Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹43.8 LAccepted-AOC UPPER SARTHI VIHAR AJABPUR KALAN PO NEHRUGRAM HARIDWAR ROAD DEHRADUN 248001 UK | DEHRADUN | UTTARAKHAND | 248001 | L1 | Accepted-AOC Accepted - AOC | |
| 2 | L2₹45.4 L+₹1.7 L (3.78%)Rejected-AOC 4578 STREET 15 15A AGGARWAL ROAD DARYAGANJ CENTRAL DELHI DELHI 110002 UDYAM DL 01 0031798 | CENTRAL DELHI | DELHI | 110002 | L2 | Rejected-AOC Rejected - AOC | |
| 3 | L3₹46.1 L+₹2.4 L (5.39%)Rejected-AOC 9 NAROTTAM KUNJ MADHU NAGAR AGRA CANTT 282001 | AGRA | UTTAR PRADESH | 282001 | L3 | Rejected-AOC Rejected - AOC |
Tender Value
₹49 L
EMD Value
₹98,000
Closing Date
30 Jun 2020, 6:00 pmClosed
GE DEHRADUN
GE DEHRADUN, MALL ROAD, GARHI CANTT
Repair and maint of transformer/UG cable and connected work at Garhi Cantt under GE Dehradun
2020_MES_339806_2
8194/A/E8
Open Tender
Civil Works
Item Rate
240 days
GE DEHRADUN
Class D Cat b(i)
8 documents required · 8 mandatory
₹500
Yes
GE DEHRADUN
₹98,000
Yes
9 Sept 2020
15 Jun 2020
2 Jul 2020
15 Jun 2020
30 Jun 2020
18 Jun 2020
Amount
Disconnecting all electrical connections of transformers upto 250 KVA, dismounting from structure, draining out oil in barrels, transporting the tranformer and barrels to the workshop for necessary repairs, transporting back to the site, reinstalling on platform or structure (four/two pole) as directed, commissioning & testing including making all arrangments (cranes, truck etc.) for lifting and transportation complete. Note: Item rate incl necessary transport, tools & plant and labour, lugs thimbles, PVC sleeves, etc required for shifting, installation, connection and commissioning of transformer.
All as per item 1 but transformer of capacity above 300 KVA but upto 500 KVA.
Dismantling and opening up for repair transformer up to 250 KVA, removing & lifting up top plate of transformer, taking out burnt oil seal, stud, nut, bolt, HT bushing, off load tap changer, butcholz relay, gate valve, dead plug etc. taking out of the compete core and winding, cleaning the tank thoroughly, carrying out necessary repairs for minor leakages (if any), refixing core in it's position after repairs, reassemling the complete transformer, tanking up oil collected in barrels and toping up extra oil (if required), dehydration of oil and testing of transformer complete. (Notes : 1. Repair/replacement of core and winding, new oil and other accessories shall be measured and paid for separately. 2. Minor parts such as nut, bolts, lugs, copper wire/strips for connections etc. are included in the rates quoted for this item.)
All as per item 3 but transformer of capacity above 300 KVA but up to 500 KVA.
M&L for repairs to unserviceable transformer core, rewinding with fresh copper wire or strip including insulation paper, bobins etc, drying up in the hot air oven till the moisture is removed & insulation resistance improves to the desired level complete for the following size transformers:-
(b) 300 KVA to 350 KVA
(c) 200 to 250 KVA
(d) 100 KVA to160 KVA
M&L for repairs to unserviceable transformer core, rewinding with fresh aluminium wire or strip including insulation paper, bobins etc, drying up in the hot air oven till the moisture is removed & insulation resistance improves to the desired level complete for the following size transformers:-
Note for item No 5&6:- (i) Repairs shall be got done from the workshop authorised by UPCL for repairs of such capacity transformers having complete facility for such repairs and testing. (ii) Necessary routine tests as per IS shall be done at workshop and after installation and certificate shall be submitted before commissioning of transformer. (iii) After repairs and conducting necessary tests, test certificate shall be submitted before commissioning of transformer. (iv) Old winding shall be removed and cut in the presence of Engr-in-Charge. (v) New winding shall be of the same specifications as existing winding. (vi) Any defect observed during defect liablity period shall be rectified by the contractor without any extra cost. (vii) Make of the transformers shall be accessed from the site/Engr-in-Charge.
M & L for painting with two coats of enamel paint of approved colour over a coat of red oxide metal primer after scrapping thoroughly the existing corroded paint, dirt/dust, oil and grease from the steel surface of the for the following size transformers complete. Make: DUCO of ICI or any other equivalent make and brand.
(a) Transformer upto 100 KVA (11/0.433 KV)
(b) Transformer above 100 KVA but upto 200 KVA (11/0433KV)
(c) Transformer above 200 KVA but upto 500 KVA (11/0433KV)
Supply and fix transformer off load tap changer suitable for 400 to 500 KVA transformers 11 KV/433 volts minimum five steps type including removing the existing u/s one complete all as specified.
All as per Item No 8 here and above but below 400 KVA
Supply & for topping up the new transformer oil or in replacement in transformers and voltage stabilizers in situ complete all as specified and directed. Note:- (i) Oil shall be in company sealed barrels with BDv not less than 40 KV at 2.5 mm gap. Make: Savita/Power oil/Castrol/Apar
S&F silica gel dark blue type laboratory grade in the transformer including removing the old one complete all as specified.
Filtration/dehyderartion of the existing transformer oil at site in transformers and voltage stabilizers of any make and capacity, upto required dielectric strength as per IE rules complete.(The diectric strength should not be less than 50 KV after filtration process) (ii) Topping up of transformer oil as well as dehyderation shall be done on same day.
Supply and fix in replacement of alluminium body silica gel breathers of standard size suitable for 400 to 500 KVA transformers 11 KV/433 volts transparent type including removing the existing u/s one complete all as specified.
All as per item No 13 here and above but for tranformers below 400 KVA.
Supply and fix in replacement transformer oil temperature gauge of standard size suitable for 100 to 500 KVA transformers 11 KV/433 volts analogue type including removing the existing u/s one complete all as specified.
Supply and fixing in replacement of HT bushing with brass studs 11 KV incl gasket nut bolts washers etc complete suitable for any type or any size of transformer incl removing the existing u/s one complete all as specified.
Supply and fixing in replacement of brass LT studs incl gasket nut bolts insulator washer etc complete suitable for transformer of cap upto 200 KVA incl removing the existing u/s one complete all as specified.
All as per Item No 17 here and above but of cap from 250 to 500 KVA
Disconnecting all electrical connections of transformers outdoor type upto 200 KVA HT 11KV/433 V 3 phase, 50Hz with off load tapping and standard fitting , dismounting from platform or structure (four/two pole) as directed, shifting to proposed site (within jurisdiction of GE Dehradun), reinstalling on platform or structure (four/two pole) as directed, connecting up, testing with proper load balancing as per engineering practice, confirming to IS 2026 including connected panel all as directed including making all arrangments (cranes, truck etc.) for lifting and transportation complete. Note: Item rate incl necessary transport, tools & plant and labour lugs thimble PVC sleeves etc required for shifting, installation, connection and commissioning of transformer.
All as per item No 19 here and above but 250 to 500 KVA
M&L for repair to servo stabilizer 25 KV incl transportation of stabilizer to workshop and dismantling of all parts incl taking out of coil assembly, repair to winding and baking for removal of moisture, replacement of oil seal, stud, nut, bolt, repair to servo motor, replacement to faulty cards etc and making all necessary wiring and minor repair for automatic operation of servo stabilizer complete incl fixing of repaired servo stabilizer to MH Dehradun complete incl all necessary connections complete all as directed by Engr in Charge. (Windings, dehydration of oil, new oil and other accessories shall be measured and paid for separately)
Notes :- (i) Repairs shall be got done from the workshop authorised by UPCL for repairs of such capacity stabilizers having complete facility for such repairs and testing. (ii) Necessary routine tests as per IS shall be done at workshop and after installation and certificate shall be submitted before commissioning. (iii) After repairs and conducting necessary tests, test certificate shall be submitted. (iv) Old winding shall be removed and cut in the presence of Engr-in-Charge. (v) New winding shall be of the same specifications as existing winding. (vi) Any defect observed during defect liablity period shall be rectified by the contractor without any extra cost. (vii) Make of the stabilizer shall be accessed from the site/Engr-in-Charge.
S&F in replacement switch air break gang operated triple pole out door type with drop out switch fuse unit on HT 11 KV 50 cycle AC suitable for current rating upto 200 Amps mechanically operated mounted on insulators (12 insulators, cast resin) and frame with operating mechanism workable from ground level including locking arrangement complete all as directed Make :- Elpro/Pactil/Alstom/MEI/ATLAS
S&F in replacement horn gap type fuses 11KV mounted on post insulators with gun metal clamps and copper horn complete of required capacity to suit load at site including two coats of aluminium paint over a coat of red oxide primer on MS work complete all as specified and directed. Make :- Elpro/Pactil/Alstom/MEI/ATLAS
Disconnecting all electrical connections of LT panel , dismounting from foundation, shifting to proposed site (within jurisdiction of GE Dehradun), reinstalling on foundation as directed, connecting up with power transformer and outgoing/incoming feeders, testing with proper load balancing as per engineering practice confirming to IS, including making all arrangments (cranes, truck etc.) for lifting and transportation complete all as directed Engr in charge. Note: Item rate incl necessary transport, tools & plant, labour, LT connection cables , earthwork and PCC for foundation etc required for shifting, installation and commissioning complete.
S&F of Cable route indicator showing "MES HT U/G cable 11 KV" or "MES LT U/G cable" and route of cable with arrow made of CI in suitable eliptical shape and fixed with MS rod 12mm dia, 70 cm long (all words embosed) and fixed in position, complete all as specified.
M & L for under ground XLPE insulated, screened, PVC bedded galvanized steel strip or wire armored, electric power cable (heavy duty) with aluminium conductor, 11000 volts (earthed) grade copper sheet wrapped cross sectional area 185 sqmm 3 core including taking out/down of old unservicable cable all as directed. Make:- Havell/Finolex/KEI/Polycab/Grandlay
All as per item No 26 here and above but 150 Sqmm 3 core
All as per item No 26 here and above but 120 Sqmm 3 core
All as per item No 26 here and above but 95 Sqmm 3 core
M & L for cable end jointing kit for 11 KV (earthed) grade cable for outdoor termination cold shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of 240 to 300 sqmm including testing after jointing complete all as specified & directed Make: Havells/Raychem/3M Birla/Denson
All as per item No 30 here and above but 120 to 185 Sqmm 3 core
All as per item No 30 here and above but 95 Sqmm 3 core
M & L for cable end jointing kit for 1.1 KV grade cable for outdoor termination heat shrinkable type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of 240/300 sqmm including testing after jointing complete all as specified & directed Make: Havells/Raychem/3M Birla/Denson
All as per item No 33 here and above but 120 to 185 Sqmm 3.5 core
All as per item No 33 here and above but 50/70/95 Sqmm 3.5 core
M&L for trolly for transformer having four rubber tyres (Make: JK / CEAT / BKT) and rim of size 700x16mm and two load spring mounted axial, rear fixed type and front moveable with towing handle made of 75mm medium channel & hook attached with chasis. The chasis shall be made out of min 125 mm medium channel and plateform of size 3658 mmx1829 mm of 6 mm thick chequered sheets and cross members of suitable size channel. Load spring should be able to carry load of 500 KVA transformer complete. The trolley shall be fenced all around with 900 mm height 1.4 mm dia wire mesh of size 25mm welded or fixed with nut bolts and washer with the angle iron frame of size 25x25mm complete incl painted in signal red colour two coats over one coat of red oxide primer including dismatnling of existing trolly complete.
S&F in replacement CT 11 KV single phase, cast resin self cooled type having CT ratio 300/150/5+5A with copper double wound dual ratio to be fitted in existing VCB panel including taking down old unserviceable CT complete as per IS 2705 accuracy class-I burden 15 VA separate core for metering & separate core for protection duly calibrated according to load and testing all as specified and directed. Make: ABB/Pragati/ Kappa/AE/Simens/Schneider
S&F in replacement 3 phase Vacuum Circuit Breaker (VCB trolley) switchgear, motorized as well as manually charged, fully interlocked, horizontal draw out, rated Voltage 12 KV, rated current 800 Amps, insulation level 28 KV/75kVpk, short circuit current rating 26.3 KA for 3 sec, opening and closing coil voltage 30 Volts DC and spring charging motor 150 watts 230 Volts, 50 Hz and testing complete one to one replacement . Make: ABB VD4 Sr No 17127 or equalent in Crompton/Schneider
S&F in replacement 3 phase Vacuum Circuit Breaker (VCB trolley) switchgear, motorized as well as manually charged, fully interlocked, horizontal draw out, rated Voltage 12 KV, rated current 800 Amps, insulation level 28 KV/75kVpk, short circuit current rating 26.3 KA for 3 sec, opening and closing coil voltage 110 Volts DC and spring charging motor 150 watts 230 Volts, 50 Hz and testing complete one to one replacement. Make : ABB VInd or equalent in Crompton/Schneider
Material and labour for earthing complete with galvanized steel plate electrodes of size 600mm x 600mm x 6mm thick buried directly in ground with earth pit not less than 2.25m deep below normal ground level with top edge of plate not less than 1.5 m below normal ground level connected to galvanized strip of 32x6 mm earth lead by means of nuts bolts check nuts GI washers earth wire protected by galvanized iron pipe 40 mm bore (light grade) including concrete pit in PCC (1:3:6) type CI, precast RCC cover slab of size 30x30x10 cm with one handle for lifting made out of 8 mm dia MS bar funnel wire mesh 20 mm bore galvanized iron pipe (medium grade) for watering charcoal or coke and salt in alternate layers necessary earth work in soft/loose soil complete all as shown in electrical plate No 5 of SSr part 1 including testing on completion all as specified and directed. incl demolition to existing one complete. NOTE 1. The unit rate includes for protection pipe 40 mm dia and GI strip 32x6 mm dia from top of earth plate up to 7.5 meter above ground level.
Excavation in trenches not exceeding 1.5m wide and not exc. 1.5m depth and getting out in hard/dense soil complete all as specified and as directed.
Removing of excavated soil to a distance n exc 50 mtr and deposited where directed at a level not exc 1.5 mtr above the starting point complete all as specified and directed.
Returning, filling, including spreading, leveling, watering and well ramming in layers not exc. 25cmin soft/loose soil complete all as specified and as directed.
Supply and lay for dry river sand filling for cable protection with a layer of 8cm deep before laying and 15cm covering above the top edge of cable after laying complete all as specified and as directed. (Note : Punned thickness shall be measured).
M&L sub class B bricks locally available of size 25 x 12.5 x 7.5 cm laid dry width wise across the line of cable in trenches for protection of UG cable complete.
M&L PCC (1:3:6) type C2 using 40mm graded aggregate as in foundation for stay set /Pole/ FPB etc including fair finish even and fair to exposed surfaces without using extra cement complete all as specified and as directed.
M & L PCC (1:3:6) type C-1 (with using 20 mm graded stone aggregate) as coping of pole including necessary form work as required complete as directed
M&L 80 mm bore steel for tubing light grade ISI marked for protection of cable including necessary joint complete all as specified and as directed. (Make TATA/JINDAL/swastik/BST).
Excavation over area n. exc 1.5 m deep and getting out in soft/loose soil incl dressing up soil etc for laying of gravel in sub stn or switch yard complete all as specified and directed.
Surface excavation not exceeding 15 cm deep incl dressing up soil etc for laying of gravel in sub stn or switch yard complete all as specified and directed.
M&L PCC (1:3:6) type C2 using 40mm graded aggregate as in foundation of transformer plinth, paver blocks etc complete all as specified and as directed.
M& L for 150 mm thick graded gravel 20 mm packed in 33 or 11KV outdoor sub stn yard all as specified 10 cm deep complete all as directed at site by Engr in charge.
M&L for laying of machine pressed precast conctete interlocking paver block any shape and size confirming to IS 15658-2006 of 60 mm thickness, M-35 Grade with grey cement and without pigment joints filled with sand over and including 25mm thick sand filling complete
M&L for chequered cement concrete tiles 20cm x20cm x 25mm thick, set, jointed and pointed in neat pigmented cement slurry in floors incl taking old existing complete
Brick work for construction of platform with steps for transformer with sub class 'B' brick straight or curved on plan exc 6 mm radius built in CM 1:4 complete all as specified
M&L rendering 15mm thick in CM (1:4) on fair faces of brick or concrete surface finished even & smooth without using extra cement and steel trowel all as specified
M&L for filling of red bajri or moorum in floor or in foundations spread levelling and ramming incl watering complete all as directed by Engr in charge.
M&L for RCC work (Nominal Mix) type B1 20 mm grade stone aggregate for slab supported on walls incl form work required for the same complete all as specified and directed by Engr in charge.
M & L for TMT bars of 10 mm dia and over for RCC work incl cut to shape in suitable length, binding with mild steel wires complete all as specified.
S&F framed work as in doors or gates or frames for cage fencing to transformer of angle or other section with gusset plates rails braces etc complete drilled for fixing of wire mesh, steel sheet or other covering doors etc to be prepared for hanging or sliding with and including either hooks and hinges or steel hanging door fittings also fastening, painting with non corrosive bituminious paint and fixing with transformer plinth with the help of fastner or grouting of T bolts of required size including dismantling existing rusted cage complete.
Supply and fixing of GI wire mesh (mesh size 25x25 mm) dia of wire 1.4mm complete welded or fixed with nut bolts and washer with the angle iron frame of size 25x25mm in section of max 800x1250 mm or as required at site for fencing to transformer to be fixed with plinth including dismantling of rusted wire fence complete all as directed by Engr in charge.
Dismantling fencing wire mesh, any type complete all as specified
Dismantling RCC posts or struts any section, including taking out embedded portion and making good disturbed ground complete all as specified
Excavating in post holes (or similar holes) each n exc 0.5 cum, getting out and removing surplus soil to a distance n exc 50m complete all as specified
S&F mild steel work such as in angle iron for posts, horns including flat iron fillets, nut, bolts,10mm dia MS bars as in tie bars fixed to fencing posts for fixing of barbed wire, securing wire mesh etc. including necessary cuttings, drilling, bolting or riveting etc as per site requirement and other similar works complete mild steel, conforming to Fe-290 Gde E-165
Supply only chain link fencing made of 4mm dia mild steel galvanised wire and 100x100 mm mesh complete all as specified.
Fixing only chain link fencing including line wires, any mesh, size and type to any type of standards, rails, straining bolts, etc. including provision of binding wire complete all as specified.
Supply and fixing of powder coated or GI perforated type cable trays of size 100 mm wide x 50mm x 1.6 mm thick with all the tray accessories fixed to wall or iron gantry including supports, bends, anchor fasteners, GI hardware etc.
Demolition of brick work masonry, built in cement mortar and pre-cast concrete articles complete all as specified and as directed
M/s Kamal Traders
M/s SCHOLASTIC ENTERPRISES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .