| 1 | L1₹21.0 LAccepted-AOC 121 MADHAV SQUAR OPP AVANTIKA COMPLEX LIMDA LANE JAMNAGAR 361001 | JAMNAGAR | GUJARAT | 361001 | L1 | Accepted-AOC L1 AND REASONABLE | |
| 2 | L2₹23.2 L+₹2.2 L (10.6%)Rejected-Finance 108 MARUTI COMPLEX NEAR DIGVIJAY TIN FACTORY MILE STONE BUILDING KV ROAD JAMNAGAR 361001 | JAMNAGAR | JAMNAGAR | GUJARAT | 361001 | L2 | Rejected-Finance NOT L1 | |
| 3 | L3₹24.5 L+₹3.5 L (16.8%)Rejected-Finance | L3 | Rejected-Finance NOT L1 | |
| 4 | L4₹24.6 L+₹3.6 L (17.0%)Rejected-Finance INS VALSURA JAMNAGAR | JAMNAGAR | GUJARAT | 360520 | L4 | Rejected-Finance NOT L1 | |
| 5 | L5₹24.6 L+₹3.6 L (17.0%)Rejected-Finance INS VALSURA JAMNAGAR | JAMNAGAR | GUJARAT | 360520 | L5 | Rejected-Finance NOT L1 |
Tender Value
₹23.5 L
EMD Value
₹47,000
Closing Date
8 Apr 2025, 6:00 pmClosed
GE A JAMNAGAR
INFANTRY LINES JAMNAAGR
SPECIAL REPAIR FOR REPLACEMENT OF ONE NO.125 KVA DG SET AGAINST BER FOR SEWAGE INSTALLATION AT JAMNAGAR MILITARY STATION
2025_MES_701154_1
8120
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
JAMNAGAR
AS PER TENDER DOCUMENTS
6 documents required · 6 mandatory
₹500
GE ARMY JAMNAGAR
₹47,000
3 May 2025
12 Mar 2025
10 Apr 2025
13 Mar 2025
8 Apr 2025
25 Mar 2025
Amount
1.Diesel Engine Generating set 415 volts 125 KVA 3 -phase 0.8 power factor 50 Hz, 1500 RPM self exicited self regulated brushless AC generator installed including accoustic enclosure suitable for ambient at Jamnagar and confirming to condition under Alternator IS 13364(Part-II), Genset-ISO8528 & Engine BS 5514 /ISO 3046 DG set ISO 8728 incl AMF Panel complete all as specified and directed . NOTE:- (i) The capacity of Generator set shall be net after all due derating factors as per relevant ISI standard. (ii) The quoted rate shall be deemed to be inclusive of first fill of lubricant oil and final successful acceptance test. (iii) The quoted rate shall be deemed to be inclusive of 12 hours test run at site including of one hour on 10% overload in presence of representative detailed by accepting Officer, all arrangements are to be made by the contractor for tests. (iv) Rate quoted shall be deemed to be included in making necessary holes to walls and making good to distrubed surfaces of match to original specification and connection up all as specified and directed. (A). Alternator:- Standard design alternator rated at 125 KVA/100kW, 3phase 415V, 50Hz, 173.9 Amp current rating with automatic votage regulator with +/-1% voltage regulation at rated voltagenet output at site after considering derating as per site conditions at 0.8 (lag) power factor regulated screen protected drip proof IP 23 enclosure brushless design with winding in pole faces, insulating class 'H' and from no load to full load. The alternator shall be confirming to IS 13364(Part-II), Genset-ISO8528 and shall be inposition to generate supply with frequency regulation with in + 1% tolerace. The alternator will be suitable for topical climate of Jamnagar. (i) Insualation class - 'H' (ii) Temparature rise - 125 Degree Centigrade. (iii) Excitation : Self Excited (iv) Regulation performance: The voltage is kept constant with +1% manual voltage adjustment within + 5%. (v) Frequency regulation - Isochronous
(B) Diesel Engine:- Adequate capacity Diesel engine suitable for 125KVA coupled drive independently above alternator and after considering derating as per site conditons after generating and reducing power consumed by accessories, directly coupled through flexible coupling, multi cylinder multi stroke direct injection, cold starting 1500 RPM,6 cylinder, in-line 4 stroke as per relevant BS 5514 /ISO 3046 with an overload capacity of 10% for one hour in 12 hours continuous running complete with standard accessories all as specified and required for safe handling and operation salient features of accessories shall be as under:- (i) Fly wheel with housing (ii) Cooling system:- Mounted radiator with fan & belts (iii) Cooling Water pump:- Centrufugal type belt driven. (iv) Exhaust System :- Exhaust System complete with exhaust piping of Exhaust gas turbo charger type Exhaust manifold Silencer : Residential type Bellows (v) fuel System :- Fuel injection system with fuel injectors, fuel injection Fuel filters (vi) Lub oil System:- Lubricating oil filter ,Lubricating oil pump (vi) Air Intake System :- Air intake Manifold ,Air cleanleer dry type (viii) Starting System :- Electric Self starter with maintenace free batteries including battery charging alternator. (ix)Starter gear ring Start and stop push button (x)Ignition key / Switch (xi)Handling and operation : Salient features of accessories shall be as under: (xii)Radiator with blower fan (xiii)Corrosion inhibitor coolant (xiv)Paper element filters for fuel, lub oil and by pass. (xv)Electronic governer controlled direct fuel injection system (xviFly wheel housing and fly wheel. (ix) Batteries:- Maintenece free Batteries of 1 X 12 Volt (88AH)of specific gravity as recommended by manufacture capacity complete with copper conductor multistrnded leads of suitabloe length from self starter to the battary terminals complete with initial charge and initial fill of electrolite all as specified.
(v) Special paint treatment with pure polyester powder / epoxy to be provided for better weather resistance. (vii) For effective acoustic / weather sealing a special type weather sealing gaskets, new frame rubber gaskets to used. (viii) Working space is to be provided around the equipment for easy maintenance / repairs. (ix) Necessary cut out provision for entry and exist of fuel lines cable to be incorporated in the enclosure as per the requirement. (x) A see through transparent window ( glass or acrylic) in front of engine panel to provided for monitoring the operation. (xi) Ducting if required, bellows, mechanical hardware like locks, hinges fasteners etc to be provided. (xii) Deliverables. 75 DBA @ 1mtr at 75% load under free field conditions. The temp inside the enclosure will be within as per manufacturers recommendations above ambient temp. (xiii) The enclosure should be proided with bulk head light fitting for inside illumination (xiv) The battaries should be placed inside the enclosure beside the DG set on a suitable insulated plat form. (xv) the DG set should be provided with external Emergency stop push buttom. (xxv) The accoustic enclosure parts shall be of powder coated after pre treat ment process. The powder coating shade should be Genset Green. The base frame should be painted with epoxy based black shade. The following itmes are deemed to be included in the rate quoted for all DG sets:- (i) DHPP for testing purpose shall be supplied by the contractor without any extra cost to Govt. (ii) The contractor shall arrange for artificial load for testing for final testing to DG Set at site and the cost is deemed to be including in above offer. (iii) Testing of sound level should carred out at the site in presence of GE. Documents : Standard ducuments as per manufacturer specifications such as maintenance & operation maufacturer specifications such as maintenance & operation manual, parts catalogue, Display charts such as maintenance and oil change chart/board (for generator and diesel engine) and log book as directed by Engr-in-charge.
Supply and connection including testing of XLPE insulated, screened,PVC bedded,galvanised steel strip or wire armoured ,electric power cable (heavy duty) with aluminium conductor,1100 volts, grade cross sectional area 400 sqmm 3.5 coreconforming to relevent IS.(Note: Cable to be connected between Transformer to AMF Panel) including taking down old unserviceable UG cable of any type complete all as specified and as directed by Engr in Charge.
Supply and connection including testing of XLPE insulated, screened,PVC bedded,galvanised steel strip or wire armoured ,electric power cable (heavy duty) with aluminium conductor,1100 volts, grade cross sectional area 240 sqmm 3.5 coreconforming to relevent IS.(Note: Cable to be connected between AMF Panel to DG Set and AMF control panel to distribution panel.) including taking down old unserviceable UG cable of any type complete all as specified and as directed by Engr in Charge.
M&L for Earthing with galavanised steel earth plate elctrode 600mm x 600mmx6mm thick buried directley in ground, (earth pit not less than 2.25m below ground level), with the top edge of the plate not less then 1.5 m below the normal ground level, connected to GI earth strip of size 32x6mm thick soldered and riveted to earth plate,GI earth strip will be protected by using 40mm bore GI pipe (light grade) from earth plate to equipment and watering pipe 20mm bore (light grade), chamber and coping shall be made in PCC (1:3:6) type C1 using 20mm graded stone aggregate, RCC pit cover 50mm thick in 1:2:4 type B1 using 20mm graded stone aggregate reinforeced with 8mm dia TMT bar @ 80mmc/c both way with lifting hook made out of 8mm dia TMT bar duly embedded in RCC cover in lieu of CI pit cover with angle iron frame including excavation and earth work and removal of surplus soil complete all as shown in electrical plate No 3 of SSR Part I and as specified including charcoal dust, common salt complete and earth lead connected to earthing test point/main point and testing of earthing complete as directed. (Note:- Main earthing lead from earth plate to test point & upto 7.5mtr to be provided and the cost of the same shall deemed to be included in the quoted rate).
M & L for brick work with sub class `B` bricks using old size bricks straight on plan built in cement mortar 1:6 etc all complete all as specified and as directed by Engr in Charge.
M & L for PCC 1:2:4 type B2 in using 40 mm graded stone aggregate even thick finished even and smooth complete all as specified and as directed by Engr in Charge.
M & L for hardcore of gauge n exc. 63 mm, deposited, spread and levelled in layers n exc. 15 cm thick, watered and rammed to a true surface etccomplete all as specified and as directed by Engr in Charge.
M & L for moorum/red bajri filling in floors or pavings, laid in layers n exc. 15 cm thick, spread, levelled and rammed including watering etc complete all as specified and as directed by Engr in Charge.
M & L for 15 mm thick rendering in CM 1:6 on fair faces of brick work / concrete work and finished even& smooth without using extra cement complete all as specified and as directed by Engr in Charge.
Excavation in trenches n.exc 1.5M wide and n.exc 1.5 M in depth and getting out in soft/Loose soil all as specified and directed by Engr-In-charge.
Returning, filling in, including levelling, watering and well ramming in layers, n.exc 25 cm each in soil all as specified and directed by Engr-In-charge.
Removing excavated material n.exc 50m and depositing where directed at a level n.exc 1.5 m above the starting point all as specified and directed by Engr-In-charge.
M&L dry river sand in trenches for cable cushioning & protection including spreading, ramming complete all as specified and as directed by Engr in Charge..
Supplying and laying un-reinforced precast concrete cable cover, LV low voltage type -I flat size 250 mm x 150 mm x 40 mm complete all as specified and as directed by Engr in Charge.
Rameshwar Enterprise (BID ID -3274996)
M/s. Vimal Enterprise (BID ID -3278643)
Hirachand Sunderji and co (BID ID -3278679)
JAYESH TRADING CORPORATION (BID ID -3278385)
SHRI SAINATH ENGINEERS (BID ID -3278132)
MONA GENERATOR SEVICES PVT. LTD. (BID ID -3275147)
fakhrie apostrical (BID ID -3276290)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .