Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹11.5 LAccepted-AOC NO 3 WD BUILDING JP AGARWALLA ROAD BHARALUMUKH KAMRUP ASSAM 781009 UDYAM AS 03 0009483 | KAMRUP METRO | ASSAM | 781009 | L1 | Accepted-AOC Lowest Bidder | |
| 2 | L2₹13.7 L+₹1.9 L (16.3%)Rejected-AOC WZ 409 0 B 1ST FLOOR PLOT NO 12 JANAK PARK HARI NAGAR NEW DELHI 110064 | NEW DELHI | WEST DELHI | DELHI | 110064 | L2 | Rejected-AOC Become L2 | |
| 3 | L3₹13.8 L+₹2.0 L (17.3%)Rejected-AOC CHANDMARI WARD NO 19 PO PS TEZPUR DIST SONITPUR ASSAM | SONITPUR | ASSAM | 784001 | L3 | Rejected-AOC Become L3 | |
| 4 | L4₹14.3 L+₹2.5 L (21.5%)Rejected-AOC | L4 | Rejected-AOC Become L4 |
Tender Value
₹15 L
EMD Value
₹30,000
Closing Date
24 Mar 2020, 6:00 pmClosed
GE SOUTH TEZPUR
GE SOUTH TEZPUR MISSION CHARALI
Repair/maintenance of earthing PIT, Panel, ACB Capacitor Bank and allied works at SAA under GE (S) Tezpur
2020_MES_328524_1
8484
Open Tender
Civil Works
Item Rate
180 days
GE SOUTH TEZPUR
As per NIT
4 documents required · 4 mandatory
₹500
Yes
GE SOUTH TEZPUR
₹30,000
Yes
23 May 2020
25 Feb 2020
26 Mar 2020
25 Feb 2020
24 Mar 2020
10 Mar 2020
Amount
M & L Earthing complete with GI earth plate electrode 60cm X60cm X 6 mm thick buried directly in ground (earth pit not less than 2.25 mtrs deep below ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, connecting to galvanized earth strip 32 x 6 mm as earthing conductor by means of bolts, nuts, check nuts and washers of GI and all as shown in Electrical plate No.5 of SSR Part I and including testing on completion all as specified locations and as directed. Note: 1.The above quoted rate shall include cost of main earthing lead of 32 x 6mm GI earth strip, charcoal, salt, excavation and earth work in any type of soil CI cover, funnel with 20mm dia light grade GI water pipe including GI protection pipe 40mm dia light grade for earth strip etc. 2. The cost of earth pit is deemed to be included in the unit rate. 3. The cost of taking down old unsv earthing with all its accessories is deemed to be included in the unit price.
Decarbonising/ cleaning of Existing LT panel cubical type of various sizes consists of bus bar and circuit chamber, metering chambers CTs and relays chambers, checking the bus bar joints, bus bar and circuit spouts, cleaning and applying Anti - Track Busbar Insulation Tape to the bus bars, checking the current transformer, applying Monoplast compound at the bus bar joints after tightening of joints ,replaced new suiable size of lugs /suitable copper control cable and reassembling , if any rusted sheet replced with new sheet as per existing size complete all as directed. Note:- Cost of lubricant/ cleaning agents (CRC & rust remover) / hardware like springs/ bolts/ nuts/ washers,lugs/ suitable copper cables cost of labour, T&P required for replacement shall be etc. shall be deemed to be included in the rate quoted.
Repair/overhauling of LT air circuit breaker of any size and make and capacity and replacement of minor items like springs, washers, bolts and nuts and other insulating materials including calibration and testing of control and protection devices of equipments in the following steps: (i) Disconnect and taking out the breaker after taking power shut down of the respective panel and check for defects and painting one coat of synthetic enamel paint in inner campartment of panel. (ii) Overhauling/ servicing the ACB by opening all parts and lubricating with petrolium jelly and moving parts with grease etc as per the requirement. (iii) Re-assemble the ACB complete and install to its original position and test and commission the breaker for both tripping mechanism and closing mechanism for proper functioning of the breaker all as specified and as directed. Note:- Cost of lubricant/ cleaning agents (CRC & rust remover) / hardware like springs/ bolts/ nuts/ washers,cost of labour, T&P required for replacement shall be etc. shall be deemed to be included in the rate quoted.
S & F LED indicating Lamps for R, Y, B phases complete including taking down ols U/S lamp as specified and directed.
Supply and Fix Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with MS clamps, bolts and nuts of approved size, for 25x15cm size complete all as specified and directed.
S & F CPRI approved Automatic Power Factor Correction (APFC) Panel indoor type by OEM for 3 Phase, 415 V & 50 Hz system of capacity 60 KVAR with incoming MCCBs including Ammeter, voltmeter, phase indication lamps, PF Meter, necessary contactors, CT, Push button On/Off, Auto/Manual Operation including taking down old unserviceable APFC panel including all its accessories complete all as specified and directed. The following are the items are to be included. Note for Item No 8 & 9 :- The cost of disconnection of existing cable and re-connecting with new panel is deemed to be included in the unit price.
S & F CPRI approved Automatic Power Factor Correction (APFC) Panel indoor type by OEM for 3 Phase, 415 V & 50 Hz system of capacity 80 KVAR with incoming MCCBs including Ammeter, voltmeter, phase indication lamps, PF Meter, necessary contactors, CT, Push button On/Off, Auto/Manual Operation including taking down old unserviceable APFC panel including all its accessories complete all as specified and directed. The following are the items are to be included. Note for Item No 8 & 9 :- The cost of disconnection of existing cable and re-connecting with new panel is deemed to be included in the unit price.
Supply and fix MCCB 4 pole, microprocessor based Release range 100 Amps to 250 Amps, 415V,AC,50Hz ,50 KA Manual versions With Conforms to IS/IEC 60947-2,Ics=100% Icu,Suitable for Isolation Adjustable Over Load setting: 0.4 - 1.0 x In ,Adjustable Short Circuit setting: 1.5 - 10 x Ir , ,Wide Range of snap fit Internal and External Accessories including Taking down MCCB all as specified and directed.
Supply and fix MCCB 4 pole, thermal magnetic based Release range 20 Amps to 100 Amps, 415V, AC,50Hz ,36 KA Manual versions With Conforms to IS/IEC 60947-2,Ics=100% Icu,Suitable for Isolation Adjustable Over Load setting: 0.4 - 1.0 x In ,Adjustable Short Circuit setting: 1.5 - 10 x Ir , ,Wide Range of snap fit Internal and External Accessories including Taking down MCCB all as specified and directed.
Supply & Fix Aluminium Lugs of various sizes (16 sqmm - 400 sqmm ) as per site requirement including taking down old unserviceable lugs complete all as specified and directed.
Supply and laying, testing and commisioning 7 core 1.5sqmm PVC insulated , FR PVC round sheathed copper flexible 1100 Volt grade confirming to IS 694 for connection of AHU units from control panel complete all as specified and directed.
Material and labour for removing/scraping the paint of FPB / LT Panel by applying one coat of synthetic enamel paint all as specified and directed.
Material and labour for removing/scraping the paint of street light panel applying one coat of synthetic enamel paint complete all as specified and directed.
Material and labour for removing/scraping the paint of centrifugal Pump set of any capacity by applying one coat of synthetic enamel paint all as specified and directed.
Supply and fix SMPS based battery charger with output of 12V, Voltage step down (230/12 v), current Max 10A and automatic tickle & boost charging of charging voltage 13.6 V - 14.3V, with over and under Voltage protection, Input voltage variation range 170-260V, with charging indication of power ON, Battery Charging and Battery Full including removal of existing unserviceable one complete all as specified and as directed.
S & F battery including taking down old unserviceable low maintenance Lead Acid type of capacity 12 volts 150 AH including removal of existing unserviceable one and keeping it in self custody which becomes contractors property after the schedule of credit recovery complete all as specified and as directed.
M & L testing of Earth resistance at earthing various location using Earth tester complete all as specified. Note - The cost of usage of the testing apparatus is deemed to be included in the unit rate. The conntractor shall submit the test report in a prescribed format as suggested by Engr in charge.
Supply & Fix capacitor gas filled heavy duty cylindrical of 5 to 15 KVAr, 440V including taking down old unsv capacitors complete all as specified and directed.
Supply & Fix capacitor gas filled heavy duty cylindrical of 20KVAr, 440V including taking down old unsv capacitors complete all as specified and directed.
Supply & Fix, in repairs Galvanised iron strip 32 x 6mm buried in ground or fixed to Roof, Walls by using appropriate insulating Boxes with screws complete all as specified and directed.
Supply and fix MCCB 4 pole, microprocessor based Release range 160 Amps to 400 Amps, 415V,AC,50Hz ,50 KA Manual versions With Conforms to IS/IEC 60947-2,Ics=100% Icu,Suitable for Isolation Adjustable Over Load setting: 0.4 - 1.0 x In ,Adjustable Short Circuit setting: 1.5 - 10 x Ir , ,Wide Range of snap fit Internal and External Accessories including Taking down MCCB all as specified and directed.
Supply & Fix, in repairs Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex. head screw complete all as specified and directed
Flint India
MAHANTA ENTERPRISES
Shree Krishna Traders
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .