Loading…
Loading…
Tender Value
₹10 L
Closing Date
8 Jul 2026, 6:00 pmClosed
Executive Engineer, RANDER DIVISION
Work of emergency work for locate fault and attending the same for restore the power supply 11/22 kv 3c*185/240 sq.mm U/G cable in Adajan sub division under Rander division. If it is required, works to be carried out in other sub division of Rander Division office.
317658
RND-484 : DGVCLDRND/0520/06/2026 Approved Date: 24-06-2026
Open
Electrical - All
Surat
2 documents required · 2 mandatory
25 Jun 2026
25 Jun 2026
25 Jun 2026
8 Jul 2026
25 Jun 2026
Name of Work: Work of emergency work for locate fault and attending the same for restore the power supply 11/22 kv 3C 185/240 sq.mm U/G
cable in All Scheme for Adajan Sdn under Rander division. If it is required works to be carried out in other scheme and other sub division under
Rander Division office.
Item Code Description Unit
Labour charge for excavation of cable trench of 400mm width x 1200mm depth, in any
1 9925000001 type of soil for laying of cable of size up to 240 mm2 (For additional cable 200 mm Meter
additional width shall be considered i.e. half trench length is to be considered)
Labour charge for excavation of cable trench of 600mm width x 1200mm depth, in any
2 9925000002 type of soil for laying of cable of size up to 240 mm2 (For additional cable 200 mm Meter
additional width shall be considered i.e. half trench length is to be considered)
Labour charge for laying of 11kV / 22 kV XLPE Cable of size up to 240 mm2 &
preparation of sand layer 100mm thick, in the cable trench & covering the cable with
150 mm dia (Inner), thickness 25 mm, 1.0 meter long RCC half round muffs and
providing and fixing of 4inch width yellow colour polyethylene tape with printing
"CAUTION ELECTRIC CABLE BELOW" at 0.75 m depth from ground surface after laying
cable in trench. This will provide indication that electric cable is passing underground so
as to protect cable from mechnical injuries, refilling the same, as per Instruction of
Engineer in Charge (EIC).
Supply & fixing of heat shrink type end terminations (outdoor) for upto 11kV 3C x
mm2 size XLPE cable as per DGVCL technical specification
Supply & fixing of heat & shrinkable end terminations (outdoor) for upto 22 kV 3C x
mm2 size XLPE cable as per DGVCL technical specification)
Supply & fixing of heat shrinkable straight through joint for upto 11kV 3C x 185 mm2
size XLPE cableas per DGVCL technical specification.
Supply & fixing of heat shrinkable straight through joint type for upto 22kV 3C x
mm2 size XLPE cable as per DGVCL technical specification
Labour charge for excavation of 2100mm long x 1200mm wide x 1200 mm deep joint
pits for installation of 11kV / 22kV Straight through joints as per instruction of
engineer-in-charge & covering the cable with 150 mm dia (Outer), thickness 25 mm,
1.0 meter long RCC half round muffs & refilling same as per instruction of EIC .
Locate the fault and repair the same in 11 kv XLPE underground cable with fault locater
9 machine within the time duration of four hour after information either through SMS , Nos
Mobile Phone or personally informed to you
Testing of cable at various points and commissioning the feeder as per instruction of
engineer-in-charge.Test result shall be submitted by contractor with bill.
In Words : - Ten Lakh Only
Estimated Total (In Rs.) :
Contractor Sign & Stam
Executive Engineer (O&M)
DGVCL,Rander Division
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
1. Draft Letter tender RND-484.pdf
2. Schedule-b for FL Adajan Sub division.pdf
Download all tender documents and submit your bid