Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.3 CrAccepted-AOC | ₹2.3 Cr | L1 | Accepted-AOC L1 Bidder |
| 2 | L2₹2.3 Cr+₹3.8 L (1.66%)Rejected-Finance 19 LAKE TEMPLE ROAD KOLKATA 700029 | KOLKATA | WEST BENGAL | 700029 | ₹2.3 Cr+₹3.8 L (1.66%) | L2 | Rejected-Finance Higher
Quoted Rate. |
| 3 | L3₹2.4 Cr+₹11.4 L (4.98%)Rejected-Finance 11TH FLOOR ECO CENTRE BUSINESS TOWER P NO 4 EM BLOCK SECTOR V KOLKATA 91 | KOLKATA | 24 PARAGANAS NORTH | WEST BENGAL | 700091 | ₹2.4 Cr+₹11.4 L (4.98%) | L3 | Rejected-Finance Highest
Quoted Rate |
Tender Value
Refer Docs
EMD Value
₹4 L
Closing Date
27 Dec 2022, 12:00 pmClosed
SE, PWD, Kolkata Electrical Circle
P-16, India Exchange Place Extn. KIT Building, 2nd Floor, Kolkata-700073
Construction of a G plus 5 storied Academic Building for the Open Campus-cum-Regional Centre of NSOU-SITC of 260 Ton Capacity Air Cooled AC Chiller Plant(2ndcall).
2022_WBPWD_421753_1
PWD/SE/KEC/NIT-18(2nd call)/22-23
Open Tender
A/C ORG
Item Rate
90 days
Rajarhat
Please refer Tender documents.
8 documents required · 8 mandatory
₹4 L
Office of the SE, PWD, Kolkata Electrical Circle
4 Apr 2023
14 Nov 2022
29 Dec 2022
14 Nov 2022
27 Dec 2022
29 Nov 2022
24 Nov 2022
Amount
Air Cooled chiller with VFD :- Supply, Installation, Testing, & Commissioning of AHRI certified micro-processor controlled Variable speed Air Cooled Screw Chillar having actual capacity of minimum 260 TR (Actual Capacity at design condition), comprising of semi-hermetic Screw Compressors and direct driven motor, each chiller shall have minimum 2 compressors and individual refrigerant circuits, chiller shall be equipped with insulated shell and tube type flooded/ DX type cooler/evaporator, air-cooled condenser made of copper tube and aluminium fins as per OEM Standard, high efficiency condenser fans, including spring isolators mounting for chiller unit. The chiller package shall also be complete with refrigerant copper piping, factory charged R-134a refrigerant gas and Automatic feedback control system wiring, incoming suitable electrical isolator complete with accessories as required, automatic & safety controls including electronic expansion valve etc. Easch compressor must be equipped with dedicated VFD. [MCHE (Micro Chanel Heat Exchanger) will not be acceptable]
1. Minimum Cooling Capacity : 260 TR Screw - (Actual Capacity @ following Design Conditions) 2. Type of Refrigerant : R-134A 3. Chilled Water 'In' : 12 Deg C 4. Chilled Water 'Out': 7 Deg. C 5. Chiller Fouling Factor : 0.0001 (FPS) 6. The electrical panel should be IP55 protected (As per OEM Satndard) 7. Air Entering Temp. to the Condenser : 35 º C. 8. Minimum IKW/TR should be less than equal to 1.46 at design condition (Including Fan Power) 9. Minimum COP at AHRI Condition not less than 3.2 & IPLV Minm 5.00 at AHRI conditions as per ECBC Plus gudiline. 10. EVAP Pressure drop shall be as per OEM standard. (Make : Daikin / Climaveneta/ Kirloskar/ Carrier/ Bluestar/ Voltas/ Johnson Control/ Mitsubishi)
SITC of 200 mm dia Butterfly Valve (Make - Honeywell/ AUDCO/ Advance) (Installed at inlet/outlet pipe of chiller) - 2 Nos.
SITC of 200 mm dia Balancing Valve(Make-Honeywell/ AUDCO/ Advance) (Installed at inlet/outlet pipe of chiller for proper flow control) - 1 No.
SITC of Flexible Connection - 200 mm dia(Make - Cori/ Resistoflex) - 2 Nos.
SITC of 4" Dial SS Pressure Gauge complete with syphon and isolation gauge cock.(HGURU/ AWAREE) (Installed at inlet/outlet pipe of chiller for monitoring pressurel) - 2 Nos.
Supply, erection, testing & commissioning of Alcohol in glass type industrial thermometer complete with thermowell. (Make : HGURU/ AWAREE) (Installed at inlet/outlet pipe of chiller for monitoring temperature) - 2 Nos.
SITC of 25 mm NB Ball Valve For descalling and drain (Make - Honeywell/ AUDCO/ Advance) (Installed at inlet/outlet pipe of chiller for drain water & descalling). --- 2 Nos.
SITC of 15 mm NB Ball Valve For air purge valve /auto air vent(Make - Honeywell/ AUDCO/ Advance) (Installed at inlet/outlet pipe of chiller to remove air from system) - 1 No.
SITC of Water flow switch for chillers (Make - Honeywell/ ANERGY) - 1 No.
Design, Supply, Iinstallation & Testing, Commissioning of HVAC Electrical Control Panel with Microprocessor Controller - 1 No. There should be provision for Integrated Electrical distribution system for power circuit & control circuit for Compressors & water pumps, Starters, Cu. Tubing & placement of instrument like Pressure Gauge of Refregerant System, Supply of Heater for Compressor, Compressor oil, Oil Pressure Indicator, Trip arrangement for High Pressure & Low Pressure Cut Off, Anti-freezing Cut Off, Reversal of Phases & Phase failure Cut Off, Flow Switch Cut Off, Automatic Chilled Water Bypass System in case of partial load condition. Customer will provide Single Point Electrical Power Source to HVAC Panel. Bidder should design & supply the HVAC Panel including supply and laying of power & control cables as required accordingly.
CHILLED WATER PUMP Supply, erection, testing & commissioning of Chilled water duty, end suction back pull out type centrifugal pumpset at (having Bronze/CI Impeller) with TEFC, IP-55, Class F insulated Sq. cage induction motor, complete with common base frame, spring vibration isolators, coupling and coupling guard for the following duty & including items as specified below : (Make - Kirloskar/ Grundfoss/ xylem/ Armstrong/ Flowmore/ KSB) (i)Rated Flow 650 USGPM at 30 MWC head (1 W + 1 S)
200 mm dia Butterfly Valve (Make - Honeywell/ Advance/ Oswal/ Kirloskar/ L&T) (Installed at inlet & outlet of each pump)
200 mm dia Check Valve/NRV (Make - Honeywell/ Advance/ Oswal/ Kirloskar/ L&T) (Installed at Outlet of each pump)
200 mm dia Y Strainer (Make - Honeywell/Advance/ Oswal/ Kirloskar/ L&T) (Installed at Inlet of each pump to isolate the perticals from system)
4" Dial SS Pressure Gauge complete with syphon and isolation gauge cock.(Make - HGURU/ Tameson/ Equivalent) ( Installed at Inlet & Outlet of each pump to monitor pressure)
25 mm NB Ball Valve For drain (Make - Honeywell/ Advance) ( to drain out water during maintenance)
SITC of Purgeing Valve/Auto air vent with 15 mm Ball valve (Installed at each Room branch header & main headers) (Make - Anergy/ Advance/ AUDCO)
Supply, Erection, Testing & Commissioning of MS ERW Chilled Water (Supply & Return) Piping (Class C) complete with flange, Tee, bend & other necessary fittings including weilding joints & MS supports and TF quality thermocol density 24 kg/cum insulation with chicken wire mesh sand cement plaster (Pipes upto 150 NB shall be Heavy Grade as per IS: 1239 Part I and from 200 NB & above Pipes shall be as per IS: 3589 of specified thickness.) (Make-Tata/ Jindal/ SAIL) (i) 200mm NB(Insulation 75 mm thick)
Do----Do----Do (ii) 50mm NB (Insulation 50 mm thick)
Do----Do----Do (iii) 40mm NB (Insulation 50 mm thick)
Do----Do----Do (iv) 32mm NB (Insulation 50 mm thick)
Do----Do----Do (v) 20 mm NB (Insulation 50 mm thick)
Chilled water In-duct type Indoor FCU units with compact 3 Row Cu. cooling coil, multi-speed fan motor, the blower shall be dynamicaly balanced and designed for silent operation, the filters shall be washable synthetic media type arranged for convenient cleaning and replacement and inbuilt drain pump. The Unit should be equipped with Ball Valves / Stainer & Actuator as required. The unit is to be supplied with chorded remote controller. (i)3 TR (Make - Daikin/ Johnson Control/ EdgeTech/ Zeco/ VTS/ Citizen) (Allocation sheet attached)
2.5 TR (Make - Daikin/ Johnson Control/ EdgeTech/ Zeco/ VTS/ Citizen) (Allocation sheet attached)
2 TR (Make - Daikin/ Johnson Control/ EdgeTech/ Zeco/ VTS/ Citizen) (Allocation sheet attached)
1.5 TR (Make - Daikin/ Johnson Control/ EdgeTech/ Zeco/ VTS/ Citizen) (Allocation sheet attached)
Supply, erection, testing & commissioning of 1000 litre capacity PVC multi-layer expansion / cushion tank, insulated with cover of thermocol, sand, cement plaster as per chilled water piping alongwith air separator (Make - Syntex/ Patton/ Supreme), provision of make up water inlet, overflow outlet, Air release vent, etc.
Supply and Laying of Rigid PVC Drain Pipe (Medium Class)with respective fittings ,proper supports at 5 feet interval and duly insulated with 6 mm thick closed cell nitrile rubber insulation. (Make: Oriplast/ Supreme/ Filolex/ Ashirbad/ Astral) (i) 20 mm NB
(ii) 32 mm NB
(iii) 40 mm NB
Supply and fixing of Flexible double Canvas connection in between each FCU & Al. Supply Air grill mounted on Gypsum Boxing cover. (Custom Make or Asper direction of EIC)
Supply & fixing of Powder coated extruded Alluminium return air grilles (Make:- Green air/ADS/ Premier/ Systemair/ Caryaire/ Air Enterprise) without volume control dampers.
Supply & fixing of Al powder coated extruded Alluminium Supply air grilles (Make:- Green air /ADS / Premier/ Systemair/ Caryaire/ Air Enterprise) with alluminium volume control damper.
Major & minor civil works inclusive of cutting, grouting, mending good damages for fixing of iron supports and placement of chilled water pipes etc, required to execute before and after the HVAC works for mending good damages to original finish painting. (Foundation of installation of chillar, pumps, electrical panel is not within the scope of this work)
Supply & fixing of drop ceiling made of gypsum / E-board (3 mm thick) incl. Al. channel & complete with linkages, levers, fittings, supports, all accessories any other item required to make the system complete to cover the indoor units of concealed split unit incl. painting the board as per direction of EIC.
Supply, fabrication & fixing of trap door with 3 mm thick ACP board (MAKE- Aludecor/ Urobond or others reputed make) complete with inkages, levers, fitings.support all accessories for IDU maintenance ad per direction of EIC.
Shinryo Suvidha Engineers India Pvt Ltd
BLUE STAR LIMITED
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .