Tender for Attend the cable fault at site FROM RECIVING the message from CONCERN S/DN AND LOCATING THE FAULT UNDERGROUND CABLE and Rectify the fault (XLPE cable will be supplied by DGVCL) with cable end termination and straight through joints kits (to be supplied by contractor) as per norms under all scheme for the year 2024-2025 for Kadodara-1 ,Kadodara Ind & Palsana Sub division under Kadodara Division.
286282
KAD/O&M/EXP/N-Procure/2026/03/No.222 date. 07-03-2026 SR. NO.03
Open
Electrical
Works
Surat
3 documents required · 3 mandatory
₹1,180
DAKSHIN GUJARAT VIJ COMPANY LTD.
₹40,000
13 Mar 2026
13 Mar 2026
13 Mar 2026
24 Mar 2026
13 Mar 2026
(Name of Work:- ARC work of Attend the cable fault at site within 03 HRS FROM RECIVING the message from D.E/JE OF
CONCERN S/DN AND LOCATING THE FAULT UNDERGROUND CABLE
Sr. Item Code Total
Description Unit Rate Amount
Labour charge for excavation of cable trench of 400mm width Meter
x 1200mm depth, in any type of soil for laying of cable of size
up to 240 mm2 (For additional cable 200 mm additional width
shall be considered i.e. half trench length is to be considered
Labour charge for excavation of cable trench of 600mm width Meter
x 1200mm depth, in any type of soil for laying of cable of size
up to 240 mm2 (For additional cable 200 mm additional width
shall be considered i.e. half trench length is to be considered
Labour charge for excavation of cable trench of 400mm width Meter
x 1500mm depth, in any type of soil for laying of cable of size
up to 240 mm2 (For additional cable 200 mm additional width
shall be considered i.e. half trench leng th is to be considered
Labour charge for laying of 11kV / 22 kV XLPE Cable of size up Meter
to 240 mm2 & preparation of sand layer 100mm thick, in the
cable trench & covering the cable with 150 mm dia (Outer),
thickness 25 mm, 1.0 meter long RCC half round muffs and
providing and fixing of 4inch width yellow colour polyethylene
4 9925000004 tape with printing"CAUTION ELECTRIC CABLE BELOW' at
m depth from ground
surface after laying cable in trench. This will provide indication
that electric cable is passing underground so as to protect
cable from mechanical injuries, refilling the same, as per
Instruction of E gineer in Charge (EIC) .
Providing & fixing concrete stone route marker of 300 mm No
width x 150 mm thick x 650 mm height embedded in earth at
least 300 mm below & 350 mm above ground level
respectively at distance approx. 50 meters along the length of
cable. The RCC concreting (1:2:4)(all necessary materials will
5 9925000009 be in bidder's scope) of route marker is to be carried out
mm width x 150 mm thick x 300 mm below ground level as per
instruction of EIC. The route marker should be with name of
company with approved yellow colour-DGVCL. The distance
from marker to cable and cable depth with feeder name etc.,
marked with arrow sign is to be painted on it. The route
marker is to be fixed at location near to any fixed permanent
location (not necessary to fix exact on top of cable) as per
Labour charge for erecting of 11kV / 22 kV XLPE cable of size perJob
up to 240 mm 2 on DP Structure with fixing of 02 Nos polymer
cleats on top and middle part. Polymer cleats, nut bolts etc.
fixing material to be provided by contractor.
Providing & fixing of 6.11kg/cm2 , class4,Green color, perJob
110mm O.D. 8.5mm thickness H.D.P.E. pipe confirms to IS
4984 and BIS certification on the erected DP structure for the
mechanical protection of cable by inserting the cable inside
7 9925000015 HDPE pipe. The HDPE pipe shall be erected in such a way that
300mm shall be below the ground level and the rest 2700 mm
shall be supported on the DP Structure with 01 No Polymer
cleat. All materials including polymer cleat and Nut bolt to be
provided by contractor.
Providing and fixing of pipe type earthing from 80 mm dia No
class-B GI pipe with pit to be filled with salt & coke and
construction of chamber as per DGVCL Drg. No. dg /100 for DP
and cable. The earthing pit should be joined with cable by G.I.
strip of size 1" width & 2 mm thick. All material GI pipe, Coke
Salt etc will be supplied by bidder.
Supply & fixing of heat shrink type end terminations (outdoor) No
9 9925000017 for up to 11kV 3C x 185 mm2 size XLPE cable as per DGVCL
technical s ecification
Supply & fixing of heat & shrinkable end terminations No
10 9925000018 (outdoor) for up to 22 kV 3C x 185 mm 2 size XLPE cable
( as per DGVCL technical specification)
Supply & fixing of heat shrinkable type end terminations No
11 9925000019 (indoor) for up to 11kV 3C x 185 mm 2 size XLPE cable as per
DGVCL technical specification
Supply & fixing of heat & shrinkable end terminations (indoor) No
12 9925000020 for up to 22 kV 3C x 185 mm 2 size XLPE cable as per DGVCL
technical specification
Supply & fixing of heat shrinkable straight through joint for up No
13 9925000021 to 11kV 3C x 185 mm 2 size XLPE cables as per
DGVCL technical specification.
Supply & fixing of heat shrinkable straight through joint type No
14 9925000022 for up to 22kV 3C x 185 mm 2 size XLPE cable as per DGVCL
technical specification
Labour charge for excavation of 2100mm long x 1200mm wide No
x 1200 mm deep joint pits for installation of 11kV / 22kV
Straight through joints as per instruction of engineerin-charge
& covering the cable with 150 mm dia (Outer), thickness
mm, 1.0 meter long RCC half round muffs & refilling same as
per instruction of EIC .
Testing of cable at various points and commissioning the No
16 9925000025 feeder as per instruction of engineer-in-charge.Test result shall
be submitted by contractor with bill.
Preparation and submission of 6 (six) copies, of complete Set
layout drawings with GIS mapping as per actual cable routing
showing road crossing, HDPE pipe sleeving, jointing locations,
9925000047 Laying of any size of 11/ 22 KV XLPE /PILCCable in readymade per
trench or in open space cable
9925000048 To Attend the cable fault at site within 03 hrs from receiving No
19 the message from D.E of concern S/dn and locating the fault
under ground cable.
TOTAL AMOUNT :-Twenty Seven Lac Only 27,00,000/-
TOTAL AMOUNT :-Twenty Seven Lac Only 27,00,000/-
Ex. Eng. (O&M),
Kadodara Division, DGVCL.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
NOTICE.pdf
Integrity Part.pdf
Technical Specification.pdf
DRAFT TENDER CONDITION.pdf
SCHEDULE-B.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .