completion all as specified locations and as directed by the Engineer-in-Charge incl taking down old unsv one. Note: 1.The above quoted rate shall include cost of main earthing lead of 32 x 6mm GI earth strip, charcoal, salt, excavation and earth work in any type of soil CI cover, funnel with 20mm dia light grade GI water pipe including GI protection pipe 40mm dia light grade for earth strip etc. 2. The cost of earth pit is deemed to be included in the unit rate.
Disconnecting all incoming/outgoing cables and earth strips, removing the transformer of capacity 100-160 KVA from the platform / two pole structure / floor and loading it in the vehicle carefully using crane and transporting it to the contractor's workshop, carry out the required repairs and transport the transformer back to the site , install it, reconnect all the incoming/out going cables and earth strips by properly crimping using lugs of suitable size lugs, taping the LT / HT bushes / bus bars, using LT / HT insulation tape and testing complete of following capacity all as directed by Engr-in-Charge. Note :- (a) Shifting and fixing transformer from own arrangent temporarily from MES Area to that area ( Back up Transformer will be provided by MES) (b) The cost of transportation of 2 transformers between Existing location and the Workshop is deemed to be included in the unit price. (c) Gasket set, LT/HT side porcelein / ceramic bushing, spindle for HT/LT side , rewinding, dehydration of oil (if required) shall be measured and paid separately in respective items as supply and fix.
All as per Item No- 43, but for capacity 200-315 KVA capacity
All as per Item No- 43 but for capacity 400-500 KVA capacity
S & F brass spindle for terminal on HT side threaded complete with nut, washers etc of suitable dia for transformer of of capaicty 100-160 KVA
All as per Item No-46, but for capacity 200-315 KVA capacity
All as per Item No- 46, but for capacity 400-500 KVA capacity
All as per Item No- 46, but for LT Side & capacity 100-160 KVA capacity
All as per Item No- 46, but for LT Side & capacity 200-315 KVA capacity
All as per Item No- 46 , but for LT Side & capacity 400-500 KVA capacity
Labour for Dehydration/ filtration of transformer oil of Capacity 100 KVA to 2.5 MVA with ultra high vacuum filteration machine and checking dielectric strength (BDV), dielectric dissipation factor, neutralizing value (total activity) not less than 60 KV with 2.5 mm Gap sludge content, flush point of transformer oil from Standard Testing Laboratory all as specified .Refilling the transformer oil in the shell of transformer after carrying out filtration and heating up oil to achive reqd dielectric strength and submitting the test result before and after filteration of oil in presence of Engr- in- charge on proper proforma duly signed.
Supply and fill new Transformer oil as per IS 335 with high viscosity , high resistance to oxidation & thermal stability mainting BDV Value of not less than 60 KV in 2.5 mm rod gap complete all as specified and directed by Engineer-in-charge.
S & F dehydrating breather for 100-160 KVA transformer with dehydrating agent (Silica gel) including taking down existing breather complete all as specified.
All as per Item No- 54 , but for 200-315 KVA transformer
All as per Item No- 54, but for 400-500 KVA transformer
Supply and fix in repair ceramic bushing on HT side of transformer of capacity 100-160 KVA
All as per Item No- 57, but for 200-315 KVA transformer
All as per Item No- 57, but for 400-500 KVA transformer
All as per Item No- 57, but for LT side of 100-160 KVA transformer
All as per Item No- 57, but for 200-315 KVA transformer
All as per Item No- 57, but for 400-500 KVA transformer
Supply and fixing in replacement of complete gasket (Cock sheet) 6 mm thick complete of capacity of following transformer including conical rubber bush for Transformer of capacity 100-160 KVA
All as per Item No- 63, but for 200-315 KVA transformer
All as per Item No- 63, but for 400-500 KVA transformer
Material and labour for painting to 100-160 KVA transformer scrapping and removing oil paint and applying 01 coats of synthetic enamel paint by taking due care for HT/LT side supply all as specified and directed by Engineer-in-charge .
All as per Item No- 66, but for 200-315 KVA Transformer
All as per Item No- 66, but for 400-500 KVA Transformer
M & L for winding of HV coils,using new copper wire/strip of proper size including insulating materials (double insulation) as per existing size of core of transformer up to 500 KVA capacity complete including heating , varnishing complete all as specified and directed by Eng in charge
M & L for winding of LV coils,using new copper wire/strip of proper size including insulating materials (double insulation)as per existing size of core of transformer up to 500 KVA capacity complete incl heating , varnishing complete all as specified and directed by Eng in charge.
M & L for winding of HV/LV coils coils,removing U/S insulating materials, double reinsulation with insulating papers using same copper strip and rewinding as per existing size of core of transformer up to 500 KVA capacity complete incl heating , varnishing complete all as specified and directed by Eng in charge.
Calibration and testing of combined inverse time over current and intstantaneous relay, checking and cleaning / decarbonising its moving and fixed contacts and ensure physical healthyness with visual check for healthy tripping of over current and earth fault, adjusting tripping time, flag setting, ratio setting, instantaneous time setting etc as per installed capacity of transformer to be saved on maximum, short circuit current in accordance with percentage impedance of transformer with artificial current injection on primary side with current injection machine of HT VCB,s complete all as specified and directed by Engineer-in charge. Note : Spares / meters shall be measured and paid seperatly. The job of calibration, & setting shall be done in presence of MES rep / concern JE. Contactor shall provide the necessary test report of calibration done to department before claiming the payment. 2. Contractor shall provide all testing equipment , T&P, and injection kit for testing and creating the artifical fault for testing the proper functionality of relays and instruments on designed settings..
M&L for complete Overhauling/Repair of 33 KV VCB with panel, rated voltage- 36 KV cleaning of all parts, adjusting contacts, springs locking arrangements tripping coil circuits (closed/open) etc cleaning of CT and PT supporting insulators bush trolley auxiliary contact. Make female contact and check all wiring including minor item required for repair complete all as specified and directed
Overhauling/Repair of 11 KV VCB with panel, rated voltage- 36 KV cleaning of all parts, adjusting contacts, springs locking arrangements tripping coil circuits (closed/open) etc cleaning of CT and PT supporting insulators bush trolley auxiliary contact. Make female contact and check all wiring including minor item required for repair complete all as specified and directed
M&L for complete Overhauling/Repair of Float cum Boost Charger, cleaning of all parts, check all wiring , Checking Output Voltage, Checking entire DC Circuit from Charger to the panel Fuse including replacement of minor item required for repair complete all as specified and directed by Engr in Charge
S & F in repair 3 phase digital type Amp meter 0 - 200 Amps class 0.5 of size 96mm x 96mm to match the ratio of existing CTs complete all as directed by Engineer in charge.
S & F in repair 3 phase digital type Volt meter 0 - 11 KV class 0.5 of size 96mm x 96mm to match the ratio of existing PTs.complete all as directed by Engineer in charge.
S & F in repair 3 phase digital type Volt meter 0 - 33 KV class 0.5 of size 96mm x 96mm to match the ratio of existing PTs
S & F in repair Programmable numerical inverse time over current / earth fault relay suitable for VCB 11/12 KV of make ABB Model No - REJ-601 or Equiv of Kirloskar / Areva complete
S & F in repair Epoxy Resin Body for switchgear VMX type 11 KV VCB, 630 Amp Complete all as specified and directed.
S & F Top clamps with hardware (pair) R/B phase 630 / 800 Amps complete all as specified and directed.
S & F Top clamps with hardware (pair) Y phase 630 / 800 Amps complete all as specified and directed.
S & F in repair Half collar (Pair) of VCB 630 Amps complete all as specified and directed
S & F in repair Brass nut of VCB 630 Amps complete all as specified and directed
S & F in repair Spider for VCB 630 Amp Complete all as specified and direted
S & F in repair Epoxy Resin Spout bushings triple pole assembly fit for 11 KV VCB panel Complete all as specified and direted
S & F in repair Gromet VCB 630 Amp Complete all as specified and direted
S & F in repair Drive insulator with M10 Nyloc Nut for VCB 630 Amp Complete all as specified and direted
S & F in repair Drive Beam (Pair) VCB 630 Amp Complete all as specified and directed
S & F in repair closing coil assembly 110 volt for VCB complete all as specified and directed
S & F in repair tripping coil assembly 110 Volt for VCB complete all as specified and directed
S & F in repair TNC switch , 110 Volt complete all as specified and directed
S & F in repair vacuum interrupter suitable for VCB VMX type 630/400A Model. VG2 BW524/99/Ro
S & F in bakelite HRC fuse base with carrier 32A, 415 V with HRC fuse 5 amps complete all as specified and directed.
S & F in repair Buffer for VCB 11KV complete all as specified and directed.
S & F in repair push button actuator 1 No element, 22.5 mm dia (TCH) assembly
Material and lobour for cradles hexagonal / rectangular fabricated with galvanised steel wire 3.15 or 4 mm dia complete all as specified and directed
Stringing / restringing only existing cradles hexagonal / rectangular, GI earthing wire of any shape and size complete all as specified and directed. Note- 1. Span Between two consecutive poles shall be measured as one unit.
Labour only for , identifying, dignosing, tracing, checking & rectifying High Tension (11KV/33KV) faults, tracing location by disconnecting Jumpers, Climbing on the HT poles, checking of insulators and conductors for its healthlyness, megering the lines, insulators for identitfying the faults, faults in panels, VCB`s, and other switch gears, tracing fault in HT/LT cables through meger etc at any location, any time round the clock and rectifying it to restore the supply within time limit at locations comes under maintaince responsibility of AGE E/M South Army (SAA) under GE (S) Tezpur complete all as specified and directed. Note:- 1. On receiving the intimation of any type of faults through any mode / media, the contractor is responsible to locate the fault by deploying the dedicated team comprising of sufficient manpower Skilled electricians and helpers required in numbers as per the gravity/nature of the work involved to restore the power supply and communicate with SBA (On duty operator in Sub station) on duty and getting shutdown and permit card for working on HT lines and deposit the permit card after rectification of fault and fully completion of work . All the activities to trace the fault and rectifying & restoring the supply shall be carried out within specific reasonable time as given by the Engineer-in-charge. 2. The cost of required tools (T& P) and safety equipments required for the job to be provided by contractor and cost for same is deemed to be included in this unit price. No extra charges will be paid by department. 3.Safty of manpower deployed for the job is contractors responsibility . In case of any accident , department will not be responsible and no extra payment shall be paid to the contractor in account of this.
Supply, fixing / stringing Aluminium conductor steel rainforced of any type and size on existing steel tubular / PCC poles including winding, jumpering with alkathine pipe etc complete all as specified and as directed.
Supply, fixing testing and commissioning in repair CT , 11 KV, dry type, indoor, 200/100 (primary)-5 A (Secondary) for fixing with Spout bushing complete all as specified and directed.
All as in Item No- 104 above but for capacity 5 KVAR. Make- MOC Type in L&T and equivalent in Havells/ABB
All as in Item No- 104 above but for capacity 10 KVAR. Make- MOC Type in L&T and equivalent in Havells/ABB
All as in Item No- 104 above but for capacity 20 KVAR. Make- Make- MOC Type in L&T and equivalent in Havells/ABB
Supply & Fix in repair capacitor MDXL ultra heavy duty cylindrical type capacitor of 1 KVAR, 440V complete all as specified and directed.
All as in Item No- 108 above but for capacity 2 KVAR.
All as in Item No- 108 above but for capacity 3 KVAR.
All as in Item No- 108 above but for capacity 5 KVAR.
All as in Item No- 108 above but for capacity 10 KVAR.
All as in Item No-108 above but for capacity 20 KVAR.
All as in Item No- 114 above but for 12 steps.
S & F in repair microprocessor based protection release of ACB of any capacity complete all as specified and directed
S & F in repair mechanical operation counter of ACB of any capacity complete all as specified and directed
S & F in repair racking padlock assembly for ACB of any capacity complete all as specified and directed
S & F in repair spring charge indication for ACB of any capacity complete all as specified and directed
S & F in repair shunt release type EA1 : 415 V AC for ACB of any capacity complete all as specified and directed
S & F in repair Earth fault release Type EF 2 (30 %, 40%, 50 % In) for ACB of any capacity complete all as specified and directed
S & F in repair Under Voltage release Type MV, 415 V for ACB of any capacity complete all as specified and directed
S & F in repair AN1 remote annunciation module 240 V for ACB of any capacity complete all as specified and directed
Labour for restringing/tilting, clamping, bending, jumpering etc to remove excess sag of loose ACSR overhead line using essential T&P such as manila rope, puller and teipod etc upto permissible sag between two poles continuously upto termination point. Note- 1. Three runs of ACSR shall be measured as one unit. 2. Span Between two consecutive poles shall be measured as one unit. 3. The cost of required tools (T& P) and safety equipments required for the job to be provided by contractor and cost for same is deemed to be included in this unit price. No extra charges will be paid by department.
Labour for trimming/cutting to small tree branches girth not exc 30 cm upto minimum 2 Mtr clearance, tightening to stay strand in proper angle complete all as specified and directed by Engr in charge. Note- 1. Span Between two consecutive poles (max up to 100 mtrs) shall be measured as one unit. 2. The cost of required tools (T& P) and safety equipments required for the job to be provided by contractor and cost for same is deemed to be included in this unit price. No extra charges will be paid by department.
NOTES: 1. The amount of schedule of credit shall be deducted from the total of this BOQ for arriving at contract sum. 2. The rates for RCC/PCC shall deemed to include the cost of formwork, shuttering etc., required for complete and proper execution of the item. Refer Schedule "A" notes for details.
HEMONTA DAS
M/s JK Jangid and Company
M/s SCHOLASTIC ENTERPRISES
SONI ENTERPRISE
Purbanchal Construction Co
M/s Dhani Enterprise
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .