Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹7.6 LAccepted-AOC | L1 | Accepted-AOC single bidder L1 |
| Sl No | Description | Qty | Unit | M K V Engineering L1 |
|---|---|---|---|---|
| 1.00Electrical Work | ||||
| 1.00 | 1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm | 5 | metre | 120 ₹600 Lowest |
| 1.00 | OD4853/2025-2026:Supply and installation of wall mounting cubicle type dust and vermin proof CAPE make BRES 44, 400 x 400 x 200 mm Glass Fibre Reinforced Polyester Enclosure with hinged door, IP66, IK 10 outdoor meterbox or equivalent with base plate for fixing KSEB meter, cut out & Neutral link and 20A , 10kA SPN MCB, C curve , with sufficient holes for fixing KSEB electronic energy meter, cut outs and neutral link. Supply and providing 1No 20A,10kA ,32A MCCB , 1 No 32A HRC fuse units with 20A HRC fuse link and 1No 32A 2way neutral link in the meter portion. Necessary holes are to be provided in the box for entry and exit of wire. The inter connection should be done using 4sq.mm copper wire. | 1 | 1 nos | 27,000 ₹27,000 Lowest |
| 1.00 | 90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG) | 240 | metre | 90 ₹21,600 Lowest |
| 1.00 | 2.10.1:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, ""C"" curve, miniature
circuit breaker suitable for inductive load of following poles in the existing MCB
DB complete with connections, testing and commissioning etc. as required.
Single pole | 4 | each | 300 ₹1,200 Lowest |
| 1.00 | 1.24.3:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch | 2 | each | 335 ₹670 Lowest |
| 1.01 | 1.24.5:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet | 2 | each | 218 ₹436 Lowest |
| 1.01 | 2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps | 1 | each | 500 ₹500 Lowest |
| 1.01 | 2.14.2:Supplying and fixing following rating, double pole, (single phase and neutral),240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.
40 amps | 1 | each | 3,000 ₹3,000 Lowest |
| 1.01 | OD10417/2024-2025:Supplying suspended/surface mounted LED luminaire having >=2000lumen with mounting frame and fixtures of make Phillips BN 021C LED 20S PSU NW GR or equivalent | 10 | no | 1,000 ₹10,000 Lowest |
Tender Value
₹7.6 L
EMD Value
₹19,067
Closing Date
30 Jan 2026, 5:00 pmClosed
The Assistant Executive Engineer Electrical HEESD
O/o The chief Engineer, Harbour Engineering Electrical Sub Division, Kamaleswaram, TVPM
GENERAL-Electrical works-2025-26-Annual Maintenance of various harbours in kozhikode division-General Electrical Work
2026_HED_830228_1
HED/CEHED/TR/94/2025_6_11_10/1
Open Tender
Electrical Works
Item Rate
365 days
Kozhikode Division
Please refer Tender documents.
7 documents required · 7 mandatory
₹1,685
₹19,067
24 Sept 2026
23 Jan 2026
2 Feb 2026
23 Jan 2026
30 Jan 2026
23 Jan 2026
Electrical Work
1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
OD4853/2025-2026:Supply and installation of wall mounting cubicle type dust and vermin proof CAPE make BRES 44, 400 x 400 x 200 mm Glass Fibre Reinforced Polyester Enclosure with hinged door, IP66, IK 10 outdoor meterbox or equivalent with base plate for fixing KSEB meter, cut out & Neutral link and 20A , 10kA SPN MCB, C curve , with sufficient holes for fixing KSEB electronic energy meter, cut outs and neutral link. Supply and providing 1No 20A,10kA ,32A MCCB , 1 No 32A HRC fuse units with 20A HRC fuse link and 1No 32A 2way neutral link in the meter portion. Necessary holes are to be provided in the box for entry and exit of wire. The inter connection should be done using 4sq.mm copper wire.
90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)
2.10.1:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, ""C"" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
1.24.3:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
1.24.5:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.14.2:Supplying and fixing following rating, double pole, (single phase and neutral),240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 amps
OD10417/2024-2025:Supplying suspended/surface mounted LED luminaire having >=2000lumen with mounting frame and fixtures of make Phillips BN 021C LED 20S PSU NW GR or equivalent
1.25:Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
1.27.2:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)
90.4.5.4:Supply, Installation, testing and commissioning of ceiling fan of following sizes including wiring the down rods of standard length (up to 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required. 1200mm sweep - ceiling fan complete with service value minimum 4.0(cub meter/minute/Watt), Air delivery minimum 210(cubic meter/minute), Copper winding suitable for 230V/240V single phase AC supply
OD10420/2024-2025:Supply and fixing 7/9 W LED ,BC, lamp OSRAM or equivalent
1.33:Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required.
OD4856/2025-2026:Scaffolding charges for dismantling and repairing work .
1.34:Supplying and fixing brass batten/ angle holder including connection etc. as required.
OD4857/2025-2026:Engaging labourers for checking the electrical installations, cables etc and rectifying faults if any as per the direction of the departmental officers at site. wireman
1.41:Installation, testing and commissioning of pre - wired, fluorescent fitting/ compact fluorescent fitting of all types, complete with all accessories and tube etc. directly on ceiling/ wall, including connection with 1.5 sq.mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required.
OD10418/2024-2025:Supplying surface/suspended mounted smartbrite luminaire SM 270C LED 30S 6500 PSU WH Philips or equivalent
90.12.6.41:Supply & laying of one No. PVC insulated and PVC sheathed armoured aluminium power cable of 1.1 KV grade of the following sizes in the existing masonry open duct as required.4 core 16 sq mm
90.12.7.41:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 16 sq mm with factory made clamp
90.12.9.2:Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench50/38 mm or nearest size
1.42:Installation, testing and commissioning of pre-wired, fluorescent fitting / compact fluorescent fitting of all types, complete with all accessories and tube etc., including supplying and fixing ball and socket arrangement, 2 no. down rods of 20 mm dia X 1.6 mm thick steel conduit upto 30 cm length, painting and wiring the down rods and connection with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required.
1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
OD10421/2024-2025:Engaging labourers for checking electrical installations, cable etc. and rectifying the faults if any as per the instruction form the departmental officers at site
90.15.4.11:Supply Conveyance, installation, testing and commissioning of 200W LED Flood light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing, acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
90.15.4.2:Supply Conveyance, installation, testing and commissioning of 36/40W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
90.15.4.3:Supply Conveyance, installation, testing and commissioning of 70W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD Less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
90.15.4.7:Supply Conveyance, installation, testing and commissioning of 100W LED Flood light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing, acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
OD4850/2025-2026:Supply and installation of 100w Highbay LED, Bay light , System efficacy is 150 lumens/watt,Designed for operations under diverse environments ranging from -10˚C to 55˚C, IK08 polycarbonate cover provides strong protection under harsh conditions, Pressure die-cast housing offers excellent corrosion-resistance and robustness
OD4851/2025-2026:Supply and fixing pipe clamping arrangement using 30 cm, 65mm medium GI pipe supported by 50x50x6 mm Angle iron clamped on roof structure using 10 mm anchor bolt 4 nos and additional GI rods for fixing solar street light on builidng including all accessories
OD4852/2025-2026:Supplying and fixing all in one solar street light 40W with high efficiency mono crystalline solar PV module LiFePo4 battery with in built BMS technology MPPT charge controlller Aluminium extruded body IP65 with serviceable battery compartment high efficacy LED greater thatn 150LPW and PIR dimming provided for optimizing battery autonomy on roof structure.
9.1.33:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm)
9.3.29:Supplying and making straight through joint with cast resin compound including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm
14.10:Providing and laying in position reinforced cement concrete 1 :2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required (excluding reinforcement).
OD4859/2025-2026:Scrapping and cleaning the surface and painting two coats of best quality synthetic enamel paint of approved color over two coat of epoxy based industrial primer on electrical panel including all cost.
OD4860/2025-2026:Supplying and making end termination nickel plated single compression brass cable gland for 4 core 4 sq mm PVC insulated and PVC sheathed armoured copper conductor cable 1.1 KV grade, including providing earth clip and superior quality copper cable socket.
OD4861/2025-2026:Supply & laying of one number PVC insulated and PVC sheathed armoured copper power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.4 core 4 sq mm
Civil works
15.2.1:Demolishing cement concrete manually / by mechanical means including disposal of material within 50 metres lead as per direction of Engineer - in-Charge.Nominal concrete 1:3:6 or richer mix (i/c equivalent design mix)
stage.html
html • 0.03 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_1394624.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.04 MB
BOQ_1394624.xls
BOQ • 0.33 MB
viewsbd.pdf
Tender Documents • 1.67 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .