Executive Engineer Ukai Division No.1, Ukai
Supplying and erecting, Commissioning and testing of Diesel Generating set of HR Dam at Ukai Dam.
273754
Nivida No.31 of 2025-26
Open
Electrical Works
Works
Tapi
8 documents required · 8 mandatory
₹900
Executive Engineer Ukai Division No.1,Ukai
₹12,000
6 Feb 2026
6 Feb 2026
6 Feb 2026
19 Feb 2026
6 Feb 2026
Name of Work: Supplying and erecting, commissioning and testing of Diesel Generating set of HR Dam at ukai Dam
Per Description Item Rate Words Per Amount
Supplying and erecting, commissioning and testing of Diesel
Generating set confirming to IS: 4722:1968 & BS:5514
having continuous rating, 3 phase, 415 volts, 50 cycles A.C.
supply comprising of a totally enclosed air/water cooled diesel
engine with multi-cylinders developing suitable BHP not less
than following capacity at 1500 RPM with 10% overload for
one hour in 24 hours with standard accessories like fly wheel,
lubricating oil cooler, "A" class governor, heavy duty fuel wheel
and lubricating oil filter, oil bath air filler, lubricating oil
1 pressure gauge, end exhaust manifold, standard set of tools
with adjustable spanners, screw drivers, cylinder head to
cover, joint cylinder head to exhaust, element lube oil filter,
/ 24 volts electric starting equipment complete with standard
heavy duty battery, dynamo, cut-outs, ammeter, necessary
wiring, pressure gauge, starter etc and heavy duty Residential
type exhaust silencer and vertical hot air duct both
logged with asbestos rope, save oil trays, exhaust piping of
required length, standard wall/floor mounted fuel with level
indicator and piping and drip proof alternator, self excited, self
regulated, screen protected, with excitation system, capable of
delivering the rated system output at 415 volts, 3 phase,
PF, 50 Hz, 4 wire, running at 1500 RPM, conforming to IS-
4722- 1968 with voltage regulation +/- 5% of rated voltage
from no load to full load. Both the engine and alternator fitted
on a common fabricated steel base plate with antivibration
mounting engine and alternator both connected to each
other by flexible flange coupling and with floor/wall mounted
control panel box comprising of voltmeter ammeter, selector
switches, ACB / MCCB / MCB of adequate capacity,
indicator lamps duly wired with HRC fuses. The alternator &
control panel shall be connected with provided suitable
capacity armoured cable and complete with Acoustic
enclosure (canopy) made out of 16 SWG CRCA Sheet, sound
absorbing material Rockwool of 64 density & 100 mm thick
conforming to IS:8183 / PU Foam of 40 Density - at least
mm. The resin bonded rockwool covered from inside the
canopy by perforated sheet with 3/4 mm holes, sound level not
more than 75 dB at a distance of 1 mtr, as per PVCT norms.
Erection, commissioning and satisfactory testing as per
requirement with first filling of fuel, oil, etc. with guarantee /
Warrantee of complete system for Two years. & with obtaining
all necessary certificate from Electrical Inspector. The
Capacity and Ratings of DG sets are as below.
(M) Continuous rating of 125 KVA ,BHP not less than 154 Rupees Ten Lakh TwentyNine
1 BHP 1029194.04 Thousand One Hundred Ea.
NinetyFour Paise Four Only
Providing & erecting approved make AMF control panel
suitable for following size of 3 phase, 415 V., 50 cycles, A.C.
diesel generating set complete of scope as detailed below:
1) Power module: A pair of electromechanically interlocked
contactors (for mains & generator) Overload relay for
generator contactor Neutral contactor for mains and generator
Power socket for connections.
2 2) Control and metering module: Line voltage monitor.
Generator voltage monitor Ammeter 3 items attempt start
facility. Air circuit breakers/MCB/MCCB of suitable rating for
auto/manual operation. Auto/manual switch. Emergency stop
push buttons. Manual start push button. frequency meter.
Engine hour meter. Two earthing studs.
3) Protection module: The engine shutdown in the unlikely
event of Low lube oil pressure High cylinder head temperature.
V belt failure.
4) Indicators with alarm Load on generator.
5) Indicators Load on mains Engine fails to start . Emergency
stop battery charger.
The AMF Panel of following capacity
(C) AMF Control Panel for100 KVA/125 KVA3 phase DG Set Rupees One Lakh TwentyOne
1 121201.01 Thousand Two Hundred One Ea.
Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured
cable multistrand Aluminium conductor for 1.1 KV. to be laid
on wall with necessary clamps or in existing trench / pipe of
following size of cables
Rupees Five Hundred Fourty
17 (F) 3 1/2 core 120 Sq. mm ( 70 Sq. mm 1/2 core)
Paise ThirtyFive Only
Solder less crimping type Aluminium lugs conforming to IS
suitable for cable of following size evenly crimped with high
pressure tool & connected to switchgear terminals with
brass/cadmium plated nut bolts in an approved manner.
Rupees FourtyFive Paise
FourtyFive Only
I/We am/are willing to carry out the work at …………………………………………………………………% above/below percent (shouldbe written in figured and
words) of the estimated rates mentioned above. Amount of my/our tender works out as under.
Estimated amount Estimated amount
Put to tender Rs……………. Put to tender Rs…………….
Deduct : ……. % Above RS…………… Deduct : ……. % Below RS……………
Net Rs…………… Net Rs……………
*(Please strike out whitchever is not applicable).
Note 1 – All work shall be carried out as per public works department handbook and other specification of Division ot as directed.
Note 2 – All the columns is schedule should be filled in ink and the total of the entries in the last column should be struck by the contractor under his
Note 3 – Rates quoted include clearance of site (prior commencement of work and at its close ) in all respects and hold good for work under all
conditions, site, moisture,weather etc.
Note 4 – To be continued on additional sheets, if found necessary.
Note 5 - The rates quoted by the Contractor must be inclusive of all taxes prevailing on due date of bid submission except GST. However, any subsequent
changes in the tax structure by Government after due date of bid submission will be compensated (+/-) on availability or submission of actual
documentation. Contractor will have to intimate Engineer regarding changes occurred in the tax structure after bid submission. If the contractor fails to
provide such information and if any financial obligation may arise due to change in tax structure, same will be recovered from the contractor. GST will be
paid separately on the bills. Hence, it is the responsibility of the contractor to pay the GST to the concerned Authority.
Deputy Executive Engineer Executive Engineer
Electrical Sub Division Ukai Division No
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
Nivida No.31 of 2025-26.pdf
2.0 Special condion Electric (5).pdf
5.0 Approved make list 2013 2014 Part 1.pdf
6.0 Approved make list 2013 2014 Part 2.pdf
FINAL _ SBD New DG Set at HR.pdf
Schedule B New DG Set.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .