SE
SE E/M Circle PWD, Gorakhapur
Remaining essential electrical works at Jananayak Chandrashekhar University, Ballia.
2026_CEEMP_1205669_1
1730/Nivida Suchana (Azm Zone) GKPCircle-EM/2026-27 Date 24.10.2026
Open Tender
Electrical Works
Item Rate
60 days
Azamgarh
Please refer Tender documents.
3 documents required · 3 mandatory
₹2,354
Executive Engineer E/M Division PWD Azamgarh
₹6.3 L
Yes
Azamgarh
27 Nov 2026
5 Nov 2026
27 Nov 2026
5 Nov 2026
27 Nov 2026
5 Nov 2026
10 Nov 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supplying, installation, testing and commissioning of 2000 KVA capacity (continuous loading) BEE 5 Star rated (Corresponding Level as per BIS amended upto date of receipt of tender) , 11/0.433 KV step down, 3 Phase, 50 Hz, Dyn 11 vector group, ONAN (Oil Natural Air Natural) copper wound transformer (Electrolytic grade 99.9% pure copper, Core made of first grade Cold Rolled Grain Oriented (CRGO) Core grade MOH or better, suitable for out door applications with On Load Tap Changer (OLTC) on HV side having AVR relay and Remote Tap Changer Control (RTCC) for automatic sensing of incoming voltage, automatic operation of OLTC and facility for remote and manual operation of OLTC HV side in range of +5% to -15% in steps of 2.5%, having cable end boxes on HV side suitable for 3x300 sq.mm XLPE cable of 11 KV grade, including bus trunking arrangement on LV side including supplying and laying of copper conductor multicore control cable from transformer to HT breaker/panel for safety tripping, complete with all accessories and safety provisions as per relevant IS Code including first filling of filtered dehydrated oil, i/c supplying and grouting of suitable M.S. Channel with all accessories and transformer shall be confirming to IS : 2026 (Part 1 to Part 5), IS : 1180 and as per CPWD specificationscomplete in all respects etc as required at site. The maximum flux density in any part of the core and yoke at rated voltage and frequency shall be such that the flux density with + 12.5 percent combined voltage and frequency variation from rated voltage and frequency does not exceed 1.9 Tesla. The permissible temperature-rise shall not exceed 40 0C for oil and 45 0C for winding. Inside of tank shall be painted with varnish or liquid resistant paint. For external surfaces one coat of thermo setting powder paint or one coat of epoxy primer followed by two coats of polyurethane base paint shall be used. IS: 1180 (Part 3) shall be referred to for paint thickness for normal to medium corrosive atmosphere. For highly polluted atmosphere and special application external paint work shall be as per direction of Engineer-in-Charge. Design ambient condition : a) airtemperature 50 0C, b) Relative Humidity 90 % Max, c) Seismic Zone as per location of site, d) Altitude as per location/site. Noise level Shall not exceed limits as per NEMA TR-1 with all accessories running measured as per IEC 551 / NEMA standard. The transformer should have QR code which should contain drawing, test report OEM manual, Geo- Tag of manufacturing location etc. Marking Each transformer shall be provided with rating plate made of anodized aluminium/ stainless steel material securely fixed on the outer body, easily accessible as per IS: 1180 Part-3. The entries on the rating plate shall be indelibly marked.Fitting and Accessories : The following fittings shall be provided:- a) Two earthing terminals with the earthing symbol b) Oil level gauge indicating oil level at minimum, 30°C and maximum operating temperature; c) Air release device (for non-sealed type transformers) d) Rating and terminal marking plates; e) Silica gel breather f) Drain-cum-sampling valve (¾″ nominal size thread, IS 554) preferably steel with plug for three phase transformers; g) Thermometer pocket with cap; h) Oil filling holes having (1¼″ nominal size thread) with cover (for sealed type transformers without conservator); i) Lifting lugs for the complete transformer as well as for core and winding assembly; j) Pressure relief device or explosion vent k) One filter valve on the upper side of the tank Unidirectional flat rollers m) Inspection hole n) HV side neutral grounding strip(where one of the HV bushing terminal is connected to earth); o) Buchholz relay. p) Arcing horns or suitable rating lightning arrestors for HT side – 3 Nos. q) Bird guard; r) Oil temperature indicator and winding temperature indicators for transformers above 200 kVA with suitable tripping mechanism above permissible limit s) Jacking pads t) Additional Neutral separately brought out on bushing for earthing. u) Magnetic oil level gauge with low oil level alarm contact; v) Non return valve (for conducting pressure test); w) Pressure relief device or explosion vent x). Monogram Plate y) Inspection cover z). Detachable type radiators with top and bottom shutoff valve. aa) Oil Conservator with Oil level indicator, minimum level marking and drain plug . bb) Necessary hardware, clamps, lugs etc. for termination on HV/MV etc. With Mineral Oil Filed (5 Years Warranty) DSR No. 24.6.4 | 1 | No | - | - |
| 2 | Supply and Laying of aluminium conductor PVC insulated armoured served sheathed cables 1100V grade. At a depth of 750 mm below ground level over a cushion 75mm thick sand all aroundand provide with burnt bricks on side and on top complete in all respect including excavationand refilling. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. a 10 sq mm 2 core SOR No. 10.1.2 | 600 | Mtr | - | - |
| 3 | 95 sq mm3-1/2 core SOR No. 20.1.14 | 140 | Mtr | - | - |
| 4 | 120 sq mm3-1/2 core SOR No. 20.1.15 | 280 | No | - | - |
| 5 | 150 sq mm3-1/2 core SOR No. 20.1.16 | 1,350 | Mtr | - | - |
| 6 | 300 sq mm 3-1/2 core SOR No. 20.1.19 | 150 | Mtr | - | - |
| 7 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of insulated and PVC sheathed/XLPE aluminium conductor cable of 1.1 KV grade as required. 10 sq mm 2 core DSR No. 11.1.2 | 40 | Nos | - | - |
| 8 | 95 sq mm3-1/2 core DSR No. 11.1.24 | 2 | Nos | - | - |
| 9 | 120 sq mm3-1/2 core DSR No. 11.1.25 | 2 | Nos | - | - |
| 10 | 150 sq mm3-1/2 core DSR No. 11.1.26 | 6 | Nos | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.11 MB
BOQ_2284838.xls
BOQ • 0.29 MB
BalliaT2.pdf
Tender Documents • 6.10 MB
shuddhid.pdf
PDF • 0.21 MB
Corigendumb.pdf
PDF • 0.18 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .