Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹28.8 LAccepted-AOC KALIAPPA COMPLEX TRICHY ROAD RANGANATHAPURAM SULUR COIMBATORE 641402 | COIMBATORE | TAMIL NADU | 641402 | ₹28.8 L Quoted ₹29.7 L | L1 | Accepted-AOC lowest bidder |
| 2 | L2₹31.2 LRejected-Finance 213 F BLOCK MEGA MARGANPATTE HADAPSAR PUNE 411013 | PUNE | MAHARASHTRA | 411013 | ₹31.2 L | L2 | Rejected-Finance unsuccessful bidder |
| Sl No | Description | Qty | Unit | SUPER COOL L1 | Crown Chemicals L2 |
|---|---|---|---|---|---|
| 1.00Repairs/Maintenance of DG Sets,street lights and solar lights at 17 FBSU,257SU Mukkunnimala and AFSC Muttathara. | |||||
| 2.00 | Comprehensive and preventive maintenance of DG set of capacity 160 KVA to ensure the generator's reliability, efficiency, and longevity of DG sets.The following key tasks typically to be performed during B & C check of DG set as per the running hours and OEM recommendation .Make of DG Set Ashok Leyland (Mukkunni Mala) /Kirloskar
(340 TRU Muttathara )
a) Check and clean fuel injectors.
b) Inspect and adjust valve clearances.
c) Examine the turbocharger for wear or damage.
d) Inspect and clean the air intake system.
e) Check the cylinder head and piston rings for wear
f) Change the fuel filter,bypass filter and oil filter
g) Change the Air filter
h) Change the water seperator
j) Radiator cleaning with chemical
k) Replace the coolent and engine oil
l) Checking all electrical wiring and replace the unserviceable electromechanical switches,pressure gauges,indicators
m) Checking the mechanical coupling between alternator shaft and prime mover to reduce the mechanical vibrations during hunting/start/stop of engine /Alternator
n) Testing of emission system and minimise the obstruction by removing and cleaning , leakage arresting in exhaust pipe and Air Filter replacement if required | 2 | Job | 8,075 ₹16,150 | 8,500 ₹17,000 |
| 3.00Note 1. All tests mentioned above are to be carriout by OEM of DG set . 2.Test certificates must be submitted by the contractor duly signed by OEM representative,Engineer in charge and contractor for claiming the RAR. 3. All the spare parts required for B & C Check of DG set will be measured and paid under the respective items of the following schedule. | |||||
| 4.00 | All as per item No 2. here in above but of capacity 125 KVA DG set Kirloskar
location- 17 FBSU Service cell | 1 | Job | 7,850 ₹7,850 | 8,000 ₹8,000 |
| 5.00 | All as per item No 2. here in above but of 100 KVA capacity DG Set Kirloskar Location :- 17 FBSU computer cell | 1 | Job | 7,100 ₹7,100 | 7,500 ₹7,500 |
| 6.00 | All as per item No 2. here in above but of capacity 62.5 KVA capacity DG set Kirloskar Location:-Tarmac Area (Shanghumugham) | 1 | Job | 5,200 ₹5,200 | 5,500 ₹5,500 |
| 7.00 | All as per item No 2. here in above but of capacity 30 KVA capacity DG set kirloskar Location:-257 SU - D/Area Pump House /17 FBSU Offrs Mess | 2 | Job | 3,300 ₹6,600 | 3,500 ₹7,000 |
| 8.00 | All as per item No 2. here in above but of capacity 25 KVA DG set kirloskar Location:-17 FBSU MAP PH/OTM Accn PH | 2 | Job | 2,800 ₹5,600 | 3,000 ₹6,000 |
| 9.00 | All as per item No 2. here in above but of capacity 7.5 KVA DG set kirloskar Location:-Mukkinimala Tech Area | 1 | Job | 1,400 ₹1,400 | 1,800 ₹1,800 |
| 10.00 | Supply only lubrication oil filter element with 'O' ring required at site for 160 KVA capacitiy DG Sets. | 2 | Each | 1,400 ₹2,800 | 1,800 ₹3,600 |
Updated dates
Tender Value
₹37 L
EMD Value
₹74,000
Closing Date
12 Nov 2025, 6:00 pmClosed
GE AF Trivandrum
Office of Garrison Engineer AF, Pulayanarkotta, Thuruvikkal Post, Trivandrum-695011
REPAIR REPLACEMENT OF EXTERNAL WATER SUPPLY SYSTEM INCLUDING PUMPS VALVES VALVE CHAMBERS AND PANEL BOARDS AND REPAIR MAINTENANCE OF DG SETS STREET LIGHTS AND SOLAR LIGHTS AT 17 FBSU AF 257SU MUKKUNNIMALA AND AFSC MUTTATHARA UNDER GE AF TRIVANDRUM
2025_MES_734649_1
8567
Open Tender
Electrical and Maintenance Works
330 days
Trivandrum
As per Tender Documents
7 documents required · 7 mandatory
₹500
Yes
GE AF Trivandrum
₹74,000
Yes
14 Jan 2026
10 Oct 2025
15 Nov 2025
10 Oct 2025
12 Nov 2025
24 Oct 2025
Amount
Repairs/Maintenance of DG Sets,street lights and solar lights at 17 FBSU,257SU Mukkunnimala and AFSC Muttathara.
Comprehensive and preventive maintenance of DG set of capacity 160 KVA to ensure the generator's reliability, efficiency, and longevity of DG sets.The following key tasks typically to be performed during B & C check of DG set as per the running hours and OEM recommendation .Make of DG Set Ashok Leyland (Mukkunni Mala) /Kirloskar (340 TRU Muttathara ) a) Check and clean fuel injectors. b) Inspect and adjust valve clearances. c) Examine the turbocharger for wear or damage. d) Inspect and clean the air intake system. e) Check the cylinder head and piston rings for wear f) Change the fuel filter,bypass filter and oil filter g) Change the Air filter h) Change the water seperator j) Radiator cleaning with chemical k) Replace the coolent and engine oil l) Checking all electrical wiring and replace the unserviceable electromechanical switches,pressure gauges,indicators m) Checking the mechanical coupling between alternator shaft and prime mover to reduce the mechanical vibrations during hunting/start/stop of engine /Alternator n) Testing of emission system and minimise the obstruction by removing and cleaning , leakage arresting in exhaust pipe and Air Filter replacement if required
Note 1. All tests mentioned above are to be carriout by OEM of DG set . 2.Test certificates must be submitted by the contractor duly signed by OEM representative,Engineer in charge and contractor for claiming the RAR. 3. All the spare parts required for B & C Check of DG set will be measured and paid under the respective items of the following schedule.
All as per item No 2. here in above but of capacity 125 KVA DG set Kirloskar location- 17 FBSU Service cell
All as per item No 2. here in above but of 100 KVA capacity DG Set Kirloskar Location :- 17 FBSU computer cell
All as per item No 2. here in above but of capacity 62.5 KVA capacity DG set Kirloskar Location:-Tarmac Area (Shanghumugham)
All as per item No 2. here in above but of capacity 30 KVA capacity DG set kirloskar Location:-257 SU - D/Area Pump House /17 FBSU Offrs Mess
All as per item No 2. here in above but of capacity 25 KVA DG set kirloskar Location:-17 FBSU MAP PH/OTM Accn PH
All as per item No 2. here in above but of capacity 7.5 KVA DG set kirloskar Location:-Mukkinimala Tech Area
Supply only lubrication oil filter element with 'O' ring required at site for 160 KVA capacitiy DG Sets.
All as per item No. 10 here in before but 125 KVA DG set.
All as per item No. 10 here in before but 100 KVA DG set.
All as per item No. 10 here in before but 62.5 KVA DG set
All as per item No. 10 here in before but 30 KVA DG set
All as per item No. 10 here in before but 25 KVA DG set
All as per item No. 10 here in before but 7.5 KVA DG set
Supply only fuel filter element with 'O' ring as required at site for 160 KVA capacities of DG Set
All as per item No. 17 here in before but 125 KVA DG set.
All as per item No. 17 here in before but 100 KVA DG set.
All as per item No. 17 here in before but 62.5 KVA DG set
All as per item No. 17 here in before but 30 KVA DG set
All as per item No. 17 here in before but 25 KVA DG set
All as per item No. 17 here in before but 7.5 KVA DG set
Supply only Air filter element inner and outer as required at site with 'O' ring as required at site for 160 KVA DG Sets .
All as per item No. 24 here in before but 125 KVA DG set.
All as per item No. 24 here in before but 100 KVA DG set.
All as per item No. 24 here in before but 62.5 KVA DG set
All as per item No. 24 here in before but 30 KVA DG set
All as per item No. 24 here in before but 25 KVA DG set
All as per item No. 24 here in before but 7.5 KVA DG set
Supply only Solenoled shut off valve assembly complete suitable to operate with 12 volts DC
Supply only Solenoled shut off valve assembly complete suitable to operate with 24 volts DC
Supply only Lube oil pressure sensor for Engine
Supply only Speedo meter cable including outer and inner cable
Supply only Start/Stop Push button switch complete with base
Supply only Ignition switch heavy duty with keys suitable for DG set
Supply only silencer for Genset of capacity 160 KVA
Supply only silencer for Genset of capacity 100 KVA
Supply only gun metal gate/ globe valve with handle, heavy duty, of 15/20mm bore in the fuel line
Supply only radiator 'V' belt for 25/ 30 KVA capacity DG set
Supply only radiator 'V' belt for 62.5 capacity DG set
Supply only radiator 'V' belt for 100 KVA capacity DG set
Supply only radiator 'V' belt for 125 KVA capacity DG set
Supply only radiator 'V' belt for 160 KVA capacity DG set
Supply only Flexible over flow pipe steel armoured flexible with suitable end sockets of size 15 mm dia of suitable length and size
Supply only lub oil of grade SAE 15 W - 40
Supply only distilled water
Supply only Coolent suitable
Supply only battery of 12 V , 100 AH
Supply only battery of 12 V , 150 AH
Supply only battery of 12 V , 180 AH
Supply only oil level indicator.
Supply only Oil drain hose set
Supply only DG set Control unit capacity 25/30KVA
Supply only DG set Control unit capacity 62.5 KVA
Supply only DG set Control unit capacity 125 KVA
Supply only DG set AVR unit capacity 25/30KVA
Supply only DG set AVR unit capacity 62.5 KVA
Supply only DG set AVR unit capacity 160 KVA
Supply only temparature guage as per sample
Supply only Water separator filter for DG set of any cap. Make:- MICO/BOSS/Kirloskar
Supply only Exhaust fan suitable for DG set of 20 to 62.5 KVA cap. Make:- Globe/Crompton/Usha
Disconnection and removing DG set radiator 160KVA , and transporting to work shop for repairs and descaling the radiator thoroughly completely with CTC solution/ any other chemical solvent agent as approved indian standards , stopping of leakage at place to copper cores and tubes by brazing scrapping the existing oil paint, dusting and painting the radiator with enameled paint etc., reinstalling and commissioning all as directed by Engineer-in-Charge.
All as per item No 63 above but of capacity 125 KVA
All as per item No 63 above but of capacity 100 KVA
S&F in replacement of self starter assembly suitable for 25 KVA DG Set and testing complete all as specified and directed by Engineer in charge.
S&F in replacement of self starter assembly suitable for 30 KVA DG Set and testing complete all as specified and directed by Engineer in charge.
S&F in replacement of self starter assembly suitable for 62.5 KVA DG Set and testing complete all as specified and directed by Engineer in charge.
S&F in replacement of self starter assembly suitable for 100 KVA DG Set and testing complete all as specified and directed by Engineer in charge.
M&L for repairing of fuel injection pump (FIP) of cap 25 KVA /30 KVA and taking out it to authorised workshop and replacing unserviceable element, delivery valve, balance wait, lever, bearing after repairing fixing to the engine testing for satisfactory function all as directed by Engineer-in-Charge
All as per item No. 70 here in before but 62.5 KVA DG set
All as per item No. 70 here in before but 160 KVA DG set
M&L for repairing of dynamo including removing from position FROM 30KVA and remove the burnt out armature , clean the internal surfaces , servicing, supply and fix new armature with brushes and brush holder , necessary lathe work with bushes etc all as directed
S&F in replacement of Water pump of 100 KVA capacity.
S&F in replacement of Oil seal assembly of 125 KVA /160 kvacapacity as per sample.
M&L for repairing of 20 /30 KVA alternator and transport to an authorised work shop for repair/rewinding by taking out copper wire from stator and rewinging the same with super enamalled bared copper conductor and varnishing with class F insulation ,and replace the carbon brushes and reassembling the aleternator and transporting back and refixing in position , testing and commissioning all as specified and as directed
All as per item No.76 above but of capacity 100 KVA/125KVA
All as per item No.76 above but of capacity 160 KVA
S&F in replacement of diode rectifier set circuit mounted on alternator incl base plate and copper wiring of existing gauge for 62.5 KVA DG Set complete all as directed.
All as per item No 79 here in above but of capacity 100 KVA
All as per item No 79 here in above but of capacity 125 KVA
All as per item No.79 here in above but of capacity 160 KVA
M&L for Repairs to acoustic enclosure provided for DG sets by necessary welding work/patchup works, providing new hinges etc including making good the repaired portion by painting to match with the existing all as specified and as directed
S & F in repairs of Door panels duly hinged and insulated suitable for out door type DG sets acustic enclosure as per sample with hinges and door locks
S & F in repairs of Door locks with catcher (right/left) suitable for out door type DG sets acustic enclosure as per sample with hinges and door locks
S & F in repairs of Grills with frame suitable for acustic enclosure as per sample
S & F in repairs of Side panels thermally insulated suitable for DG acustic enclosure
M&L for repairing of 12V self starter by removing, dismantling and taking it to authorised workshop and replacing unserviceable coil tapping re-fixing to the engine testing for satisfactory function all as directed by Engineer-in-Charge
M & L for preparing external surfaces of canopy ,engine, alternator, connected panel, base frame, radiator, battery stand etc,free from foreign materials and applying two coats of superior quality synthetic enamel paint of approved colour by spray painting,over a coat of primer paint cleaning meter panel and writing MES No to the DG sets of following capacities complete all as specified and directed. 160 KVA capacity Kirloskar/CUMMINS installed in 257 SU/340TRU with AMF panel and acoustic enclosure
All as per item No.89 herein above but of capacity 125/ 100 KVA at computer cell at 17 FBSU/MES Service cell with AMF panel and acoustic enclosure
All as per item No.89 herein above but of capacity 62.5 KVA capacity with AMF Panel for 17 FBSU, Tarmac with Acustic enclosure
All as per item No.89 herein above but 20 to 30 KVA capacity kirloskar DG set for 17 FBSU, 257SU, with Acustic enclosure
All as per item No.89 herein above but 7.5 KVA capacity kirloskar DG set for 17 FBSU, 257SU, with AMF Panel and Acustic enclosure
Supply and replacement of Control contactor including 2 NO-2NC.Make:- TC/ any command approved make
Supply and replacement of Contactor MCX22 .Make:- L&T/ SIEMENS/C&S / any command approved make
Supply and replacement of Contactor MCX31. Make:- L&T/ SIEMENS/C&S / any command approved make
Supply and replacement of Contactor MCX33, 415 volt. . Make:- L&T/ SIEMENS/C&S / any command approved make
Supply and replacement of Contactor MCX32 415 volt . Make:- L&T/ SIEMENS/C&S / any command approved make
Supply and replacement of Contactor 60 A . Make:- L&T/ SIEMENS/C&S / any command approved make
Supply and replacement of Contactor MCX04 four pole . Make:- L&T/ SIEMENS/C&S / any command approved make
Supply and replacement of Contactor MCX03 four pole . Make:- L&T/ SIEMENS/C&S / any command approved make
Supply and replacement of Contactor 4 pole 250 A make.Schneider/L&T/ SIEMENS/C&S / any command approved make
Supply and replacement of Contactor 4 pole 180 A make.Schneider/L&T/ SIEMENS/C&S / any command approved make
Supply and replacement of Contactor coil suitable capacity for 100 to 160KVA DG set. Make :- L&T/ SIEMENS/C&S / any command approved make
M&L for preventive maintenance of AMF panel of DG set of capacity 160KVA by replacing defective wiring circuits as per colour code, cut outs etc all as sper specified and directed.
M&L for preventive maintenance of AMF panel of DG set of capacity 125KVA by replacing defective wiring circuits as per colour code, cut outs etc, all as sper specified and directed.
M&L for preventive maintenance of AMF panel of DG set of capacity 100KVA by replacing defective wiring circuits as per colour code, cut outs etc all as sper specified and directed.
M&L for preventive maintenance of AMF panel of DG set of capacity 62.5KVA by replacing defective wiring circuits as per colour code, cut outs etc, all as sper specified and directed.
M&L for preventive maintenance of AMF panel of DG set of capacity 7.5KVA by replacing defective wiring circuits as per colour code, cut outs etc all as sper specified and directed.
Supply and replacement of VMR/Single phase preventor . Make:-Minilac/ AE/MECCO/ any command approved make.
Supply and replacement of Add on block 2No-2NC. Make:- TC / AE/MECCO/ any command approved make.
Supply and replacement of 12V/24V 11 pin PLA realy with base. Make:- As per OEM
Supply and replacement of Indicator lamp/push button/element all as per sample. Make:- AE/MECCO
Supply and replacement of AMF controller of DG set of any cap. Make:- C&S Siemens/L&T/ any command approved make
Note:- (a) Any emergency complaints of DG set which cause interruption for providing stand by supply to User shall be attended by the Contractor within 8 hours after receiving the complaint by telephonically/through writting from concerned JE E/M/AGE E/M. In case of any delay in attending the complaint more than 8 hrs after handing over of emergency / urgent work, the contractor shall be liable to pay the penalty as described in penalty caluse given here as under. If the nature of job is such that the work cannot be completed within period of 8 hrs then the facts shall be brought to the notice of the GE/Engr-in-Charge and the period for the working to the complaint shall be decided by the GE/EIC,
Note (Cond/-):The penalty shall be applicable to the contractor if the delay is noticed by the Engr-in-Charge more than eight hrs after handing over works of urgent nature to the contractor. if the delay is more than twelve hrs period and the GE is not satisfied with the reason for delay then penalty at the rate of Rs 500/- per job/day shall be deducted from the dues of the contractor. Please note that this penalty is exclusively other then the condition 56 of IAFW -2249 and shall be treated as interim condition of the contract and shall be enforce above as and when delay in individual job isnoticed and no claim whatsoever on this account shall be entertained by the Deptt. The decision of the Accepting Officer in this regards shall be final and binding. (c) The contractor shall maintain a record of all urgent work at and if the work is repeated due to poor workmanship, he will be liable to repair the same without any extra expenditure to the Govt.
M&L for Comprehensive maintenance and servicing of Fire detection system installed at the following locations at 17 FBSU,and its lodger Units repair/ replacement of all defective and unserviceable parts as per specifications during contract period and attending of breakdown as and when intimated including necessary periodical safety checking and testing the entire system/ cleaning of detectors and attending complaints within 24 hrs including sunday/holiday and submit the service report by every quarter. each job to be done in each quarter. (Note :- Spares required during comprehensive maintenance period shall be measured and paid seperately).
AFNET (Old): Fire alarm panel 10 Zone ( Conventional Ravel RE 150 - 1 No. Manual call points - 2 Nos Electronic sounders - 2 Nos, Smoke/ Heat detector - 18 Nos , Response indicator - 10 Nos
AFNET (New): Fire alarm panel Addressable ( Ravel - 1 No. Manual call points - 4 Nos Electronic sounders - 3 Nos, Smoke/ Heat detector - 15 Nos , Response indicator - 10 Nos
HQ,CBRN cell /FCC Old logistic Immols Server Room : Fire alarm panel ( Addressible Morley IAS CONNEXION ) - 1 No. Manual call points - 2 Nos Electronic sounders - 2 Nos, Smoke/ Heat detector - 5 Nos
257 SU,AF (Mukkunnimala) : Fire alarm panel ( Addressible Morley IAS CONNEXION ) - 1 No. Manual call points - 5 Nos Electronic sounders - 5 Nos, Smoke detector -20, Heat detector - 12 Nos
17FBSU, Hydraulic Lab : Fire alarm panel ( Addressible AVANI ) - 1 No. Manual call points - 1 Nos Electronic sounders - 1 Nos, Smoke detector - 6 Nos
Note for Sl No 118 to 123 (a) The rate quoted shall be inclusive of attending complaints within 24 hours (Spares required during comprehensive maintenance period shall be measured and paid seperately). (b) Any item that is not included in OEM AMC schedule but required at site for smooth functioning of fire alarm system , shall be paid by the contractor on this account. (c) The maintenance of fire alarm system shall be done through OEM/ authorised service provider the tenderer has to submit intent of MOU from OEM/ authorised service provider within fifteen days of acceptance of tender. (d) Contractor shall conclude AMC with OEM and copy of the agreement will be submitted to Engr-in- charge and GE before commencement of AMC
Supply only addressable heat detector Make: Ravel UL Listed/ any command approved make
Supply only addressable multi detector Make: Ravel UL Listed/ any command approved make
Supply only addressable conventional sounder Make: Ravel UL Listed/ any command approved make
Supply only battery SMF 12V 7AH. Make:Exide/ any command approved make
Taking out unserviceable UG cables and Supply and laying only in trenches or passing through pipes/ poles etc LT XLPE cable heavy duty 1100 Volts grade with aluminium conductor of the following connections with provn of cable lugs and glands as required of following sizes.
(a) 6 Sqmm 4 core
(b) 10 Sqmm 4 core
(c) 16 Sqmm 4 core
(d) 35 Sqmm 3.5 core
Supply and replacement of existing Unserviceable Street light fittings with new High Power LED fitting to ensure uniform distribution with die cast aluminium IP 66 street light of capacity 80 W LED fittings with suitable fixing accessories all as specified and as directed. (Note : Rate for removing of unserviceable light fitting from street light pole and refixing new fitting shall deemed to be included in the item rate)
Supply and replacement of existing unserviceable conventional bollard fittings with new energy saving bamboo landscape luminaire 8 W capacity LED type prewired with IP 65 protection including 1 mtr height powder coated hollow pipe or bollard all as specified and as directed. (Note : Rate for removing of unserviceable light fitting from PCC platform and refixing new fitting with nut bolt shall deemed to be included in the item rate)
Supply and replacemnt of existing unserviceable Flood light fitting with new High Power LED flood light fitting to ensure uniform distribution with die cast aluminium IP 66 street light of capacity 100W LED fittings with suitable fixing accessories all as specified and as directed. (Note : Rate for removing of unserviceable light fitting from street light pole and refixing new fitting shall deemed to be included in the item rate)
Supply and replacemnt of existing unserviceable post top lantern with new generation, IP 65 LED post-top family, energy saving, environmental friendly, long life aesthetically designed with symmetrical light distribution, spun aluminium landscape luminaire with high power LEDs as light source with Clear Cover of capacity 25W LED fittings with suitable fixing accessories all as specified and as directed. (Note : Rate for removing of unserviceable light fitting from street light pole and refixing new fitting shall deemed to be included in the item rate) New offers bright illumination for different applications.
Supply and fixing in repair Cable Junction box made out of polycarbonate material IP55/65 with metric knockouts for cable entry for 16/25 Sq mm cable size 200X140X95 mm including 1 No MCB 6 Amps TPN with DIN bar and 4 Nos FRP insulators and fixing the box to street light pole made of 25x 3mm flat iron with clamps, nuts and bolts complete as directed by Engineer-in-charge
M&L for removing of LED street light fitting from pole for replacement of unserviceable LED driver with new LED Driver suitable for existing 45/60/70/90 W LED street light fittings all as specified and directed.
M&L for removing of LED flood light fitting from pole for replacement of unserviceable LED driver with new LED Driver suitable for existing 120/150 W LED flood light fittings all as specified and directed.
M&L for preparation of surfaces of solar street Light poles 4.5 Mtr of Height, battery box clamps, nuts & bolts etc and applying one coat of aluminium paint including writing numbering of poles in black background and white letters complete all as specified and directed.
S & F in repairs 24 hour digital time switch suitable for operation on 230 Volts AC complete all as specified and directed.
M&L for fixing of street light bracket made of 40 mm dia GI tubing light grade, 1.2 metre long, bent to shape fixed to pole with 50mm x 6mm Flat iron clamps with nuts and bolts including painting two coats of aluminium paint over a coat of zinc chrome primer all as directed.
M&L for painting on steel tubular poles of height 7.5 Mtr above gound level by applying two coats of Aluminium paint over one coat of red oxide primer on street light pole bracket /clamps terminal box etc including applying two coats of cement based paint over one coat of suitable primer for coping and writing pole number in black and white Paint complete all as specified and directed.
M&L for painting on PCC poles of height 7.5 Mtr above gound level by applying two coats of exterior weather coat paint over one coat of suiable primer on existing poles including copping and writing pole number in black and white Paint complete all as specified and directed.
M&L for Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers,welding, bending cold or hot,drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint
Excavation in trenches not exc 1.5m wide and not exc 1.5m in depth for laying UG cable not exc 1.5m in depth and getting out in soft/loose soil complete all as specified and directed
Removing excavated material not exc 50m and depositing where as directed at a level not exc 1.5m above the starting point complete all as specified and directed
Returning, filling of excavatted soil upto a depth of 30cm after riddling the excavated soil for cushioning of cable and refilling of trench with normal excavated soil
Supply and lay in trenches burnt bricks sub-class ‘B’ of size 150 x115x75mm for cable protection complete all as specified and directed
M/L for PCC 1:3:6 Type C1 with 20 mm graded aggregate for coping , over road cutting surface complete including necessary foam work complete all as specified and directed
Repair/Replacement of external water supply system including pumps,Valves ,valve chamber and Panel Boards at 17 FBSU AF,257 SU at Mukkunnimala and Muttathara Complex.
Excavation in trenches not exc 1.5m wide and not exc 1.5m in depth for laying UG cable not exc 1.5m in depth and getting out in soft/loose soil all as specified and as directed.
Returning, filling, incl spreading levelling, watering and well ramming in layers not exc 25cm with soil comlete all as specified and directed
Removing excavated material not exc 50m and depositing where as directed at a level not exc 1.5m above the starting point all as specified and as directed
Taking up or down old GI Pipe/PVC pipe/PP-R pipe of size 25mm dia with all fittings such as unions, reducer sockets, socket reducing bends, elbows, tee, checknuts, caps, plugs etc of following sizes for repair/rerouting/replacement/ kept aside complete all as specified and directed.
(a) All as per item No 156 above but of size 32mm dia
(b) All as per item No 156 above but of size40 mm dia
(c) All as per item No 156 above but of size50 mm dia
(d) All as per item No 156 above but of size65mm dia
(e) All as per item No 156 above but of size80 mm dia
(f) All as per item No 156 above but of size100mm dia
Supply, laying & testing galvanised iron water tubing of size 25mm dia, medium grade, ISI marked with and including all GI fittings such as unions, reducer sockets, socket reducing bends, elbows, tee, checknuts, caps, plugs etc. laid in trenches/floor complete all as specified and directed. Make- TATA/Jindal/Prakash.
(a) All as per item No 163 above but of size 40 mm dia
(b) All as per item No 163 above but of size50 mm dia
(c) All as per item No 163 above but of size80 mm dia
(d) All as per item No 163 above but of size100mm dia
Supply, laying & testing UPVC (ASTM) pipes of size 25mm dia, ISI marked and confiming to IS 4986 including all fittings such as unions, reducer sockets, socket reducing bends, elbows, tee, checknuts, caps, plugs etc. laid in trenches/floor /wall complete all as specified and directed.
(a) All as per item No 168 above but of size 32 mm dia
(b) All as per item No 168 above but of size 40 mm dia
(c) All as per item No 168 above but of size 50 mm dia
(d) All as per item No 168 above but of size 65 mm dia
(e) All as per item No 168 above but of size 80mm dia
(f) All as per item No 168 above but of size 100mm dia
Relaying only PVC/PP-R pipe of size 25mm dia in trenches/floor//wall with complete fittings as required all as specified and directed.
(a) All as per item No 175 above but of size 32 mm dia
(b) All as per item No 175 above but of size 40 mm dia
(c) All as per item No 175 above but of size 50 mm dia
(d) All as per item No 175 above but of size 65 mm dia
(e) All as per item No 175 above but of size 80mm dia
(f) All as per item No 175 above but of size 100mm dia
M&L for replacement of CPVC pipe of 40mm outer dia SDR 11 & Plain CPVC SDR 11 fittings on walls/ceiling or laying in floors complete with fittings duly insulated with glass wool and aluminium cladding all as specified and directed.
M&L for replacement of CPVC pipe of 25mm outer dia SDR 11 & Plain CPVC SDR 11 fittings on walls/ceiling or laying in floors complete with fittings duly insulated with glass wool and aluminium cladding all as specified and directed.
S&F in repair Stop valves, 25mm dia cast copper alloy,screwed down,high pressure,with crutch or butterfly handle, screwed both ends for iron pipe or for unions and fixed
S&F in repair Brass CP mixer 15mm dia for mixing hot & cold water screwed down for iron pipe and fixed
M&L for replacement of U/S Water tanks 2 layer of capacity 250/300Ltr , open or closed,white colour including float valve, complete fittings required for connecting inlet and outlet pipes,hoisted and fixed in position all as specified and directed.
M&L for tracing of leak and rectifying leak in 3- layer PP-R (Polypropylene random copolymer) pipes SDR 7.4 (PN16) UV stabilized and antimicrobial fusion welded having thermal stability for hot & cold water supply all PP-R plain & brass threaded polypropylene random fittings laid in trenches( pipe of size 50 to 90 mm Outer Dia including replacing of necessary nipple and bend/ elbow and replacing of additional small lenghth of PP-R pipe as follows and ckecking of leak after completion of work complete all as specified and as directed. (Note PP-R pipe required shall be measured and paid seperately under respective item)
(a) 50mm outer dia
(b) 90mm outer dia
Supply and fix in repair Gun metal globe or gate valve of size 25mm dia with iron wheel head screwed both ends conforming to IS 778 of 84 for iron pipe complete all as specified and directed. Make- Zoloto/Bir/Prakash.
(a) All as per item No 190 here in before but of size 40 mm dia
(b) All as per item No 190 here in before but of size 50 mm dia
Supply and fix in repair CI Sluice valve of size 80mm dia flanged, heavy duty, class PN 1.6, as per IS-14856 including brass spindle, with hand wheel, nuts bolts and gaskets complete all as specified and directed, Make- Zoloto/Bir/Kirloskar/RMCO.
(a) All as per item No 193 here in before but of size 100 mm dia
Repairs/ servicing to sluice valve by taking out unserviceable spindle along with worn-out check nuts from the sluice valve of size 80mm dia bore after removing the top cover and stuffing box of sluice valve spindle, and refixing with new spindle with check nut, gland packing, gasket, replacing of rusted unserviceable nuts/ bolts/ washers with SS with new nuts, bolts, gaskets etc for arresting all leakages/ smooth operation complete all as specified and directed. Note :- Rate are included cost of Spindle along with check nuts and nuts/ bolts.
(a) All as per item No 195 here in before but of size 100 mm dia bore
M & L for making CD Joints through JIFFY COUPLING complete with GI nut, bolts, rubber O rings & all accessories and arresting the leakage for pipes of size 80mm dia bore complete all as specified and directed.
(a) All as per item No 197 here in before but of size 100/150 mm dia bore
Supply and fix in repair cast Iron butterfly valve confirmimg to IS: 13095 operating with lever suitable for 80mm GI pipe all as specified and directed. Make- Zoloto/Bir/Kirloskar/RMCO.
Supply and fix in repair cast Iron butterfly valve confirmimg to IS: 13095 operating with lever suitable for 63mm GI pipe all as specified and directed. Make- Zoloto/Bir/Kirloskar/RMCO.
Supply and fix in repairs CI Ball Foot Valve Heavy duty of CI body and cover with Nitrile Rubber coated ball with Covering ring one side flanged complete of size 50mm dia all as specified and directed. Make- Normax or equivalant .
(a) All as per item No 201 here in before but of size 80 mm dia
Supply and fix in repair 100 mm Non return Sluice valve flanged end, cast iron body, flanged and drilled and non rising type stainless steel spindle with nut, long body, class P N 1.6, conforming to IS 14846 of 2000 including all flange joint with rubber or fiber board, bolts, nuts and washers complete all as specified and directed by Eng-in-Charge.(Make: KIRLOSKAR,ZOLOTO,UPADHYAY,LEADER,VENUS,VAG)
Supply and fix in repair 80 mm Non return Sluice valve flanged end, cast iron body, flanged and drilled and non rising type stainless steel spindle with nut, long body, class P N 1.6, conforming to IS 14846 of 2000 including all flange joint with rubber or fiber board, bolts, nuts and washers complete all as specified and directed by Eng-in-Charge.(Make: KIRLOSKAR,ZOLOTO,UPADHYAY,LEADER,VENUS,VAG)
Supply and fix Pressure gauge 100 mm dia with ball valve of pressure 25 Kg/Sqcm(MAKE: H GURU,GLYCERINE FIELD,FIEG/ any command approved make)
Supply and fix in repair Cast Iron Air Valves with single air Outlets, conforming to IS 14845 of size 50 mm dia bore and fixing up in GI/CI/DI Water supply mains of size 150/100/80 mm dia (MAKE: (MAKE:Normax/Kirloskar/ LEADER/ any command approved make.)
Supply and fix in repair DOL starter suitable for 3 to 5 HP induction motor, 3 Phase 415 Volts, 50 Hz complete all as specified and directed. Make - L&T/Siemens/Havells/C&S/ any command approved make.
Supply and fix in repair automatic star delta starter suitable for 7.5 to 10 HP induction motor, 3 Phase 415 Volts, 50 Hz complete all as specified and directed. Make - L&T/Siemens/Havells/C&S/ any command approved make..
Supply and fix in repair Single phase preventer for 3 phase 415V AC power supply complete all as specified and directed. Make : Minilec/ L&T/BCH/ any command approved make..
Servicing of Chlorine dozing pump of capacity 6ltr/hour by renewing unserviceable parts like injection valve,diaphram etc complete all as specified and directed. Make: RMCO/Declibac/ any command approved make.
Dismantling, transporting to work shop, Cutting and removing burnt centrifugal mono block motor winding, cleaning the slots and rewinding with approved quality super enamelled copper conductor winding wire of existing size and capacity including insulating materials, varnishing baking etc and reinstalling in existing position, testing etc for three phase, 440 volts motors of Pump capacity 3 HP to 5HP complete all as specified and directed :-
All as per item No 211 here in before but of 7.5 HP Capacirty
All as per item No 211 here in before but of 10 HP Capacirty
All as per item No 211 here in before but of 30 HP Capacirty
Material and labour for dismantling, transporting to workshop for servicing of pump sets including replacement of Ball bearing, mechanical water seal including any rusted nut,bolt, brackets and greasing etc and applying two coat of synthetic enamel paint over one coat of red oxide primer etc and reinstallation in existing position ,testing complete all as specified and directed.for the pump set of capacity 3/5 HP.
All as per item No 215 here in before but of 7.5 HP Capacirty
All as per item No 215 here in before but of 10 HP Capacirty
All as per item No 215 here in before but of 30 HP Pump set
S & F in repairs UPVC flat submersible, water proof cable, 3 core 4 Sqmm copper conductor, multi stranded 1100V grade complete all as specified and directed.
M & L for mechanized cleaning and disinfection of PVC tank of 5000Ltr capacities by adopting six step cleaning process with trained technitians of professional water tank cleaning company/firm with the help of adequate equipments to the entire satisfaction of Engineer in Charge as follows:-
(i) Dewatering of tank by using suitable capacity pump.
(ii) Removal of sludge(silt) by using sludge pump and sludge sucker.
(iii) Washing the floor, wall and roof, pipe line and motor inside the tank by using High Pressure Machine. Generating pressure of 60-180bars [pressure Adjustable]. Having rotary as well as flat jet for effectively cleaning of all the nooks and corners including ceiling of the Tank.
(iv) Vacuum cleaning of tank using Industrial Wet and Dry Vacuum Cleaners for moping of all the dirt particles in the base of the Tank.
(v) Spraying anti bactirial agent (sodium hypochlorite liquid) inside the tanks for antibacterial treatment. (Note : Anti bactirial agent should contain 10-12% chlorine and appx qty required is 1 litre per 50000Ltr tank)
(vi) Eliminate the atmospheric bacteria remaining in the tanks by using Ultra Voilet Lamps for UV radiation and makes the tank 100% bacteria free.
(vii) Writing the date of cleaning and capacity etc in bold letters.
M & L for mechanized cleaning and disinfection of SWT of capacity 50KL by adopting six step cleaning process with trained technitians of professional water tank cleaning company/firm with the help of adequate equipments to the entire satisfaction of Engineer in Charge as follows:- (i) Dewatering of tank by using suitable capacity pump. (ii) Removal of sludge(silt) by using sludge pump and sludge sucker. (iii) Washing the floor, wall and roof, pipe line and motor inside the tank by using High Pressure Machine. Generating pressure of 60-180bars [pressure Adjustable]. Having rotary as well as flat jet for effectively cleaning of all the nooks and corners including ceiling of the Tank. (iv) Vacuum cleaning of tank using Industrial Wet and Dry Vacuum Cleaners for moping of all the dirt particles in the base of the Tank. (v) Spraying anti bactirial agent (sodium hypochlorite liquid) inside the tanks for antibacterial treatment. (Note : Anti bactirial agent should contain 10-12% chlorine and appx qty required is 1 litre per 50000Ltr tank) (vi) Eliminate the atmospheric bacteria remaining in the tanks by using Ultra Voilet Lamps for UV radiation and makes the tank 100% bacteria free. (vii) Painting of outer side concrete surfaces with one coat of weather proof emulsion paint of approved colour over one coat of emulsion primer after removing/cleaning all foreign materials from the surface including writing the date of cleaning and capacity etc in bold letters. (viii) Painting of outer side metal surfaces with one coat of epoxy paint of approved colour over one coat of epoxy primer after removing/cleaning all foreign materials from the surface.
All as per item No 228 here in before but Static Water tank of capacity 10KL
All as per item No 228 here in before but UG Sump of capacity 3 lakh Ltr.
All as per item No 228 here in before but UG Sump of capacity 1 lakh Ltr.
All as per item No 228 here in before but UG Sump of capacity 50KL
All as per item No 228 here in before but UG Sump of capacity 20Kl.
All as per item No 228 here in before but UG Sump of capacity 10KL.
M & L for mechanized cleaning and disinfection of following Shallow wells of capacity 5 to 10 Mtr by adopting six step cleaning process with trained technitians of professional water tank cleaning company/firm with the help of adequate equipments to the entire satisfaction of Engineer in Charge as follows:- (i) Dewatering of tank by using suitable capacity pump. (ii) Removal of sludge(silt) by using sludge pump and sludge sucker. (iii) Washing the floor, wall and roof, pipe line and motor inside the tank by using High Pressure Machine. Generating pressure of 60-180bars [pressure Adjustable]. Having rotary as well as flat jet for effectively cleaning of all the nooks and corners including ceiling of the Tank. (iv) Spraying anti bactirial agent (sodium hypochlorite liquid) inside the tanks for antibacterial treatment. (Note : Anti bactirial agent should contain 10-12% chlorine and appx qty required is 1 litre per 50000Ltr tank) (v) Eliminate the atmospheric bacteria remaining in the shallow well by using Ultra Voilet Lamps for UV radiation and makes the well 100% bacteria free. (vi) Painting of outer side concrete/masonry surfaces with one coat of weather proof emulsion paint of approved colour over one coat of emulsion primer after removing/cleaning all foreign materials from the surface including writing the date of cleaning and capacity etc in bold letters. (viii) Painting of upper side metal grill cover with one coat of epoxy paint of approved colour over one coat of epoxy primer after removing/cleaning all foreign materials from the surface.
Supply only calcium based granular disinfectant for water treatment high stable (65 to 70%) in packing of 45 Kg plastic drum complete all as specified and directed. Make : PURICHLOR or equivalant
M&L for servicing of Submersible pumpset of capacity 5 HP/7.5HP/10HP by lifting/dismantling from shallow well , transporting to a reputed workshop including replacement of unserviceable parts such as water seals,bearing ,bushes,lube oils etc including necessay lathe work and applying two coat of synthetic enamel paint over one coat of epoxy primer transporting back and connecting,testing and commissioning lowering into the shallow well complete all as specified and directed. Note:- rates are deemed to be inclusive of taking up the pump from shallow well, transportation and refixing after servicing in the same position.
M&L for lifting and dismantling of borewell submersible pump of capacity 2HP/8.5HP by removing CI/GI pipe, transporting to a reputed workshop including replacement of unserviceable parts such as water seals,bearing ,bushes,lube oils etc including necessay lathe work and applying two coat of synthetic enamel paint over one coat of suitable primer transporting back and connecting,testing and commissioning lowering into the bore well complete all as specified and directed. Note:- rates are deemed to be inclusive of taking up the pump from bore well, transportation and refixing after servicing in the same position.
M&L for repairing of existing valve chamber of size 600mmx600mmx750mm internal size including removing of foreign materials from chamber , PCC 1:2:4 type B1 for coping, 15mm thick rendering in cement mortar 1:4 including replacement of rusted mild steel cover 4mm thick on 40x40x6mm angle iron frame work with 2 coats of synthetic enamel paint over a coat of zinc chrome primer and locking arrangements complete all as specified and directed.
M&L for Repairing of existing valve chamber of size 900mmx900mmx1200mm internal size including removing of foreign materials from chamber , PCC 1:2:4 type B1 for coping, 15mm thick rendering in cement mortar 1:4 including replacement of rusted mild steel cover 4mm thick on 40x40x6mm angle iron frame work with 2 coats of synthetic enamel paint over a coat of zinc chrome primer and locking arrangements complete all as specified and directed.
M&L for Construction of valve chamber of size 1200mmx900mmx900mm internal size including necessary earth work,excavation, PCC 1:4:8 type D2 for foundation, brick work in cement mortar 1:4, PCC 1:2:4 type B1 for coping, 15mm thick rendering in cement mortar 1:4 including provision of mild steel cover 4mm thick on 40x40x6mm angle iron frame work with 2 coats of synthetic enamel paint over a coat of zinc chrome primer and locking arrangements complete all as specified and as shown on drawings.
All as per item No. 241 here-in-before but of internal size 600mmx600mmx750mm.
M&L Servicing of solar water heater system of 100 ltr/200Ltr capacity complete by cleaning collector plate / panel and descaling with suitable chemical flushing out solar panel, arresting leakage in the system, replacing hot water hose pipe of existing sizes & PUF insulation of pipe , painting the solar panel frame with two coats of epoxy paint over one coat of epoxy primer of approved make and colour complete all as specified and directed
M&L for replacement of Storage tank suitable for 200 ltr capacity, outer body made out of high engineering plastic and inner container made out of SS 304 L Plasma TIG welded and insulated with PUF insulation complete with heating element 2 KW with thermostat including hoisting to the inlet and outlet connections from solar panel complete.
M&L for replacement of Storage tank suitable for 100 ltr capacity, outer body made out of high engineering plastic and inner container made out of SS 304 L Plasma TIG welded and insulated with PUF insulation complete with heating element 2 KW with thermostat including hoisting to the inlet and outlet connections from solar panel complete.
M&L for replacement of solar plate collector with 4mm thick glass, frame made of aluminium section complete panel of approx. size 1.00 mtr X 2.00 mtr maximum working pressure 245 Kpa (2.45 Bar) including necessary water connection.
S&F in repairs themostat suitable for 100 Ltr/200Ltr capacity solar water heater complete all as specified and directed. Make: TATA/ any command approved make.
S&F in repairs heating coil capacity 2KW suitable for solar water heater complete all as specified and directed. Make: TATA/USHA/Crompton/ any command approved make.
S&F in repairs borosilic vacuum tube suitable for 100/200 Ltr capacity solar water heater complete all as specified and directed. Make V Guard/Crompton/ any command approved make..
S&F in repairs gun metal non return valve of size 20 mm dia ISI maked ,screwed complete all as specified and directed.
Supply only Chlorine test kit with coloured ample complete with all testing fitments and OT solution in rexine finish box. Make RMCO or equivalent
M&L for preparation of old painted surface by removing rust/foreign material from the outer surface of Iron removal filter,Dual media filter,Activated carbon filter and Valve chamber cover with angle iron and painting with two coat of synthetic enamel paint over one coat of epoxy primer after removing of rust/foreign material from outer surface all as specified and directed.
Collection of water sample from UG Sump/Shallow well/Bore well at 17FBSU and its lodger units, transporting to authorised water analysis laboratory for testing and submitting the report to Engr-in-Charge all as specified and directed.
M&L for repair/servicing of water filtration plant of 25 Cum/Hr capacity by replacing filteration media meterials with new in duel media filter, Activated carbon fillter and Iron removal filter including testing of filteration plant to function to the entire satisfaction of Engineer in Charge as follows:-
Media required for 1300 mm dia 1500mm height Dual media Filter
Anthricite
Filtering Sand
Fine Silex
Coarse Silex
Gravel (6-2)
Pebbles (20-12)
Pebbles (40-25)
Media required for 1300 mm dia 1500mm height Activated carbon Filter
Activated carbon filter
Fine Silex
Coarse Silex
Gravel (6-2)
Pebbles (20-12)
Pebbles (40-25)
Media required for 1500 mm dia 1500mm height Iron Removal Filter
Manganese Dioxide
Filtering Sand
Fine Silex
Coarse Silex
Pebbles (20-12)
Crown Chemicals (BID ID -3464314)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.72 MB
BOQ_822623.xls
BOQ • 1.38 MB
ps.pdf
Additional Documents • 0.56 MB
tenderpages.pdf
Tender Documents • 1.12 MB
Download all tender documents and submit your bid