Loading…
Loading…
Tender Value
₹42.3 Cr
EMD Value
₹42.3 L
Closing Date
13 Apr 2026, 6:00 pmClosed
Superintending Engineer, Project Implementation Unit, Health & Family Welfare Department.
Construction of New Modern Hospital building with 100 bedded facilities at Sub District Hospital, Petlad Ta: Petlad in Dist : Anand.
287414
2025-26/165/01
Open
Civil Works
Gandhinagar
1 document required · 1 mandatory
₹24,000
PIU-General Fund A/c 11-114
₹42.3 L
17 Mar 2026
17 Mar 2026
17 Mar 2026
13 Apr 2026
17 Mar 2026
Name of Work :- Construction of New Modern Hospital building with 100 bedded facilities at Sub District Hospital,Petlad Ta: Petlad in Dist : Anand.
Memorandum showing item of work to be carried out
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Ch-4 Excavation for foundation up to 1.5 mt. depth including sorting out and stacking of useful materials and disposing off
Rupees One hundred Twenty
1 It.code.04001A 6454.00 the excavated stuff upto any lead & lift (A) Loose or soft soil Cmt 122.94
Two Paise Ninety Four Only
Ch-4 Excavation for foundation for depth from 1.5 m to 3.0 m including sorting out and stacking of useful materials
Rupees One hundred Thirty
2 It.code.04002A 6198.00 and disposing off theexcavated stuff upto 50 Meter lead.(A) Loose or soft soil Cmt 136.30
Six Paise Thirty Only
Ch-4 Excavation for foundation for depth from 3.0 m to 5.0 m including sorting out and stacking of useful materials
Rupees One hundred Forty
3 It.code.04003A 7123.00 and disposing off the excavated stuff upto 50 Meter lead.(A) Loose or soft soil Cmt 149.65
Nine Paise Sixty Five Only
Excavation for foundation for depth from 5.0 m to 6.0 m including sorting out and stacking of useful materials
Ch-4 Rupees One hundred
and disposing off the excavated stuff upto 50 Meter lead.(A) Loose or soft soil ,Extra for additional depth more
4 It.code.04003A + 837.00 Cmt 171.83 Seventy One Paise Eighty
04004A Pg.No.60 Three Only
Box cutting the road surface to proper slope and camber for making a base for road work including removing the Rupees One hundred Nine
excavated stuff and depositing on the road side slope as directed upto 50Mt.lead. Paise Forty One Only
Ch-4 Filling available excavated earth (excluding rock)in trenches, plinth,sides of foundations etc. in layers not exceeding
Rupees One hundred Thirty
6 It.code.4006 14124.00 20 cm. in depth consolidation each deposited layer by ramming and watering. Cmt 136.92
Six Paise Ninety Two Only
Providing Filling in Sunk Portion with cinder of best approved quality including watering ,ramming consolidation and
Rupees Three hundred Thirty
7 RA 144.00 dressing etc. complete as directed in toilet and bath sunken area at all floor up to all lead and lif Cu.M 335.91
Five Paise Ninety One Only
Ch-4 Filling in foundation and plinth with murrum or selected soil in layers of 20cm thickness including watering ramming
Rupees Two hundred Ninety
8 It.code. 4008A 4957.00 and consolidating etc. complete Cmt 294.38
Four Paise Thirty Eight Only
Ch-4 Filling in plinth with sand under floors including watering ramming, consolidating and dressing complete
Rupees Four hundred Eighty
One Paise Eighty Only
Applying general insecticide pest control treatment to floors, cupboards etc including labour materials etc. complete.
Using Imidacloprid 30.5 SCas Per IS 6313 part II( (0.075% concentration by mass) is recommended 10.5ml chemical Rupees Ninety One Paise
diluted with 5 liters of water application 0.5 litre chemical /Sqm of surface is recommended as per I.S. Sixty Three Only
Providing and laying cement concrete 1:3:6 (1-Cement : 3- coarse sand : 6- hand broken stone aggregates 40 Rupees Three Thousand
11 05003A, 5.3.2 305.00 mmnominal size) and curing complete excluding cost of formwork in (A) Foundation and Plint Cmt 3095.25 Ninety Five Paise Twenty
Provdg. & laying cement concrete 1:2:4 (1cement:2 corse sand :4 hand broken stone aggregate 20 mm nominal size)
Ch.5-It.code. Rupees Three Thousand
and curing complete including cost of form work in (A) Foundation and plinth
12 5010AA 1164.00 Cmt 3757.61 Seven hundred Fifty Seven
(5.3.13)Pg.No.67 Paise Sixty One Only
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Providing and laying in position M-30 grade concrete for reinforced cement concrete work, using cement concrete
work using cement content as per approved Design Mix manufactured in fully automatic batching plant and
transported to site of work in transit mixer for any lead having continuous agitated mixer, manufactured as per mix
design of specified grade for reinforced cement concrete work including pumping of batching plant from transit mixer
to site of laying, cost of water tight Centering , shuttering by using 18 mm thick water proof ply with Exposed work in
centring, shuttering & Providing formwork of steel cup lock system including centring shuttering strutting and
propping etc. propping and centering below supporting floor to ceiling and removal of the same for in situ reinforced Rupees Five Thousand Four
13 RA 2347.00 concrete and plain concrete work in flat surfaces such as soffits of suspended floors slabs Landings walls, Fins and Cmt 5408.87 hundred Eight Paise Eighty
beams, column and the like, floors etc & sides and soffits of beams, Haunching cantilevers Girders, using grouting if Seven Only
required, admixture in recommended proposition as per IS:9103 to accelerated, retard, setting of concrete, improve
workability as per direction of engineer in charge and approved , rates includes all heights Up to 4.50 mt, excluding
reinforcement. (No extra will be paid in variation of cement level, minimum cement level will be as per IS 456) for
reinforced concrete work in: (A) Footing Design Mix
Providing and laying in position M-30 grade concrete for reinforced cement concrete work, using cement concrete
work using cement content as per approved Design Mix manufactured in fully automatic batching plant and
transported to site of work in transit mixer for any lead having continuous agitated mixer, manufactured as per mix
design of specified grade for reinforced cement concrete work including pumping of batching plant from transit mixer
to site of laying, cost of water tight Centering , shuttering by using 18 mm thick water proof ply with Exposed work in
centring, shuttering & Providing formwork of steel cup lock system including centring shuttering strutting and
propping etc. propping and centering below supporting floor to ceiling and removal of the same for in situ reinforced Rupees Six Thousand Four
14 RA 489.00 concrete and plain concrete work in flat surfaces such as soffits of suspended floors slabs Landings walls, Fins and Cmt 6400.83 hundred Paise Eighty Three
beams, column and the like, floors etc & sides and soffits of beams, Haunching cantilevers Girders, using grouting if Only
required, admixture in recommended proposition as per IS:9103 to accelerated, retard, setting of concrete, improve
workability as per direction of engineer in charge and approved , rates includes all heights Up to 4.50 mt, excluding
reinforcement. (No extra will be paid in variation of cement level, minimum cement level will be as per IS 456) for
reinforced concrete work in: (C) RCC Floor Beam Plinth or Tie beam
Providing and laying in position M-30 grade concrete for reinforced cement concrete work, using cement concrete
work using cement content as per approved Design Mix manufactured in fully automatic batching plant and
transported to site of work in transit mixer for any lead having continuous agitated mixer, manufactured as per mix
design of specified grade for reinforced cement concrete work including pumping of batching plant from transit mixer
to site of laying, cost of water tight Centering , shuttering by using 18 mm thick water proof ply with Exposed work in
centring, shuttering & Providing formwork of steel cup lock system including centring shuttering strutting and
propping etc. propping and centering below supporting floor to ceiling and removal of the same for in situ reinforced
concrete and plain concrete work in flat surfaces such as soffits of suspended floors slabs Landings walls, Fins and Rupees Seven Thousand Six
15 RA 314.00 beams, column and the like, floors etc & sides and soffits of beams, Haunching cantilevers Girders, using grouting if Cmt 7653.42 hundred Fifty Three Paise
required, admixture in recommended proposition as per IS:9103 to accelerated, retard, setting of concrete, improve Forty Two Only
workability as per direction of engineer in charge and approved , rates includes all heights Up to 4.50 mt, excluding
(No extra will be paid in variation of cement level, minimum cement level will be as per IS 456) for reinforced concrete
work in: Up to Plinth Level.(C) Column
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Providing and laying in position M-30 grade concrete for reinforced cement concrete work, using cement concrete
work using cement content as per approved Design Mix manufactured in fully automatic batching plant and
transported to site of work in transit mixer for any lead having continuous agitated mixer, manufactured as per mix
design of specified grade for reinforced cement concrete work including pumping of batching plant from transit mixer
to site of laying, cost of water tight Centering , shuttering by using 18 mm thick water proof ply with Exposed work in
centring, shuttering & Providing formwork of steel cup lock system including centring shuttering strutting and
propping etc. propping and centering below supporting floor to ceiling and removal of the same for in situ reinforced Rupees Seven Thousand
16 RA 54.00 concrete and plain concrete work in flat surfaces such as soffits of suspended floors slabs Landings walls, Fins and Cmt 7039.64 Thirty Nine Paise Sixty Four
beams, column and the like, floors etc & sides and soffits of beams, Haunching cantilevers Girders, using grouting if Only
required, admixture in recommended proposition as per IS:9103 to accelerated, retard, setting of concrete, improve
workability as per direction of engineer in charge and approved , rates includes all heights Up to 4.50 mt, excluding
reinforcement. (No extra will be paid in variation of cement level, minimum cement level will be as per IS 456) for
reinforced concrete work in: (C) RCC Coping (Design Mix)
Providing and laying in position M-30 grade concrete for reinforced cement concrete work, using cement concrete
work using cement content as per approved Design Mix manufactured in fully automatic batching plant and
transported to site of work in transit mixer for any lead having continuous agitated mixer, manufactured as per mix
design of specified grade for reinforced cement concrete work including pumping of batching plant from transit mixer
to site of laying, cost of water tight Centering , shuttering by using 18 mm thick water proof ply with Exposed work in
centring, shuttering & Providing formwork of steel cup lock system including centring shuttering strutting and
propping etc. propping and centering below supporting floor to ceiling and removal of the same for in situ reinforced
concrete and plain concrete work in flat surfaces such as soffits of suspended floors slabs Landings walls, Fins and Rupees Seven Thousand Six
17 RA 297.00 beams, column and the like, floors etc & sides and soffits of beams, Haunching cantilevers Girders, using grouting if Cmt 7653.42 hundred Fifty Three Paise
required, admixture in recommended proposition as per IS:9103 to accelerated, retard, setting of concrete, improve Forty Two Only
workability as per direction of engineer in charge and approved , rates includes all heights Up to 4.50 mt, excluding
(No extra will be paid in variation of cement level, minimum cement level will be as per IS 456) for reinforced concrete
work in: Above Plinth Level.
(A) Column (i) Ground Floor Design Mix
Providing and laying in position M-30 grade concrete for reinforced cement concrete work, using cement concrete
work using cement content as per approved Design Mix manufactured in fully automatic batching plant and
transported to site of work in transit mixer for any lead having continuous agitated mixer, manufactured as per mix
design of specified grade for reinforced cement concrete work including pumping of batching plant from transit mixer
to site of laying, cost of water tight Centering , shuttering by using 18 mm thick water proof ply with Exposed work in
centring, shuttering & Providing formwork of steel cup lock system including centring shuttering strutting and
propping etc. propping and centering below supporting floor to ceiling and removal of the same for in situ reinforced
concrete and plain concrete work in flat surfaces such as soffits of suspended floors slabs Landings walls, Fins and Rupees Seven Thousand Six
18 RA 293.00 beams, column and the like, floors etc & sides and soffits of beams, Haunching cantilevers Girders, using grouting if Cmt 7694.53 hundred Ninety Four Paise
required, admixture in recommended proposition as per IS:9103 to accelerated, retard, setting of concrete, improve Fifty Three Only
workability as per direction of engineer in charge and approved , rates includes all heights Up to 4.50 mt, excluding
(No extra will be paid in variation of cement level, minimum cement level will be as per IS 456) for reinforced concrete
work in: : Above Plinth Level.
(A) Column (i) FIRST Floor Design Mix
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Providing and laying in position M-30 grade concrete for reinforced cement concrete work, using cement concrete
work using cement content as per approved Design Mix manufactured in fully automatic batching plant and
transported to site of work in transit mixer for any lead having continuous agitated mixer, manufactured as per mix
design of specified grade for reinforced cement concrete work including pumping of batching plant from transit mixer
to site of laying, cost of water tight Centering , shuttering by using 18 mm thick water proof ply with Exposed work in
centring, shuttering & Providing formwork of steel cup lock system including centring shuttering strutting and
propping etc. propping and centering below supporting floor to ceiling and removal of the same for in situ reinforced
concrete and plain concrete work in flat surfaces such as soffits of suspended floors slabs Landings walls, Fins and Rupees Seven Thousand
19 RA 266.00 beams, column and the like, floors etc & sides and soffits of beams, Haunching cantilevers Girders, using grouting if Cmt 7735.65 Seven hundred Thirty Five
required, admixture in recommended proposition as per IS:9103 to accelerated, retard, setting of concrete, improve Paise Sixty Five Only
workability as per direction of engineer in charge and approved , rates includes all heights Up to 4.50 mt, excluding
(No extra will be paid in variation of cement level, minimum cement level will be as per IS 456) for reinforced concrete
work in: : Above Plinth Level.
(A) Column (i) SECOND Floor Design Mix
Providing and laying in position M-30 grade concrete for reinforced cement concrete work, using cement concrete
work using cement content as per approved Design Mix manufactured in fully automatic batching plant and
transported to site of work in transit mixer for any lead having continuous agitated mixer, manufactured as per mix
design of specified grade for reinforced cement concrete work including pumping of batching plant from transit mixer
to site of laying, cost of water tight Centering , shuttering by using 18 mm thick water proof ply with Exposed work in
centring, shuttering & Providing formwork of steel cup lock system including centring shuttering strutting and
propping etc. propping and centering below supporting floor to ceiling and removal of the same for in situ reinforced
concrete and plain concrete work in flat surfaces such as soffits of suspended floors slabs Landings walls, Fins and Rupees Seven Thousand
20 RA 102.00 beams, column and the like, floors etc & sides and soffits of beams, Haunching cantilevers Girders, using grouting if Cmt 7776.77 Seven hundred Seventy Six
required, admixture in recommended proposition as per IS:9103 to accelerated, retard, setting of concrete, improve Paise Seventy Seven Only
workability as per direction of engineer in charge and approved , rates includes all heights Up to 4.50 mt, excluding
(No extra will be paid in variation of cement level, minimum cement level will be as per IS 456) for reinforced concrete
work in: : Above Plinth Level.
(A) Column (i) Terrace Floor Design Mix
Providing and laying in position M-30 grade concrete for reinforced cement concrete work, using cement concrete
work using cement content as per approved Design Mix manufactured in fully automatic batching plant and
transported to site of work in transit mixer for any lead having continuous agitated mixer, manufactured as per mix
design of specified grade for reinforced cement concrete work including pumping of batching plant from transit mixer
to site of laying, cost of water tight Centering , shuttering by using 18 mm thick water proof ply with Exposed work in
centring, shuttering & Providing formwork of steel cup lock system including centring shuttering strutting and
propping etc. propping and centering below supporting floor to ceiling and removal of the same for in situ reinforced Rupees Eight Thousand
21 RA 37.00 concrete and plain concrete work in flat surfaces such as soffits of suspended floors slabs Landings walls, Fins and Cmt 8337.98 Three hundred Thirty Seven
beams, column and the like, floors etc & sides and soffits of beams, Haunching cantilevers Girders, using grouting if Paise Ninety Eight Only
required, admixture in recommended proposition as per IS:9103 to accelerated, retard, setting of concrete, improve
workability as per direction of engineer in charge and approved , rates includes all heights Up to 4.50 mt, excluding
reinforcement. (No extra will be paid in variation of cement level, minimum cement level will be as per IS 456) for
reinforced concrete work in: (C) RCC Lintel, sill and Mullians Bands i) Ground Floor (Design Mix)
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Providing and laying in position M-30 grade concrete for reinforced cement concrete work, using cement concrete
work using cement content as per approved Design Mix manufactured in fully automatic batching plant and
transported to site of work in transit mixer for any lead having continuous agitated mixer, manufactured as per mix
design of specified grade for reinforced cement concrete work including pumping of batching plant from transit mixer
to site of laying, cost of water tight Centering , shuttering by using 18 mm thick water proof ply with Exposed work in
centring, shuttering & Providing formwork of steel cup lock system including centring shuttering strutting and
propping etc. propping and centering below supporting floor to ceiling and removal of the same for in situ reinforced Rupees Eight Thousand
22 RA 39.00 concrete and plain concrete work in flat surfaces such as soffits of suspended floors slabs Landings walls, Fins and Cmt 8379.10 Three hundred Seventy Nine
beams, column and the like, floors etc & sides and soffits of beams, Haunching cantilevers Girders, using grouting if Paise Ten Only
required, admixture in recommended proposition as per IS:9103 to accelerated, retard, setting of concrete, improve
workability as per direction of engineer in charge and approved , rates includes all heights Up to 4.50 mt, excluding
reinforcement. (No extra will be paid in variation of cement level, minimum cement level will be as per IS 456) for
reinforced concrete work in: (C) RCC Lintel, sill and Mullians Bands i) First Floor (Design Mix)
Providing and laying in position M-30 grade concrete for reinforced cement concrete work, using cement concrete
work using cement content as per approved Design Mix manufactured in fully automatic batching plant and
transported to site of work in transit mixer for any lead having continuous agitated mixer, manufactured as per mix
design of specified grade for reinforced cement concrete work including pumping of batching plant from transit mixer
to site of laying, cost of water tight Centering , shuttering by using 18 mm thick water proof ply with Exposed work in
centring, shuttering & Providing formwork of steel cup lock system including centring shuttering strutting and
propping etc. propping and centering below supporting floor to ceiling and removal of the same for in situ reinforced Rupees Eight Thousand Four
23 RA 38.00 concrete and plain concrete work in flat surfaces such as soffits of suspended floors slabs Landings walls, Fins and Cmt 8420.22 hundred Twenty Paise
beams, column and the like, floors etc & sides and soffits of beams, Haunching cantilevers Girders, using grouting if Twenty Two Only
required, admixture in recommended proposition as per IS:9103 to accelerated, retard, setting of concrete, improve
workability as per direction of engineer in charge and approved , rates includes all heights Up to 4.50 mt, excluding
reinforcement. (No extra will be paid in variation of cement level, minimum cement level will be as per IS 456) for
reinforced concrete work in: (C) RCC Lintel, sill and Mullians Bands i) Second Floor (Design Mix)
Providing and laying in position M-30 grade concrete for reinforced cement concrete work, using cement concrete
work using cement content as per approved Design Mix manufactured in fully automatic batching plant and
transported to site of work in transit mixer for any lead having continuous agitated mixer, manufactured as per mix
design of specified grade for reinforced cement concrete work including pumping of batching plant from transit mixer
to site of laying, cost of water tight Centering , shuttering by using 18 mm thick water proof ply with Exposed work in
centring, shuttering & Providing formwork of steel cup lock system including centring shuttering strutting and
propping etc. propping and centering below supporting floor to ceiling and removal of the same for in situ reinforced
Rupees Eight Thousand Four
concrete and plain concrete work in flat surfaces such as soffits of suspended floors slabs Landings walls, Fins and
24 RA 18.00 Cmt hundred Sixty One Paise
beams, column and the like, floors etc & sides and soffits of beams, Haunching cantilevers Girders, using grouting if
Thirty Four Only
required, admixture in recommended proposition as per IS:9103 to accelerated, retard, setting of concrete, improve
workability as per direction of engineer in charge and approved , rates includes all heights Up to 4.50 mt, excluding
reinforcement. (No extra will be paid in variation of cement level, minimum cement level will be as per IS 456) for
reinforced concrete work in: (C) RCC Lintel, sill and Mullians Bands i) Third & Terrace Floor (Design Mix)
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Providing and laying in position M-30 grade concrete for reinforced cement concrete work, using cement concrete
work using cement content as per approved Design Mix manufactured in fully automatic batching plant and
transported to site of work in transit mixer for any lead having continuous agitated mixer, manufactured as per mix
design of specified grade for reinforced cement concrete work including pumping of batching plant from transit mixer
to site of laying, cost of water tight Centering , shuttering by using 18 mm thick water proof ply with Exposed work in
centring, shuttering & Providing formwork of steel cup lock system including centring shuttering strutting and
propping etc. propping and centering below supporting floor to ceiling and removal of the same for in situ reinforced Rupees Six Thousand Seven
25 RA 860.00 concrete and plain concrete work in flat surfaces such as soffits of suspended floors slabs Landings walls, Fins and Cmt 6752.04 hundred Fifty Two Paise Four
beams, column and the like, floors etc & sides and soffits of beams, Haunching cantilevers Girders, using grouting if Only
required, admixture in recommended proposition as per IS:9103 to accelerated, retard, setting of concrete, improve
workability as per direction of engineer in charge and approved , rates includes all heights Up to 4.50 mt, excluding
reinforcement. (No extra will be paid in variation of cement level, minimum cement level will be as per IS 456) for
reinforced concrete work in: (C) RCC Basement & Ground Floor Slab Beam
Providing and laying in position M-30 grade concrete for reinforced cement concrete work, using cement concrete
work using cement content as per approved Design Mix manufactured in fully automatic batching plant and
transported to site of work in transit mixer for any lead having continuous agitated mixer, manufactured as per mix
design of specified grade for reinforced cement concrete work including pumping of batching plant from transit mixer
to site of laying, cost of water tight Centering , shuttering by using 18 mm thick water proof ply with Exposed work in
centring, shuttering & Providing formwork of steel cup lock system including centring shuttering strutting and
propping etc. propping and centering below supporting floor to ceiling and removal of the same for in situ reinforced Rupees Six Thousand Seven
26 RA 505.00 concrete and plain concrete work in flat surfaces such as soffits of suspended floors slabs Landings walls, Fins and Cmt 6793.16 hundred Ninety Three Paise
beams, column and the like, floors etc & sides and soffits of beams, Haunching cantilevers Girders, using grouting if Sixteen Only
required, admixture in recommended proposition as per IS:9103 to accelerated, retard, setting of concrete, improve
workability as per direction of engineer in charge and approved , rates includes all heights Up to 4.50 mt, excluding
reinforcement. (No extra will be paid in variation of cement level, minimum cement level will be as per IS 456) for
reinforced concrete work in: (C) RCC First Floor Slab Beam
Providing and laying in position M-30 grade concrete for reinforced cement concrete work, using cement concrete
work using cement content as per approved Design Mix manufactured in fully automatic batching plant and
transported to site of work in transit mixer for any lead having continuous agitated mixer, manufactured as per mix
design of specified grade for reinforced cement concrete work including pumping of batching plant from transit mixer
to site of laying, cost of water tight Centering , shuttering by using 18 mm thick water proof ply with Exposed work in
centring, shuttering & Providing formwork of steel cup lock system including centring shuttering strutting and
propping etc. propping and centering below supporting floor to ceiling and removal of the same for in situ reinforced Rupees Six Thousand Eight
27 RA 453.00 concrete and plain concrete work in flat surfaces such as soffits of suspended floors slabs Landings walls, Fins and Cmt 6834.28 hundred Thirty Four Paise
beams, column and the like, floors etc & sides and soffits of beams, Haunching cantilevers Girders, using grouting if Twenty Eight Only
required, admixture in recommended proposition as per IS:9103 to accelerated, retard, setting of concrete, improve
workability as per direction of engineer in charge and approved , rates includes all heights Up to 4.50 mt, excluding
reinforcement. (No extra will be paid in variation of cement level, minimum cement level will be as per IS 456) for
reinforced concrete work in: (C) RCC Second Floor Slab Beam
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Providing and laying in position M-30 grade concrete for reinforced cement concrete work, using cement concrete
work using cement content as per approved Design Mix manufactured in fully automatic batching plant and
transported to site of work in transit mixer for any lead having continuous agitated mixer, manufactured as per mix
design of specified grade for reinforced cement concrete work including pumping of batching plant from transit mixer
to site of laying, cost of water tight Centering , shuttering by using 18 mm thick water proof ply with Exposed work in
centring, shuttering & Providing formwork of steel cup lock system including centring shuttering strutting and
propping etc. propping and centering below supporting floor to ceiling and removal of the same for in situ reinforced Rupees Six Thousand Eight
28 RA 58.00 concrete and plain concrete work in flat surfaces such as soffits of suspended floors slabs Landings walls, Fins and Cmt 6875.39 hundred Seventy Five Paise
beams, column and the like, floors etc & sides and soffits of beams, Haunching cantilevers Girders, using grouting if Thirty Nine Only
required, admixture in recommended proposition as per IS:9103 to accelerated, retard, setting of concrete, improve
workability as per direction of engineer in charge and approved , rates includes all heights Up to 4.50 mt, excluding
reinforcement. (No extra will be paid in variation of cement level, minimum cement level will be as per IS 456) for
reinforced concrete work in: (C) RCC Terrace Floor Slab Beam
Providing and laying in position M-30 grade concrete for reinforced cement concrete work, using Exposed cement
concrete work using cement content as per approved Design Mix manufactured in fully automatic batching plant and
transported to site of work in transit mixer for any lead having continuous agitated mixer, manufactured as per mix
design of specified grade for reinforced cement concrete work including pumping of batching plant from transit mixer
to site of laying, cost of water tight Centering , shuttering by using 18 mm thick water proof ply with Exposed work in
centring, shuttering & Providing formwork of steel cup lock system including centring shuttering strutting and
propping etc. propping and centering below supporting floor to ceiling and removal of the same for in situ reinforced Rupees Seven Thousand
29 RA 18.00 concrete and plain concrete work in flat surfaces such as soffits of suspended floors slabs Landings walls, Fins and Cmt 7255.82 Two hundred Fifty Five Paise
beams, column and the like, floors etc & sides and soffits of beams, Haunching cantilevers Girders, using grouting if Eighty Two Only
required, admixture in recommended proposition as per IS:9103 to accelerated, retard, setting of concrete, improve
workability as per direction of engineer in charge and approved , rates includes all heights Up to 4.50 mt, excluding
reinforcement. (No extra will be paid in variation of cement level, minimum cement level will be as per IS 456) for
reinforced concrete work in: (C) RCC Weathershed Ground Floor
Providing and laying in position M-30 grade concrete for reinforced cement concrete work, using Exposed cement
concrete work using cement content as per approved Design Mix manufactured in fully automatic batching plant and
transported to site of work in transit mixer for any lead having continuous agitated mixer, manufactured as per mix
design of specified grade for reinforced cement concrete work including pumping of batching plant from transit mixer
to site of laying, cost of water tight Centering , shuttering by using 18 mm thick water proof ply with Exposed work in
centring, shuttering & Providing formwork of steel cup lock system including centring shuttering strutting and
propping etc. propping and centering below supporting floor to ceiling and removal of the same for in situ reinforced Rupees Seven Thousand
30 RA 18.00 concrete and plain concrete work in flat surfaces such as soffits of suspended floors slabs Landings walls, Fins and Cmt 7296.94 Two hundred Ninety Six
beams, column and the like, floors etc & sides and soffits of beams, Haunching cantilevers Girders, using grouting if Paise Ninety Four Only
required, admixture in recommended proposition as per IS:9103 to accelerated, retard, setting of concrete, improve
workability as per direction of engineer in charge and approved , rates includes all heights Up to 4.50 mt, excluding
reinforcement. (No extra will be paid in variation of cement level, minimum cement level will be as per IS 456) for
reinforced concrete work in: (C) RCC Weathershed First Floor
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Providing and laying in position M-30 grade concrete for reinforced cement concrete work, using Exposed cement
concrete work using cement content as per approved Design Mix manufactured in fully automatic batching plant and
transported to site of work in transit mixer for any lead having continuous agitated mixer, manufactured as per mix
design of specified grade for reinforced cement concrete work including pumping of batching plant from transit mixer
to site of laying, cost of water tight Centering , shuttering by using 18 mm thick water proof ply with Exposed work in
centring, shuttering & Providing formwork of steel cup lock system including centring shuttering strutting and
propping etc. propping and centering below supporting floor to ceiling and removal of the same for in situ reinforced Rupees Seven Thousand
31 RA 13.00 concrete and plain concrete work in flat surfaces such as soffits of suspended floors slabs Landings walls, Fins and Cmt 7338.05 Three hundred Thirty Eight
beams, column and the like, floors etc & sides and soffits of beams, Haunching cantilevers Girders, using grouting if Paise Five Only
required, admixture in recommended proposition as per IS:9103 to accelerated, retard, setting of concrete, improve
workability as per direction of engineer in charge and approved , rates includes all heights Up to 4.50 mt, excluding
reinforcement. (No extra will be paid in variation of cement level, minimum cement level will be as per IS 456) for
reinforced concrete work in: (C) RCC Weathershed Second Floor
Providing and laying in position M-30 grade concrete for reinforced cement concrete work, using Exposed cement
concrete work using cement content as per approved Design Mix manufactured in fully automatic batching plant and
transported to site of work in transit mixer for any lead having continuous agitated mixer, manufactured as per mix
design of specified grade for reinforced cement concrete work including pumping of batching plant from transit mixer
to site of laying, cost of water tight Centering , shuttering by using 18 mm thick water proof ply with Exposed work in
centring, shuttering & Providing formwork of steel cup lock system including centring shuttering strutting and
propping etc. propping and centering below supporting floor to ceiling and removal of the same for in situ reinforced Rupees Seven Thousand
32 RA 2.00 concrete and plain concrete work in flat surfaces such as soffits of suspended floors slabs Landings walls, Fins and Cmt 7379.17 Three hundred Seventy Nine
beams, column and the like, floors etc & sides and soffits of beams, Haunching cantilevers Girders, using grouting if Paise Seventeen Only
required, admixture in recommended proposition as per IS:9103 to accelerated, retard, setting of concrete, improve
workability as per direction of engineer in charge and approved , rates includes all heights Up to 4.50 mt, excluding
reinforcement. (No extra will be paid in variation of cement level, minimum cement level will be as per IS 456) for
reinforced concrete work in: (C) RCC Weathershed Third & Terrace Floor
Providing and laying in position M-30 grade concrete for reinforced cement concrete work, using cement concrete
work using cement content as per approved Design Mix manufactured in fully automatic batching plant and
transported to site of work in transit mixer for any lead having continuous agitated mixer, manufactured as per mix
design of specified grade for reinforced cement concrete work including pumping of batching plant from transit mixer
to site of laying, cost of water tight Centering , shuttering by using 18 mm thick water proof ply with Exposed work in
centring, shuttering & Providing formwork of steel cup lock system including centring shuttering strutting and
propping etc. propping and centering below supporting floor to ceiling and removal of the same for in situ reinforced Rupees Seven Thousand
33 RA 464.00 Cmt 7724.60 Seven hundred Twenty Four
concrete and plain concrete work in flat surfaces such as soffits of suspended floors slabs Landings walls, Fins and
beams, column and the like, floors etc & sides and soffits of beams, Haunching cantilevers Girders, using grouting if Paise Sixty Only
required, admixture in recommended proposition as per IS:9103 to accelerated, retard, setting of concrete, improve
workability as per direction of engineer in charge and approved , rates includes all heights Up to 4.50 mt, excluding
reinforcement. (No extra will be paid in variation of cement level, minimum cement level will be as per IS 456) for
reinforced concrete work in: (C) Base Slab (Design Mix)
Providing and laying controlled cement concrete M.200 and curing complete excluding the cost of formwork and
Rupees Four Thousand
34 RA 141.00 reinforcement for reinforced concrete work in (A) Foundations, footings, Base of columns and Mass concrete. at Cmt 4080.69
Eighty Paise Sixty Nine Only
Grade Slab at Plinth level
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Providing and laying in position M-30 grade concrete for reinforced cement concrete work, using cement concrete
work using cement content as per approved Design Mix manufactured in fully automatic batching plant and
transported to site of work in transit mixer for any lead having continuous agitated mixer, manufactured as per mix
design of specified grade for reinforced cement concrete work including pumping of batching plant from transit mixer
to site of laying, cost of water tight Centering , shuttering by using 18 mm thick water proof ply with Exposed work in
centring, shuttering & Providing formwork of steel cup lock system including centring shuttering strutting and
propping etc. propping and centering below supporting floor to ceiling and removal of the same for in situ reinforced Rupees Seven Thousand
35 RA 460.00 concrete and plain concrete work in flat surfaces such as soffits of suspended floors slabs Landings walls, Fins and Cmt 7724.60 Seven hundred Twenty Four
beams, column and the like, floors etc & sides and soffits of beams, Haunching cantilevers Girders, using grouting if Paise Sixty Only
required, admixture in recommended proposition as per IS:9103 to accelerated, retard, setting of concrete, improve
workability as per direction of engineer in charge and approved , rates includes all heights Up to 4.50 mt, excluding
reinforcement. (No extra will be paid in variation of cement level, minimum cement level will be as per IS 456) for
reinforced concrete work in: (C) Ground Floor Slab (Design Mix)
Providing and laying in position M-30 grade concrete for reinforced cement concrete work, using cement concrete
work using cement content as per approved Design Mix manufactured in fully automatic batching plant and
transported to site of work in transit mixer for any lead having continuous agitated mixer, manufactured as per mix
design of specified grade for reinforced cement concrete work including pumping of batching plant from transit mixer
to site of laying, cost of water tight Centering , shuttering by using 18 mm thick water proof ply with Exposed work in
centring, shuttering & Providing formwork of steel cup lock system including centring shuttering strutting and
propping etc. propping and centering below supporting floor to ceiling and removal of the same for in situ reinforced Rupees Seven Thousand
36 RA 460.00 concrete and plain concrete work in flat surfaces such as soffits of suspended floors slabs Landings walls, Fins and Cmt 7765.72 Seven hundred Sixty Five
beams, column and the like, floors etc & sides and soffits of beams, Haunching cantilevers Girders, using grouting if Paise Seventy Two Only
required, admixture in recommended proposition as per IS:9103 to accelerated, retard, setting of concrete, improve
workability as per direction of engineer in charge and approved , rates includes all heights Up to 4.50 mt, excluding
reinforcement. (No extra will be paid in variation of cement level, minimum cement level will be as per IS 456) for
reinforced concrete work in: (C) First Floor Slab (Design Mix)
Providing and laying in position M-30 grade concrete for reinforced cement concrete work, using cement concrete
work using cement content as per approved Design Mix manufactured in fully automatic batching plant and
transported to site of work in transit mixer for any lead having continuous agitated mixer, manufactured as per mix
design of specified grade for reinforced cement concrete work including pumping of batching plant from transit mixer
to site of laying, cost of water tight Centering , shuttering by using 18 mm thick water proof ply with Exposed work in
centring, shuttering & Providing formwork of steel cup lock system including centring shuttering strutting and
propping etc. propping and centering below supporting floor to ceiling and removal of the same for in situ reinforced Rupees Seven Thousand
37 RA 416.00 concrete and plain concrete work in flat surfaces such as soffits of suspended floors slabs Landings walls, Fins and Cmt 7806.84 Eight hundred Six Paise
beams, column and the like, floors etc & sides and soffits of beams, Haunching cantilevers Girders, using grouting if Eighty Four Only
required, admixture in recommended proposition as per IS:9103 to accelerated, retard, setting of concrete, improve
workability as per direction of engineer in charge and approved , rates includes all heights Up to 4.50 mt, excluding
reinforcement. (No extra will be paid in variation of cement level, minimum cement level will be as per IS 456) for
reinforced concrete work in: (C) Second Floor Slab (Design Mix)
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Providing and laying in position M-30 grade concrete for reinforced cement concrete work, using cement concrete
work using cement content as per approved Design Mix manufactured in fully automatic batching plant and
transported to site of work in transit mixer for any lead having continuous agitated mixer, manufactured as per mix
design of specified grade for reinforced cement concrete work including pumping of batching plant from transit mixer
to site of laying, cost of water tight Centering , shuttering by using 18 mm thick water proof ply with Exposed work in
centring, shuttering & Providing formwork of steel cup lock system including centring shuttering strutting and
propping etc. propping and centering below supporting floor to ceiling and removal of the same for in situ reinforced Rupees Seven Thousand
38 RA 63.00 concrete and plain concrete work in flat surfaces such as soffits of suspended floors slabs Landings walls, Fins and Cmt 7847.95 Eight hundred Forty Seven
beams, column and the like, floors etc & sides and soffits of beams, Haunching cantilevers Girders, using grouting if Paise Ninety Five Only
required, admixture in recommended proposition as per IS:9103 to accelerated, retard, setting of concrete, improve
workability as per direction of engineer in charge and approved , rates includes all heights Up to 4.50 mt, excluding
reinforcement. (No extra will be paid in variation of cement level, minimum cement level will be as per IS 456) for
reinforced concrete work in: (C) Third & Terrace Slab (Design Mix)
Providing and laying in position M-30 grade concrete for reinforced cement concrete work, using cement concrete
work using cement content as per approved Design Mix manufactured in fully automatic batching plant and
transported to site of work in transit mixer for any lead having continuous agitated mixer, manufactured as per mix
design of specified grade for reinforced cement concrete work including pumping of batching plant from transit mixer
to site of laying, cost of water tight Centering , shuttering by using 18 mm thick water proof ply with Exposed work in
centring, shuttering & Providing formwork of steel cup lock system including centring shuttering strutting and
propping etc. propping and centering below supporting floor to ceiling and removal of the same for in situ reinforced Rupees Seven Thousand Six
39 RA 127.00 concrete and plain concrete work in flat surfaces such as soffits of suspended floors slabs Landings walls, Fins and Cmt 7616.71 hundred Sixteen Paise
beams, column and the like, floors etc & sides and soffits of beams, Haunching cantilevers Girders, using grouting if Seventy One Only
required, admixture in recommended proposition as per IS:9103 to accelerated, retard, setting of concrete, improve
workability as per direction of engineer in charge and approved , rates includes all heights Up to 4.50 mt, excluding
reinforcement. (No extra will be paid in variation of cement level, minimum cement level will be as per IS 456) for
reinforced concrete work in:(E) Stair case (i) Ground Fl.Design Mix
Providing and laying in position M-30 grade concrete for reinforced cement concrete work, using cement concrete
work using cement content as per approved Design Mix manufactured in fully automatic batching plant and
transported to site of work in transit mixer for any lead having continuous agitated mixer, manufactured as per mix
design of specified grade for reinforced cement concrete work including pumping of batching plant from transit mixer
to site of laying, cost of water tight Centering , shuttering by using 18 mm thick water proof ply with Exposed work in
centring, shuttering & Providing formwork of steel cup lock system including centring shuttering strutting and
propping etc. propping and centering below supporting floor to ceiling and removal of the same for in situ reinforced Rupees Seven Thousand Six
40 RA 64.00 concrete and plain concrete work in flat surfaces such as soffits of suspended floors slabs Landings walls, Fins and Cmt 7657.83 hundred Fifty Seven Paise
beams, column and the like, floors etc & sides and soffits of beams, Haunching cantilevers Girders, using grouting if Eighty Three Only
required, admixture in recommended proposition as per IS:9103 to accelerated, retard, setting of concrete, improve
workability as per direction of engineer in charge and approved , rates includes all heights Up to 4.50 mt, excluding
reinforcement. (No extra will be paid in variation of cement level, minimum cement level will be as per IS 456) for
reinforced concrete work in: (E) Stair case (i) First Fl. Design Mix
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Providing and laying in position M-30 grade concrete for reinforced cement concrete work, using cement concrete
work using cement content as per approved Design Mix manufactured in fully automatic batching plant and
transported to site of work in transit mixer for any lead having continuous agitated mixer, manufactured as per mix
design of specified grade for reinforced cement concrete work including pumping of batching plant from transit mixer
to site of laying, cost of water tight Centering , shuttering by using 18 mm thick water proof ply with Exposed work in
centring, shuttering & Providing formwork of steel cup lock system including centring shuttering strutting and
propping etc. propping and centering below supporting floor to ceiling and removal of the same for in situ reinforced Rupees Seven Thousand Six
41 RA 51.00 concrete and plain concrete work in flat surfaces such as soffits of suspended floors slabs Landings walls, Fins and Cmt 7698.95 hundred Ninety Eight Paise
beams, column and the like, floors etc & sides and soffits of beams, Haunching cantilevers Girders, using grouting if Ninety Five Only
required, admixture in recommended proposition as per IS:9103 to accelerated, retard, setting of concrete, improve
workability as per direction of engineer in charge and approved , rates includes all heights Up to 4.50 mt, excluding
reinforcement. (No extra will be paid in variation of cement level, minimum cement level will be as per IS 456) for
reinforced concrete work in: (E) Stair case (i) SECOND Fl. Design Mix
Providing and laying in position M-30 grade concrete for reinforced cement concrete work, using cement concrete
work using cement content as per approved Design Mix manufactured in fully automatic batching plant and
transported to site of work in transit mixer for any lead having continuous agitated mixer, manufactured as per mix
design of specified grade for reinforced cement concrete work including pumping of batching plant from transit mixer
to site of laying, cost of water tight Centering , shuttering by using 18 mm thick water proof ply with Exposed work in
centring, shuttering & Providing formwork of steel cup lock system including centring shuttering strutting and
propping etc. propping and centering below supporting floor to ceiling and removal of the same for in situ reinforced Rupees Six Thousand Eight
42 RA 523.00 concrete and plain concrete work in flat surfaces such as soffits of suspended floors slabs Landings walls, Fins and Cmt 6881.87 hundred Eighty One Paise
beams, column and the like, floors etc & sides and soffits of beams, Haunching cantilevers Girders, using grouting if Eighty Seven Only
required, admixture in recommended proposition as per IS:9103 to accelerated, retard, setting of concrete, improve
workability as per direction of engineer in charge and approved , rates includes all heights Up to 4.50 mt, excluding
reinforcement. (No extra will be paid in variation of cement level, minimum cement level will be as per IS 456) for
reinforced concrete work in: (D) RCC Wall up to Ground floor (Design Mix)
Providing and laying in position M-30 grade concrete for reinforced cement concrete work, using cement concrete
work using cement content as per approved Design Mix manufactured in fully automatic batching plant and
transported to site of work in transit mixer for any lead having continuous agitated mixer, manufactured as per mix
design of specified grade for reinforced cement concrete work including pumping of batching plant from transit mixer
to site of laying, cost of water tight Centering , shuttering by using 18 mm thick water proof ply with Exposed work in
centring, shuttering & Providing formwork of steel cup lock system including centring shuttering strutting and
propping etc. propping and centering below supporting floor to ceiling and removal of the same for in situ reinforced Rupees Six Thousand Nine
43 RA 46.00 concrete and plain concrete work in flat surfaces such as soffits of suspended floors slabs Landings walls, Fins and Cmt 6922.98 hundred Twenty Two Paise
beams, column and the like, floors etc & sides and soffits of beams, Haunching cantilevers Girders, using grouting if Ninety Eight Only
required, admixture in recommended proposition as per IS:9103 to accelerated, retard, setting of concrete, improve
workability as per direction of engineer in charge and approved , rates includes all heights Up to 4.50 mt, excluding
reinforcement. (No extra will be paid in variation of cement level, minimum cement level will be as per IS 456) for
reinforced concrete work in: (D) RCC Wall up to First Floor Slab lvl. (Design Mix)
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Providing and laying in position M-30 grade concrete for reinforced cement concrete work, using cement concrete
work using cement content as per approved Design Mix manufactured in fully automatic batching plant and
transported to site of work in transit mixer for any lead having continuous agitated mixer, manufactured as per mix
design of specified grade for reinforced cement concrete work including pumping of batching plant from transit mixer
to site of laying, cost of water tight Centering , shuttering by using 18 mm thick water proof ply with Exposed work in
centring, shuttering & Providing formwork of steel cup lock system including centring shuttering strutting and
propping etc. propping and centering below supporting floor to ceiling and removal of the same for in situ reinforced Rupees Six Thousand Nine
44 RA 46.00 concrete and plain concrete work in flat surfaces such as soffits of suspended floors slabs Landings walls, Fins and Cmt 6964.10 hundred Sixty Four Paise Ten
beams, column and the like, floors etc & sides and soffits of beams, Haunching cantilevers Girders, using grouting if Only
required, admixture in recommended proposition as per IS:9103 to accelerated, retard, setting of concrete, improve
workability as per direction of engineer in charge and approved , rates includes all heights Up to 4.50 mt, excluding
reinforcement. (No extra will be paid in variation of cement level, minimum cement level will be as per IS 456) for
reinforced concrete work in: (D) RCC Wall up to Second floor (Design Mix)
Providing and laying in position M-30 grade concrete for reinforced cement concrete work, using cement concrete
work using cement content as per approved Design Mix manufactured in fully automatic batching plant and
transported to site of work in transit mixer for any lead having continuous agitated mixer, manufactured as per mix
design of specified grade for reinforced cement concrete work including pumping of batching plant from transit mixer
to site of laying, cost of water tight Centering , shuttering by using 18 mm thick water proof ply with Exposed work in
centring, shuttering & Providing formwork of steel cup lock system including centring shuttering strutting and
propping etc. propping and centering below supporting floor to ceiling and removal of the same for in situ reinforced Rupees Seven Thousand Five
45 RA 46.00 concrete and plain concrete work in flat surfaces such as soffits of suspended floors slabs Landings walls, Fins and Cmt 7005.22
Paise Twenty Two Only
beams, column and the like, floors etc & sides and soffits of beams, Haunching cantilevers Girders, using grouting if
required, admixture in recommended proposition as per IS:9103 to accelerated, retard, setting of concrete, improve
workability as per direction of engineer in charge and approved , rates includes all heights Up to 4.50 mt, excluding
reinforcement. (No extra will be paid in variation of cement level, minimum cement level will be as per IS 456) for
reinforced concrete work in: (D) RCC Wall up to Terrace floor (Design Mix)
Providing laying controlled cement concrete M-250 and curing complete excluding the cost of form work and Rupees Four Thousand
46 RA 94.00 reinforcement for reinforced concrete work in (A) for foundation, footing, Bases of columns etc and Mass concrete Cmt 4745.43 Seven hundred Forty Five
Paise Forty Three Only
Providing & laying controlled cement concrete M-250 with curing etc. complete incl. the cost of form work but Rupees Seven Thousand
47 RA 7.00 excluding the cost of reinforcement for R.C.C. work for column up to plinth. Cmt 7838.95 Eight hundred Thirty Eight
Paise Ninety Five Only
Providing & laying controlled cement concrete M-250 with curing etc. complete incl. the cost of form work but
Rupees Five Thousand Eight
excluding the cost of reinforcement for R.C.C. work for Ground beam & Plinth beams etc.
48 RA 35.00 Cmt 5898.96 hundred Ninety Eight Paise
Ninety Six Only
Providing & laying controlled cement concrete M-200 with curing etc. complete including the cost of form work but
Rupees Five Thousand Eight
excluding the cost of reinforcement for R.C.C. work in foundation and plinth for Copping.
49 RA 7.00 Cmt 5898.96 hundred Ninety Eight Paise
Ninety Six Only
Providing & laying controlled cement concrete M-200 with curing etc. complete including the cost of form work but Rupees Seven Thousand
50 RA 12.00 excluding the cost of reinforcement for R.C.C. work at Ground Floor for Column. Cmt 7965.82 Nine hundred Sixty Five Paise
Eighty Two Only
Providing & laying controlled cement concrete M-200 with curing etc. complete including the cost of form work but Rupees Six Thousand Five
51 RA 40.00 excluding the cost of reinforcement for R.C.C. work at Ground Floor for Beam, Lintel, Chajja. Cmt 6596.56 hundred Ninety Six Paise
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Providing and Laying controlled Cement Concrete M-200 and curing etc. Complete including the cost of form work
Rupees Six Thousand Seven
but excluding the cost of reinforcement for R.C.C. work at Ground Floor for Slabs & Shelves etc.
52 RA 34.00 Cmt 6785.92 hundred Eighty Five Paise
Ninety Two Only
Providing and laying Controlled CC road Tri mix M-200 having thickness 100 mm including preparing sub base with
providing and fixing channels of 75 mm as per required level slope and thickness of concrete road leveling of placed
concrete with surface vibrators finishing surface with power floater and trowel light booming on the surface including Rupees Six hundred Nine
providing expansion joint by concrete cutter machine and filling joint by using color 200 as per manufacturers Paise Eighty Two Only
specifications and making construction joint of 5 mm x 50 mm by using concrete cutter machine etc complete as
directed by Engineer in charge.
Avrage 05014C Providing TMT Bar FE 500/500D reinforcement for R.C.C. work including bending, binding and placing in position
(5.4.11 complete upto any floor any height
pg-72+ Rupees Seventy Eight Paise
05014C+05016A Thirty Four Only
05014C Providing TMT Bar FE 500/500D reinforcement for R.C.C. work including bending, binding and placing in position Rupees Seventy Seven Paise
(5.4.11 ) complete. Twenty Nine Only
06002B Brick work using common burnt clay building bricks having crushing strength not less than 35 kg./Sq.Cm. in foundation Rupees Four Thousand Two
55 6.13 621.00 and plinth in Cement Mortar 1:6 (1- Cement : 6 -fine sand)(B) Conventional. Cmt 4214.33 hundred Fourteen Paise
Pg.No.84 Thirty Three Only
Brick work using common burnt clay building bricks having crushing strength not less than 35 kg./Sq.Cm. in foundation
Ch-6 06002B Rupees Four Thousand Two
and plinth in Cement Mortar 1:6 (1- Cement : 6 -fine sand)(B) Conventional. Extra for brick work in superstructure
56 6.13 + 06007A2A 73.00 Cmt 4256.76 hundred Fifty Six Paise
above floor two
Pg.No.84 Seventy Six Only
level Item No. 1(6.12) (B) Conventional
Ch-6 06008A2A Half brick masonry in common brunt clay building bricks having crushing strength not less than 35 Kg/Sq.Cm. in
Rupees Six hundred Ninety
57 6.3 92.00 Cement mortar 1:4 (1- Cement : 4 -coarse sand ) in foundation and plinth (B) Conventional Smt 694.68
Four Paise Sixty Eight Only
14015BA Providing and laying cement concrete flooring 1:2:4 (1-cement : 2-coarse sand : 4-graded stone aggregate 20mm
Rupees Three hundred Sixty
58 14.71 112.00 nominal size) laid in one layer and finished with a floating coat of neat cement. (B) 50mm thick. Smt 369.13
Nine Paise Thirteen Only
Providing 15 mm thick cement plaster 1:3 (1 cement: 3 sand) in Sunken floor single coat on brick / concrete Floor &
wall for interior plastering & finishing with a floating coat of neat cement slurry with providing and mixing water Rupees Two hundred Ninety
proofing compound in cement mortar & neat cement slurry in proportion recommended by the manufacturer Paise Eighty Eight Only
specification etc complete for all floor.
Providing and laying autoclave aerated concrete blocks as per drawing (Thickness 200 mm) in single or multiple
layers with approved block laying polymer modified adhesive mortar. Crushing strength of aerated concrete block
shall not be less than 40 KG/sqcm, minimum density in oven dry condition between 651 to 750 KG/CUM, thermal
conductivity shall not exceed 0.30 w/mk, fire resistant 4 hours, in true line level and plumb and cleaning the surface
Rupees Four Thousand Five
Ch.6-It.code.6014 with necessary tool tackles The drying shrinkage shall be not more than 0.05 percent for Grade 1 blocks and
60 962.00 Cmt 4598.92 hundred Ninety Eight Paise
Pg.No.88 percent for Grade 2 blocks when tested in accordance with IS : 6641 (Part-2)-1972 etc. including curing, scaffolding,
Ninety Two Only
racking / flush jointing etc complete, as per drawing / specification etc, complete As per drawings and design supplied
by architect and instruction given E.I.C. For all civil, plumbing, electrical & infrastructure works.
a) Ground FLoor
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Providing and laying autoclave aerated concrete blocks as per drawing (Thickness 200 mm) in single or multiple
layers with approved block laying polymer modified adhesive mortar. Crushing strength of aerated concrete block
shall not be less than 40 KG/sqcm, minimum density in oven dry condition between 651 to 750 KG/CUM, thermal
conductivity shall not exceed 0.30 w/mk, fire resistant 4 hours, in true line level and plumb and cleaning the surface
Ch.6-It.code.6014 Rupees Four Thousand Six
with necessary tool tackles The drying shrinkage shall be not more than 0.05 percent for Grade 1 blocks and
61 +06008E2A 961.00 Cmt 4641.35 hundred Forty One Paise
percent for Grade 2 blocks when tested in accordance with IS : 6641 (Part-2)-1972 etc. including curing, scaffolding,
Pg.No.88 Thirty Five Only
racking / flush jointing etc complete, as per drawing / specification etc, complete As per drawings and design supplied
by architect and instruction given E.I.C. For all civil, plumbing, electrical & infrastructure works.
Providing and laying autoclave aerated concrete blocks as per drawing (Thickness 200 mm) in single or multiple
layers with approved block laying polymer modified adhesive mortar. Crushing strength of aerated concrete block
shall not be less than 40 KG/sqcm, minimum density in oven dry condition between 651 to 750 KG/CUM, thermal
conductivity shall not exceed 0.30 w/mk, fire resistant 4 hours, in true line level and plumb and cleaning the surface
Ch.6-It.code.6014 Rupees Four Thousand Six
with necessary tool tackles The drying shrinkage shall be not more than 0.05 percent for Grade 1 blocks and
62 +06008E2A 872.00 Cmt 4683.78 hundred Eighty Three Paise
percent for Grade 2 blocks when tested in accordance with IS : 6641 (Part-2)-1972 etc. including curing, scaffolding,
Pg.No.88 Seventy Eight Only
racking / flush jointing etc complete, as per drawing / specification etc, complete As per drawings and design supplied
by architect and instruction given E.I.C. For all civil, plumbing, electrical & infrastructure works.
c) Second Floor
Providing and laying autoclave aerated concrete blocks as per drawing (Thickness 200 mm) in single or multiple
layers with approved block laying polymer modified adhesive mortar. Crushing strength of aerated concrete block
shall not be less than 40 KG/sqcm, minimum density in oven dry condition between 651 to 750 KG/CUM, thermal
conductivity shall not exceed 0.30 w/mk, fire resistant 4 hours, in true line level and plumb and cleaning the surface
Ch.6-It.code.6014 Rupees Four Thousand
with necessary tool tackles The drying shrinkage shall be not more than 0.05 percent for Grade 1 blocks and
63 +06008E2A 276.00 Cmt 4726.21 Seven hundred Twenty Six
percent for Grade 2 blocks when tested in accordance with IS : 6641 (Part-2)-1972 etc. including curing, scaffolding,
Pg.No.88 Paise Twenty One Only
racking / flush jointing etc complete, as per drawing / specification etc, complete As per drawings and design supplied
by architect and instruction given E.I.C. For all civil, plumbing, electrical & infrastructure works.
d) Third Floor & Terrace
Providing and laying autoclave aerated concrete blocks as per drawing (Thickness 100 mm ) in single or multiple
layers with approved block laying polymer modified adhesive mortar. Crushing strength of aerated concrete block
shall not be less than 40 KG/sqcm, minimum density in oven dry condition between 651 to 750 KG/CUM, thermal
conductivity shall not exceed 0.30 w/mk, fire resistant 4 hours, in true line level and plumb and cleaning the surface
Rupees Four Thousand Five
Ch.6-It.code.6014 with necessary tool tackles The drying shrinkage shall be not more than 0.05 percent for Grade 1 blocks and
64 82.00 Cmt 4598.92 hundred Ninety Eight Paise
Pg.No.88 percent for Grade 2 blocks when tested in accordance with IS : 6641 (Part-2)-1972 etc. including curing, scaffolding,
Ninety Two Only
racking / flush jointing etc complete, as per drawing / specification etc, complete As per drawings and design supplied
by architect and instruction given E.I.C. For all civil, plumbing, electrical & infrastructure works.
a) Ground Floor
Providing and laying autoclave aerated concrete blocks as per drawing (Thickness 100 mm ) in single or multiple
layers with approved block laying polymer modified adhesive mortar. Crushing strength of aerated concrete block
shall not be less than 40 KG/sqcm, minimum density in oven dry condition between 651 to 750 KG/CUM, thermal
conductivity shall not exceed 0.30 w/mk, fire resistant 4 hours, in true line level and plumb and cleaning the surface
Ch.6-It.code.6014 Rupees Four Thousand Six
with necessary tool tackles The drying shrinkage shall be not more than 0.05 percent for Grade 1 blocks and
65 +06008E2A 95.00 Cmt 4641.35 hundred Forty One Paise
percent for Grade 2 blocks when tested in accordance with IS : 6641 (Part-2)-1972 etc. including curing, scaffolding,
Pg.No.88 Thirty Five Only
racking / flush jointing etc complete, as per drawing / specification etc, complete As per drawings and design supplied
by architect and instruction given E.I.C. For all civil, plumbing, electrical & infrastructure works.
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Providing and laying autoclave aerated concrete blocks as per drawing (Thickness 100 mm ) in single or multiple
layers with approved block laying polymer modified adhesive mortar. Crushing strength of aerated concrete block
shall not be less than 40 KG/sqcm, minimum density in oven dry condition between 651 to 750 KG/CUM, thermal
conductivity shall not exceed 0.30 w/mk, fire resistant 4 hours, in true line level and plumb and cleaning the surface
Ch.6-It.code.6014 Rupees Four Thousand Six
with necessary tool tackles The drying shrinkage shall be not more than 0.05 percent for Grade 1 blocks and
66 +06008E2A 102.00 Cmt 4683.78 hundred Eighty Three Paise
percent for Grade 2 blocks when tested in accordance with IS : 6641 (Part-2)-1972 etc. including curing, scaffolding,
Pg.No.88 Seventy Eight Only
racking / flush jointing etc complete, as per drawing / specification etc, complete As per drawings and design supplied
by architect and instruction given E.I.C. For all civil, plumbing, electrical & infrastructure works.
c) Second Floor
Providing and laying autoclave aerated concrete blocks as per drawing (Thickness 100 mm ) in single or multiple
layers with approved block laying polymer modified adhesive mortar. Crushing strength of aerated concrete block
shall not be less than 40 KG/sqcm, minimum density in oven dry condition between 651 to 750 KG/CUM, thermal
conductivity shall not exceed 0.30 w/mk, fire resistant 4 hours, in true line level and plumb and cleaning the surface
Ch.6-It.code.6014 Rupees Four Thousand
with necessary tool tackles The drying shrinkage shall be not more than 0.05 percent for Grade 1 blocks and
67 +06008E2A 8.00 Cmt 4726.21 Seven hundred Twenty Six
percent for Grade 2 blocks when tested in accordance with IS : 6641 (Part-2)-1972 etc. including curing, scaffolding,
Pg.No.88 Paise Twenty One Only
racking / flush jointing etc complete, as per drawing / specification etc, complete As per drawings and design supplied
by architect and instruction given E.I.C. For all civil, plumbing, electrical & infrastructure works.
d) Third & terrace floor
Providing 15mm thick cement plaster in single coat on Rough (Similar)side of single or half brick walls for interior
plastering upto floor two level and finished even and smooth in (ii) Cement mortar 1:4 (1- cement :4-sand) (i) Ground Rupees One hundred Eighty
Floor Two Paise Six Only
Ch.17- Providing 15mm thick cement plaster in single coat on Rough (Similar)side of single or half brick walls for interior
It.code.17.60(ii)+17 plastering above floor two level and finished even and smooth in (ii) Cement mortar 1:4 (1-cement :4-sand) (ii)First Rupees Two hundred Nine
.94(i) 17007B Floor Paise Twenty Nine Only
Ch.17- Providing 15mm thick cement plaster in single coat on Rough (Similar)side of single or half brick walls for interior
It.code.17.60(ii)+17 plastering above floor two level and finished even and smooth in (ii) Cement mortar 1:4 (1-cement :4-sand) Rupees Two hundred Thirty
.94(i) 17007B (ii) SECOND Floor Six Paise Fifty Two Only
Ch.17- Providing 15mm thick cement plaster in single coat on Rough (Similar)side of single or half brick walls for interior
Rupees Two hundred Sixty
It.code.17.60(ii)+17 plastering above floor two level and finished even and smooth in (ii) Cement mortar 1:4 (1-cement :4-sand)
71 963.00 Smt 263.75 Three Paise Seventy Five
.94(i) 17007B (ii) Third & Terrace Floor
Providing 10mm thick cement plaster in single coat on brick/concrete walls for interior plastering upto floor two level
and finished even and smooth in (i)Cement mortar 1:3 (1- cement:3-sand) (i) Ground Floor Rupees One hundred
It.code.17.58(1a)+1
72 7534.00 Smt 177.72 Seventy Seven Paise Seventy
Ch.17- Providing 10mm thick cement plaster in single coat on brick/concrete walls for interior plastering above floor two
It.code.17.58(i) level and finished even and smooth in (i)Cement mortar 1:3 (1- cement:3-sand) Rupees One hundred Ninety
17.91+17.93 (i) First Fl. Nine Paise Sixty One Only
Ch.17- Providing 10mm thick cement plaster in single coat on brick/concrete walls for interior plastering above floor two
It.code.17.58(i) level and finished even and smooth in (i)Cement mortar 1:3 (1- cement:3-sand) Rupees Two hundred Twenty
17.91+17.93 (i) Second Floor One Paise Forty Nine Only
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Ch.17- Providing 10mm thick cement plaster in single coat on brick/concrete walls for interior plastering above floor two
It.code.17.58(i) level and finished even and smooth in (i)Cement mortar 1:3 (1- cement:3-sand) Rupees Two hundred Forty
17.91+17.93 (i) Third & Terrace Floor Three Paise Thirty Eight Only
Ch.17- 20mm thick sand faced cement plaster on walls upto height 10 metres above ground level consisting of 12mm thick
Rupees Three hundred Fifty
76 It.code.17.95 5460.00 backing coat of C.M. 1:3 (1-cement : 3-sand) and 8mm thick finishing coat of C.M. 1:1 (1-cement : 1-sand) etc. Smt 352.44
Two Paise Forty Four Only
Pg.No.144 complete. GF & FF
Ch.17- 20mm thick sand faced cement plaster on walls above height 10 metres above ground level consisting of 12mm thick
Rupees Three hundred
It.code.17009 backing coat of C.M. 1:3 (1-cement : 3-sand) and 8mm thick finishing coat of C.M. 1:1 (1-cement : 1-sand) etc.
77 4805.00 Smt 379.67 Seventy Nine Paise Sixty
17.95+ 17.94(2) complete. - SF & Tarrace
Providing throating or plaster drip and moulding to R.C.C. chhajja
It.code.5.4.18 Rupees Forty Three Paise
no.5018 Pg.No.68 Five Only
17015 Providing cement vata (10cm. x 10 cm. size) quarter round in cement mortar 1:1 including neat cement finishing,
Rupees Twenty Four Paise
79 Ch-17 116.00 watering etc. complete. Rmt 24.28
Twenty Eight Only
Providing & Fixing the Chicken wire mesh Jali 16 x24 or approved size 22 gauge applying between the RCC and
Rupees Three hundred Fifty
79 RA 2054.00 masonry junction in proper line, level and plumb with all material, labour, tools, tackles and equipment including Smt 359.52
Nine Paise Fifty Two Only
fixing the jali with nails, etc complete as directed by the Engineer-in-charge.
Wall painting (two coats) with plastic emulsion paint of approved brand and manufacture on undecorated wall surface
Ch.18-18031 to give an even shade including throughly brushing the surface free from mortar droppings and other foreign matter
Pg.149 18.57 + and sand papered smooth & Applying two coats of Birla or Asian acrylic lappy ( putty) and two coats of primer of Rupees One hundred Twenty
Ch.19-19032 approved brand and manufacture on new wall surface to give an even shade including thoroughly brushing the Three Paise Forty Four Only
Pg.No.153 surface free from mortar dropping and other foreign matter and sand papered smooth.
Finishing wall with weather proof exterior emulsion paint two coats on wall surface & two coats of primer of
Rupees One hundred Thirty
81 RA 10382.00 approved brand to give an required shape even shade after thoroughly brushing the surface to remove all dirt, and Smt 133.89
Three Paise Eighty Nine Only
remains of loose powdered materials.etc complete
Providing 20 mm thick water proof cement plaster using water proofing powder 1Kg/1bag of cement for all floors on
brick / concrete wall work using water proofing materials in C M 1: 4 ( 1 cement 4 coasrse sand) including finishing
with a flooting coat of neat cement slurry etc complete for all floor. and shall be guaranteed for minimum period of 10 Rupees Two hundred Ninety
years after handing over the completed building by the main contractor to be finished as directed. Stamp paper Two Paise Ninety Only
guarantee 10 years to be furnished before receiving any payment from the client.
Providing and laying 18 mm thick polished granite stone machine cut in single piece (Max. available) in sill and jambs
Rupees Three Thousand Two
of Door, window, Ventilation frame laid over 10 mm thick cement mortar 1 : 3 (1 cement : 3 coarse sand) and jointed
83 RA 1570.00 Smt 3282.50 hundred Eighty Two Paise
with grey cement slurry with matching pigment incl. rubbing and polishing half rounding edge etc. complete colour
and shed as approved by architect engineer in charge.
Providing and laying 24" x 24" vitrified glossy/ satin/ matte finish 8 mm thick tile flooring over 20 mm (average) base
Rupees One Thousand Three
Ch.14-It.code. of cement mortar 1:6 ( 1 cement: 6 coarse sand) on new surface or fixing on existing flooring by adhesive material
84 3483.00 Smt 1311.18 hundred Eleven Paise
14022A Pg.No.137 including dismentaling of existing flooring and jointed with color cement slurry including finised with flush pointing &
cleaning the surface etc. complete for light shade
It Code Providing and laying polished Kota stone slab flooring over 20mm (Average) thick base of cement mortar 1:6 (1- Rupees One Thousand
85 No.14012aa 3343.00 cement : 6-coarse sand) or L.M. 1.1.5 laid over and jointed with grey cement slurry including rubbing and polishing Smt 1019.39 Nineteen Paise Thirty Nine
Pg.No.135 etc. complete. (B) 25mm thick Only
Providing and laying Ceramic tiles 6mm thick in flooring treads of steps and landing laid on a bed of 12mm thick
cement mortar 1:3 (1- cement : 3-coarse sand ) finishing with flush pointing in white cement. Rupees Nine hundred Ninety
Seven Paise Sixteen Only
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Providing and laying coloured glazed tiles of the size 300 mm x 450 mm x 8 mm in skirting, risers of steps and dedo on Rupees One Thousand Four
87 9780.00 10 mm. thick cement plaster 1:3 (1 cement : 3 coarse sand) & jointed with white cement slurry. Smt 1488.24 hundred Eighty Eight Paise
Twenty Four Only
Providing and laying Tactile flooring tiles 300mm x 300mm in flooring 12 mm. Thick cement mortar 1:3 (1 cement :
As Per Patdi SDH Rupees One Thousand Sixty
88 305.00 coarse sand) pointing in white ceand jointed with white cement slurry. Smt 1064.54
(Item No.78) Four Paise Fifty Four Only
Providing and laying polished Granite slab flooring over 20 mm (average) base of cement mortar 1:6 (1 cement : 6 Rupees Two Thousand One
89 RA 363.00 coarse sand) laid and jointed with grey cement slurry including rubbing and polishing complete.18 mm thick Smt 2181.60 hundred Eighty One Paise
Providing and laying polished granite stone slab 18 mm thick in risers of steps, dedo and pllars laid on 10 mm thick Rupees Two Thousand Three
90 RA 475.00 cement mortar 1:3 (1 cement : 3 coarse sand) and jointed with gray cement slurry including half round moulding, Smt 2344.92 hundred Forty Four Paise
rubbing & polishing etc. complete. Ninety Two Only
Providing and fixing Colour Anodized aluminium work for doors, windows, ventilators and partitions (Sliding window
like Two Track, Three Track, Four Track, fix window/ Openable window / Fix-Partition, etc),with extruded built up
standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS :
1285, fixed with rawl plugs and screws or with fixing clips, or with expansion hold fasteners including necessary filling
up of gaps at junctions, at top, bottom and sides with required PVC/neoprene felt etc. Aluminium sections shall be Rupees Five hundred Eighty
smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap Two Paise Thirty Eight Only
beading for glazing / paneling, C.P. brass / stainless steel screws, fixture like aldrop, handle, hinges / pivots & window
Bearings & concealed lock etc all complete at all floors/all levels/all heights as per architectural drawings and the
directions of Engineer-in-charge. (Glazing and paneling to be paid under relevant Item)
Providing and fixing 4 mm thick ground glass (Frosted or obscured on one side) & (PIU approved brand list) fix in
aluminium door, window, ventilator shutters and partitions any size, any shape etc. P & F with EPDM/ PVC rubber
Rupees Seven hundred Sixty
92 RA 740.00 gasket etc all complete at all floors/all levels/all heights as per the architectural drawings and the directions of Smt 767.39
Seven Paise Thirty Nine Only
Engineer-in-Charge. Actual laying installed glass shall be measured (Cost of aluminium snap beading shall be paid in
Providing and fixing 4 mm thick Sheet glass selected quality (PIU approved brand list) fix in aluminium door, window,
ventilator shutters and partitions any size, any shape etc. P & F with EPDM/ PVC rubber gasket etc all complete at all Rupees Seven hundred
93 RA 564.00 floors/all levels/all heights as per the architectural drawings and the directions of Engineer-in-Charge. Actual laying Smt 715.71 Fifteen Paise Seventy One
installed glass shall be measured (Cost of aluminium snap beading shall be paid in basic item) Only
Providing and fixing Stainless steel mosqito net jali ,S.S.315 Grade with wire of 0.56 mm (PIU approved brand list) fix
in aluminium door, window, ventilator shutters of any size, any shape with etc all complete at all floors/all levels/all
Rupees One Thousand Fifty
94 RA 135.00 heights as per the architectural drawings and the directions of Engineer-in-Charge. Actual laying installed Jali shall be Smt 1055.23
Five Paise Twenty Three Only
measured. (Cost of aluminium snap beading shall be paid in basic item)
It No 10.1 code No Providing and fixing M.S. grill of required pattern of windows etc. with M.S.. flats at required spacing and frame
10025AA alround square or round headed bolts and nuts or by screws.including applying a priming coat of red lead paint and Rupees One hundred Six
Pg.No.101 two coats of oil painting etc complete (A)Plain grill Paise Twenty Three Only
Steel work, welded in built up sections framed work including cutting, hoisting, fixing in position and applying a
Rupees Nine Thousand One
11002A 11.4 priming coat of read lead paint. (A)In beams and joists, channels angles Tees, flats, with connecting plates or angle
96 185.90 qntle 9108.48 hundred Eight Paise Forty
Pg.No.119 cleats as in main and cross beams. Hip and jack rafters, purlins conneted to common rafters and the like .
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Design and Supply and installation of glass façade with fixed glazing made of 12mm thick clear toughen glass with
OZONE SPIDER with OSP‐A22 ‐1 WAY SPIDER FOR CEILING FIXING;316 GRADE; FINISH‐SSS; 94mm ; OSP‐A44 ‐2 WAY
SPIDER FOR WALL FIXING; 316 GRADE; FINISH‐SSS; 200mmx 94mm ;OSP‐A4 ‐ 4 WAY SPIDER WITH FIN; 316 GRADE;
FINISH‐SSS; 94+94mm x 200mm;OSP‐AFB‐36‐FL ‐ARTICULATED FLAT HEAD BOLT FOR 15MM THK OF GLASS;
GRADE; FINISH‐SSS; GLASS HOLE DIA. 38 MM;OSP‐FP‐350 ‐FIN PLATE 350MM X 93MM; GLASS HOLE DIA.‐22MM, SSS
Rupees Three Thousand
As Per Patdi SDH FINISH; OSP‐FP‐400 ‐FIN PLATE 400MM X 93MM; GLASS HOLE DIA.‐22MM, SSS FINISH; OSP‐FP‐450 ‐FIN PLATE
97 308.00 Smt 3878.40 Eight hundred Seventy Eight
(Item No.85) 450MM X 93MM; GLASS HOLE DIA.‐22MM, SSS FINISH; OSP‐SP‐VS‐400 ‐VERTICAL SPLICE PLATE 400MM; GLASS
Paise Forty Only
HOLE DIA. 22MM; SSS FINISH. The contact between glass surface and metal shall be protected by EPDM washers. The
glass hole shall be protected from direct contact with metal by Derlin bush. A spring washer confirming to SS316 act
as a locking mechanism to secude nut in place ensuring full tightness for long period of time. Contractor must
submitted wind load, Structural stability and warranty certificate.
Providing and fixing flush door both sides laminated shutter fabricated from 35 mm thick solid core malemine faced
three layered pre laminated flat pressed wood based exterior grade bonded BWP/BWR synthetic resin having
Rupees Three Thousand Six
stamped IS 12823 grade I type II including three coats of lacquer polishing to exposed wooden surfaces and including
98 RA 76.00 Smt 3617.14 hundred Seventeen Paise
providing and fixing of Floor door stopper & fixing of S.S finish decorative type heavy guage designs fixtures /
fastening etc. complete As per drawings and design supplied by architect and instruction given by authority and E.I.C.
Providing and fixing bright finish brass hydraulic door closer of approved model and make with necessary screws and
Rupees One Thousand Four
As Per Patdi SDH finishing etc. complete.
99 50.00 Each 1422.84 hundred Twenty Two Paise
Eighty Four Only
PProviding and fixing 3 mm thick PVC sheets as signange and display of health signs/information of required size
As Per Patdi SDH having retro reflective letters/design as per requiement, fixing the same through approved adhesive etc. complete Rupees Three hundred Eighty
(Item No.93) work shall e carried out as per instruction of Engineer-in-charge (Approved make PVC foamed sheet only) (45 x 15 Two Paise Seventy Nine Only
Providing and Fixing Best Quality of S.S. Metal Letter on Outerside Wall at Any Height Including Polishing & Anchoring Rupees Nine hundred
As Per Patdi SDH
101 100.00 Labour Etc Complete as Directed by Engineer in charge. Each 929.20 Twenty Nine Paise Twenty
Providing and laying cement concrete work 1:2:4 (1- Cement : 2- Coarse sand : 4- graded stone aggregates 20 mm
05011BA Rupees Four Thousand One
nominal size) and curing complete excluding cost of formwork and reinforcement for reinforced concrete work in (B)
102 5.4.1 302.00 Cmt 4142.24 hundred Forty Two Paise
Slabs, landing, shelves, Balconis , Lintels, Beams, Girders and Cantilever upto floor two level.
Pg.No.67 Twenty Four Only
Providing and laying broken chine mosaic flooring for terrace using 12 mm to 20 mm broken pieces of glazed tiles to
Rupees Seven hundred
It No. 14035 be laid over cement mortar 1:3 to plain or slope and to be tempered to bring mortar creme out upto surface using
103 4012.00 Smt 779.70 Seventy Nine Paise Seventy
Pg.No.138 white cement including rounding off junctions and extending them upto 15 cm along the wall,clearing with water and
oxalic acid etc. as directed.
Providing and fixing rolling shutters of approved make made of 80 mm wide M.S. laths inter-locked together through
their entire length and jointed together at the ends by end locks mounted on specially designed pipe shaft with Rupees Three Thousand Five
104 17.00 bracket plates, guide channels and arragements for inside and outside locking with push-pull operation including the Smt 3554.40 hundred Fifty Four Paise
cost of hood cover and spring etc. complete.(A) Shutters having width below 3.5 M. Forty Only
Providing and fixing stainless steel railing 50mm dia.(16 gauge-Grade 304) TOP RAIL with 1 mtr c/c VERTICAL SUPPORT
37.5mm dia.(16 gauge-Grade 304), 3 NO. 25mm dia.(16 gauge-Grade 304) HORI. MEMBER ., including welding,
grinding, buffing, polishing and making curvature (wherever required) ,for staircase on the side of waist slab with
Rupees Three Thousand
suitable arrangement as per drwaing, (for payment purpose only hand rail Running meter will be consider, and other
105 RA 337.00 RMT 3847.54 Eight hundred Forty Seven
stainless steel members shall are inclusive of fixing accessories such as Baluster, supports, horizontal members, nuts,
Paise Fifty Four Only
bolts, fasteners etc.)Rate includes for all lead & lift. etc, complete as per drawings and design supplied by architect
and instruction given by authority and E.I.C.
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Providing, fixing and construction of sandwich type platform of 18 mm thick Granite polished stone top, 80 mm wide
edge full moulded Facia Patti with 25mm thick one side polished Kota stone for bottom & vertical supports sandwich
Rupees Eight Thousand Six
type at 1.00 m interval including necessary cement mortar 1:2 Kota shall be fixed in cement joints and pointing as
106 RA 57.00 Smt 8693.12 hundred Ninety Three Paise
specified in Kitchen / Pantry / Counter / Laboratory etc with necessary adhesive, making of edges, polishing curing
daily mopping with water and kerosene etc comp as directed of Engineer-in-charge. (Measured only vision finished
Providing and fixing Flexible Homogeneous Vinyl Flooring of With treatment of Plyurethane Reinforced Surface,
Rupees One Thousand Eight
As Per Patdi SDH Densely Compacted, Anti-Bactaril and fungicidal and Antistatic havng thickness of 2.00mm With weight of 3150 g/m2
107 577.00 Smt. 1893.75 hundred Ninety Three Paise
(Item No.99) with levelling, chemical adhasive for fixing, corner junction.
Seventy Five Only
Wall Painting (two coats) with antibacterial polyrethane epoxy paint approved brand and manufacture on internal
As Per Patdi SDH Rupees Four hundred Fifty
108 439.00 walls to give an even and smooth surface. Thoroughly brushing the surface free from mortar dropings and other forein Smt. 454.50
(Item No.100) Four Paise Fifty Only
matter and sand prepared smooth.
Providing & applying two Componant ,non slumping ,non-sagging, thixotropic epoxy bedding compond & adhesive
compatible with for tiles for coving at radius of 25 mm or as directed by the architect's / Engineer-in-charge make it
As Per Patdi SDH Rupees Five hundred Seventy
109 550.00 fit for tiles inclusive of Labour, material and Equipment etc. for all heights, location, shape & size as directed by the RMT 575.70
(Item No.101) Five Paise Seventy Only
architect/Bank engineer incharge. (Actual Length shall be measured for payment.)
Providing corrugated G.I. sheet of class-3 roofing fixed with glavanished iron J or L Hooks, Bolts and nuts 8mm
It No. 15001a Rupees Seven hundred Thirty
110 750.00 diameter with bitumen and G.I. limpet washer or G.I. limpet washer. filled with white lead complete excluding the Smt 734.19
Pg.No.137 Four Paise Nineteen Only
cost of purlins, Rafters and Trusses.(1) 0.80 mm thick sheet.
Corner Guard Protection System in entire hospital : Supply and Installation of Corner Guard protection system fixed to
Rupees Seven hundred
As Per Patdi SDH brick wall/or tile/dado at the corner from finished floor level. It should be adjustable end cap. Providing and fixing
111 280.00 RMT 788.81 Eighty Eight Paise Eighty
(Item No.103) brush/mirror finish S.S 304 grade Angle 40.0 x 40.0 x 3.0 mm &. 1.00mt. Ht. x 3.75 kg/mt. = 3.75 kg.
Providing and applying 2mm thick Texture Plaster Terre Palette (Earthen Textures, Spectrum, Coral or equivalent)
As Per Patdi SDH incorporating fine filaments made of polymer and aggregating natural stone powder with making grooves on existing Rupees Three hundred Fifty
(Item No.104) base coat of 18 mm thick smooth mala plaster etc. Complete Colour and shade as approved by Architect/ Engineer in One Paise Forty Eight Only
charge for all floor all height.
19005 +19001 Painting Two coats over & including a priming coat on new steel and other metal surfaces with enamel paint, brushing
19.19+ interior to give an even shade including cleaning the surface of all dirt, dust and other foreign matter.. Rupees One hundred Five
19.2 Paise Forty Nine Only
Painting two coats (excluding priming coat) on new steel and other metal surface with enamel paint, brushing, interior
Ch.19 Rupees Ninety Two Paise
114 676.00 to give an even shade including cleaning the surface an even shade including cleanicn the surface of all dirt, dust and Smt. 92.20
19002Pg.No.150 Twenty Only
other foreign matter.
Providing & Plantation of semi carpet Lawn (Selection 1) the scope includes prepaid ground for planting of lawn, soil
spreading, mixing of soil & manures, rolling the same etc comp. Labour cost for Lawn Plantation semi carpet Lawn
As Per Patdi SDH Cost including carting, loading & unloading at site etc and includes required dose of pesticides & Ant termite Rupees Two hundred Forty
(Item No.109) treatment Labour charges for maintenance of semi carpet Lawn including tools & tackles. including Providing, mixing Eight Paise Forty Six Only
& spreading fertilizer Manure ,1 year maintenance etc complete as directed by architect /E.I.C
Providing & Plantation of Shrubs (mini 3 feet height) by digging of pit size 1x1x1 feet, adding soil, farm yard manure,
As Per Patdi SDH DAP, Pesticide, Plantation of sapling. Making proper tree basin & putting proper support including Providing, mixing & Rupees One hundred Fifty
(Item No.111) spreading fertilizer Manure ,1 year maintenance etc complete as directed by architect /E.I.C One Paise Fifty Only
Providing & Plantation of Green belt trees by digging of pit size 2x2x2 feet, height 10 feet adding soil, farm yard
As Per Patdi SDH manure , DAP, pesticide, plantation of sapling. Making proper tree basin & putting proper support including back
117 50.00 No. 50.50 Rupees Fifty Paise Fifty Only
(Item No.112) filling the trench, watering etc including Providing, mixing & spreading fertilizer Manure ,1 year maintenance etc
complete as directed by architect /E.I.C
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Bowing and developing flowering plants grown in nusery having approximate height 4 to 5 ft or Height ad per
Rupees One hundred
As Per Patdi SDH Landscaps Plan with natural growith of soil packed in polithyline bag or Earthern pot. Including organic & chemical
118 50.00 No. 171.70 Seventy One Paise Seventy
(Item No.113) fertilizer Pesticides, fungicides, hormones & maintaining the plants up to three months as deserted. Bottol palm.
Providing and fixing eco-friendly light weight calcium silicate false ceiling tiles having Tegular edge & 15 mm Thick
Densified edges on the Tile Periphery for Extra Strength The Light weight calcium silicate ceiling tiles shall have , light
reflection 85% noncombustible as per B.S. 476 part IV, 100% humidity resistanceandalsohaving
thermalconductivity0.043° w/m KC.for the best thermal Insulation . The Light weight calcium Silicate tile shall be of
approved texture Fine fissured/ Spintone/Cosmos having NRC value of 0.5 & Globe having NRC value of 0.75 NRC or
equivalent of size 595 X 595 mm to be laid on true horizontal level suspended inter locking metal gridof hot dipped Rupees One Thousand Six
119 9706.00 galvanized steel sections (galvanizing @120 grams per sqm including both side) consisting of main ‘T’ runner suitably Smt 1674.15 hundred Seventy Four Paise
spaced at joints to get required length and size of 24X38mm made from 0.30 mm thick (minimum) sheet, 1200mm Fifteen Only
centre to centre, and cross ‘T’ of size 24X28mm made out of 0.33mm (Minimum) sheet spaced 1200mm along spaced
between main ‘T’ at 600mm centre to centre to form agrid of 1200X600mm and secondary cross ’T’ of length 600mm
and size 24x28mm made of 0.30 mm thick (Minimum) sheet to be interlocked at middle of the 1200X600mm panel to
form grid of size
Main Door Signage
3Stainless Steel plate of grade 304 having size 500x150x1mm thick (brush finish) shall be used as base / background.
Rupees Fourteen Thousand
As Per Patdi SDH The height of the font shall be 30mm for name pasting and the designation shall have 15mm height pasted below the
120 8.00 Nos. 14942.95 Nine hundred Forty Two
(Item No.121) name of person.
Paise Ninety Five Only
Providing and fixng curtain For Door/Window using Fire retardent Material including necessary hanging attachments
Rupees One Thousand
As Per Patdi SDH like hooks/ rings, 25mm SS rod/ alluminium channel/ Socket on rod ends/ middle supporting sockets including 1 inch
121 410.00 Smt 1717.00 Seven hundred Seventeen
(Item No.123) Adjustable Curtain S.S. Rod up to 12 ft long with best quality Curtain Knobs and bracket or socket (2 nos 1 set) etc.
Supply & Installation of Cubicle/ Privacy Curtains for Hospital Track Material Made of Aluminium alloy (6063-T6), with
corrosion resistanceproperties and Standard white powder coatingTrack Size (Approximate)Gauge 1.7mm Height
25mm Width 20mm Runner type Wheel or Glider Type Runner material Made of Nylon of PVC Hooks Stainless Steel
202 or more Bends Tracks are bendable to a radium of 300 mm at 90 degree to cover the whole bed Track height As
per site requirement Track roof suspenders Made of aluminium pipe of at least 12 mm diameter and the Upper
Circular Plate made of aluminium with at least 50 mm diameter.These should be white powder Coated and fixed with
the ceiling is with anchors, bolts, screws etc.Track wall supports Aluminium white Powder coated Tack bridge clamp
Aluminium white Powder coated Curtain Removal Point Optional : Curtain runner removal point for loading and Rupees One Thousand Six
As Per Patdi SDH
122 400.00 unloading of runners Curtain Material Polyester Blended Standard Curtain Size Height At least 84 inch or more Width RMT 1696.80 hundred Ninety Six Paise
At least 46 inch or more Mesh(Net) Size At least 18 inch or more from top of the curtain and made of nylon Curtains Eighty Only
Type:Stain Retardant Cubicle Curtains These Curtains should be made up of fabrics with inherent antibacterial and
flame retardant properties.These curtains should be wrinkle free and shrink proof with Anti odour and Anti-fungal
properties.It should meet the international Antimicrobial Test JISL 1902/ISO20743These Curtains should have Dire
retardent,stain retardant qualities with water repellent quality with rust proof SS grommets 6" on centers. Designs
and Colours should be approved by the user department.
Providing & fixing of reinforcement bars ( reiforcement bars shall be paid extra under relevant item of work ) after
drilling the hole of required diameter & depth ,cleanning of the same ,providing /filling the hole with Injection Mortar
(HIT HY 150 of Hilti or approved equivalant ),inserting reinforcement bar etc. complete as per Manufacturers & Rupees Three hundred
As Per Patdi SDH
123 50.00 architects instruction.The work shall be carried out by the technical workmens/agency approved by the manufacturer Each 317.14 Seventeen Paise Fourteen
and under technical supervision of Manufacturer of Injection grout including all materials,tool tackles ,labour Only
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Providing & fixing of reinforcement bars ( reiforcement bars shall be paid extra under relevant item of work ) after
drilling the hole of required diameter & depth ,cleanning of the same ,providing /filling the hole with Injection Mortar
Rupees Three hundred
As Per Patdi SDH (HIT HY 150 of Hilti or approved equivalant ),inserting reinforcement bar etc. complete as per Manufacturers &
124 45.00 Each 378.75 Seventy Eight Paise Seventy
(Item No.126) architects instruction.The work shall be carried out by the technical workmens/agency approved by the manufacturer
and under technical supervision of Manufacturer of Injection grout including all materials,tool tackles ,labour
etc.complete.(B) 10mm Dia
Providing & fixing of reinforcement bars ( reiforcement bars shall be paid extra under relevant item of work ) after
drilling the hole of required diameter & depth ,cleanning of the same ,providing /filling the hole with Injection Mortar
As Per Patdi SDH (HIT HY 150 of Hilti or approved equivalant ),inserting reinforcement bar etc. complete as per Manufacturers & Rupees Four hundred Thirty
(Item No.127) architects instruction.The work shall be carried out by the technical workmens/agency approved by the manufacturer Four Paise Thirty Only
and under technical supervision of Manufacturer of Injection grout including all materials,tool tackles ,labour
etc.complete.(C) 12mm Dia
Providing & fixing of reinforcement bars ( reiforcement bars shall be paid extra under relevant item of work ) after
drilling the hole of required diameter & depth ,cleanning of the same ,providing /filling the hole with Injection Mortar
As Per Patdi SDH (HIT HY 150 of Hilti or approved equivalant ),inserting reinforcement bar etc. complete as per Manufacturers & Rupees Five hundred Fifty
(Item No.128) architects instruction.The work shall be carried out by the technical workmens/agency approved by the manufacturer Four Paise Forty Nine Only
and under technical supervision of Manufacturer of Injection grout including all materials,tool tackles ,labour
etc.complete.(D) 16mm Dia
Providing & fixing of reinforcement bars ( reiforcement bars shall be paid extra under relevant item of work ) after
drilling the hole of required diameter & depth ,cleanning of the same ,providing /filling the hole with Injection Mortar
Rupees Seven hundred
As Per Patdi SDH (HIT HY 150 of Hilti or approved equivalant ),inserting reinforcement bar etc. complete as per Manufacturers &
127 20.00 Each 792.85 Ninety Two Paise Eighty Five
(Item No.129) architects instruction.The work shall be carried out by the technical workmens/agency approved by the manufacturer
and under technical supervision of Manufacturer of Injection grout including all materials,tool tackles ,labour
etc.complete.(E ) 20mm Dia
Ch.4/B- Providing and laying and fixing 50 mm thick expansion joint by hydro cell semi rigid UV resistance with high Rupees One Thousand Four
128 It.code.5048 134.00 performance laminated closed cell polythene foam joint filler in sheet foam as directed, etc. complete. Smt 1491.03 hundred Ninety One Paise
Pg.No.78 Three Only
Ch.4/B- Providing and fixing 25 cm Wide & 3mm thick exterior composite panel on existing expansion joint horizontally &
Rupees One Thousand Fifty
129 It.code.5053 500.00 vertically with all material, hardware, acessories & fittings etc completed. Smt 1054.34
Four Paise Thirty Four Only
Ch.20- Providing and fixing 60 mm diameter backup rod having minimum density 22 kg per cum (ASTMD - 3575) &
Rupees Sixty Nine Paise
130 It.code.20044 700.00 compression strength of 0.40 kg per sqm (ASTM - 5249) and finishing with polysulphide sealant etc. complete. For 50 RMT 69.07
Pg.No.156 mm wide expansion joint
Making up the even groove, cleaning by air/water blasting and resealing with DOW CORNING make CCS Silicon type of Rupees Three Thousand Six
As Per Patdi SDH
131 250.00 liquid seals for widths 40mm x 10mm after using appropriate back up material of SUPREME make RMT 3641.05 hundred Forty One Paise Five
Drilling of pilot 250/325 mm dia bore hole in all strata including dual over burdan strata by combination DR / DTH
Rig. including lowering of 200/250 mm dia MS ERW pipes in bore hole with 4 to 6 mm Gravel ,Lowering of the
Rupees Three Thousand
submersible motor of 3HP along with flat PVC cable as suggested by Hydrologist. Geohydrological ground water
132 RA 45.00 RMT 3307.65 Three hundred Seven Paise
investigation charges for Deep tubewell (with vehical charges & with water sample, and finalizing with devlopment of
Sixty Five Only
bore by back washing &,Geohydrological ground water investigation etc complete.
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Cat Eye / Road Stud / RPM: Supplying of Molded Twin Shanks Raised Pavement Markers made of polycarbonate and
ABS moulded body and reflective panels with micro prismatic lens capable of providing total internal reflection of the
light entering the lens face and shall support a load of 13635 kgs. tested in accordance to ASTM D 4280 Type H and
complying to Specifications of Category A of MORTH Circular No RW/NH/33023/10-97 DO III Dt 11.06. 1997. The
height, width and length shall not exceed 20 mm, 130 mm and 130 mm and with minimum reflective area of 13 Sqcm Rupees Three hundred
It Code No.26162A
133 240.00 on each side and the slope to the base shall be 35 +/- 5 degree. The strength of detachment of the integrated No 326.23 Twenty Six Paise Twenty
cylindrical shanks, (of diameter not less than 19 +/- 2 mm and height not less than 30+/- 2 mm) from the body is to be Three Only
a minimum value of 500 Kgf. Fixing will be by drilling holes on the road for the shanks to go inside, without nails and
using epoxy resin based adhesive as per manufacturers recommendation and The color of the marker should be as per
the IRC 35-2015 and as directed by Engineer-in-charge.
Road marking with hot applied thermoplastic paints with reflectorising glass beads on bitumin surface providing and
laying a hot applied thermoplastic compound 2.5 mm thick including reflectorising glass beads @ 250gms per sqm
area, thickness of 2.5mm is excluding of surface applied glass beds as per IRC:35-2015. The finished surface to be
level, uniform and free from streaks and holes. zebra patta /bump patta lane/center line/ edge line/cut patta. The Rupees Three hundred Sixty
134 130.00 white color marking should provide liminance coefficinet on cemend road shalll be min 130 mcd/m2/lux and Asphalt Smt 367.72 Seven Paise Seventy Two
road shall be min 100 mcd/m2/lux during the service life during the day time. The marking should meet the Only
performance criteria for night time reflectivity, wet reflectivity and skid resistance as mentioned in the section-15 of
IRC 35-2015. Warranty for the Retro reflectivity should be two years.
Providing and fixing pre-cast Rubber Dye / steel Dye inter locking concrete block 60mm thick with grade of concrete
M300 pnumatic compressed / vibrated mechanically and as per approved design Confirming to IS 15658 : 2006 Rupees Seven hundred Six
including 35 mm Sand layer for levelling and filling the joint with sand in proper line and level as per guidlines of IRC : Paise Ninety Three Only
SP 63-2018 etc. Complete.
FLUSH PARTITION (laminate finish) :
Providing & fixing flush partition up to false ceiling ht (thickness of partition is 75 mm) having 12 mm thick Marin
plywood IS 710 both side on aluminum framing. Aluminum framing size for vertical & horizontal support is 50 mm x
25 mm. All exposed surfaces finished with 1 mm thick laminate of approved shade without any air gap and grooving as
per design. Necessary framing to be erected above false ceiling. No extra cost to be paid for the same. Before Rupees Four Thousand Five
As Per Patdi SDH installation, make hole/face plate for conduit pipes of electrical / networking cables with open able stud from
135 180.00 Smt 4512.31 hundred Twelve Paise Thirty
(Item No.141) partition Including all materials and labor etc. Make necessary grooves as per shown in drawing. All bottom ends are One Only
covered with Ghana teak bidding Patti finished with laminate Complete with all necessary hardware & adhesives as
per details given in drawing and as per instructions of Architect/consultant/Engineer In charge. Contractor has to
provide all necessary cut outs (race ways.) for Electrical works & no extra payment shall be made for it.
Applying and providing Expansion joint sealing System on 100 mm vide joint including cleaning of exansion joint by
mechanical means provision of adhesive and flexible membrane with required bond length as per menufracturer Rupees Four Thousand
It Code No.5050
136 169.00 specification and 4mm thick alluminium strip covering with one side sloted and bolted with suitable system, inclusive Smt 4772.00 Seven hundred Seventy Two
of all manpower, machinery and material as per specification and as directed. Only
It Code Providing and fixing 35 mm thick shutters for Doors, windows and clear story windows including anodised alluminium Rupees Three Thousand
137 No.10004ca 63.00 butt hinges with necessary screws. (A) Indian Teak Wood(iii) Partly panelled and partly glazed. Smt 3752.41 Seven hundred Fifty Two
Pg.No.97 Paise Forty One Only
Fabricating, Supplay and Fixing in position SS Dasa for staircase with brush finish and SS 304 grade as per Indian
Rupees One Thousand Eight
standrd and detailed drawing including grinding,cleaning and filling the welded spots with SS finish (only Length will
138 RA 350.00 RMT 1876.25 hundred Seventy Six Paise
be paid for payment ). The work to be executed as per Architect drawing and E.I.C. etc. complete for all floors.
Twenty Five Only
Providing and Fixing 6 mm thick Lexan Polycarbonate multi wall roofing sheet fixed with hilti screw and rubber silicon Rupees One Thousand Four
It code No.15019
139 420.00 sealer and alluminium strip of size 50 x 3 mm etc complete as directed by Engineer in charge. Smt 1441.90 hundred Forty One Paise
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Providing and fixing single layer waterproof gypusm board 12.5 mm thick of the make Newgood Group Co. Ltd. or
equivalent & Newgood Group Co. Ltd. company sections using waterproof board of size 1220 mm x 1830 mm x
mm suspended by G.I suapender of size 25 mm x 3 mm with intermediate channel of size 18 mm x 40 mm x 0.80 mm
It Code No.16007 at 1220 mm center to center ceiling section of size 40 mm x 35 mm x 0.55 mm at 457 mm center to center and Rupees Six hundred Six Paise
Pg.No.142 perimetre chanel A of size 20 mm x 27 mm x 30 mm x 0.50 mm at edges & drops including paper tap sand sofit cleat, Ninety Five Only
anchor fastener, scoch bolt connecting cleat joining compound top coat on ceiling including making necessary opening
for light fitting, diffuser etc. complete as per detail drawing as directed.
Providing and applying a seamless lightweight multi- layered system comprising of primer and finish coat 75 mm thick
epoxy coving on the wall to floor joint epoxy 75mm thick Epoxy Coving System which consist of surface preparation,
Rupees Seven hundred
As Per Patdi SDH primer coat. Make coving (VATA) coving with Florscreed C , make finish putty with Florscreed C and silica micro. Then
141 160.00 RMT 786.57 Eighty Six Paise Fifty Seven
(Item No.165) Apply two coat Florthane-PU paint of standard make with approved colour and floor pattern design by architect
applied as a top coat. After 48hour of drying etc. Comp. as per the instructions of I/C.
Writing letter or figures on any surface with black japan paint (stops,comas, hyphens and the like not to be measured
and paid for separately)(i) Block (Letters/Figures) (Per 10 Letter pet CM.HT)
It Code No.19023a Letter Rupees Three Paise Thirty
Pg.No.152 Per Four Only
Writing letter or figures on any surface with black japan paint (stops,comas, hyphens and the like not to be measured
and paid for separately) (ii) Indian (Letters/Figures)
It Code No.19023b Letter Rupees Three Paise Fifty
Pg.No.152 Per Two Only
Extra over above items for using thick white paint instead of black japan paint. (i) Block (Letters/Figures)
It Code No.19024a Letter
144 70.00 0.07 Rupees Paise Seven Only
Supplying and fitting of X-ray protective lead sheet (2 mm or as per site requirement) on existing wooden/matel/flush
As Per Patdi SDH Rupees Six hundred Ninety
145 25.00 door or on new door but including 6 mm ply wood & Hardware accessories (SS D handle 152, SS Aldrop 254 mm long, Kg. 696.90
(Item No.171) Six Paise Ninety Only
Goderej door closer, SS Tower Bolt etc complete
Supplying and fitting of lead glass of approved quality for X-ray protection of 10 mm thick.
As Per Patdi SDH Rupees Eight Thousand One
(Item No.172) hundred Eighty One Only
Providing & Fixing garware make non transparent NR CHARCOAL , 20 suncontrol film 1mm thick with 42% of solar
As Per Patdi SDH Rupees Four hundred Sixty
147 450.00 energy reflectance. To be fixed on window glass panels as per instruction in proper maner without any crach,currling Smt 469.65
(Item No.173) Nine Paise Sixty Five Only
and whole etc. up to the corner and edges of glass panel.
Supplying and fitting of waterproof ISI branded of approved quality Ply wood for all type of work like furniture and
Rupees One Thousand Two
As Per Patdi SDH table top or door surfacing etc complete 12mm
148 144.00 Smt 1237.25 hundred Thirty Seven Paise
Twenty Five Only
Providing and Fixing Special quality Sheet glass one side vision (reflected ) as per desided by engineer incharge of
As Per Patdi SDH Rupees Eight hundred Fifty
149 231.00 approved quality bedded in puty and fixed with wooden beadings including the cost of wooden beadings of first class Smt 858.50
(Item No.175) Eight Paise Fifty Only
teak wood and necessary cutting of Glass (4) 4 mm thick
Applying Melamine polishing of Asian paint or Royal paint in any shade as per instruction of engineer incharge. the
work shall be carried out by specilized agency only as per approved manufacture's specification in two or three coat
As Per Patdi SDH Rupees Four hundred Fifty
150 180.00 up to satisfaction of engineer incharge on previously Polished wood or wood Base Surface to give an even surface Smt 454.50
(Item No.176) Four Paise Fifty Only
including cleaning the surface by sandpaper Smooth and also including coat of wood Filler as directed by Engineer-in-
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
providing and fixing single layer 12.5 mm GYPROC make all four side tepered perforated gypsum acoustical board
having eight quadrents having 12 mm hexagonal shaped perforations and backed acoustical fleece peneling supported
on Gypsteel ULTRA 48 x 34 x 36 x 0.5 mm C stud placed on every 610 mm canter to canter in Gypsteel ULTRA 50 x 32 x
32 x 0.5 mm width floor channel, for horizontal support between the C-stud place Noggin Channel on board joint,
As Per Patdi SDH Rupees One Thousand Eight
151 225.00 then board screw fixed to stud at designed spacing all square and tapered edges of the boards are to be jointed and Smt 1818.00
(Item No.177) hundred Eighteen Only
finished so as to have a flush look which includes filling and finishing with gyproc jointing compound, gyproc joint
paper tape and laying of 50 mm glass wool or synthetic wool with paint and also include 100 mm aluminium skirting
as directed by Engineer-in-charge.
Providing and fixing insulated fire rated GI Sheet doors conforming to FD 120-I 30 classification of IS 3614 :2021 with
fire rating of 120 minutes integrity and 30 minutes insulation. The factory manufactured door frame and shutter
assembly shall be made out of minimum 1.20 mm thick GI Sheet with minimum 120 GSM coating as per IS: 277. Door
and frame should be finished with powder coating in standard RAL shade finish having DFT of minimum 30 microns.
The door should carry a minimum 500 Hrs of salt spray test. All accressesories like hardware, vision panel, fire &
smoke seal etc to be supplied by Fire door manufacturer only as per the guidelines laid down in IS 3614:2021.Every
door must carry a label confirming to type of door & its fire rating.The door must carry a 5years valid test evidence
As Per Patdi SDH Rupees Five Thousand Three
152 90.00 from CBRI-Roorkee / NTH-Kolkata/ NABL accrediated lab which operates in accordance with ISO/IEC 17025.The Door Smt 5302.50
(Item No.178) hundred Two Paise Fifty Only
frame shall be single rebate grooved profile of size minimum 100mm x 57mm made out of 1.20mm (18gauge)
minimum thick galvanized steel sheet. Frames shall be butt / mitered joint and field assembeled with bolting system.
Frames to have inbuilt grooved to accomodate Intumuscent fire seal strip 10X4MM, It shall be fixed in grooves,
specifically cut in rebate on all the 3 sides of the frame . The frame should also be provided with fire rated EPDM
smoke seal 12X12 mm conforming to IS: 3614:2021 or as per test evidence..
. All provisions should be mortised & provided with necessary inbuilt reinforcement to receieve appropriate hardware.
Frames should be provided with back plate bracket for anchor fastner with 8-10 mm dia and minimum 80 mm long
HDG fasteners, with Polyamide sleeves(Payable in extra item) for installation of frame in finished plastered masonary
wall opening. Note :- For grouting of Steel frames in masonary installations ;cement sand mixture 1:3 ratio by civil
contractor/fire rated PU foam or such fire rated material may be recommended except head member. Door leaf
should be minimum 46mm thick fully flush double skin door. Door leaf must be manufactured from 1.2mm(18gauge)
thick galvanised steel sheet. The infill material shall be mineral wool of minimum density 100 kg/cum. All doors shall
be factory prepped for receiving appropriate hardware and provided with necessary reinforcement for hinges, locks,
and door closers. The edges should be interlocked with a bending radius of 1.4mm. For double leaf doors integrated
astragals has to be provided on the meeting stile for both active and inactive leaf. The shutters shall be mounted to
the frame with SS 304 grade ball bearing type hinges of size 100x 75x3 mm alongwith all suitable hardware.Vision lite
size 200x300 mm or 150 x 400mm(max area 0.06sqm) wherever applicable should be provided with single layered
clear fire rated glass panes as per guidelines laid down under IS 3614 : 2021 vide clause no. 7.2.7 table no. 2 with a
clipon arrangement.The glass will be provided with fire rated ceramic tape of min.2 mm thickness with min.15mm
width alround on either face. Every Glass pane must carry a permanent marking of its glass manufacturer Note:-As per
drawings and design supplied by architect and instruction given by authority and E.I.C.
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Providing and fixing Un-insulated fire rated GI Sheet doors conforming to FD 120 classification of IS 3614 :2021 with
fire rating of 120 minutes integrity. The factory manufactured door frame and shutter assembly shall be made out of
minimum 1.20 mm thick GI Sheet with minimum 120 GSM coating as per IS: 277. Door and frame should be finished
with powder coating in standard RAL shade finish having DFT of minimum 30 microns. The door should carry a
minimum 500 Hrs of salt spray test. All accressesories like hardware, vision panel, fire & smoke seal etc to be supplied
by Fire door manufacturer only as per the guidelines laid down in IS 3614:2021.Every door must carry a label
confirming to type of door & its fire rating. The door must carry a 5years valid test evidence from CBRI-Roorkee / NTH-
Kolkata/ NABL accrediated lab which operates in accordance with ISO/IEC 17025.The Door frame shall be single Rupees Five Thousand Four
As Per Patdi SDH rebate grooved profile of size minimum 100mm x 57mm made out of 1.20mm (18gauge) minimum thick galvanized
153 120.00 Smt 5433.80 hundred Thirty Three Paise
(Item No.179) steel sheet. Frames shall be butt / mitered joint and field assembeled with bolting system. Frames to have inbuilt Eighty Only
grooved to accomodate Intumuscent fire seal strip 10X4MM, It shall be fixed in grooves, specifically cut in rebate on
all the 3 sides of the frame . The frame should also be provided with fire rated EPDM smoke seal 12X12 mm
conforming to IS: 3614:2021 or as per test evidence... All provisions should be mortised & provided with necessary
inbuilt reinforcement to receieve appropriate hardware.Frames should be provided with back plate bracket for anchor
fastner with 8-10 mm dia and minimum 80 mm long HDG fasteners, with Polyamide sleeves(Payable in extra item) for
installation of frame in finished plastered masonary wall opening.
Note :- For grouting of Steel frames in masonary installations ;cement sand mixture 1:3 ratio by civil contractor/fire
rated PU foam or such fire rated material may be recommended except head member.Door leaf should be minimum
46mm thick fully flush double skin door. Door leaf must be manufactured from 1.2mm(18gauge) thick galvanised steel
sheet. The infill material shall be resin bonded paper honey comb infill. All doors shall be factory prepped for
receiving appropriate hardware and provided with necessary reinforcement for hinges, locks, and door closers. The
edges should be interlocked with a bending radius of 1.4mm. For double leaf doors integrated astragals has to be
provided on the meeting stile for both active and inactive leaf.The shutters shall be mounted to the frame with SS
grade ball bearing type hinges of size 100x 75x3 mm alongwith all suitable hardware.Vision lite size 300x400 mm or
150 x 800mm(max area 0.12sqm) wherever applicable should be provided with single layered clear fire rated glass
panes as per guidelines laid down under IS 3614 2021 vide clause no. 7.2.7 table no. 2 with a clipon arrangement. The
glass will be provided with fire rated ceramic tape of min.2 mm thickness with min.15mm width alround on either
face. Every Glass pane must carry a permanent marking of its glass manufacturer Note:-As per drawings and design
supplied by architect and instruction given by authority and E.I.C.
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Lead Lined Doors:Providing and fixing Lead Lined Door of Navair make, comprising of Hardwood Frames, interlayered
with specified thickness of lead sheet and shutter comprising with approved material as per manufacturer
specification, the whole system shall be in accordance to AERB norms. The lead sheet Overlaps in frame & edge to
edge lead lining in shutters must be considered as approved by EIC.Door Frame: The Door Frames shall be hardwood
red merandi Frame, The Frame Shall be fully lead lined of 2 MM lead Sheet with 99% purity and as defined by AERB.
Frames should be fixed by anchor fasteners for installation on a finished plastered masonry wall opening. The size of
frame shall be min. 120 X 70 mm or as per approved manufacturer standard, with layered specified thickness of Lead
Line Sheets (in door type) being overlapped from either side, the finish of frame etc. shall be as per direction of
Engineer in Charge. Frame rebate shall be as per manufacturer standard, the finish of the door frame shall be wooden
primer finish as per EIC. The door frame shall be fixed with anchor fastener / dash fasteners or as per manufacturer Rupees Twenty Two
As Per Patdi SDH
154 60.00 and as approved by EIC. Shutter: Door leaf shall be 44 mm thick with commercial ply & laminate both side with or Smt 22725.00 Thousand Seven hundred
without vision lite.incase vision lite is required it shall be only Lead Glass as recomomnded by AERB/DRC .The internal Twenty Five Only
construction of the door should be rigid with lead line of 2mm thick all across the inside of the exposed surface.
Shutter shall be made with 6mm commercial borad and 35mm commercial board sandwitch between 2mm lead
sheet. All doors should be factory prepped for receiving appropriate hardware and provided with necessary
reinforcement for hinges, locks, and door closers as per ANSI Standard , the shutter shall be finished with approved
1mm thick laminate both side. Hardware: The hardware shall be fire rated hardware in accordance with requirement
of doors and as specified in the door type in the BOQ. The necessary reinforcement to be taken care if required while
placement of hardware. All the hardware shall be as approved by EIC and from approved makes only.
All hardware shall be with min. 2 years of warranty. Any miscellaneous items, accessories, screws, sealant, seals, filler
material etc. all to be consider to do the job and give full solution. No complaint shall be entertained & no additional
payment to be done. The whole system shall be factory prepped, the approved manufacturer and prime contractor
shall ensure about the zero leakage with including all hardware & fixtures. Note:-As per drawings and design supplied
by architect and instruction given by authority and E.I.C.
6 MM Thick Clear Fire rated Glass saint gobain make 200x300mm Rupees One Thousand Six
As Per Patdi SDH
155 30.00 Each 1666.50 hundred Sixty Six Paise Fifty
Mortise Shash Lock With SS Lever Handle Of SL7260/ TLH612 Becker F.S. Make (Required For Service Room Loction Rupees Three Thousand Two
As Per Patdi SDH
156 30.00 Such As AHU, Electrical Rooms Etc.) Set 3292.60 hundred Ninety Two Paise
Mortise Dead Lock with 80mm cylinder body both side key DL7260 Becker F.S. Dead Lock Make. (Required For Rupees Three Thousand
As Per Patdi SDH
157 30.00 SERVICES Door Location) Each 3075.45 Seventy Five Paise Forty Five
SS D Type Pull Handle of 300mm mm Long of PHD2230 Becker F.S Make. Rupees One Thousand Six
As Per Patdi SDH
158 30.00 Set 1676.60 hundred Seventy Six Paise
Door closers of BLC-604 Becker F.S Make. (Required For All Fire Doors Except Shaft Door) Rupees Two Thousand Three
As Per Patdi SDH
159 30.00 Each 2373.50 hundred Seventy Three Paise
As Per Patdi SDH SS 304 grade 300mm Long Towe Bolt of Becker FS Make with necessary screws as required. Rupees Four hundred
(Item No.186) Fourteen Paise Ten Only
As Per Patdi SDH Anchor fastners of HILTI of maximum 120mm length. Rupees Sixty Five Paise Sixty
(Item No.187) Five Only
As Per Patdi SDH Smoke seal 12x12mm Rupees One hundred Fifty
(Item No.188) One Paise Fifty Only
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Providing and fixing thermal insulation with Resin Bonded rock wool conforming to IS: 8183, having density
Rupees Two Thousand
It Code No.22017 kg/m3,50 mm thick,wrapped in 200 G Virgin Polythene Bags fixed to wall with screw, rawel plug & washers and held
163 130.00 Cmt 2738.08 Seven hundred Thirty Eight
Pg.No.173 and in position by criss cossing GI wire etc. complete as per directions of Engineer in- Charge.
Paise Eight Only
Providing and fixing in all exterior face panels breathable vapour barrier underneath the cement fiber board as per Rupees One hundred
It Code No.22018
164 75.00 National Building Code 2009 complete as per direction of Engineer-in-charge. Smt 171.73 Seventy One Paise Seventy
Providing erecting and fixing double coated ISI water tank of required capacity each with all necessary fittings and Rupees Three Paise Ninety
connection etc. complete on terrace Five Only
Bed Head panel : Horizontal Bed Head Panel made by high strength aluminium section,thickness of aluminium section
3 mm. Bed Head Panels offered by us are available in Aluminum Powder coated with provision for Gas Outlets & Rupees Four Thousand Eight
166 RA 421.00 Electrical 5/15 Amps switch sockets. As per the demand of the clients, our bed head panel is offered with Nurse Call Rmt 4885.98 hundred Eighty Five Paise
cutout. Ninety Eight Only
Providing and fixing 4 mm thick both side laminated compact sheet selected quality (PIU approved brand list) fix in
aluminium door, window, ventilator shutters and partitions any size, any shape etc. P & F with EPDM/ PVC rubber Rupees One Thousand Three
167 RA 794.96 gasket etc all complete at all floors/all levels/all heights as per the architectural drawings and the directions of Smt 1308.09 hundred Eight Paise Nine
Engineer-in-Charge. Actual laying installed sheet shall be measured (Cost of aluminium snap beading shall be paid in Only
Providing laying and jointing in true line and level 15mm dia. U.P.V.C. Pipe ( SCH- 40) for cold water including fittings
23061 as approved by Engineer In Charge. Pipe shall be fixed on the wall with the help of clamp at every two metre C/C or Rupees Seventy Two Paise
168 60.00 shall be concealed as directed including necessary fittings etc. including testing of pipe and joints and fixing the same Rmt 72.65
ch-23 pg-183 Sixty Five Only
with adhesive solvent, including cost of all materials.
Providing laying and jointing in true line and level 25mm dia. U.P.V.C. Pipe ( SCH- 40) for cold water including fittings
23062 as approved by Engineer In Charge. Pipe shall be fixed on the wall with the help of clamp at every two metre C/C or Rupees Ninety One Paise
169 80.00 shall be concealed as directed including necessary fittings etc. including testing of pipe and joints and fixing the same Rmt 91.84
ch 23 pg-184 Eighty Four Only
with adhesive solvent, including cost of all materials.
Providing laying and jointing in true line and level 40mm dia. U.P.V.C. Pipe ( SCH- 40) for cold water including fittings
23064 as approved by Engineer In Charge. Pipe shall be fixed on the wall with the help of clamp at every two metre C/C or Rupees One hundred Forty
170 408.00 shall be concealed as directed including necessary fittings etc. including testing of pipe and joints and fixing the same Rmt 148.12
ch-23 pg-184 Eight Paise Twelve Only
with adhesive solvent, including cost of all materials.
23028B1 Providing and fixing screw down bib taps of following size.(B) Brass chromium plated screws down Bib Tap (i) 15mm
Rupees One hundred Eighty
Six Paise Eighty Three Only
Providing and fixing 25mm size UPVC Ball Valve with necessary Adhesive and fittings as directed by Engineer in
Rupees Five hundred Forty
172 R.A 10.00 charge. Each 549.68
Nine Paise Sixty Eight Only
Providing and fixing 40mm size UPVC Ball Valve with necessary Adhesive and fittings as directed by Engineer in Rupees One Thousand Three
173 R.A 4.00 charge. Each 1345.71 hundred Forty Five Paise
Seventy One Only
SPECIAL NEED FOR DISABLED TOILET
Providing and Fixing EWC wall hung, Wash basin, Grab bar, Hinged rail & special faucet with spachula including seat
cover, and flush valve, fittings, nuts, bolts and gasket etc complete for disabled toilet of approved make and
conforming to IS Standards. Wash basin with one pair mounting brackets, Waste coupling 32 mm size full thread with Rupees Sixty One Thousand
174 RA 3.00 80 mm heightJaquar make with 7 years warranty: Chrome plated, Bottle trap Jaquar make with 7 years warranty: SET 61124.19 One hundred Twenty Four
Chrome plated etc., EWC S Trap & Cistern complete with fittings & seat cover, one no. hinged rail 750 mm & Two nos Paise Nineteen Only
of grab rails 600 mm ,etc. complete. Refer following product wise details,
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
ANAND SOR 2024- Providing and fixing water closet squatting Pan (Indian type W.C. Pan) size 580mm (Earthwork, bed concrete, foot
25 reste and trap to be measured and paid for separately) (A) Vitreous China.(I) Long pattern = White colour. Rupees Nine hundred Eighty
ITEM CODE : 23009 Paise Forty Seven Only
ANAND SOR 2024- Providing and fixing wash down water closet (European type, W.C. Pan) with integral P or S trap including jointing the
Rupees One Thousand Three
25 trap with soil pipe in Cement Mortar 1:1 (1-Cement : 1-fine sand) (Seal and cover to be measured and paid for
176 49.00 NOS. 1356.81 hundred Fifty Six Paise Eighty
ITEM CODE : 23010 separately)(A) vitreous China Pattern :(i) in white colour.
ANAND SOR 2024- Providing and fixing washbasin with single hole for pillar tap with C.I. or M.S. brackets painted white including sutting
Rupees One Thousand Five
25 holes and making good the same but excluding fittings.(A) Vitreous China:(ii) Flat Back washbasin 550 mm x v 400mm
177 104.00 NOS. 1526.65 hundred Twenty Six Paise
ITEM CODE : 23018 size. (i) In white colour
Sixty Five Only
ANAND SOR 2024-
Rupees One Thousand
25 Providing and fixing Urinal or approved quality
178 20.00 NOS. 1074.86 Seventy Four Paise Eighty
ITEM CODE : 23033 including conecting the Urinal with waste pipe , tap etc. complete.(A) White earthenware flat back or corner type
ITEM NO. : 23.122 size 430mm x 260mm x 350mm
Providing and fixing 12.5 Litres low level flushing cistern with a pair, of C.I. or Mild brackets, complete with fittings
ANAND SOR 2024- such as lead valve less syphon, 15mm nominal size brass ball valve with polythene float, C.P brass handle unions and
Rupees Two Thousand Three
25 couplings for connections, with inlet, outlet and overflow pipes, 40mm dia. porcelain enamelled flush bend including
179 77.00 NOS. 2370.39 hundred Seventy Paise Thirty
ITEM CODE : 23013 cutting holes in walls and making good the same connecting the flush bend with cistern and closet (overflow pipe to
ITEM NO. : 23.115 be measured and paid for separately)(A) Vitreous China (I) In white colour
WASTE COUPLING FOR BASIN
ANAND SOR 2024-
Providing and fixing C.P. brass waste for washbasin or sink. (B) 40mm dia
Rupees Eighty Nine Paise
180 ITEM CODE : 104.00 NOS. 89.83
Eighty Three Only
ANAND SOR 2024- PILLER COCK
25 Providing and fixing pillar tap, capstan head, screw down high pressure with screws, shanks and back nuts.
Rupees Three hundred Eight
181 ITEM CODE : 104.00 (i) 15mm dia NOS. 308.73
Paise Seventy Three Only
ANAND SOR 2024-
Providing and fixing chromium plated, bottle trap with necessary couplings of approved quality for wash basin.
25 Rupees Two hundred Ninety
ITEM CODE : 23036 Five Paise Eighty Only
ANGLE VALVE Rupees Two Thousand
183 RA 200.00 Providing & fixing 15mm C.P. Angle valve with C.P. copper connecting pipe 450 mm long and nuts, washer and brass NOS. 2765.38 Seven hundred Sixty Five
flange complete, including cutting and making good the wall where required. Paise Thirty Eight Only
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
TWO WAY BIB COCK
Providing & fixing in position following approved quality water saving CP fittings / Fixtures of 15 mm nominal dia. with
ISI mark / approved make of following type including providing & fixing specials, wall flanges and fixing to concealed / Rupees Three Thousand
184 RA 77.00 exposed pipe line with leak proof threaded joints using tephlon tapes, testing the joints hydraulically to a pressure of NOS. 3828.91 Eight hundred Twenty Eight
10 kg./ sq.cm, rectifying the leaky joints. if any, including cleaning etc. complete all as per specification. Paise Ninety One Only
Providing & fixing in position following approved quality water saving CP fittings / Fixtures of 15 mm nominal dia. with
ISI mark / approved make of following type including providing & fixing specials, wall flanges and fixing to concealed / Rupees Two Thousand Three
185 RA 77.00 exposed pipe line with leak proof threaded joints using tephlon tapes, testing the joints hydraulically to a pressure of NOS. 2301.79 hundred One Paise Seventy
10 kg./ sq.cm, rectif.ying the leaky joints. if any, including cleaning etc. complete all as per specification. Nine Only
BRAIDED HOSE PIPE
Providing and fixing Hand Shower (Health Faucet) with 8mm dia, ABS/brass body with double lock 1.50m long Flexible Rupees Seven hundred
186 RA 77.00 tube (Brass plated stainles steel flexible hose) and wall hook of approved quality confirming to IS standards. NOS. 789.82 Eighty Nine Paise Eighty Two
Providing, laying and jointing in true line and level 160 diametre U.P.V.C (Type B) conforming to IS 13592-1992 with
one end plain and other end socketed with rubber ring, & fittings conforming to ISI 14735-1999 of approved make for
drainage system pipe line, pipe shall be jointed with each other with rubber lubricant, pipe shall be fixed on wall using
ANAND SOR 2024- of PVC clamp of the size 160 mm diametre x 210 mm length x 196 mm heigh at every 2000 mm center to center or Rupees Eight hundred Thirty
187 25 48.00 shall be concealed in walls as directed including necessary fittings such as bends, shoes etc. including testing of pipes Rmt 834.38
Four Paise Thirty Eight Only
ITEM CODE : 23066 and joints and jointed with adhesive solvent cement including cost of all materials.
For Soil & waste, Vent and Rain water pipe lines. 160 mm dia.
ANAND SOR 2024-
Rupees Eight hundred
Seventy Six Paise Ninety Only
Providing & fixing uPVC Floor P-Trap of following size having not less than 55mm effective water seal, fixing the trap in
position and connecting with waste water pipe by cement solvent/ as per manufacturer's recommandation,
embedding the trap in cement concrete 1:2:4 to correct level and gradient, providing and fixing 150 x 150 mm size top Rupees One Thousand Eight
189 RA 84.00 tile with central strainer & flat cover/ flush strainer, closing the side inletes with plugs if required etc. complete all as Each 1850.32 hundred Fifty Paise Thirty
per specification and as directed by the Engineer in charge. Two Only
Make : Astral, Supreme.
Providing and fixing stainless steel (SS304) Perforated grating 'of 18 gauge thick, with 'circular perforation
Rupees Two Thousand Eight
including Cockroach trap of 'approved pattern over CI/PVC 'traps. The grating shall be of size 153mm x 153mm or
190 RA 84.00 Each 2898.70 hundred Ninety Eight Paise
circular of 100mm dia '(as directed) and shall 'be set in cement, sand mortar 1:3 etc. complete.
Providing and fixing Height Riser of 110 x 75 x 50 size of approved make. Complete all as per specification and as Rupees One Thousand One
191 RA 84.00 directed by the Engineer in charge. Each 1113.02 hundred Thirteen Paise Two
Make : Astral, Supreme. Only
Making Khurras 45x45cm with average minimum thickness of 50 mm. cement concrete 1:2:4 (1 cement:2 coarse sand
Rupees One Thousand Four
:4 graded stone aggregate of 20mm nominal size) over P.V.C. sheet 1mx1mx400micron, finished with 12mm cement
192 RA 30.00 Each 1492.78 hundred Ninety Two Paise
plaster 1:3 (1 cement: 3 coarse sand) and a QUOTE of neat cement rounding the edge sand making and finishing the
Seventy Eight Only
outlet complete depth as per site requirement.
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Constructing Manhole with R.C.C. top slab in 1:2:4 mix (1cement :2-coarse sand : 4-graded stone aggregate 20mm
nominal size) foundation concrete 1:3:6 mix (1-cement : 3- coarse sand :6-Brick bats 40 + 50mm size) inside
plastering 15mm thick with Cement Mortar 1:3 (1Cement : 3-coarse sand) finished with a floating coat of neat
ANAND SOR 2024- cement and making channels in cement concrete 1:2:4 mix (1-Cement :2-Coarse sand :4-stone aggregate 20mm
25 nominal size) finished smooth complete including curing and festing (i) Inside size 900mm x 1200mm and 1.5M. deep Rupees Eleven Thousand
193 ITEM CODE : 12.00 including C.I. cover with frame size 560mm diameter total weight of cover and frame to be not less than 128 kgs. Each 11042.74 Forty Two Paise Seventy
24008A (Wt. of cover 64 Kg. and Wt. of frame 64 Kg.)(A) With 230mm thick walls of brick msonry using brick having crushing Four Only
ITEM NO. : 24.27 strength not less than 35Kg. / Sq.cm. in Cement Mortar 1:5 (1- Cement: 5-Coarse sand) (1) A type depth
Metre for 150mm diameter sewer.
Constructing Manhole with R.C.C. top slab in 1:2:4 mix (1cement :2-coarse sand : 4-graded stone aggregate 20mm
nominal size) foundation concrete 1:3:6 mix (1-cement : 3- coarse sand :6-Brick bats 40 + 50mm size) inside
plastering 15mm thick with Cement Mortar 1:3 (1Cement : 3-coarse sand) finished with a floating coat of neat
ANAND SOR 2024-
cement and making channels in cement concrete 1:2:4 mix (1-Cement :2-Coarse sand :4-stone aggregate 20mm
25 Rupees Nineteen Thousand
nominal size) finished smooth complete including curing and festing (i) Inside size 900mm x 1200mm and 1.5M. deep
194 ITEM CODE : 17.00 Each 19349.63 Three hundred Forty Nine
including C.I. cover with frame size 560mm diameter total weight of cover and frame to be not less than 128 kgs.
24008B Paise Sixty Three Only
(Wt. of cover 64 Kg. and Wt. of frame 64 Kg.)(A) With 230mm thick walls of brick msonry using brick having crushing
strength not less than 35Kg. / Sq.cm. in Cement Mortar 1:5 (1- Cement: 5-Coarse sand) (2) B type depth
Metre for 150mm diameter sewer.
Constructing Manhole with R.C.C. top slab in 1:2:4 mix (1cement :2-coarse sand : 4-graded stone aggregate 20mm
nominal size) foundation concrete 1:3:6 mix (1-cement : 3- coarse sand :6-Brick bats 40 + 50mm size) inside
plastering 15mm thick with Cement Mortar 1:5 (1Cement : 5-coarse sand) finished with a floating coat of neat
ANAND SOR 2024-
cement and making channels in cement concrete 1:2:4 mix (1-Cement :2-Coarse sand :4-stone aggregate 20mm Rupees Twenty Three
nominal size) finished smooth complete including curing and festing (i) Inside size 900mm x 1200mm and 1.5M. deep Thousand Four hundred
195 ITEM CODE : 5.00 Each 23470.48
including C.I. cover with frame size 560mm diameter total weight of cover and frame to be not less than 128 kgs. Seventy Paise Forty Eight
(Wt. of cover 64 Kg. and Wt. of frame 64 Kg.)(A) With 230mm thick walls of brick msonry using brick having crushing Only
strength not less than 35Kg. / Sq.cm. in Cement Mortar 1:5 (1- Cement: 5-Coarse sand) (3) C type depth
Metre for 150mm diameter sewer.
Providing & laying UPVC under ground drainage pipes & Fittings of Approved make for storm water drains & Sewer
lines of following size conforming to IS:15328 to proper level & grade, jointing including providing coupler with solvent
cement / welded joints / as per manufacturer's requirement, encasing the pipe alround using cement concrete 1:3:6 Rupees One Thousand Five
196 RA 240.00 complete if required all as per specifictions, drawing and as directed by the E.I.C. item includes Providing and fixing Rmt 1588.73 hundred Eighty Eight Paise
UPVC fittings such as Bendes, Tees & Y, Reducers, Blanking Plugs, Couplers, Adaptors etc For Sewer line and Storm Seventy Three Only
water Drains NOTE:- Cement concrete for encasing shall be paid under relevant item.160 mm DN (SN 8kN/m²)
200 mm DN (SN 8kN/m²) Rupees Two Thousand Two
197 RA 280.00 Rmt 2240.18 hundred Forty Paise Eighteen
Construction of Percolation well of size 3000 mm Dia including excavation, backfilling, watering, soling, compaction,
Reinforcement etc. complete. It includes Brick Massonry work (Calss of 7.5) R.C.C work of for walls, top and bottom
slabs, Rubble soiling and also having 100mm thick PCC in M-15 at bottom level. also In bottom layer Loose boulders,
Gravels and Coarse Sand layer also as per mendtioned in drawing. It shall be plastered with 20mm thick Plaster with
Rupees Five Lakh Five
198 RA 1.00 neat coat in CM 1:3 on internal and outside of chamber with 20mm thick sand faced cement plaster in CM 1:4 two Each 505000.00
coat at all sides. Top shall be covered with FRP Reccessed heavy duty Solid Top Manhole cover with clear opening of
600x600mm with frame and cover as Mentioned in Drawing. It shall be completed with all respect in ture line level,
plumb with neat & clean surface as per coordinated infrastructure detail drawing up to the level of satisfaction.
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Valve Chamber (For Drainage)
Construction of Valve Chamber of size 900X900X1500 mm including excavation, backfilling, watering, soling,
compaction, Reinforcement, Rungs etc. complete. It includes Brick Masonry work (Class of 7.5) and R.C.C work of for
walls, top and bottom slabs, also having Rubble soiling and 100mm thick PCC in M-15 at bottom level. It shall be
plastered with 20mm thick Plaster with neat coat in CM 1:3 on internal and outside of chamber with 20mm thick sand Rupees Fifty Thousand Five
199 RA 1.00 faced cement plaster in two coat CM 1:4 at all sides. Top shall be covered with FRP Reccessed surface heavy duty Solid Each 50500.00
Top Manhole cover with clear opening of 600mm diameter with frame and cover as Mentioned in Drawing. It shall be
completed with all respect in ture line level, plumb with neat & clean surface as per coordinated infrastructure detail
drawing up to the level of satisfaction.
Providing and fixing PP-R (Poly propylene Random copolymer) pipes and fittings conforming to IS: 15801: 2019, and
international standards British Standard (BS EN) for PPR pipes and fittings would be under the EN ISO 15874 SKZ - Das
Kunststoff-Zentrum, the standard for PPR (Polypropylene Random Copolymer) pipes and fittings is typically governed
by the DIN (Deutsches Institute für Normung), which translates to the German Institute for Standardization. The
relevant DIN standard for PPR pipes is DIN 8077, and for PPR fittings, it is DIN 8078. Saudi Standards, Metrology and
Quality Organization (SASO) set the standards for products in Saudi Arabia. For PPR (Polypropylene Random
Copolymer) pipes and fittings, the specific SASO standard would be SASO 2874/2019. ISO (International Organization
Rupees One hundred Sixty
200 RA 193.00 for Standardization) 9001-2015 WRAS (Water Regulations Advisory Scheme) BS EN ISO 15874 Series: European Rmt 161.60
One Paise Sixty Only
standard for plastics piping systems for hot and cold water installations - Polypropylene (PP). Different parts of this
series cover pipes, fittings, and joints. BS 6920: Suitability of non-metallic products for use in contact with water
intended for human consumption with regard to their effect on the quality of the water.NSF/ANSI 14: NSF/ANSI
anti-microbial fusion welded, having thermal stability for cold water supply, including all PP- R plain & brass threaded
polypropylene random fittings, i/c fixing the pipe.
Internal work - Exposed on wall 20 mm (PN-16 SDR 7.4)
25 mm (PN-16 SDR 7.4)
Rupees One hundred Eighty
One Paise Eighty Only
32 mm (PN-16 SDR 7.4)
Rupees Two hundred Thirty
Three Paise Thirty One Only
40 mm (PN-16 SDR 7.4)
Rupees Two hundred Ninety
Two Paise Ninety Only
50 mm (PN-10 SDR 7.4)
Rupees Four hundred Forty
Six Paise Forty Two Only
65 mm (PN-10 SDR 7.4) Rupees Six hundred Fifty Five
Paise Forty Nine Only
80 mm (PN-10 SDR 7.4)
Rupees One Thousand Thirty
Nine Paise Twenty Nine Only
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Providing and fixing PP-R (Poly propylene Random copolymer) pipes and fittings conforming to IS: 15801: 2019, and
international standards British Standard (BS EN) for PPR pipes and fittings would be under the EN ISO 15874 SKZ - Das
Kunststoff-Zentrum, the standard for PPR (Polypropylene Random Copolymer) pipes and fittings is typically governed
by the DIN (Deutsches Institute für Normung), which translates to the German Institute for Standardization. The
relevant DIN standard for PPR pipes is DIN 8077, and for PPR fittings, it is DIN 8078. Saudi Standards, Metrology and
Quality Organization (SASO) set the standards for products in Saudi Arabia. For PPR (Polypropylene Random
Copolymer) pipes and fittings, the specific SASO standard would be SASO 2874/2019. ISO (International Organization Rupees One hundred
207 RA 794.00 for Standardization) 9001-2015 WRAS (Water Regulations Advisory Scheme) BS EN ISO 15874 Series: European Rmt 179.78 Seventy Nine Paise Seventy
standard for plastics piping systems for hot and cold water installations - Polypropylene (PP). Different parts of this Eight Only
series cover pipes, fittings, and joints. BS 6920: Suitability of non-metallic products for use in contact with water
intended for human consumption with regard to their effect on the quality of the water.NSF/ANSI 14: NSF/ANSI
anti-microbial fusion welded, having thermal stability for cold water supply, including all PP- R plain & brass threaded
polypropylene random fittings, i/c fixing the pipe.
Concealed work, including cutting chases and making good the walls etc. 20 mm (PN-16 SDR 7.4)
25 mm (PN-16 SDR 7.4)
Rupees One hundred Ninety
Two Paise Ninety One Only
32 mm (PN-16 SDR 7.4) Rupees Two hundred
209 RA 48.00 Rmt 274.72 Seventy Four Paise Seventy
Providing and fixing of gunmetal, male or female threaded isolation control valve (Ball Valve / Gate Valve), confirming Rupees One Thousand Nine
210 RA 56.00 to latest IS PN 25 with necessary specials, union, nipples etc., to complete the job. 20 mm NOS. 1931.12 hundred Thirty One Paise
25 mm Rupees Two Thousand
211 RA 63.00 NOS. 2735.08 Seven hundred Thirty Five
Paise Eight Only
32 mm Rupees Four Thousand Six
Paise Sixty Seven Only
40 mm Rupees Five Thousand
213 RA 2.00 NOS. 5092.42 Ninety Two Paise Forty Two
50 mm Rupees Seven Thousand Six
214 RA 2.00 NOS. 7626.51 hundred Twenty Six Paise
65 mm Rupees Eleven Thousand Six
hundred Fifteen Only
80 mm Rupees Seventeen Thousand
216 RA 15.00 NOS. 17088.19 Eighty Eight Paise Nineteen
Providing following size Cast Iron / Spiroidal Iron Singal Air valve of PN 1.6 of approved quality and make conforming
to IS:14845 with ISI mark & Copper/Brass isolation Gate valve of PN as per air valve of approved quality and make
conforming to IS:778/IS:13114, Tapers and specials etc. including making necessary screwed / flanged joints by Rupees One Thousand Eight
217 RA 4.00 providing all jointing materials testing the joints and valves hydraulically to a pressure & duration as specified along NOS. 1867.49 hundred Sixty Seven Paise
with the pipeline all as per the specifications and as directed by the E.I.C. 25 mm size Forty Nine Only
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
DOMESTIC WATER TREATMENT PLANT
Supply installation, testing and commissioning of dometic water treatment plant comprising of Pressure sand filter,
and softner Plant accrording to input water quality/analysis. Water treatment plant consisting of FRP tank, filter
media, resins, brine tank, CPVC SCH 80 piping, isolation valves, instruments supports. The scope shall include CPVC
SCH 80 interconnection piping, Butterfly Cast Iron valves, NRV, instruments, autoback wash arrangement, Brine Rupees Three Lakh Fifty
218 RA 1.00 preparation tank & agitator platform, 1 nos Agitator require capacity and Ventury etc.complete the job .Scope shall SET 353500.00 Three thousand Five hundred
also includes one month operation including consumable and training for operation of staff. Only
Inlet Flow Range : 12.5 m3/hour.
Input Water Parameters: - As per Site
Output Water Hardness : < 50 PPM
Centtrifugal Monoblock Transfer pump
Supplying, installing, testing and commissioning of centrifugal pumps Complete with SS-316 casing, S.S 316 impeller
and SS-316 shaft, C.I. Base CED (Cathode Electrode Deposition) coating & head TEFC motor (with mechanical seal)
driven by 415 V AC, 3 phase, 50HZ., motor running at 2900 rpm speed , dry run protection, antivibration paid, 2 pole
Motor & IE3 Efficiency, shall be supplied with all accessories viz., base plate, coupling, motor etc. complete.
Contractor to submit performance curves and technical catalogue of the proposed model for review and information.
Panel mounted microprocessor based multi pump controller with large graphical display with VGA 240 x 320 pixels
and IP 55 enclosure, diodes to indicate pump ready, earthing, pump running and fault condition, Cascade Operation.
Each incomer and Outgoing feeder should be capable for protection against Overload, Short Circuit and Phase reversal Rupees One Lakh Fifty One
condition and shall be capable to communicate with other controllers following. The PLC shall support MODBUS-IP thousand Five hundred Only
communication for its compatability to intergrate with 3rd party BAS system. Controller shall authorise Read/Write
command via BMS.All alarms should be displayed in the controller. System should be equipped with dry running
protection. Indication of all type of faults / on-off status / electrical parameters shall be available on panel and central
IBMS monitors. On-off operation for all pumps shall be available on BMS system. SITC of elctronic type low water level
controler with LED panel to operate pump (necessary contacts along with minium one PLC operated spare contacts
required), shall prevent the pump from dry running
Mounting Height : 500mm from the bottom of Raw Water tank. Electronic type low, Medium & High water level
controller with LED panel to operate pump (necessary contacts along with minimum one PLC operated spare contacts
required),level controller with operational mode as one pump working at Medium level and cut off at High level
complete the job.
Mounting Height (Medium Level) : (Domestic Treated water Tank)
Mounting Height (Hight Level ): (Domestic Treated water Tank) with probe & all control wiring from Pump room Panel
to operate the system automatic/manual & shall prevent the pump from dry running.
Scope shall also include power and control cable of required size, termination, cable tray from Pump to Control panel,
control cable as whereever required etc. complete the job.
Set of accessories such as GI C Class headers of suction and discharge for (working and Standby pump assembly) with
CED Coating, Gun Metal Isolation valves, Gun Metal non return valves, pressure gauge with Isolation Valve of PN
etc. complete the job.
Capacity per pump - 12.5 m3/hour, Head - 30 mt, 1 Set = 2 Nos. Pump (1 Working + 1 Standby - cascade operation).
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
HYDRO PNEUMATIC SYSTEM FOR Domestic Water Distribution,
Variable Speed Hydro-booster System
Compact self contained Hydro-booster system comprising of following
SITC of In-line, vertical multistage, centrifugal clear water pumps with SS-304 casing, S.S 304 impeller and SS-304
shaft, C.I. Base CED (Cathode Electrode Deposition) coating & head TEFC motor (with mechanical seal), dry run
protection, antivibration paid, 2 pole Motor & IE3 Efficiency. Vendor to submit performance curves and technical
catalogue of the proposed model for review and information.
Panel mounted microprocessor based multi pump controller with large graphical display with VGA 240 x 320 pixels
and variable frequency drive (VFD) integrated in a single body, pressure sensor transmitter, IP 55 enclosure, diodes to
indicate pump ready, earthing, pump running and fault condition, Cascade Operation. Each incomer and Outgoing
Rupees Two Lakh Two
220 RA 1.00 feeder should be capable for protection against Overload, Short Circuit and Phase reversal condition and shall be SET 202000.00
capable to communicate with other controllers following. The PLC shall support MODBUS-IP communication for its
compatability to intergrate with 3rd party BAS system. Controller shall authorise Read/Write command via
BMS.System should be capable to compensate for frictional losses at lower flows. All alarms should be displayed in
the controller. System should be equipped with dry running protection. Indication of all type of faults / on-off status /
electrical parameters shall be available on panel and central IBMS monitors. On-off operation for all pumps shall be
available on BMS system. Electronic type low water level controller with LED panel to operate pump (necessary
contacts along with minimum one PLC operated spare contacts required), with probe & all control wiring from Panel
to tank to operate the system automatic/manual & shall prevent the pump from dry running.
Scope shall also include power and control cable of required size, termination, cable tray from Pump to Control panel,
control cable as whereever required etc. complete the job.
Pre-charged diaphragm pressure vessel with interchangeable membrane, charging connection, connected to outlet
header with necessary flanges, gaskets, isolating valves, nuts/bolts etc. complete (size of pressure vessel shall be as
per manufacturer recommendation).
Set of accessories such as GI C Class headers of suction and discharge for (working and Standby pump assembly) with
CED Coating, Cast iron control valves, Cast Iron non return valves, pressure transducers, pressure gauge with Isolation
Valve of PN 10 etc. complete the job.Require complete company fitted ready-to-connect packaged system.
Capacity per pump - 2.5 m3/hour, Head - 30 mt, 1 Set = 1 Nos. Pump (1 Working + 1 Standby - cascade operation),
Location - UGT Pump Room
Supply, Installation, Testing and Commissioning of 50 mm thick Pre Fabricated Modular Operation Theater Panels
(Walls and Ceiling) made out Polyurethane foam injected at 40 Kg/m3 sandwiched between 0.8 mm thick GP and SP
sheet on front side and 0.5 mm GP and SP/PPGI sheet on back-side. The inner surface walls be fixed to the bricks wall
with essential support. There will be minimum possible cavity/gap in between solid and steel walls and will be variable
to suit the architects lay out for the flush mounting of the equipments. The wall and ceiling panels must comply with
necessary provision of to JIS Z 2801/ISO 22196, BS EN 1363-1:2020, EN 1363-2:1999, EN 1364-1:2015, DIN 52210-
2:1984-08, DIN 4102-1, Class A2. Any Third-party compliance certificate mandatory. Panel should be covered with Rupees Six Thousand Five
221 368.00 protective sheath of 300 d.f.t Anti-bacterial Paint having undergone Washability/Water resistance Test JIS K Smt 6550.00
hundred Fifty Only
5663.7.12, permeability test less than 200 unit of permeability, Anti-bacterial effect against staphyloccoccus aureus,
Escherichia coli (via HALO test) and safety and causative agents such as formaldehyde, toluene, xylene,
paradichlorobenzene etc. Third party (NABL approved Lab) certification for EGP and thickness test certificate to be
at time of supply.
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Supply, Installation, Testing and Commissioning of Ceiling Filtration System - The ceiling filtration system in the
surgical theatre should ensure a unidirectional distribution of sterile air, covering all areas affected by the airflow. It
should consist of a laminar flow system incorporated within a frame made from thick extruded aluminum profiles,
complete with a sealed gasket to prevent leaks. The system should incorporate "H 14" class HEPA filters positioned in
the ceiling plenum. These filters should achieve an MPPS average efficiency greater than 99.95% and a 3-micron DOP
efficiency greater than 99.99%. The filters should also be designed to handle a final pressure drop of no more than Rupees Three Lakh Ninety
600 Pa, operate at a maximum temperature of 60 degrees Celsius, and function effectively within a relative humidity thousand Only
range of 40-50%. The filtration ceiling system should be capable of maintaining a constant airflow velocity of 0.25 m/s
at the diffuser. This should be accomplished through the use of a diffuser or flow equalizer that ensures uniform and
constant air distribution over the entire surface area.
The flooring within the surgical theatre should consist of a minimum of 2mm thick antistatic seamless PVC, ensuring
durability and safety. This floor should be smooth, non-slip, and made from an impervious material with sufficient
conductivity to dissipate static electricity effectively, yet not so conductive as to risk electric shock to personnel. The
PVC used should be of very high quality, particularly designed for electrostatic charge dissipation, and should not be
less than 2 mm in thickness. The installation process should utilize continuous rolls, and joints should be seamlessly
welded using special PVC thermal welding units with welding bars of the same color to ensure uniformity and prevent
contamination. The sheets should be highly durable, capable of resisting shocks, indentations, and scratches. The
conductive material should be uniformly impregnated within the PVC as grains to enhance its antistatic properties.
Additionally, the flooring should be inert to body fluids, chemicals, and disinfectants, and remain unaffected by
temperature variations typical within an operating theatre. It should efficiently discharge electric charges up to 2 kV,
and the electrical resistance (point to ground) should be maintained within 2.5x10^4 to 5x10^6 ohms, ensuring no Sq Rupees Four Thousand Two
buildup of electrical charge beyond 100 volts. Floor installation should be performed by skilled workers from Mtrs. hundred Fifty Only
accredited agencies authorized by the PVC sheet supplier. The structure holding the filtration system, including the
filter frames and top plenum, should be made from either aluminum or stainless steel. The system should be CE/UL
certified and designed to achieve an ISO 14644/1 classification of ISO 5, with a bacteriological class of B (5 CFU/m3)
and particle decontamination kinetics CP of 5 minutes. After installation, the system's performance should be
validated by a third-party government-approved environmental lab to ensure compliance with specified standards. A
positive pressure should be maintained inside the operating theatre to prevent contamination from external air
The supplier should provide test certificates for the HEPA filters and the laminar airflow systems from the original
manufacturers. Furthermore, the size of the laminar airflow system should be a minimum of 8 feet by 8 feet. Finally,
the entire system should meet CE/BIS certification standards, ensuring it adheres to both European and Indian safety
and performance regulations and including validation. The installation should include a conductive copper grid
beneath the PVC sheet, supported by liquid epoxy compounds to create a uniform and level surface. Copper strips
should be made visible by grinding and not project more than 0.5mm above the floor level to prevent damage to the
PVC sheet, with one earthing lead brought out from every 150 sq.ft area and attached to the main earthing
strip/ground. The flooring should also be mechanically shockproof, scratchproof, flame retardant, and antimicrobial.
Corners of the flooring should be uniformly curved, and a concealed cove-former (aluminium) should overlap the wall
panel to a height of approximately 25mm and be sealed perfectly and uniformly. Before laying the PVC, suitable self-
leveling compounds should be used to prevent any undulations within the operating theatre. The final surface should
be non-corrosive to biological fluids and detergents, with a color that is uniform, pleasant, and matching with the
ambience as approved by the respective consignee.
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
The door to the surgical theatre should be a hermetically sealed, single sliding door measuring 2.1 meters in height
and 1.5 meters in width. The door should be equipped with a controller capable of being operated by elbow switches,
foot switches, and a touchless sensor, providing multiple, accessible control options. The track for the door should be
made from stainless steel or aluminum, with the running surface for the top rollers angled appropriately to minimize
resistance and facilitate smoother movement. The door leaf should be suspended using high-quality hard plastic
rollers with double bearings at the top. These rollers should run under the stainless steel or aluminum track to ensure
smooth and noiseless operation. The opening and closing mechanisms of the door should be controlled by a
microprocessor for precise electromechanical movement. The material of the door should be either SMS or HPL, with
a color that matches the interior design. The door should be designed to be strong yet lightweight for ease of use. In
case the automatic mechanism fails, the door should still be able to open and close effortlessly manually. The handle Rupees Two Lakh Ninety
of the door should be made from stainless steel with a matte finish and equipped with a high-quality cylindrical or Five thousand Only
ESPg lock for security. The door leaf should incorporate a high-quality synthetic rubber gasket with long durability to
ensure hermetic sealing and maintain a 99.99% air tightness at a minimum pressure of 75Pa. The floor on either side
of the door should be perfectly level, with a maximum permissible difference of +1mm, to avoid any tripping hazards
or unsealed gaps. The overall thickness of the finished door should range from 30-60mm, with the inner part of the
door filled with CFC-free polyurethane foam, approximately 48mm thick, sealed airtight to block any microbial ingress.
The door and its controls should comply with IEE regulations, utilizing DC brushless or PMDC motors that are
effectively isolated from mains power to ensure safety and reliability.
Additionally, the door should include a vision window measuring 300mm x 300mm, featuring double-glazed panels
that are hermetically sealed to maintain the integrity of the seal.
The movement of the door should be as quiet as possible, and the time to start moving after
receiving a signal should be adjustable between 0.5 to 20 seconds.The door controller should be CE marked, BIS
certified, or IEC 60601 certified to meet international and national safety standards. A test certificate for the
hermetically sealed door frame should be included in the pre-dispatch documents to verify compliance with the
specified standards and functionality.
Supply, Installation, Testing and Commissioning of Membrane-Type Operation Switch and Communication Controller -
The Operation Switch and Comms Controller should encompass all necessary controls to ensure the proper operation
and monitoring of equipment and services in the operating room (OR). Positioned for optimal visibility in the
surgeon's line of sight and the OT staff, the wall-mounted membrane-buttons should be easily accessible to the nurse
for operation and assistance. In addition to hosting a digital clock and elapsed time indicator, the panel should feature
a medical gas alarm, clearly indicating high and low gas pressures for each gas service, including vacuum, supported by
an audible alarm. The Operation Switch and Comms Controller should also provide an alarm mute option for fault
annunciation, with pressure sensors strategically located near isolation valves. Controls for general lighting, including
ON/OFF and dimming, organized in groups for uniform illumination, should be present. Furthermore, the panel should Rupees One Lakh Ninety
225 2.00 facilitate control over operating lights (major and satellite) and camera functions (on/off and intensity). A hands-free Nos. 195000.00
Five thousand Only
telephone set with memory should be conveniently situated, and temperature and humidity controls for the room,
linked to the AHU (+/5%) using NO/NC or Chilled Water/Hot Water Actuator Control Valve (whichever is applicable),
should be adjustable from the Operation Switch and Comms Controller. Real-time indicators, such as a digital room
pressure indicator and HEPA filter bank differential pressure indicator, are essential for monitoring and maintaining a
safe and controlled environment in the operating room. Telephone with Alpha-numeric keyboard is required with
Speed-dialing option
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Hatch boxes should be provided in each operating theater to facilitate the safe and efficient removal of waste
materials to the dirty linen area or adjacent corridor. Each hatch box should be equipped with two doors, operated
electrically or motorized, designed such that only one door can be opened at a time to prevent cross-contamination.
UV lighting should be installed to ensure sterilization and should remain on when both doors are closed, automatically Rupees One Lakh Fifteen
turning off when either door is opened. Indicators should be provided on both sides of the operating theater to thousand Only
monitor the door open/close status. The material of the hatch box should also be SS304 grade stainless steel, with a
minimum size of 600mm x 600mm.
In each operating theater, an operating list board should be installed. It should be made of ceramic with magnetic
properties and should be flush with the wall to maintain cleanliness and ease of use. LED type flat panel X-ray viewing
panels should be provided, complying with relevant electrical safety codes, and mounted flush with the wall to
prevent dust accumulation and microbial growth. The body should be made of extruded aluminum, powder-coated
Rupees Twenty Eight
227 2.00 with a bacteria-resistant and disinfectant-resistant finish. The diffuser on the front panel should provide a uniformly lit Nos. 28500.00
Thousand Five hundred Only
screen, and dimming controls should be easily accessible. Additionally, a proper spring-loaded film clip with rollers
should be included to securely hold and easily remove films without causing scratches.
LED type flat panel X-ray viewing panel should be supplied. This should comply with relevant electrical safely codes.
This should be a 2-panel viewing screen. Mounting should be flush with the wall to avoid dust accumulation and
growth or organisms between wall and panel. Body should be of extruded aluminium powder coated black with
bacteria resistant and disinfectant resistant finish. The diffuser on the front panel should be a uniformly lit screen. Rupees Forty One Thousand
Dimming electronic control should be enclosed at the bottom of the cabinet. Proper spring-loaded film clip with Five hundred Only
rollers should be provided to hold the films firmly and to remove the film without scratches
Supply, Installation, Testing and Commissioning of Double-Bay Scrub Sink - The scrub station should be compact,
designed for use in the OT complex, and facilitate pre-procedural scrubbing. It should be made from heavy gauge type
304 stainless steel with a minimum thickness of 1.5mm and feature seamless welded construction polished to a satin
finish. The scrub sink should have a front access panel for easy maintenance of water control valves, waste
connections, stoppers, and strainers. Hands-free operation should be enabled through infrared sensors with Rupees One Lakh Twenty Six
programmable adjustments. Thermostatic mixing valve control should maintain constant water temperature and be thousand Only
located behind the access panel. Timing should be adjustable to meet individual usage requirements, and units should
have reduced anti-splash fronts. An additional knee/foot-operated switch should also be provided for enhanced
Supply, Installation, Testing and Commissioning of Storage Units - Storage units should be constructed with same
material, as wall and ceiling panels. The shelves, made of glass and, should be removable for cleaning. The unit should
be divided into two or more parts, each with individual glass doors equipped with a high-quality locking system. The Rupees Eighty Five
overall size of the storage unit should Thousand Only
be approximately 200 cm (H) x 120 cm (W) x 35 cm (D).
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Supply, Installation, Testing and Commissioning of Peripheral Lighting - To enhance the operational environment of
each operating theatre, peripheral lighting and clean room luminaries should be installed, with a minimum of eight
units per theatre. These lights should offer an intensity of at least 500 Lux and be housed in highly specular anodized
aluminum with an optical antiglare system to minimize visual fatigue and glare. Each peripheral light should measure
2' x 1'. The covers for these luminaries should be constructed from highly resistant, disinfectant-proof laminated
safety glass or acrylic, featuring a stylish, fine-grained surface that complements the clean and sterile environment of
the operating theatre. The body of the luminaries should be made from sheet steel, perfectly powder-coated to resist
contamination and facilitate easy cleaning, and should be ready for connection either as individual units or within a
series circuit. This setup should include digital electronic control gear utilizing multilamp technology to optimize Rupees Twelve Thousand
231 20.00 energy efficiency and light output. The installation of these luminaries should ensure that the recess frames are gas Nos. 12000.00
tight. Each fitting should be flush with the ceiling and designed to be removable from either the top or bottom for
ease of maintenance. It is crucial that the light fittings are uniformly and aesthetically distributed across the ceiling to
provide consistent illumination throughout the OT, without interfering with visibility during procedures such as green
mode endoscopy. Furthermore, the peripheral lighting system should conform to IP65 or IP54 international protection
ratings, ensuring that the fixtures are dust tight and protected against water ingress, suitable for the demanding
conditions of an operating theatre.
Supply, Installation, Testing and Commissioning of Electrical Wiring inside OT - Power distribution within each
Operating Theatre (OT) should be handled via distribution boards located locally to each theatre using Fire Resistance
Low Smoke Wiring, layed in PVC conduits of reputed brand. The sub mains power to these panels should be provided
by the general electrical contractor, and all distribution services within the departments should run from these panels.
The power distribution unit should hold certifications such as EN, CE, FDA, IEC, and BIS to ensure compliance with
international safety and performance standards. Each wall of the MOT should have a minimum of two hybrid switch
sockets (6/16A) on each wall, in compliance with IEC standards. Light fittings within the clinical areas should be
recessed LED types equipped with control gear and sealed in accordance with the IP54 standard. This standard
ensures that the fittings are protected against limited dust ingress and water spray from all directions, suitable for
clinical environments. All equipment should be fully and permanently labeled to clearly identify and describe the
function, operation, and voltage of the apparatus concerned. Upon completion of the electrical installation, tests Rupees Two Lakh Ninety
should be carried out in accordance with the relevant sections of local wiring regulations, with results duly recorded. Nine thousand Only
Each OT should have a distribution board (DBs) installed, with suitable wiring. A separate enclosure should house all
high-voltage equipment to ensure safety and isolation. The remote cabinet should contain operating lamp
transformers, mains failure relays, UPS, electrical distribution equipment, and circuit protection equipment for all
circuits within the operating theatre. All internal wiring within the DBs should terminate in connectors equipped with
screws and clamp springs. Connections should be of the clip-on type mounted on a rail approved by CE/IEC/BIS
standards and labeled with indelible proprietary labels. All internal circuits should be protected by individual fuses or
miniature circuit breakers to ensure safety and manage potential electrical faults effectively.
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
AIR HENDALING UNIT Make:KrVelocity: Not More Then 10 mt/second. , Canvass Connection-Heavy duty, non partical
shreding,Fire Retardentuger,Nikotra only , Type: PLUG,Drirect Driven,Dynamically Balanced Selection of fan-Should
run comfortably at 50 HZ at rated capecity. Motor Make:Siemence,B.B,Crompton,ABB , Type:TEFC, IP:55, Foot
Mounted, VFD compitable and I2 generation Safety: Motor should have interlocked with AHU Motor door/excess/Fire
DamperType-TWO TIRE, Floor Mounted , Inner const.:0.6mm plain G.I , Outer const.:0.8 mm G.I. Pre coated / Powder
coated Thickness of Insulation: 25mm,PUF injected having density 40 to 42 kg/m3. ,Colour:As approved by CLIENT Rupees Twelve Lakh Twenty
CONDENSING UNIT : Condensing unit for AHU with all Five thousand Only
assesories and instalation (Copper pipie provide 3 mtr Only Extra will charged extra) consider 1200 sqfeet
insulation and ducting
Double Dome OT Light with Ceiling mounted Double Dome LED OT lights having following features and enclosed
technical specifications, having Mobile App Connectivity, Battery Backup
-Light intensity Ec - 160 000 & 160 000 lux, - Light intensity adjustment - 10 – 100% (using Digital Capacitive Touch
(Fully Remote Controlled)
- Color temperature Tc (with adjustment)
-Light field diameter d10 at Ec - 100 - 150 mm
-Working range - 1 m Rupees Three Lakh Ninety
234 2.00 -Color rendering index 93Ra Nos. 390000.00
- Focusing Preset: Adjustable
- LED Average life - 50000-60000 hrs
- Diameter of Light - not less than 650 mm per dome
- Power Consumption - not more than 120W
OT Light should be BIS marked; manufacturer should have CDSCO License for this product under Class A, Compliant to
IEC standards such as IEC60601-1:2005+A2:2020, IEC 60601-2-41:201 (Relevant Test Certificates to be submitted with
Bid) Clause-wise Technical Compliance to be
Single-arm surgery/anesthesia pendant designed for Operating Theatres should feature a compact, modular
configuration to meet the precise requirements of hospitals, enabling customization to suit specific operational needs
of both Operating Theatres and Intensive Care Units. It should be equipped with robust ceiling support capable of
mounting a selection of arms. The extension arm, pivotal for functionality, should allow horizontal movement with a
radius of 800-900mm and provide a level rotation ranging from 0 to 330/340 degrees, with both the extension arm
and terminal box designed to rotate together and independently for maximum versatility. The pendant should support
a net loading capacity of min. 100 kg, accommodating a variety of medical instruments and devices securely. For
Rupees Two Lakh Eighty
235 2.00 medical and electrical services, it should offer configurations that include at least two oxygen outlets, two vacuum Nos. 284000.00
Four thousand Only
outlets, one medical air, one medical air at 7 bar, and an optional nitrous oxide outlet (In-scope of MGPS vendor)
Additionally, there should be six main sockets, each capable of supporting 5 to 15 amps, conforming to universal
standards to facilitate the operation of various medical and electronic devices. In terms of materials and construction,
the pendant should be crafted from high-strength aluminum alloy with a sealed design to enhance durability and
maintain sterile conditions.
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
The arm itself should be made from high-density aluminum alloy extrusion, ensuring both strength and reliability.
Installation of the pendant should be ceiling-mounted to provide a reliable and firm setup, optimizing space usage in
the Operating Theatre or ICU while seamlessly integrating with existing medical systems for managing medical gas,
electrical services, data communication, and equipment. Additionally, the pendant should include practical features
such as a stainless steel IV pole and a ward vacuum unit clamp to further enhance its utility in a medical setting. With
a net weight of approximately 105 kg, accessible by the equipment carrier, the pendant should be robust yet
manageable, ensuring it meets the rigorous demands of modern medical environments.
Providing and fixing UPS (25KVA) Of Good Quality as directed by engineer incharge
Rupees Three Lakh Seventy
Five thousand Only
Medical Gas Pipe Line Of Required dia for OT oxygen , Vaccum , Air.. Etc reuired Point(from existing line ) as directed
Rupees Three Lakh Forty
237 2.00 by engineer incharge from Outer Nearest Passage to OT Pendant Rate Including , Alarm , Valve (for all line) , Point job 345000.00
Five thousand Only
,Flowmeter and Probe . if alredy then no payment given
10 x10 Oxygen Manifold with NRV, tail pipes and middle frame with chain as per Tender
Ayurvedic College Rupees Three Lakh Fifty
Specification attached.
238 & Hospital Building 2.00 Sets 350470.00 thousand Four hundred
at Narol Seventy Only
02+02 Cylinders Emergency Oxygen Manifold with NRV middle frame and High Flow
Ayurvedic College
Regulator without Rubber Diaphragm as per Tender Specification attached. Rupees Fifty Five Thousand
239 & Hospital Building 2.00 Sets 55001.57
One Paise Fifty Seven Only
Oxygen surface mounted Outlets NFPA/HTM Standard as per Tender Specification
Ayurvedic College Rupees Five Thousand Six
attached. (BS Metal Outlet)
240 & Hospital Building 100.00 Nos 5600.45 hundred Paise Forty Five
Oxygen Flow Meter with Humidifier Bottle as per Tender Specification attached.
Ayurvedic College Rupees Three Thousand
241 & Hospital Building 100.00 Nos 3939.00 Nine hundred Thirty Nine
Oxygen Probe as per Tender Specification attached.
Ayurvedic College Rupees One Thousand Two
242 & Hospital Building 100.00 Nos 1297.85 hundred Ninety Seven Paise
at Narol Eighty Five Only
Compressed Air System as per Tender Specification attached.
Ayurvedic College Triplex System- Screw Air Compressors (Total Flow 4500LPM) with 15HP motors with start/stop operations. 1 Nos. Rupees Twenty Eight Lakh
243 & Hospital Building 1.00 heatless dryer assy each having 175 cfm maximum capacity along with 4 stage bacterial filter assy and single Receiver Sets 2854063.05 Fifty Four thousand Sixty
at Narol of 2000 liter water capacity, nrv and Isolation valve, Gauges etc. Three Paise Five Only
Surface Mounted Gas outlets for Medical AIR NFPA/HTM Standard as per Tender
Ayurvedic College Rupees Five Thousand Six
Specification attached. (BS Metal Outlet)
244 & Hospital Building 45.00 Nos 5600.45 hundred Paise Forty Five
Suitable Probe for Medical Air gas outlets as per Tender Specification attached.
Ayurvedic College Rupees One Thousand Two
245 & Hospital Building 45.00 Nos 1297.85 hundred Ninety Seven Paise
at Narol Eighty Five Only
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Surface Mounted Gas outlets for Surgical AIR NFPA/HTM Standard as per Tender
Ayurvedic College Rupees Five Thousand Six
Specification attached. (BS Metal Outlet)
246 & Hospital Building 45.00 Nos 5600.45 hundred Paise Forty Five
Suitable Probe for Surgical Air gas outlets as per Tender Specification attached.
Ayurvedic College Rupees One Thousand Two
247 & Hospital Building 8.00 Nos 1297.85 hundred Ninety Seven Paise
at Narol Eighty Five Only
Vacuum Central System as per Tender Specification attached. Rupees Twenty Two Lakh
Ayurvedic College Complete Triplex Vacuum Vane Pumps set Model ----------- - (Total 2500 Flow LPM) with Filter, interconnecting pipes, Thirty Eight thousand Nine
248 & Hospital Building 1.00 NRV, isolation valves, auto switch gear assy, exhaust silencer,bacteria filters and a single Receivers having – 1500 liters Sets 2238915.48
hundred Fifteen Paise Forty
at Narol capacity Eight Only
Surface Mounted Gas outlets for Medical Vacuum NFPA Standard as per Tender
Ayurvedic College Rupees Five Thousand Six
Specification attached. (BS Metal Outlet)
249 & Hospital Building 45.00 Nos 5600.45 hundred Paise Forty Five
Vacuum Probe Suitable for Outlet as per Tender Specification attached.
Ayurvedic College Rupees One Thousand Two
250 & Hospital Building 45.00 Nos 1297.85 hundred Ninety Seven Paise
at Narol Eighty Five Only
High Pressure Tubing as per Tender Specification attached.
Ayurvedic College Rupees Two Thousand Nine
251 & Hospital Building 45.00 Mtrs 2941.12 hundred Forty One Paise
at Narol Twelve Only
Copper Pipe: - Lloyd's certified EN13348 as per Tender Specification attached.
Ayurvedic College
12x0.7mm Copper pipe Rupees Eight hundred
252 & Hospital Building 500.00 Mtrs 870.62
Seventy Paise Sixty Two Only
15x0.9mm Copper pipe
Ayurvedic College Rupees One Thousand Two
253 & Hospital Building 650.00 Mtrs 1242.30 hundred Forty Two Paise
at Narol Thirty Only
22x0.9mm copper pipe
Ayurvedic College
Rupees One Thousand Sixty
254 & Hospital Building 350.00 Mtrs 1068.58
Eight Paise Fifty Eight Only
28x0.9mm Copper Pipe
Ayurvedic College Rupees One Thousand
255 & Hospital Building 250.00 Mtrs 1753.36 Seven hundred Fifty Three
at Narol Paise Thirty Six Only
High flow piston Regulator IS/ ISO 7396 IS/ISO 10524-2 -2016 , IS/ISO 10524-4:2008
Ayurvedic College Rupees Twenty Eight
HTM 02-01 ClassII b MDR 2017/745
256 & Hospital Building 8.00 nos 28179.00 Thousand One hundred
at Narol Seventy Nine Only
Area Alarm Panel (Digital Illuminated LED - Microprocessor Based with Touch Function Rupees Twenty Nine
Ayurvedic College
and Audio-Visual Indication) as per Tender Specification attached. 2 Gas Alarm Panel Thousand Three hundred
257 & Hospital Building 8.00 Nos 29363.73
Sixty Three Paise Seventy
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Isolation Valve: - with Nut & Nipple Type Brass Fittings/SS Flange, (no ferrule/copper
Ayurvedic College Rupees Two Thousand Nine
ring type brass fittings) as per Tender Specification attached. 15mm Isolation Valve
258 & Hospital Building 160.00 Nos 2974.45 hundred Seventy Four Paise
at Narol Forty Five Only
22mm Isolation Valve
Ayurvedic College Rupees Three Thousand
259 & Hospital Building 40.00 Nos 3444.10 Four hundred Forty Four
at Narol Paise Ten Only
28mm Isolation Valve
Ayurvedic College
Rupees Five Thousand Forty
260 & Hospital Building 30.00 Nos 5040.91
Paise Ninety One Only
Supply, Installation, Testing and Commissioning of Electric driven Fire pump suitable for automatic operation and
consisting of following: complete in all respect as required.
a) Horizontal, centrifugal, end suction pump to ensure a minimum pressure of 3.5 kg / sq.cm. at highest and farthest
outlet at specified flow of 2280 lpm at 70 m. head conforming to IS standards.
b) Casing - CI, Impeller-Bronze, Shaft - SS 410, Mechanical seal
c) Squirrel cage induction motor with suitable HP with synchronous speed 2955 RPM, Suitable for operation on 415 Rupees Two Lakh Fifty Six
261 RA 1.00 volts, 3 phase 50 Hz. AC with IP 55 protection for enclosure, horizontal foot mounted type with Class-F insulation, Set 256260.00 thousand Two hundred Sixty
Conforming to IS standards. Only
d) Common Base plat for Pump and motor and coupling, coupling guard, rubber bellows, anti-vibration arrangement,
cables & other accessories as required for complete Installation of pump set.
e) Cement concrete foundation with cement concrete plaster will be in civil scope.Contractor has to provide
foundation drawing to civil contractor.
Supply, Installation, Testing and Commissioning of Diesel Engine driven fire pump (Standby Pump) suitable for
automatic operation and consisting of following: complete in all respect as required.
a) Horizontal, centrifugal, end suction pump to ensure a minimum pressure of 3.5 kg / sq.cm. at highest and farthest
outlet at specified flow of 2280 lpm at 70 m. head conforming to IS standards.
b) Casing - CI, Impeller-Bronze, Shaft - SS 410, Mechanical seal
c) Diesel Engine with suitable HP with synchronous speed 2300 RPM, diesel tank, battery, exhaust pipe with Rupees Five Lakh Forty
262 RA 1.00 insulation, all required accessories. Set 540403.00 thousand Four hundred
Exhaust pipe will be as per manufacturer's standard. Three Only
d) Common Base plat for Pump and motor and coupling, coupling guard, rubber bellows, anti-vibration arrangement,
cables & other accessories as required for complete Installation of pump set.
e) Cement concrete foundation with cement concrete plaster will be in civil scope.Contractor has to provide
foundation drawing to civil contractor.
Supply, Installation, Testing and Commissioning of Electric driven pressurization Jockey pump suitable for automatic
operation and consisting of following: complete in all respect as required.
a) Vertical inline pump to ensure a minimum pressure of 3.5 kg / sq.cm. at highest and farthest outlet at specified flow
of 180 lpm at 70 m. head conforming to IS standards.
b) Casing - SS 304, Impeller-SS 304, Shaft - SS 304, Mechanical seal
c) Squirrel cage induction motor with suitable HP with synchronous speed 2900 RPM, Suitable for operation on 415 Rupees One Lakh Three
263 RA 1.00 volts, 3 phase 50 Hz. AC with IP 55 protection for enclosure, horizontal foot mounted type with Class-F insulation, Set 103495.00 thousand Four hundred
Conforming to IS standards. Ninety Five Only
d) Common Base plat for Pump and motor and coupling, coupling guard and other accessories as required for
complete installation of pump set.
e) Cement concrete foundation with cement concrete plaster will be in civil scope.Contractor has to provide
foundation drawing to civil contractor.
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Supply, Installation, Testing and Commissioning of 150 mm dia. Pressure Gauge (for all pipes) of range 0 - 15 Kg / cm²
Polished Stainless Steel Case with positive seal against weather, moisture & dust, with Glycerine filled, screwed, Rupees Three Thousand
nipple, isolation valve, U-type stainless steel siphon tube and complete with necessary as required. Seven hundred Five Only
Supply, Installation, Testing and Commissioning of Pressure Switches for automation of fire pumps. Pressure switches
Rupees Three Thousand
265 RA 4.00 shall be SPDT type suitable for single phase supply with diaphragm, IP 67 protection as required. Nos. 3304.00
Three hundred Four Only
Supply, Installation, Testing and Commissioning of the following sizes of flange jointed / screwed / welded, M.S. Pipes
of Class C (Heavy class) ISI marked including accessories such as MS bracket, U clamps with Anchor fasteners, tees /
elbows / reducers / couplings / unions / bends / flanges/ wrapping coating for u/g pipes etc., and laying on the surface
including painting with two coats of anticorrosive primer and two coats of approved red enamel paint after laying and Rupees Four Thousand One
266 RA 17.00 testing after Installation etc. as per specifications complete as required. Rmt. 4112.00
hundred Twelve Only
All fittings up to 50mm shall be forged and above 50mm shall be butt welded.
Rupees Two Thousand Eight
hundred Fifty Five Only
Rupees One Thousand Nine
hundred Thirty Four Only
Rupees One Thousand Three
hundred Fifty Seven Only
e) 65 mm dia Rupees One Thousand One
hundred One Only
f) 50 mm dia Rupees Nine hundred Ninety
g) 40 mm dia Rupees Seven hundred Fifty
h) 32 mm dia Rupees Six hundred Twelve
i) 25 mm dia Rupees Four hundred
Seventy Four Only
Supply, Installation, Testing and Commissioning of the following sizes of flange jointed / screwed / welded,
Underground M.S. Pipes of Class C (Heavy class) ISI marked including accessories such as MS bracket, U clamps with
Anchor fasteners, tees / elbows / reducers / couplings / unions / bends / flanges / wrapping coating 4mm thick /
150mm width as per IS:10221 etc., and two coats of anticorrosive primer and testing after Installation etc. as per Rupees Two Thousand Five
specifications complete as required. hundred Sixty Seven Only
All fittings up to 50mm shall be forged and above 50mm shall be butt welded.
Rupees One Thousand Eight
hundred Twenty Nine Only
Supply, Installation, Testing and Commissioning of C.I. Y type Strainer with S.S. Screen/SS 304 having 1.2mm
Rupees Forty Thousand Five
277 RA 2.00 perforation with require accessories. Nos. 40541.00
hundred Forty One Only
Supply, Installation, Testing and Commissioning of C.I. Sluice valve (IS: 14846,PN 16) with flanges, nut bolts, gaskets Rupees Sixty One Thousand
278 RA 4.00 complete as required. Nos. 61948.00 Nine hundred Forty Eight
a) 200 mm dia. Only
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
b) 150 mm dia. Rupees Twenty Six
279 RA 4.00 Nos. 26192.00 Thousand One hundred
Ninety Two Only
c) 100 mm dia. Rupees Seventeen Thousand
Forty Four Only
d) 80 mm dia. Rupees Eleven Thousand
281 RA 1.00 Nos. 11879.00 Eight hundred Seventy Nine
Rupees Nine Thousand Four
hundred Seventy Five Only
Supply, installation, testing and commissioning of C.I. Butterfly valve (IS:13095 , PN 16) with flanges, nut bolts, gaskets Rupees Nine Thousand
283 RA 6.00 complete as required. Nos. 9767.00 Seven hundred Sixty Seven
a) 150 mm dia. Only
Rupees Five Thousand Five
hundred Seventy Three Only
Rupees Four Thousand Two
hundred Twenty Eight Only
d) 50 mm dia Rupees Three Thousand
Three hundred Only
Supply, Installation, Testing and Commissioning of Cast iron Dual plate Check valve (PN 1.6) Rupees Ten Thousand Two
a) 150 mm dia. hundred Sixty Only
b) 100 mm dia. Rupees Seven Thousand Five
hundred Forty Only
Rupees Five Thousand Three
hundred Twenty Nine Only
Supply, Installation, Testing and Commissioning of Air vessel of size 450 x 2000 mm long fabricated from 8 mm thick
M.S Plate and installed vertically on suitable legs. legs shall be provided with M.S. plate of size 50mmx50mmx6mm at Rupees Sixty Thousand Two
bottom with necessary accessories. as required for complete installation. hundred Twenty Eight Only
Supply, Installation, Testing and Commissioning S.S. Fire Hydrant Single Landing Valve with 80 mm N.B. flanged inlet,
SS spindle controlled 63 mm dia female instantaneous outlet type. SS coupling, blank cap, chain, twist release type Rupees Four Thousand
291 RA 31.00 lug & all accessories Conforming to IS:5290. Including fixing with anchor fastener and flanged tapping from wet riser Nos. 4774.00 Seven hundred Seventy Four
complete as required. Only
Supply, Installation, Testing and Commissioning of Fire Hose Cabinet wall mounting type 18swg (750 mm x 600 mm x Rupees Three Thousand
292 RA 36.00 250 mm deep) with required accessories as per specification. Nos. 3839.00 Eight hundred Thirty Nine
Supply, installation, testing and commissioning non-percolating rubber reinforced lined Fire Hose pipe (as per IS : 636)
of 63 mm dia and 1no.x15 mtrs long. The hose shall be rated for burst pressure of 38 kg/sqcm. Hose shall be complete Rupees Three Thousand
with ISI marked SS male & female coupling (IS:903) bound as per specification. Nine hundred Forty Five Only
Supply, Installation, Testing and commissioning of 63 mm dia instantaneous pattern SS short branch pipe, 20 mm dia Rupees One Thousand
294 RA 36.00 nozzle conforming to IS 903, suitable for inter connection to hose pipe coupling complete as required by the Local Nos. 1778.00 Seven hundred Seventy Eight
Fire Authority. Only
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Supply, installation, testing and commissioning of First Aid Hose Reel conforming to IS:884 comprising of hose reel
drum, 8 mm shut off nozzle, hose reel tubing type-2 as per IS: 444 of 25 mm dia x 36 mtr. long, painting, fixed wall Rupees Eight Thousand One
type with fixing bracket, anchor fastener, bolts & nuts etc. complete as required by Local Fire Authority. hundred Thirty Five Only
Supply, installation, testing and commissioning of forged brass Ball Valve.
Rupees One Thousand One
hundred Thirty Three Only
Supply, Installation, Testing and Commissioning of 25mm Brass Sprinkler test and Drain Valve (300 PSI) assembly with
Rupees Five Thousand Six
297 RA 26.00 all required fittings as per drawing and as directed. Set 5671.00
hundred Seventy One Only
Supply, installation, testing and commissioning of Cast Iron Four Way Fire Brigade Inlet as per IS: 904 having 63 mm
Rupees Seven Thousand Six
298 RA 1.00 dia inlet with blank cap and chain with necessary fittings, flanges, nut bolts etc. complete as required. Nos. 7667.00
hundred Sixty Seven Only
Supply, installation, testing and commissioning of Cast Iron Two Way Fire Brigade Inlet as per IS: 904 having 63 mm Rupees Four Thousand
299 RA 1.00 dia inlet with blank cap and chain with necessary fittings, flanges, nut bolts etc. complete as required. Nos. 4759.00 Seven hundred Fifty Nine
Supply, Installation, Testing and Commissioning of Gun Metal Air Release Valve with necessary fittings. Size: 25 mm Rupees Two Thousand
(For Riser) Twenty Eight Only
Supply, Installation, Testing and commissioning of Quartzoid Bulb type Sprinkler Heads. Rupees Three hundred
a) Pendent Sprinkler 57°C - K-80 - standard response - UL listed Fourteen Only
b) Pendent Sprinkler with rossette plate 57°C - K-80 - standard response - UL listed Rupees Four hundred One
Supply, Installation, Testing and commissioning of Vane type Flow Indicating Switch with fittings, Flanges, nut-bolts,
Rupees Five Thousand Three
303 RA 3.00 washers etc. as per requirement. a)150mm dia. Nos. 5398.00
hundred Ninety Eight Only
Rupees Five Thousand Three
hundred Ninety Eight Only
Rupees Five Thousand Three
hundred Ninety Eight Only
Providing, fixing, testing & commissioning UL listed SS corrugated Unbraided Flexible pipe, nominal Inlet by outlet 1"x
Rupees Seven hundred
306 RA 655.00 ½" with required accessories to complete the installation. Nos. 773.00
Seventy Three Only
b) Size: 1000mm Rupees Eight hundred
Supply, installation, testing and commissioning of Pump on/off Remote switches to each internal hydrant valve with Rupees Six hundred Eighteen
required accessories. Only
Supply, installation, testing and commissioning of XLPE insulated Flexible Cable with conduit from each Pump on/off
Rupees Two hundred Thirty
309 RA 300.00 switches to Panel with all necessary accessories. Rmt. 236.00
Size: 4 core x 2.5 sq. mm
Supply, installation, testing and commissioning of Carbon Dioxide (Co2) type Fire Extinguisher of 4.5 kg confirm to
Rupees Four Thousand Five
310 RA 47.00 IS:15683, stored pressure, squeeze type with ISI marked fitted with required accessories including wall suspension Nos. 4579.00
hundred Seventy Nine Only
Supply, installation, testing and commissioning of ABC (MAP 50%) type 6 kg stored pressure, squeeze type confirm to
Rupees One Thousand Nine
311 RA 47.00 IS:15683, with ISI marked fitted with required accessories including wall suspension brackets. Nos. 1906.00
hundred Six Only
Supply and fixing of Clean Agent HCF236fa, 10 Kg modular type ceiling mounted Fire extinguisher , Stored pressure
Rupees Thirty One Thousand
312 RA 25.00 type with pressure gauge. Nos. 31355.00
Three hundred Fifty Five Only
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Providing, fixing AUTO GLOW photo luminescent Signage's as per IS standard in Block / Small Letters on rigid sheet Rupees Three hundred Thirty
313 RA 26.00 with necessary wall or Ceiling fittings as Specified Sizes:a) Fire Equipment : size: 100 x 300mm Nos. 335.00
Supply Of Self Contained Rechargeable SWGS Emergency Egress Routes Lighting With the 1X 3 W LED Lamp. The
equipment Shall Surface/hanging mounted with all require Accessories with requirement for the Fire and Safety code
of practice with 3 Hours backup. Nominal Input Voltage 230 +-10 % to 240V A.C. +-10 % 50 Hz +-10 % as specified in Rupees Three Thousand Two
specification. hundred Thirty Six Only
(Size:300 x 180mm)
Point wiring for Light / Bell with 2-1.5 sq.mm & earth wire of 1.5 sq.mm (Green) both are of ISI marked 1.1 KV grade
FRLS PVC insulated multi strand copper wires up to 10 mtr length , in below type of pipe erected with 6A Modular
type switch / bell push & accessories and earth continuity of following type, erected on PVC / Metallic/Wooden box,
single mounting base frame covered with textured/metallic/white front plate modules erected on / in wall / ceiling Rupees Four hundred Eighty
as per pipe erected, with necessary Lamp holder/ceiling rose / H.D.Connector as directed. Five Paise Eighty One Only
(f) with medium class Rigid PVC pipe and accessories erected concealed in wall/ceiling complete. Cat. III
Point wiring for FAN with 2-1.5 sq.mm & earth wire of 1.5 sq.mm (Green) both are of .ISI marked 1.1 KV Grade FRLS
PVC insulated multi strand copper wires up to 10 mtr length, in below type of pipe erected with 6A Modular type
switch and hum free EME step type electronic fan regulator mounted and accessories with earth continuity of
following type erected on PVC / Metallic/Wooden box, single mounting base frame covered with Rupees Six hundred Seventy
textured/metallic/white front plate modules erected on / in wall / ceiling as per pipe erected. with necessary ceiling Four Paise Sixty Eight Only
rose / H.D.Connector as directed.
(f) with medium class Rigid PVC pipe and accessories erected concealed in wall/ceiling complete. Cat. III
Point wiring for Modular secondary light point with 2-1.5 sq.mm & earth wire of 1.5 sq.mm (green) both are of ISI
marked 1.1 KV grade FRLS PVC insulated multi strand copper wires, in below type of pipe to be erected complete
with earth continuity and necessary connection with primary light with accessories erected on Metal / PVC / wooden Rupees One hundred Sixty
box covered with 3 mm thick PC(Polycarbonate) / Acrylic sheet for open / concealed wiring. with necessary Lamp Seven Paise Sixty Six Only
holder / ceiling rose / H.D.Connector as directed.
(f) with medium class Rigid PVC pipe and accessories erected concealed in wall/ceiling complete
Point wiring for Individual Plug with & earth wire of 1.5 sq.mm (Green) both are of ISI marked 1.1 KV grade FRLS PVC
insulated multi strand copper wires up to 10 mtr length, in below type of pipe erected complete with Modular type
switch & 5 pin Plug erected on PVC / Metallic/Wooden box covered with appropriate front plate modules erected on
Rupees Five hundred Ten
318 1-2-3. 50.00 / in wall / ceiling as per pipe erected with following type of accessories. Ea. 510.05
Paise Five Only
[I] For 6A Plug and 6 a switch with 2-1.5 sq.mm Cu. Wire from nearby switchboard/mcb db board.
(f) with medium class Rigid PVC pipe and accessories erected concealed in wall/ceiling complete. Cat. III
[II] For 16A Plug and 16 amp switch with 2-2.5 sq.mm Cu. Wire from mcb db board.
Rupees Seven hundred Forty
319 1-2-3. 292.00 (f) with medium class Rigid PVC pipe and accessories erected concealed in wall/ceiling complete. Cat. III Ea. 745.38
Five Paise Thirty Eight Only
[III] For 16A Plug and 16 amp switch with 2-4 sq.mm Cu. Wire with 2.5 sq.mm ( green) earthing wire from mcb d b Rupees Eight hundred
320 1-2-3. 25.00 board.(f) with medium class Rigid PVC pipe and accessories erected concealed in wall/ceiling complete. Cat. III Ea. 871.63 Seventy One Paise Sixty
Point wiring for on board Looped Plug with 6A Modular type switch & 5 pin socket erected on PVC / Metallic/Wooden
box, single mounting base frame covered with textured / metallic/white front plate modules erected on / in wall / Rupees Two hundred Fifty
321 1-2-4. 341.00 ceiling with following type accessories. Cat. III(f) with medium class Rigid PVC pipe and accessories erected concealed Ea. 257.55
Seven Paise Fifty Five Only
in wall/ceiling complete. Cat. III
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Point wiring for Two Way Controlled Light Point with 2-1.5 sq.mm & earth wire of 1.5 sq.mm (green) both are of .ISI
marked 1.1 KV grade FRLS PVC insulated multi strand copper wires erected in below type of pipe with 6A Modular
type switches and following type of accessories erected on PVC / Metallic/Wooden box, single mounting base frame
covered with textured / metallic/white front plate modules erected on / in wall / ceiling as per pipe erected. with Rupees Six hundred Three
necessary batten/angle holder or ceiling rose or H.D.Connector as directed. Paise Ninety Eight Only
(f) with medium class Rigid PVC pipe and accessories erected concealed in wall/ceiling complete. Cat. III
Providing following type of Modular Type Accessories mounted with PVC / metallic/Wooden box, single mounting
base frame covered with textured / metallic/white front plate , modules erected with necessary connections as per
site situation directed by Engineer In charge. Rupees One hundred Sixty
(3) Two Pin/RJ-11 Telephone Socket Paise Fifty Nine Only
[A] For One Gang
(7) Blank Plate Single. Cat.III Rupees Twenty Five Paise
Twenty Five Only
(8) Computer RJ-45 socket . Cat.III Rupees One hundred Sixty
Paise Fifty Nine Only
(4) TV Co-axial Socket outlet Rupees One hundred Sixty
Paise Fifty Nine Only
Providing and erecting ISI mark Medium class RIGID PVC PIPES of following size complete to be erected on/in wall or
ceiling erected with necessary PVC fittings & Junction boxes fixed with adhesive solution & Clamps with following dia Rupees Thirty Three Paise
327 1-3-2. 8000.00 of pipes, in approved manner as directed. Mtr. 33.33
Thirty Three Only
(c) 32 mm Rupees Fifty Four Paise Fifty
Providing & erecting PVC Corrugated Flexible Conduit with required nos. of coupling, PVC bushes, Check-nuts etc. Rupees Twenty One Paise
329 1-3-4. 500.00 complete of following sizes.(2) 25 mm Mtr. 21.21
Twenty One Only
Supplying and laying UPVC cable trunking system comprising unplasticised polyvinyl, chloride rigid material with
ignition free and flame proof confirming BS with necessary end caps Internal and external bend, flat bends, coupler, Rupees Four hundred
330 1-3-6 40.00 tee etc..All necessary accessories and measuring of following sizes. Mtr. 428.24 Twenty Eight Paise Twenty
(2) 100 mm x 50 mm trunking Four Only
Providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in
following type of pipe to be erected concealed in /flushed on wall/ceiling, with 1.5 sq. mm copper conductor FRLS
PVC insulated stranded wire of green colour for earth continuity of following size. Rupees Sixty Two Paise Sixty
(A) With medium class Rigid PVC pipe and accessories. Two Only
(a) 2 wire 1.5 sq. mm
(b) 2 wire 2.5 sq. mm Rupees Eighty Two Paise
Eighty Two Only
(f) 4 wire 2.5 sq. mm
Rupees One hundred Twenty
Six Paise Twenty Five Only
providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in
following type of pipe to be erected in / on wall / ceiling with 2.5 sq. mm copper conductor FRLS PVC insulated Rupees One hundred Twelve
stranded wire of green colour for earth continuity of following size Paise Eleven Only
(a) 2 wire 4 sq. mm
(g) 4 wire 4 sq. mm
Rupees One hundred Eighty
Paise Seventy Nine Only
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
(h) 4 wire 6 sq. mm Rupees Two hundred Sixty
Paise Fifty Eight Only
(i) 4 wire 10 sq. mm(use earth wire of 4 sq.mm ) Rupees Four hundred
337 1-4-2. 360.00 Mtr. 425.21 Twenty Five Paise Twenty
Providing and erecting Mains with ISI marked, 1.5KV grade electrolyte multi stranded, annealed copper conductor
with heat resistant PVC insulated conforms to IS 694, IEC - 227 erected in existing pipe of following size (Specifically Rupees One hundred Forty
for control panel, relays, power switchgears, motor starters & control wiring) with required size of copper lugs, nuts Two Paise Forty One Only
and bolts if required.(g) One wire 16.00 sq. mm
(h) One wire 25.00 sq. mm
Rupees Two hundred Thirty
Six Paise Thirty Four Only
Supplying and erecting Flexible PVC insulated multi strand multi core 1.1 kv grade ISI marked copper wires of
Rupees Thirty One Paise
340 1-4-5 200.00 following size to be erected as directed. Mtr. 31.31
Thirty One Only
(d) 1.50 Sq.mm 2 core round PVC sheathed
(e) 1.50 Sq.mm 3 core round PVC sheathed Rupees Forty Six Paise Forty
(h) 2.50 Sq.mm 3 core round PVC sheathed Rupees Seventy Seven Paise
Seventy Seven Only
(k) 4.00Sq.mm 4 core round PVC sheathed Rupees One hundred
343 1-4-5 200.00 Mtr. 176.75 Seventy Six Paise Seventy
Providing & Erecting approved make following size of TV Co-axial flexible cable comprising inner conductor of solid
Rupees Thirty Nine Paise
344 1-4-6 350.00 bare copper insulated with Foam PE & Secondary conductor made of poly - Aluminium film bonded Al. Braids @ Mtr. 39.39
Thirty Nine Only
suitable coverage overall sheathed with black PVC insulation.(b) RG-6
Supplying & erecting approved make Telephone Cable electrolytic copper conductor PE insulation twisted in two pairs,
& wrapped with FRLS PVC tape & sheathed with FRLS PVC or HFFR outer Jacket suitable for telephone wiring &
confirming to C-DOT erected in existing pipe. of following size of conductors & nos.of pairs. With necessary
connections. Rupees Twenty Paise
[A] Conductor Size 0.5 mm Twenty Only
(b) Armoured [Jelly Filled](2) Twenty Pairs
Rupees One hundred Ninety
Nine Paise Ninety Eight Only
Providing & erecting main Distribution (MDF) indoor type, back mounted frame as per DoT standard approved with Rupees One Thousand Three
347 1-4-9 5.00 krone strips(b) Suitable for 20 pair Ea. 1368.55 hundred Sixty Eight Paise
Fifty Five Only
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
SITC of Digital / PCM / TDM EPABX System having SMT design, system with flexible universal slots. Inbuilt Auto
attendant facility, Minimum 15 Nos. conference, Analog extension line, Calling GSM, E&M line, PRI / EI & VOIP
program me through Analog telephone digital key from Ethernet, public address cord, shall have unrestricted
simultaneous dialing facility,
QSIG protocol on PRI, 95 / STD / ISD / Local-Locking, Class of Service, Quick Dial-Single Digit dialing of any two external
number, Once only ring device, Chairman / Secretary - Do not disturb Facility, Power Down Mode, Hot Line, Hot Rupees One Lakh Seventy
348 7-1-2. 1.00 Outward Dialing, Day Night Mode, Auto Call Back, Barge-in, Call Pick Up & Call Transfer, Call transfer while Ringing Ea. 174606.78 Four thousand Six hundred
with Voice Guide System, (DISA), Caller ID (CLI), CLI Base ECF, CLI Base routing Internet Ready Port, External Music Six Paise Seventy Eight Only
Port, Call Budgeting, Call Most Calculation (ASMDR), DID Direct Inverse Dialing, External Music Input, Fax Homing,
Global Directory Printing with following capacities [[Approved by Competent Authority i.e. not Below the rank of
Executive Engineer ]
[E] No of Extension 128, No of Junctions 24, No of expandable ports : 512, Operators Console - 01 Compatible : ISDN
Supplying & erecting push button type telephone instrument having speaker phone Caller ID & hands free dialing
system & 30 memories with display system Single line [[Approved by Competent Authority i.e. not Below the rank of Rupees Five hundred Sixty
Executive Engineer ] Five Paise Sixty Only
Supplying & erecting approved make LAN cable of following size in existing pipe as per direction. Rupees Seventy Six Paise
[D] CAT - 6 e Seventy Six Only
Providing & erecting main Distribution (MDF) indoor type, back mounted frame as per DoT standard approved with Rupees Three Thousand
351 1-4-9 1.00 krone strips Ea. 3443.09 Four hundred Forty Three
(d) Suitable for 100 pair Paise Nine Only
Providing & Erecting 6 core fibre optic SM 9/125um double sheath, CSTA, Unitube, Outdoor cable (per m)
352 1-4-10 300.00 Mtr. 60.60 Rupees Sixty Paise Sixty Only
Providing & erecting Switch board for Computer or electric apparatus consisting of following modular type
accessories mounted with PVC / Metallic concealed/open box with single mounting base frame covered with
textured/metallic /white front plate,modules erected with necessary connections as directed Rupees One Thousand One
353 1-6-2 (B) 380.00 1 no. 6A/16A universal plug-switch combined. Ea. 1133.22 hundred Thirty Three Paise
3 nos. 6A Switch Twenty Two Only
3 nos. 6A 5 pin Plug
For Modular Type Accessories. Cat. III
Supplying & erecting Approved make call bell indicator with buzzing sound and Red light indicating lamp with Red light
Rupees One hundred Forty
354 1-6-9. 20.00 button to attend the call suitable for 240 v 50 c/s supply to be erected. Ea. 148.47
Eight Paise Forty Seven Only
providing and erecting Miniature circuit breaker single pole 6A to 25A suitable to operate on 240 V A.C. system and
Rupees One hundred Twelve
355 3-10-1.(B) 680.00 having breaking capacity 10 KA to be erected in existing box. confirming to IS 8828/1996 with ISI Mark Cat.III Ea. 112.11
Paise Eleven Only
Providing & erecting 240 V MCB double pole switch for motor & inductive load (C Curve) having 10 KA breaking
Rupees Two hundred Ninety
356 3-10-2. 10.00 capacity & confirms to IS : 8828 in existing box having following capacity Ea. 299.97
Nine Paise Ninety Seven Only
(A) 6 to 32 Amp. CAT.III
(B) 40 Amp. CAT.III
Rupees Three hundred Thirty
Paise Twenty Seven Only
Providing & erecting 415 V MCB Four Pole for Motor & Inductive Load (C Curve) having 10KA breaking capacity &
Rupees Five hundred Ninety
358 3-10-5. 17.00 confirms to IS :8828 in existing box having following capacity Ea. 595.90
Five Paise Ninety Only
(a) 6 to 32 Amp. Cat.III
(b)40 Amp. Cat.III Rupees Six hundred Sixty
Eight Paise Sixty Two Only
(c)63 Amp. CAT.III
Rupees Seven hundred Thirty
Seven Paise Thirty Only
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Providing and erecting Sheet Steel powder coated MCB distribution board - flush / surface mounted fitted with
busbar, neutral link, earth bar and DIN rail, Conforms to IS 8623-1 & 3, IEC 61439-1 & 3 without MCB to house
appropriate nos. of MCBs.(The DBs should be used of same company of MCB to be used) suitable for
Rupees One Thousand Four
(A) single phase incoming and horizontal single phase outgoing
361 3-11-5. 5.00 Ea. 1492.78 hundred Ninety Two Paise
(b) sheet steel double door
Seventy Eight Only
(B) three phase incoming and single phase horizontal type outgoing Per phase isolation type (PPI) Rupees Two Thousand Nine
362 3-11-5. 2.00 (b) sheet steel double door Ea. 2913.85 hundred Thirteen Paise
(ii)6 way Eighty Five Only
(iii)8 way Rupees Three Thousand
363 3-11-5. 12.00 Ea. 3412.79 Four hundred Twelve Paise
Seventy Nine Only
(iv)12 way Rupees Three Thousand
364 3-11-5. 12.00 Ea. 3874.36 Eight hundred Seventy Four
Paise Thirty Six Only
Providing and erecting Sheet Steel powder coated Vertical MCB distribution board (VTPN) - flush / surface mounted
double door (IP54) fitted with copper insulated busbar, isolated neutral bar, earth bar and DIN rail, Conforms to IS
Rupees Six Thousand Four
8623-1 & 3, IEC 61439-1 & 3, suitable for 63/100 AMP TPN MCCB + RCCB as incomer and three phase outgoing as
365 3-11-10 2.00 Ea. 6497.33 hundred Ninety Seven Paise
per following .(The DBs should be used of same company of MCB to be used)
Thirty Three Only
(B)6 way outgoing
providing and erecting Approved make RCCBs conforming to IS: 12640 and having sensitivity of 30 mA and Short
Circuit withstand capacity of 10 KA and suitable for operation on single phase 240 V,50Hz. having characteristic of Rupees Two Thousand Two
366 3-12-1. 83.00 quick action & tripping with all advance feature & do not incorporate any electronic component. for following Max. Ea. 2235.13 hundred Thirty Five Paise
rating erected as directed. Thirteen Only
(ii) 40Amps. DP Cat. III
Supplying and erecting LED indoor fittings with LEDs of wattage 0.2 Watt to 0.5 Watt assembled on single MCPCB,
with housing used as a heat sink shall be made of thick sheet Steel conforming to IS: 513/CRCA/ aluminium die cast
powder coated and high U.V. & corrosion resistance with diffuser with company mark/name 160V to 270V, Power
Factor more than 0.95, THD < 15%,
CCT 3000 K to 6500K,
Rupees One hundred Sixty
367 2-15-1 69.00 Luminaire efficacy> 85 lumens/watt ,LED Ea. 165.64
Five Paise Sixty Four Only
LED driver efficiency > 85 %
( fitting required LM-79 & LM-80 Certificates)(NOTE: Below description have shown ranges of Wattage capacity of LED
fittings.The Engineer incharge may select any wattage capacity between the ranges shown.)(A) Tube Light with
integral driver(i) 5-10 Watts, Surge-2 KV, IP-20, conventional 1 to 2 feet Cat-III
(iv) 22-24 Watts, Surge - 2KV,IP-20, conventional 4 feet Rupees Three hundred
368 2-15-1 10.00 Ea. 373.70 Seventy Three Paise Seventy
(v) 36-40 Watts, Surge-2 KV, IP-20, conventional 4 feet
Rupees Five hundred Thirty
Five Paise Thirty Only
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Supplying and erecting LED indoor fittings with LEDs of wattage 0.2 Watt to 0.5 Watt assembled on single MCPCB,
with housing used as a heat sink shall be made of thick sheet Steel conforming to IS: 513/CRCA/aluminium pressure
die cast powder coated and high U.V. & corrosion resistance with diffuser housed in aluminium casted body with
company mark/name
160V to 270V,Power Factor more than 0.95, THD < 15 %,
CCT 3000 K to 6500K,
Luminaire efficacy> 85 lumens/watt , Rupees Seven hundred Fifty
LED driver efficiency > 85 % Eight Paise Fifty One Only
( fitting required LM-79 & LM-80 Certificates)(NOTE: Below description have shown ranges of Wattage capacity of LED
fittings.The Engineer incharge may select any wattage capacity between the ranges shown.)
(A) Square/ Circular shaped Surface/Recessed Mount Downlight with provision for spring loaded mounting clips
(iv) 22-24 watts, Surge-2 KV Cat-III
(B) LED Panel Light with provision for Plane front frame with translucent cover fixed to housing complete.IP20
Rupees One Thousand
(vi) 36 watts, 24" x 24", Surge- 2KV
371 2-15-3. 318.00 Ea. 1794.77 Seven hundred Ninety Four
Paise Seventy Seven Only
Providing and erecting PVC body surface or pendent mounting LED Bulk type 9 watt Lighting Fitting with electronic
Rupees Seven hundred
driver. And lumen output from luminaire 720lm , input voltage range 90-300VAC , 50Hz cool white(3000 to 6500k),
372 2-17-3 57.00 Ea. 787.80 Eighty Seven Paise Eighty
inbuilt driver, -20degC to +60degC working temperature, AL frame with Beam Angle 120deg
Supplying and Erecting Of L.E.D. type High bay fixture having Power Consumption of following watts with, Input
Voltage 110 - 290 V.AC with full efficiency, Power Factor > 0.9 with 50/60 HZ, CCVC LED Driver used for maximum Rupees Five Thousand Two
373 2-17-4 35.00 power saving, Best Quality Aluminium alloy housing and aluminium Dome for better heat dissipation, CCT Cool white Ea. 5256.04 hundred Fifty Six Paise Four
(6000K), CRI 80, Beam angle > 120 degrees, working temperature -20 deg c to +55 deg c, Body IP 65(A) 70 to 90 watts Only
Providing & erecting Approved make Power Saving 50 Watt Ceiling Fan with double ball bearing ISI mark with Rupees One Thousand Nine
374 5-1-6. 350.00 Condenser 230 volt A.C. 50 Hz 1200 mm sweep complete having 3blades with aluminium blades with , canopy & 30 Ea. 1948.29 hundred Forty Eight Paise
cm. down rod erected with earthing.(Make shall be approved by Engineer in charge)) Twenty Nine Only
Supplying and erecting 19 / 20 mm. nominal bore Medium Class M.S. Pipe down rod erected duly painted for fan Rupees One hundred Eight
complete with proper insulation without leakage and earthing. Paise Seven Only
Supplying & erecting fan hook box of 10 mm M.S. round bar bounded to the RCC bars up to 50mm length each side
and pierced through a 16 Gauge M.S. box / Heavy Duty PVC box complete erected concealed in Ceiling with necessary Rupees One hundred Eight
finishing. Paise Seven Only
Providing 2.5mm.thick laminated acrylic sheet to cover the fan hook or Fan box. Rupees Eighteen Paise
Supplying & erecting approved make low noise decorative exhaust fan having square frame ABS body with inbuilt Rupees One Thousand
378 5-3-3. 45.00 lowers & square frame. 200mm with 1350RPM Cat.II Cat.II Ea. 1703.87 Seven hundred Three Paise
Eighty Seven Only
Supplying & erecting single phase approved make industrial exhaust fan suitable for medium duty ring mounted low
noise operation suitable for medium duty having following dia size and maximum speed in RPM Rupees Two Thousand Fifty
Four Paise Thirty Four Only
Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Aluminium conductor for 1.1 KV. to be laid
Rupees Two hundred Twenty
380 4-3-3. 645.00 on wall with necessary clamps or in existing trench / pipe of following size of cables. Mtr. 220.18
Paise Eighteen Only
(B) 3 1/2 core 35 Sq. mm ( 16 Sq. mm 1/2 core)
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
(C) 3 1/2 core 50 Sq. mm ( 25 Sq.1/2 mm core)
Rupees Two hundred Eighty
Four Paise Eighty Two Only
(F) 3 1/2 core 120 Sq. mm ( 70 Sq. mm 1/2 core)
Rupees Five hundred Forty
Paise Thirty Five Only
(G) 3 1/2 core 150 Sq. mm ( 70 Sq. mm 1/2 core)
Rupees Seven hundred Thirty
One Paise Twenty Four Only
(I) 3 1/2 core 240 Sq. mm( 120 Sq. mm 1/2 core) Rupees Nine hundred Four
Paise Ninety Six Only
Providing and erecting XLPE (IS:7098)(I)-88 ISI armoured cable multistrand / Solid Aluminium conductor for 1.1 KV. to
be laid on wall with necessary clamps or in existing trench / pipe of following size of cables. Rupees One hundred Forty
Paise Thirty Nine Only
Providing and erecting XLPE (IS:7098)(I)-88 ISI armoured cable multistrand Aluminium conductor for 1.1 KV. to be laid
Rupees One hundred Fifty
386 4-3-5. 1500.00 on wall with necessary clamps or in existing trench / pipe of following size of cables. Mtr. 153.52
Three Paise Fifty Two Only
(A) 4 core 16 Sq. mm
(B) 4 core 25 Sq. mm
Rupees One hundred Ninety
Paise Eighty Nine Only
Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Copper conductor for 1.1 KV. to be laid
on wall with necessary clamps or in existing trench / pipe at road crossing or floor of following size of cables. Rupees Nine hundred Eighty
388 4-4-5. 100.00 (B) 4 core 16 Sq. mm Mtr. 987.78 Seven Paise Seventy Eight
(B) 4 core 25 Sq. mm Rupees One Thousand Five
389 4-4-5. 200.00 Mtr. 1504.90 hundred Four Paise Ninety
Making trench in soft soil of suitable width of 90 cm deep for laying cable or locating the fault all over the run and Rupees Fifty Five Paise Fifty
back filling the same and making the surface as normal ground. Five Only
Making trench in Hard Murrum / Tar Road of suitable width of 90 cm or required depth for laying any size of cable or
Rupees Seventy Four Paise
391 4-5-2. 50.00 locating the fault all over the run and back filling the same and making the surface as normal ground. Mtr. 74.74
Seventy Four Only
(B) If additional machinery like hammer driller or JCB use [Add]
Rupees Three hundred Fifty
Seven Paise Fifty Four Only
Providing and erecting iron clad cable route marker duly marked with ELE.CABLE of size 23 cm.X 12 cm. Flushed with
Rupees Two hundred Forty
393 4-5-5. 50.00 ground in cement foundation as directed by Engineer in charge. Ea. 240.38
Paise Thirty Eight Only
Covering of cable with second class bricks or cement tiles laid cover the cable crosswise & also on both sides with
Rupees One hundred Forty
394 4-5-3. 150.00 covering of 7. 5 Cm. layer of sand above & below cable (16 bricks per meter) Mtr. 140.39
Paise Thirty Nine Only
Providing & laying approved make Double walled corrugated pipes (DWC) of polyethylene(conforming to IS 14930 II
Rupees Ninety Five Paise
395 4-5-8. 150.00 )with necessary connecting accessories of same material at required depth in existing trench for laying of cable. Mtr. 95.95
Ninety Five Only
below ground / road surface for enclosing cable (C))90 mm outer dia
(D)120 mm outer dia.
Rupees One hundred Thirty
Seven Paise Thirty Six Only
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Providing and, fixing heavy duty flange type brass cable gland with rubber ring for PVC insulated armoured cable
Rupees Thirty Three Paise
397 4-6-1. 20.00 complete with out going tails, insulating tape etc for following size of cables. Ea. 33.33
Thirty Three Only
(A) 2 to 4 core 2.5 / 4 Sq. mm
(B) 2 to 4 core 6 Sq. mm Rupees Thirty Eight Paise
Thirty Eight Only
(C) 2 to 4 core 10 Sq. mm Rupees Thirty Eight Paise
Thirty Eight Only
(D) 2 to 4 core 16 Sq. mm Rupees Forty Seven Paise
Forty Seven Only
(E) 2 to 4 core 25 Sq. mm Rupees Fifty One Paise Fifty
Providing and, fixing heavy duty flange type brass double compression type cable gland with rubber ring for PVC
insulated armoured cable complete with out going tails, insulating tape etc for following size of cables. Rupees Seventy Five Paise
(B) 3 & 1/2 core 35/50 Sq. mm Seventy Five Only
(E) 3 & 1/2 core 120 Sq. mm
Rupees One hundred Forty
Paise Thirty Nine Only
(F) 3 & 1/2 core 150 Sq. mm
Rupees One hundred Ninety
Paise Eighty Nine Only
(H) 3 & 1/2 core 240 Sq. mm
Rupees Two hundred Forty
Seven Paise Forty Five Only
Solder less crimping type Aluminium lugs conforming to IS suitable for cable of following size evenly crimped with high
pressure tool & connected to switchgear terminals with brass/cadmium plated nut bolts in an approved manner.
406 4-7-1. 140.00 Ea. 6.06 Rupees Six Paise Six Only
(B) 10 Sq.mm Rupees Thirteen Paise
(C) 16/25 Sq.mm. Rupees Fifteen Paise Fifteen
(D) 35/50 Sq.mm. Rupees Twenty Paise
(E) 70 Sq.mm. Rupees Twenty Five Paise
Twenty Five Only
(G) 120 Sq.mm. Rupees Forty Five Paise
Forty Five Only
(H) 150 Sq.mm. Rupees Sixty One Paise Sixty
(J) 240 Sq.mm. Rupees Eighty Five Paise
Eighty Five Only
Solder less crimping type Copper lugs conforming to IS suitable for cable of following size evenly crimped with high
pressure tool & connected to switchgear terminals with brass/cadmium plated nut bolts in an approved manner.
414 4-7-2. 100.00 (A) 1.5/2.5 to 6 Sq.mm Ea. 8.08 Rupees Eight Paise Eight Only
415 4-7-2. 50.00 (B) 10 Sq.mm Ea. 10.10 Rupees Ten Paise Ten Only
(C) 16 Sq.mm. Rupees Twelve Paise Twelve
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
(D) 25 Sq.mm. Rupees Fifteen Paise Fifteen
Providing and fixing approved make Perforated C type cable tray. Made from pre- galvanized sheet steel. The cable
tray should be bended as per IS 2062/1079 . with max 17.5% perforation with coupler plate / Fish plate and GI Rupees Three hundred
418 4-11-5. 400.00 hardware like nut - bolt and washers etc. erected on existing support as per Specification and as per instruction of Mtr. 322.19 Twenty Two Paise Nineteen
engineer in charge.. Only
(3) 150 X 50 X 1.5 mm Thick
(5) 300 X 50 X 1.5 mm Thick Rupees Four hundred
419 4-11-5. 300.00 Mtr. 471.67 Seventy One Paise Sixty
(7) 600 X 50 X 1.5 mm Thick
Rupees Seven hundred Sixty
Seven Paise Sixty Only
Providing and fixing approved make 'T' Junction for Perforated C type cable tray. Made from pre galvanized sheet
steel. The Junction should be bended as per IS 2062/1079. with max 17.5% perforation with coupler plate / Fish plate
and GI hardware like nut - bolt and washers etc. erected on existing support as per Specification and as per Rupees One hundred Sixty
421 4-11-.6 30.00 instruction of engineer in charge.. Ea. 167.66
Seven Paise Sixty Six Only
A. 'T' Junction
(3) 150 X 50 X 1.6 mm Thick ' T' Junction
(5) 300 X 50 X 2.0 mm Thick ' T' Junction
Rupees Two hundred Forty
Nine Paise Forty Seven Only
(7) 600 X 50 X 2.0 mm Thick ' T' Junction
Rupees Six hundred Eighty
Five Paise Seventy Nine Only
Providing and fixing approved make '90° Elbow' for Perforated C type cable tray. Made from pre galvanized sheet
steel. The Junction should be bended as per IS 2062/1079. with coupler plate / Fish plate and GI hardware like nut -
bolt and washers etc. erected on existing support as per Specification and as per instruction of engineer in charge.. Rupees One hundred Forty
Six Paise Forty Five Only
(3) 150 X 50 X 1.6 mm Thick 90° Elbow
(5) 300 X 50 X 2.0 mm Thick 90° Elbow Rupees Two hundred
425 4-11-7. 40.00 Ea. 219.17 Nineteen Paise Seventeen
(7) 600 X 50 X 2.0 mm Thick 90° Elbow
Rupees Six hundred
Seventeen Paise Eleven Only
Providing and erecting Approved make Four pole moulded case circuit breaker having breaking capacity ICU of 25 KA.
at 415 V,having normal current rating up to 25 A to 100A. with Fixed thermal & magnetic release suitable to work on Rupees Six Thousand One
427 3-4-1. 42.00 A.C. supply 50 c/s. with all internal connections, spreader tinned copper & complete erected in existing 16 G.M.S. Ea. 6173.12 hundred Seventy Three Paise
housing. Twelve Only
ICS=100% of ICU only Cat III
Providing and erecting Approved make Four pole moulded case circuit breaker having breaking capacity ICU of 35 KA.
at 415 V. having normal current rating 125A. with Fixed thermal & magnetic release suitable to work on A.C.supply
c/s. with all internal connections, spreader tinned copper & complete erected in existing 16 G.M.S. housing. Rupees Eight Thousand Fifty
ICS=100% of ICU only Cat III Five Paise Seventy Six Only
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Providing and erecting Approved make Four pole moulded case circuit breaker having breaking capacity ICU of 35 KA.
at 415 V. having Normal current rating 200A.with variable Thermal & magnetic release suitable to work on A.C.supply Rupees Sixteen Thousand
429 3-4-3. 15.00 50 c/s. with all internal connections, spreader tinned copper & complete erected in existing 16 G.M.S.housing Ea. 16221.61 Two hundred Twenty One
ICS=100% of ICU only Cat III Paise Sixty One Only
Providing and erecting Approved make Four pole moulded case circuit breaker having breaking capacity ICU of 35 KA.
and above at 415 V . having normal current rating 250A. with variable thermal & magnetic release suitable to work Rupees Twenty Thousand
430 3-4-4. 2.00 on A.C.supply 50 c/s. with all internal connections, spreader tinned copper & complete erected in existing 16 G.M.S. Ea. 20946.39 Nine hundred Forty Six Paise
housing. ICS=100% of ICU only Cat III Thirty Nine Only
Providing and erecting Approved make Four pole moulded case circuit breaker having breaking capacity ICU of 50 KA Rupees Twenty Five
and above at 415 V having Normal current rating 400A. with variable Thermal & magnetic release suitable to work on Thousand Two hundred
431 3-4-5. 4.00 A.C.supply 50 c/s. With all internal connections, spreader tinned copper & complete erected in existing 16 G.M.S. Ea. 25228.79
Twenty Eight Paise Seventy
housing. ICS=100% of ICU only Cat III Nine Only
Providing and erecting Approved make Four pole moulded case circuit breaker having breaking capacity ICU of 50 K.A.
and above at 415 V having normal current rating 800A.with variable thermal & magnetic release suitable to work on Rupees Thirty Thousand
432 3-4-7. 3.00 A.C.supply 50 c/s. with all internal connections, spreader tinned copper & complete erected in existing 16 Ea. 30733.29 Seven hundred Thirty Three
G.M.S.housing. Paise Twenty Nine Only
ICS=100% of ICU only Cat III
Providing and erecting following additional parts for panel mounting MCCBs Rupees Eight hundred
433 3-4-14 10.00 (A)Extended operating rotary handle with pad lock with three position trip,off,on suitable for 25A to 250 A panel Ea. 873.65 Seventy Three Paise Sixty
mounting cat-III Five Only
(B)Extended operating rotary handle with pad lock with three position trip,off,on suitable for 400A to 630 A panel Rupees One Thousand Three
434 3-4-14 10.00 mounting cat-III Ea. 1310.98 hundred Ten Paise Ninety
Approved make standard Draw out type 4 Pole Air circuit breaker. Having 50 kA breaking capacity with ICU=ICS=ICW
(1 sec)Vsr=690 v, Ui=1kv ,impulse voltage=12 kv with following type of relay and accessories.
(1) Manual Draw out type (MDO) with following type of relay system Rupees One Lakh Thirty
(A) Equipped with DN-1 magneto thermal release, CTs & 6NO + 6NC auxiliary contacts & secondary isolating contacts thousand Seven hundred
of following current ratings. Eighty Six Paise Ninety Two
(iii) 1250Amp 50 kA Cat III Only
Providing & erecting additional parts for Air Circuit Breakers as follows: (B) Auxiliary Contact Block for CN-CS 800 to Rupees Two Thousand
436 3-5-6. 4.00 2500 & 6 NO + 6 NC Ea. 2783.56 Seven hundred Eighty Three
Paise Fifty Six Only
(G) Shunt Release Type EA:24/48 V, 110V, 220V DC
Rupees Two Thousand Fifty
Five Paise Thirty Five Only
(I) Under Voltage Release Type MV(2) : 240V AC, 415 V AC
Rupees Two Thousand Eight
438 3-5-6. 4.00 Ea. 2893.65 hundred Ninety Three Paise
Sixty Five Only
(M) CTs for 800 C / 1000 C with 400A / 640A and 800A taps for Fixed & Drawout Type ACBs Rupees Two Thousand
439 3-5-6. 4.00 Ea. 2782.55 Seven hundred Eighty Two
Paise Fifty Five Only
(N) CTs for 1250 C / 1600 C for Fixed & Drawout Type ACBs Rupees Two Thousand Nine
440 3-5-6. 4.00 Ea. 2953.24 hundred Fifty Three Paise
Twenty Four Only
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Supplying and erecting triple pole & neutral 440V/ 500V panel mounting Aluminium Busbars with four equal Nos. of
bus having current density not more than 0.8 Amp. / sq.mm (Rated current / cross section area) duly wrapped with
colour insulating tape for phase sequence of following current carrying capacity, erected with necessary bus bar Rupees One Thousand Thirty
441 3-8-1. 20.00 supports /insulators, main cable socket to each busbar,erected in existing cubical panel with necessary connections. Mtr. 1037.27 Seven Paise Twenty Seven
(B) Suitable for 200 Amp. Capacity Only
(C) Suitable for 300 Amp. Capacity Rupees One Thousand Four
442 3-8-1. 10.00 Mtr. 1469.55 hundred Sixty Nine Paise
Fifty Five Only
(F) Suitable for 800 Amp. capacity Rupees Six Thousand Two
443 3-8-1. 10.00 Mtr. 6240.79 hundred Forty Paise Seventy
(G) Suitable for 1200 Amp.capacity Rupees Seven Thousand
444 3-8-1. 15.00 Mtr. 7957.79 Nine hundred Fifty Seven
Paise Seventy Nine Only
Providing & erecting weather proof, dust & vermin proof, floor mounted front operated indoor type cubical panel
board necessary IP-42 and above protection as per approval from engineer incharge made from 14 SWG thick CRC
M.S. sheet for outer body & doors, 16 SWG thick CRC M.S.sheet for internal partitions with necessary accesories
supporting angles/ flats channel including cutting, bending, drilling, welding, riveting with internal partitions & cable
alley as per requirements & instruction of engineer-in-charge with erection of supplied switch gears, BUSBARS,
suitable size of inter connecting PVC copper wire / copper-aluminium strips, rubber grommets, rib, bakelite control
fuses/MCB for measuring instruments, earth bus & earth bolts, foundation flange - bolts-base Plates, sufficient nos. Rupees Fourteen Thousand
445 3-16-1 30.00 of hinged doors, handles with locking arrangement and rubber gasket,heavy duty end terminal connection,danger Sq.Mtr 14902.55 Nine hundred Two Paise Fifty
notice board,necessary ventilation,earthing strip complete. The Panel shall be painted with epoxy powder coating. Five Only
(The rates excludes the cost of switchgears, bus bars, inter connecting mains & Copper Aluminium strips, meters,
Fuses etc. The dimension shall be measured excluding base beams) The panel shall be supplied with following
approved manufacturers with following size. (B) The standard companies switch gear shall be used and only
manufacturers at CPRI approved factory .
(i) with 350mm depth
(ii) With 550 mm. Depth
Rupees Nineteen Thousand
446 3-16-1 10.00 Sq.Mtr 19387.96 Three hundred Eighty Seven
Paise Ninety Six Only
(iv) with 1000 mm. depth Rupees Forty Thousand Nine
447 3-16-1 13.00 Sq.Mtr 40999.94 hundred Ninety Nine Paise
Ninety Four Only
Providing , erecting , fabricating the M.S. structure as per requirement on site incorporating proper size of M.S.
angles,square,round, flats, bars, channels, sections complete with cutting, welding, grinding & finishing duly painted Rupees Seventy Seven Paise
448 3-16-4-A 450.00 with one coat of red oxide with erection on site as per direction of engineer in charge with necessary grouting, Kg. 77.77
Seventy Seven Only
cementing, plastering & finishing complete.
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Providing and erecting multifunctional meter suitable for application of Power monitoring and showing measurement
of following Voltage, Frequency, Apparent energy, Apparent power, Active and reactive energy, Active and reactive
power, Average voltage Vavg, Peak demand power PM, QM, SM, Demand power P, Q, S, Apparent power S, S1, S2, S3,
Unbalance current, Power factor and displacement PF (signed, four quadrant), Calculated neutral current, Active,
reactive, apparent energy (signed, four quadrant), Active power P, P1, P2, P3, Voltage U21, U32, U13, V1, V2, V3, Rupees Fourteen Thousand
449 3-17-5. 11.00 Phase currents, Average current Iag, Peak demand currents, Reactive power Q, Q1, Q2, Q3, Demand current I1, I2, I3, Ea. 14123.84 One hundred Twenty Three
[Us] rated supply voltage 40...300 V AC 45...65 Hz, 40...300 V DC, Network frequency 50 Hz, Type of network 3P, Paise Eighty Four Only
Display type 7 segments LED, Display colour Red, Messages display capacity 3 fields of 4 characters, Display digits
digit(s) - 14.2 mm in height
Providing & erecting L.T. Current Transformer with bar primary 50/5 to 1000/5 ratio 15 VA burden erected in existing Rupees Two hundred
450 9-2-7. 10.00 CRCA box duly secured with insulating materials connected to the meter Ea. 274.72 Seventy Four Paise Seventy
Supplying and erecting approved make suitable panel indicator LED type lamp, lens cover, complete erected with Rupees Forty Three Paise
necessary connections. Forty Three Only
Supplying & erecting directly operated single phasing preventer complete erected and connected to supply up to 45 Rupees One Thousand
452 9-2-10. 10.00 Amp. Range. Ea. 1078.68 Seventy Eight Paise Sixty
Design, Supplying, installing, testing of factory fabricated ready made Three phase APFC Panel Cubical Panel
fabrication should be type tested as per IEC 61921, 61439:1&2 Capacitor Duty Contactor for switching as per following
Steps Incomer Switch of MCCB type Icu=Ics=50KA at 400/440 Volts, with OC, SC, internal earth fault protection
Incomer Switch of MCCB type Icu=Ics=50KA at 400/440 Volts, with OC, SC, internal earth fault protection,Copper
tinned insulated Busbar,Cubical panel should be indoor type with IP 43 and IK 10,Metalized polypropylene film tye3- Rupees Four Lakh Thirty
phase 550Volt Capacitor,De tuning Reactor for each capacitor,Panel having Short Circuit and Overload Three thousand One
protection,Each step Capacitor having suitable MCB with Sc, OL, internal earth fault relay,Each stage having Stage hundred Three Paise Fifteen
Contactor (Capacitor load rating),PF regulator master controller having suitable steps with LCD display, Rs 485 Only
Communication port, Indication LED Lamps for main incomer and ON-OFF for each capacitor bank,MS Chanel for Floor
mounting, Cable entry as per site situation,Cooling fans for panel. (E)150KVAR
Providing and fixing printed instruction chart both in English and Gujarati and duly framed with front glasses, for
Rupees One hundred Thirty
454 10-2-1. 8.00 treatment of person suffering from Electric shock with minimum 50" diagonally size. Ea. 130.29
Paise Twenty Nine Only
Providing pair of rubber hand gloves suitable for working on 11 KV/22 KV supply.
Rupees Two hundred
Fourteen Paise Twelve Only
Supplying rubber matting of following thickness as per IS:15652/IEC 61111 Rupees One Thousand
456 10-2-3 10.00 (b)4mm Sq.Mtr 1027.17 Twenty Seven Paise
(c)12mm Rupees Three Thousand
457 10.00 Sq.Mtr 3081.51 Eighty One Paise Fifty One
Supplying FIRE bucket round bottom of 9 litres capacity made out of 24 gauge G.I. sheet with extra handle at bottom
Rupees Two hundred
458 10-2-5 8.00 duly painted white inside and Red out side with FIRE mark, filled with dry-sand and kept on existing stand provided Ea. 214.12
Fourteen Paise Twelve Only
or hung on wall hook.
Supplying and erecting floor mounting stand for keeping four nos. of FIRE buckets comprising 1500 mm in length,
mm height frame made out of 30mm X30 mm X 4 mm angle iron with cross supports for legs, welded with 4 hooks Rupees Nine hundred Forty
459 10-2-6 2.00 and duly painted with one coat of red lead and two coats of approved enamelled silver paint. Ea. 942.33
Two Paise Thirty Three Only
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Providing and erecting Approved make panel mounting front fixing rotary switch (CAM Switch) with face plate with
double pair of contacts with two fix and a moving contacts, operated by means of slide, rest on disk with grooves for
sequential operation rotated by switch handle, square shaft and knob for Two way with off Rupees Three hundred
460 3-3-1. 15.00 (i)Two pole Ea. 390.87 Ninety Paise Eighty Seven
(a) 16/25A - 240 V Only
Rupees Five hundred Seventy
Four Paise Sixty Nine Only
Providing and erecting metallic vitrified danger notice board as per language suggested by engineer incharge for Rupees Sixty Nine Paise
462 3-13-1. 15.00 MEDIUM VOLTAGE installation to be erected as per IS-2551. Ea. 69.69
Sixty Nine Only
Supplying & erecting in earthpit of minimum bore dia. 225mm size approved make Safe Earthing Electrode consisting
Pipe-in-Pipe Technology as per IS 3043-1987 made of corrosion free hot dipped G.I.Pipes having Outer pipe dia of
mm having 80-200 Micron galvanising, Inner pipe dia of 40 mm having 200-250 Micron galvanising, connection
terminal dia of 14 mm with constant ohmic value surrounded by highly conductive compound with high charge
dissipation suitable for following type of applications with chamber and heavy duty cover (A)(approved make OEM
has to submit test certificate including value of earth resistance of installation duly stamped and signed by agency and
officer Incharge has to ensure the value of earthing resistane mentioned in test Certificate) & having back filling Rupees Seven Thousand
463 3-14-10 30.00 compound of (B) Inner chemical (CCM Compound)- Resistivity:- 0.2 ohm / meter testing as per IEC 62561-2017, Ea. 7095.25 Ninety Five Paise Twenty
Voltage drop:- < 1 volt at no load & dry form, Sulphar content:- <2%(C) Back fill Compound :- Earthing compound Five Only
should be capable to retain moisture for long time Necessary test report must be submitted by Agency.[B] For
Electrical installation up to 11 KV located in other than normal soil i.e. Soft Rock, Marshy Soil etc.
-Length of Pipe : 2 mtr
-Back filling Compound :1 no. Bag of 25 Kg.
[C] For Electrical Installation covering Transformer Neutrals, Lightning arrester Earthing, A.C.Plant & Sensitive
Computer System(like Automation, SCADA)i.e. independent Earthing located in other than normal soil i.e. Rupees Ten Thousand Five
464 3-14-10 10.00 Soft Rock, Marshy Soil etc.. Ea. 10593.89 hundred Ninety Three Paise
-Length of Pipe : 3 Mtrs. Eighty Nine Only
-Back filling Compound :2 nos Bags of 25 Kg.
Providing and erecting required size HOT deep Galvanised iron strip for earthing of H.T. , OCB/ ACB/ Transformer LT Rupees Seventy Seven Paise
panel board, Motors etc. using proper clamp. Seventy Seven Only
Providing and erecting required size Copper strip for earthing of H.T. OCB / ACB/ Transformer, LT panel board, Motors Rupees Seven hundred
466 3-14-3 20.00 etc. using copper clamp. Kg. 794.87 Ninety Four Paise Eighty
Providing and erecting Annealed bare Copper wire 8 to 16 SWG. Rupees Seven hundred
467 3-14-4 50.00 Kg. 794.87 Ninety Four Paise Eighty
Providing and erecting HOT deep Galvanised iron strip wire 8 to 16 SWG. Rupees Seventy Seven Paise
Seventy Seven Only
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Providing, erecting, testing & commissioning approved make oil immersed ONAN cooled, double wound, core type
indoor / outdoor copper wound 11KV/ 433V step down transformer of following capacities operating on 3 phase,
Hz 4 wire & neutral earthed system continuously rated for a full temperature rise in oil not exceeding 45 Deg.C.at
maximum ambient temp. of 50 Deg. C. complete with necessary radiator first filling of new transformer oil & standard
fitting as below complying with IS 1180( Part 1 ):2014 standards with energy efficiency level 1 Off load tap changing
range steps +2.5% to -5% on H.V for variation should be provided. The H.V. shall be connected Delta & Secondary
with star connection. The transformer should have cable-end boxes on H.T. side suitable for up to 3 core 150 sq.mm.
XLPE cable & on L.T. side suitable for bus duct or cables as per requirement complete with test certificates from Rupees Eleven Lakh Forty
manufacturers 1. Oil conservator with filling Hole & Cap - One No.2. Thermometer pocket with 6" dial type Two thousand Four hundred
thermometer switch alarm & trip contacts- Two nos.3. Silica-gel breather with charge- One No.4. Plain oil Fifty Eight Paise Forty Seven
level gauge - One No.5. Drain / Sampling / Filter valve- One No.6. Top Filter Valve - One No.6. Top Filter Valve - Only
One No.7. Explosion vent with Diaphragm - One No.8. Rating & Diagram plate - One No.9. Additional neutral
bushing for earthing - One No.10. Bi directional Roller - Four Nos.11. Earthing terminals - Two Nos.12. Lifting lugs -
Two Nos.13. Air release plug. - One No.14. Double float buchholz relay with Alarm and trip contacts.15. Control
cable as required from Transformer to VCB Panel is to be provided with necessary connection to VCB relays for
protection. as per IS 1180 level-1(c) 500 KVA Max. allowable loses at 50 % of rated load is 1.510 KW and at full load is
Providing, and erecting 11 KV D.P. 9 mtr. high Structure made of 6" x 3" ‘I’‐Section Girder, 4" x 2"channels, clamps,
nuts, bolts etc. Suitable for erection of the followings duly connected with necessary ACSR conductors. as per drawing
approved by the Engineer- in charge complete with following. Height as per IS 7 Mtr above ground )(A) 11 KV
Rupees Ninety Eight
Amps Drop out fuses with S.R.B.P. tubes carries.-Three nos (B) 11 KV G.O.D. switch complete with insulators,
Thousand Four hundred
470 10-2-10. 1.00 operating handle with galvanised pipe, Sq.bar etc. 400 Amp.- One Set (B) 11 KV G.O.D. switch complete with Ea. 98433.59
Thirty Three Paise Fifty Nine
insulators, operating handle with galvanised pipe, Sq.bar etc. 400 Amp.- One Set (C) 11 KV lightening arrestor with
clamp- Three Nos.(D) 11 KV shackle insulators- Six Nos. (E) The above D.P. structure should be earthed with
mm.X 3 mm thick double copper earth strips run separately and connected with separate copper plate earth electrode.
Providing and erecting ISI Marked 3core 120 Sq.mm XLPE insulated 11 KV armoured cable Aluminium conductor IS- Rupees One Thousand Five
471 10-2-14 100.00 7098 to be laid on wall with clamps or in provided cable trench / pipe approved manner as directed. Mtr. 1542.27 hundred Forty Two Paise
Twenty Seven Only
Providing and erecting cable end termination kit, heat shrinkable Push on type Densons/ Raychem/ Elastimold make
Rupees Fourteen Thousand
suitable for 11 KV XLPE cable 3core 95 & 120 Sq.mm
472 10-2-19 2.00 Ea. 14611.67 Six hundred Eleven Paise
(A) Outdoor type
Sixty Seven Only
(B) Indoor type
Rupees Eight Thousand Four
Paise Twenty Five Only
Supplying and erecting approved make online Un-interruptible Power Supply system comprising flat cum-boost
charger with IGBT base rectifier & Inverter & sealed maintenance free SMF batteries. The charger having operating
Rupees Seventeen Lakh Sixty
capacity for input 160-270V AC & inverter having output 230V,50 Hz Ac with 0.8 load power factor with battery,
thousand Eight hundred
474 8-15-5. 1.00 over/under voltage output with over load & short circuit protection equipment. The system housed in CRC sheet duly Ea. 1760821.88
Twenty One Paise Eighty
powder coated paint with following power backup.with MS painted batteries stand, 10% Overload capacity for
momentary load. [M]60 KVA 3 - phase with 1Hr Backup
Supplying and erecting horizontal / vertical mounting type storage water heater with copper container housed in
M.S./S.S./ABS body insulated with glass wool/puff complete with heating elements,adjustable thermostats 300C to Rupees Seven Thousand
475 8-16-2. 6.00 850C, indicating lamp, safety valve, fusible plug, etc.complete erected with coach bolts, nuts. washers & cementation Ea. 7808.31 Eight hundred Eight Paise
(B)15 Ltr-.with 2 /3K.W. heating element Cat.III Thirty One Only
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Providing & erecting water cooler having storage capacity 150 Ltr. & cooling capacity 150 Ltr.per hour @ an ambient
temp of 45˚ C. The outlet temp. of the water should drop by 15˚C within a hour, The water cooler should be Rupees Fifty Five Thousand
476 8-13-3. 6.00 comprising of hermetically sealed compressor, fan motor, condensing unit, water tank surrounded by evaporating, Ea. 55893.40 Eight hundred Ninety Three
coil, thermostats, relay etc.complete with necessary inlet & outlet connection. The body of water cooler will be made Paise Forty Only
from Stainless Steel.
[G] 1000 LPH with 3 phase Raw water pump of 1700LPH @ 3.0 kg/cm2 (1No - Kirloskar/CRI/Lubi), Dual media filter
13"x54" - 1 No, Micron catridge filter 20" x 4.0" - (1No), High pressure pump 1000LPH @ 11kg/cm2 - (1No - Rupees Two Lakh Seventeen
Kirloskar/CRI/Lubi), RO Membrane housing with RO membrane of 40*40 -(4 Nos), RO pressure tube 4" x 2E-(2Nos), 0 - thousand Two hundred
2400LPH Rotameter ( 2 Nos). Dosing pump 0 -6 LPH (1 No) with 100 Ltr Dosing tank - (1 No.), Recovery Rate 50%. Thirty Six Paise Eighty Six
Supplying & erecting approved make motor control cubical panel (Direct - on - line) made from 16 G. CRCA sheet
duly epoxy powder painted inside and outside with hinged doors and locking, arrangement consisting of suitable size
of ON- OFF isolator (AC - 3/23duty) main fuses, single phasing preventer, indicating lamps for R- Y - B phases, overload
Rupees Seven Thousand
relay, Automatic water level controller, Ammeter, Voltmeter each with two way selector switch incoming, wires duly
478 9-5-2 2.00 Ea. 7722.46 Seven hundred Twenty Two
socket crimped, main contactor & overload relay, start - stop push buttons, to be erected on angle iron frame grouted
Paise Forty Six Only
on wall as directed. The isolator, overload relay & contactors will be of L & T, Siemens or BCH make only. (A) DOL up
Providing & erecting open well horizontal mono block pump set with cast iron body, complete for three phase Rupees Fifteen Thousand
479 9-4-2. 2.00 submersible motor having[C] For 3 HP 3 phase open well horizontal mono block pump set suitable for 85 LPM to 270 Ea. 15707.52 Seven hundred Seven Paise
LPM @ 11 mtr to 33 mtr head suitable for 50/65 mm dia delivery pipe Cat.II Fifty Two Only
Providing and erecting ISI marked PVC insulated PVC Sheathed Flat flexible Submersible copper cable approved make
Rupees One hundred Forty
480 9-7-1. 120.00 of following Size. (C) 3 Core x 4 Sq. mm Mtr. 146.45
Six Paise Forty Five Only
Supply of Fibreglass Platform Step (A Type) Ladder - 8 FT having following specifications :
It should have large fully serrated Rupees Twenty Three
platform 15” wide 20” deep which locks ladder, Aluminium feet with thick rubber tread, top rail guard to serve as a Thousand Seven hundred
481 1-7-9 1.00 railing, two pairs of gusset support at the bottom step and All gussets are heavy duty steel. Capacity : 300 lbs. Step Ea. 23726.92
Twenty Six Paise Ninety Two
Width : 3’ Approx. spread : 62” Width : 29.5” Approx. Wt. : 22 Kg Approx. Cube : 11.62 Only
Supply of Fibreglass Platform Step (A Type) Ladder - 15 FT having following specifications :
It should have large fully serrated Rupees Thirty One Thousand
482 1-7-11. 1.00 platform 15” wide 20” deep which locks ladder , Aluminium feet with thick rubber tread, top rail guard to serve as a Ea. 31636.23 Six hundred Thirty Six Paise
railing, two pairs of gusset support at the bottom step and All gussets are heavy duty steel. Capacity : 300 lbs Twenty Three Only
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Supplying and erecting, commissioning and testing of Diesel Generating set confirming to IS: 4722:1968 & BS:5514
having continuous rating, 3 phase, 415 volts, 50 cycles A.C. supply comprising of a totally enclosed air/water cooled
diesel engine with multi-cylinders developing suitable BHP not less than following capacity at 1500 RPM with 10%
overload for one hour in 24 hours with standard accessories like fly wheel, lubricating oil cooler, "A" class governor,
heavy duty fuel wheel and lubricating oil filter, oil bath air filler, lubricating oil pressure gauge, end exhaust manifold,
standard set of tools with adjustable spanners, screw drivers, cylinder head to cover, joint cylinder head to exhaust,
element lube oil filter, 12 / 24 volts electric starting equipment complete with standard heavy duty battery, dynamo,
cut-outs, ammeter, necessary wiring, pressure gauge, starter etc and heavy duty Residential type exhaust silencer
Rupees Twenty Nine Lakh
(With DEF System) and vertical hot air duct both logged with asbestos rope, save oil trays, exhaust piping of required
Eighty Five thousand Four
483 10-4-2 1.00 length, standard wall/floor mounted fuel with level indicator and piping and drip proof alternator, self excited, self Ea. 2985476.17
hundred Seventy Six Paise
regulated, screen protected, with excitation system, capable of delivering the rated system output at 415 volts,
phase, 0.8 PF, 50 Hz, 4 wire, running at 1500 RPM, conforming to IS-4722- 1968 with voltage regulation +/- 5% of
rated voltage from no load to full load. Both the engine and alternator fitted on a common fabricated steel base plate
with antivibration mounting engine and alternator both connected to each other by flexible flange coupling and
with floor/wall mounted control panel box comprising of voltmeter ammeter, selector switches, ACB / MCCB / MCB
of adequate capacity, indicator lamps duly wired with HRC fuses.
The alternator & control panel shall be connected with provide`d suitable capacity armoured cable and complete with
Acoustic enclosure (canopy) made out of 16 SWG CRCA Sheet, sound absorbing material Rockwool of 64 density &
100 mm thick conforming to IS:8183 / PU Foam of 40 Density - at least 40 mm. The resin bonded rockwool covered
from inside the canopy by perforated sheet with 3/4 mm holes, sound level not more than 75 dB at a distance of
mtr, as per PVCT norms.DG set should have in built fuel tank capacity of minimum 8 hrs of continous running capacity
on full load . Erection, commissioning and satisfactory testing as per requirement with first filling of fuel (minimum up
to the 80% of fuel tank capacity), oil, etc. with guarantee / Warrantee of complete system for Two years. & with
obtaining all necessary certificate from Electrical Inspector. The Capacity and Ratings of DG sets are as below. (As per
new CPCB4+ Emission norms Engine With - Turbo Charger, EGR (Exhaust Gas Recirculation), CRS (Common Rail Fuel
System), DOC (Diesel Oxidation Catalyst), SCR (Selective Catalytic Reduction), Integrated wiring harness connected to
ECU) (U) Continuous rating of 400 KVA ,BHP not less than 480 BHP
Providing & erecting approved make AMF control panel suitable for following size of 3 phase, 415 V., 50 cycles, A.C.
diesel generating set complete of scope as detailed below:
1) Power module: A pair of electromechanically interlocked contactors (for mains & generator) Overload relay for
generator contactor Neutral contactor for mains and generator Power socket for connections.2) Control and metering
module: Line voltage monitor. Generator voltage monitor Ammeter 3 items attempt start facility. Air circuit
Rupees Three Lakh Fifty
breakers/MCB/MCCB of suitable rating for auto/manual operation. Auto/manual switch. Emergency stop push
Four thousand Nine hundred
484 10-4-3 1.00 buttons. Manual start push button. frequency meter. Engine hour meter. Two earthing studs.3) Protection module: Ea. 354998.84
Ninety Eight Paise Eighty
The engine shutdown in the unlikely event of Low lube oil pressure High cylinder head temperature. V belt failure.
4) Indicators with alarm Load on generator.
5) Indicators Load on mains Engine fails to start . Emergency stop battery charger.
The AMF Panel of following capacity. (F) AMF Control Panel for 380 KVA/ 400 KVA3 phase DG Set
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Suppy, Installation, Testing and Commisioning of 6 body mortuary cabinate of approx. Force draft type PUF Panel:
80mm thick PUF panel with both side S.S -304 grade sheet of 0.5 mm thickness & PUF density should be 40 kg/m3
Drawer Tray: Made with high grade SS 304 box pipe. MS powder coated trolly mechanism along with ancillary
material SS Tray, Temperature: -8 C to +8 C, Door: Overlap type door with heavy duty hinges & Handles with closer
along with push type gasket for easy operation Size: 32” X 32”, Lock SS: Individual lock & Key for each door,
Identification: Each Window should be facilitated for Body Identification tag (replaceable),Vapor proof lights,
Refrigeration System: Air Cooled, Split Type and Capable to run at minimum 45 deg C Ambient with CFC free
Rupees Five Lakh Ninety Five
refrigerant gas R407C/R404A for low maintenance. Compressor Type : Hermetic reciprocating/scroll type compressor,
485 RA 1.00 Ea. 595395.00 thousand Three hundred
Indoor Unit: SS tube & Copper fins type Indoor Unit with SS casing capable to maintain low relative
Ninety Five Only
humidity.Refrigerant Pipe IDU to ODU up to 5 mtr :SS/Copper inner grooved, Power: 415 V, 3 Ph, 60 Hz, Temperature
achievement and retention : Ref. System should be able to achieve temperature within 90 minutes in load condition
and can retain temperature up to 6 hours in case of power loss. Control Panel: Digital Temperature display with
microprocessor-based controller with additional temperature display & alarm indication with buzzer at mortuary
Chamber surface.
Suppy, Installation, Testing and Commisioning of 4 body mortuary cabinate of approx. Force draft type PUF Panel:
80mm thick PUF panel with both side S.S -304 grade sheet of 0.5 mm thickness & PUF density should be 40 kg/m3
Drawer Tray: Made with high grade SS 304 box pipe. MS powder coated trolly mechanism along with ancillary
material SS Tray, Temperature: -8 C to +8 C, Door: Overlap type door with heavy duty hinges & Handles with closer
along with push type gasket for easy operation Size: 32” X 32”, Lock SS: Individual lock & Key for each door,
Identification: Each Window should be facilitated for Body Identification tag (replaceable),Vapor proof lights,
Refrigeration System: Air Cooled, Split Type and Capable to run at minimum 45 deg C Ambient with CFC free
Rupees Five Lakh Three
refrigerant gas R407C/R404A for low maintenance. Compressor Type : Hermetic reciprocating/scroll type compressor,
486 RA 1.00 Ea. 503737.50 thousand Seven hundred
Indoor Unit: SS tube & Copper fins type Indoor Unit with SS casing capable to maintain low relative
Thirty Seven Paise Fifty Only
humidity.Refrigerant Pipe IDU to ODU up to 5 mtr :SS/Copper inner grooved, Power: 415 V, 3 Ph, 60 Hz, Temperature
achievement and retention : Ref. System should be able to achieve temperature within 90 minutes in load condition
and can retain temperature up to 6 hours in case of power loss. Control Panel: Digital Temperature display with
microprocessor-based controller with additional temperature display & alarm indication with buzzer at mortuary
Chamber surface.
Supply Installation Testing & Commissioning of 2MP IR Dome Camera(2.8mm Lens with Aperture of F1.6 (By
Default)/F2.0(On
demand)),Audio Support, 1/2.8” SONY - CMOS, 2MP, 0Lux with IR LED on, 2.8mm IR Distance up to 50m, Video
Analytics: Trip Wire, Intrusion Detection and Motion Detection, H.265/H.264/M-JPEG Video Compression, PoE Rupees Eleven Thousand
487 40.00 Support, NAS Storage, SD Card(512GB), Quad Stream Support, 1/1 Audio I/O, 1/1 Alarm I/O, True WDR, 3D Noise Ea. 11378.66 Three hundred Seventy Eight
Reduction, Adaptive Streaming, Smart Streaming and ROI, SNR > 70 dB, ER Compliant & Cyber Secured as per ISO / IEC Paise Sixty Six Only
27402, BIS, CE, FCC, RoHS, IK10, IP67, UL, NEMA 4X, NDAA Compliant & STQC Certified.
Supply Installation Testing & Commissioning of 2MP IR Bullet Camera(6.0mm Lens with Aperture of F1.6(By Default)
demand)),Audio Support, 1/2.8” SONY - CMOS, 2MP, 0Lux with IR LED on, 6.0mm, IR Distance up to 50m, Video Rupees Eleven Thousand
488 10.00 Analytics: Trip Wire, Intrusion Detection and Motion Detection, H.265/H.264/M-JPEG Video Compression, PoE Ea. 11378.66 Three hundred Seventy Eight
Support, NAS Storage, SD Card(512GB), Quad Stream Support, 1/1 Audio I/O, 1/1 Alarm I/O, True WDR, 3D Noise Paise Sixty Six Only
Reduction, Adaptive treaming, Smart Streaming and ROI, SNR > 70 dB, , BIS, CE, FCC, RoHS, IK10, IP67, UL, NEMA 4X,
NDAA Compliant & STQC Certified.
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Supply Installation Testing & Commissioning of 64 Channel NVR with 4K Support and 8 HDD Slots, 64 IP Channel
Inputs; 4K HDMI, 1/1 Audio I/O and 2/1 Alarm I/O, 12MP, 8MP, 5MP, 4MP, 3MP, 2MP, 720p, D1 and CIF Recording
Resolution, 4x 4K/ 10x 3MP/16x 1080p Local Decoding, 8 SATA HDD Support (Maximum 18TB Capacity per Slot, Hard Rupees Seventy Thousand
489 1.00 Disk Not Included), Save Storage Space with Adaptive Recording and Camera-wise Recording Retention, SMS & Email Ea. 70364.00 Three hundred Sixty Four
Notification, Video Pop-up, Alarms and Instant Calling from Mobile Application, Throughput - 512Mbps Uplink, Only
512Mbps Downlink, ONVIF and support for other camera brands.
SITC of 24 x 10/100/1000BASE-T PoE ports 4 x Gigabit RJ45/SFP Combo ports Advanced L2 switching and security
Rupees Forty Six Thousand
features L2+ Static Routing Optional “standard mode” or “surveillance mode” management user interface 193 W PoE
490 8.00 Ea. 46996.80 Nine hundred Ninety Six
Paise Eighty Only
Supply, Installation, Testing and Commissioning of 10TB HDD Enterprise / Surveillance Harddisk
Rupees Twenty Six
491 2.00 Ea. 26249.90 Thousand Two hundred
Forty Nine Paise Ninety Only
Supply, Installation, Testing and Commissioning of 43" 4K LED Display
Rupees Forty Two Thousand
492 6.00 Ea. 42856.32 Eight hundred Fifty Six Paise
Thirty Two Only
Supply, Installation, Testing and Commissioning of 9U Indoor Rack with required accessories like fan, 6 socket
Rupees Nine Thousand
5/15amp PDU, hardware packet
493 1.00 Ea. 9374.82 Three hundred Seventy Four
Paise Eighty Two Only
Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete
Rupees Three Thousand
494 RA 480.00 with mounting base complete as required. Ea. 3034.04
Thirty Four Paise Four Only
Supplying, installation, testing & commissioning of fault isolator complete with base as required. Rupees Three Thousand
495 RA 25.00 Ea. 3468.34 Four hundred Sixty Eight
Paise Thirty Four Only
Supplying, installation, testing & commissioning of addressable manual call point complete as required. Rupees Four Thousand One
496 RA 20.00 Ea. 4103.63 hundred Three Paise Sixty
Supplying, installation, testing & commissioning of addressable strobe complete as required. Rupees Three Thousand Five
497 RA 20.00 Ea. 3571.36 hundred Seventy One Paise
Thirty Six Only
Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm
panel, central processing unit with the following loop modules and capable of supporting not less than
devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network
communication card, minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum
4000 events history log in the non volatile memory (EPROM), power supply unit (230 ± 5 % V, 50 hz), 48 hrs back-up
with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer Rupees Four Lakh Eighty
498 RA 1.00 to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of Ea. 481568.00 One thousand Five hundred
the schedule of work under SH: PA System) and shall be complete with all accessories . The panel shall be compatible Sixty Eight Only
for IBMS system with open protocol BACnet/ Modbus over IP complete as per specifications.
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Supplying, installation, testing & commissioning of repeater panel with 320 character/ Touch screen LCD display with Rupees One Lakh Fourteen
inbuilt reset, acknowledge and silence switches complete as required. thousand Eight hundred
Seventy One Paise Thirty
Supply & laying of 2x1.5 sqmm. Fire survival arnmoured cable, 600/1000Supply, Installation, Testing and
Commissioning of rated with annealed copper conductor having glass mica fire barrier tape covered by an extruder Rupees Three hundred Eighty
500 RA 3840.00 layer of cross linkable ethaylne propylene rubber (EPR) insulation ans LSZH inner bendding steel wire armouring & Mtr. 389.86
Nine Paise Eighty Six Only
LSZH outer seath complete as required
Supplying, installation, testing & commissioning of addressable fire control module complete as required. Rupees Three Thousand One
501 RA 20.00 Mtr. 3187.56 hundred Eighty Seven Paise
Supplying & erecting Amplifier having following specification:
Power Output :250W (RMS) (300W Max.)
inputs : 6 Misc. & 2 Aux.
frequency Response :50-1500HZ I3db
Rupees Eleven Thousand
Tone Controls :Cut & Boost type
502 7-3-3. 10.00 Ea. Two hundred Ninety Eight
LED Meter :5 LED Arrays
Paise Eighty Seven Only
The amplifier suitable to operate 240V A.C.& 24volt D.C. (Battery) with automatic changeover from AC to Battery
operation, duly protected by wrong Battery Polarity connections. [[Approved by Competent Authority i.e. not Below
the rank of Executive Engineer ]
Supplying & erecting recess wall mounting speaker with 5W rated input power 3.3 K. Ohms / 3W impedance, 100 -
10000 Hz frequency response with 6 inch dia. cone type 8 ohms speakers duly fitted in ABS plastic cabinet of colour
match with wall or ceiling of following size. [[Approved by Competent Authority i.e. not Below the rank of Executive Rupees Four hundred Two
Engineer ] Paise Ninety Nine Only
(a)Round Shaped, 230mm dia. Speaker
Supplying and erecting Flexible PVC insulated multi strand multi core 1.1 kv grade ISI marked copper wires of
following size to be erected as directed. Rupees Thirty One Paise
(d) 1.50 Sq.mm 2 core round PVC sheathed Thirty One Only
Supplying & erecting Booster Amplifier having power output of 25OW (RMS,), suitable to obtain combined power
output of two, with 6 mike inputs & suitable to be used independently as a 250watt amplifier in combination with Rupees Nine Thousand Six
505 7-3-4. 10.00 mike & mixer. The booster Amplifier shall be without mike &Aux. input channels, The system shall be suitable to Ea. 9672.77 hundred Seventy Two Paise
operate on 24OV. A.C. & 24 Volts D.C. Battery. [[Approved by Competent Authority i.e. not Below the rank of Seventy Seven Only
Executive Engineer ]
Supplying & erecting four channel Echo Mixer Pre-amplifier with following specification.
(i) Suitable to operate on 24OV.A.C. & 12 V D.C. Battery supply
(ii) B.B.D. Delay system ECHO facility on all inputs through ECHO volume, Repeat & Delay system. Rupees Three Thousand Five
506 7-4-2. 10.00 (iii) Peak LED for setting optimum distortion free input levels Ea. 3595.60 hundred Ninety Five Paise
(iv) Two outputs, variable for line & fixed for recording Sixty Only
(v)Compatible with Audio Mixing consoles. [[Approved by Competent Authority i.e. not Below the rank of Executive
(a) General Features & Special Features of the all lift items shall be taken as below.
(b) for Handicap Lifts, Minimum 10 Passengers Lift Capacity shall be considered.same is to be informed to architect
/civil authority to keep necessary size of lift well.
(c) The lifts of 15/ 16 and above passenger capacity shall be taken for Hospital Lifts; Where in Description “ Stretcher
Lifts” shall be mentioned.
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
(d) The Rates of the following items are for the lift of Machine room less. For Machine room Lifts, rate for Rs.
1,50,000/- shall be deducted in Total Cost for the Lifts from 4 to 13 Passenger Lift. Rs. 2,00,000/- shall be deducted in
Total Cost for the Lifts 15 and above passenger capacity as extra cost.
(e) Add Rs. 80,000/- for the DUPLEX control for the lifts up to 10 floors and add Rs. 10,000/- for additional each floor
above 10 floors.
(A) GENERAL DESCRIPTION OF LIFTS.
[1] GEAR LESS LIFT DRIVE (MRL) comprising of High Starting torque Lift 3 phase 440 V A. C. Permanent Magnet
Synchronous motor of proper rating with high efficiency shall be used.
[2] Micro processor based / PLC, ACVVVF, vector control drive with encoder feedback closed loop system shall be used
for lift car and door operation which shall be full collective selective operation hall call demand response, UP/DOWN
hall stops, Main, Up/ Down Contactor with overload and phase reversal relay and safety controls.
[3] Car with M S platform with bracings of adequate size and to sustain the impact load cabin + passenger with safety
factor of fire for steel and side panels of Stainless steel of sheet of grade 304 duty. Car ceiling will be S.S. finishes with
aesthetic appearance with LED ceiling lights. Car flooring shall be of s/s 304 chaker plate design sugeested of engineer
in charge. of engineer in charge. Car doors shall be of stainless steel grade 304, hairline finish with centre opening /
telescopic automatic doors. Car panel will also be S.S. 304 finished with emergency stop device, mechanical door
safety device, facility of auto/ attended mode. All car panel buttons and all floor switches must be with brail language
as per lift act.
[4] All landing doors must be fire rated for 2 hour shall be fully automatic centre opening/ telescopic opening made of
hairline finish steel grade of 304 with key holes and infrared curtains with Unlocking facility from outside
[5] Appropriate battery operated emergency light in the car along with alarm switch shall be provided. Also,
Emergency Light & Fan should start immediately without any Time Delay as soon as power fails.
[6] Digital scrolling indicator system for up-down arrow along with floor position indicator shall be provided inside the
car and at all floors.
[7] Full height infra red curtain with multiple cross / crossing light beams shall be provided.
[8] Automatic Rescue Device (ARD) shall be provided accordingly of passenger capacity with Manual Rescue Operation
( Manual Cranking Facility).
[9] Audio visual indication in the lift car showing over loading shall be provided such that doors kept open till excess
load is removed.
[10] Spring buffers/PU Buffers shall be provided.
[11] Car fan as per passenger capacity with automatic sleep timer shall be provided.
[12] Voice annunciator with suitable music shall be provided in lift car.
[13] Self diagnostics system for operational and safety parameters shall be provided in control panel.
[14] Mechanical over speed governor with governor calibration as per actual site parameters and submission of
calibration certificate submission, door key holes in the floor doors, fireman switch shall be provided.
[15] Lift machine hoisting arrangement in the lift machine room and monkey ladder for lift pit should be provided by
the lift agency, along with the other steel structure works, foundations for the machine etc…
[16] In the hoist way fascia plate shall be provided without any extra cost, where ever required as / if directed by
engineer in charge.
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
[17] Permanent wiring with necessary safety devices like RCCB in all circuit, Over Voltage Under Voltage protection
and THD eliminator in circuit for lift machine room and lift well with proper numbers of light points, with fixtures,
exhaust fan and plug points shall be provided by the agency. Only 3 phase Power Supply shall be made available by
department in lift machine room. Necessary Earthing as per Lift Act/Rules shall be arranged by Lift Agency.
[18] Any civil/ electrical works for additional and alteration in lift shaft and machine room related to erection of lift
shall be made by lift agency without any extra cost. (granite/marble fixing around all landing door openings are not in
lift agency’s scope.)
[19] Agency has to provide all working drawings and documents and liaison services for obtaining all necessary
permission from lift inspector and other authorities. [20] acrylic transparent licence/display A4 size holder in lift
[20A] As per statutory requirement of Govt. Of Gujarat lift & escalator act 2000, lift agency has to provide
1. Car top safety barricade
2. Push & talk communication system.
3. Fireman's switch operation at Ground Floor. 4.carrying out third party lift
inspection during/after lift erection and provide report by third party authorized by concern licensing authority
5.agency has to provide third party insurance upto completion of free maintenance period and submit the document
[21] Car Panel Operating Buttons with floor position indicator/buttons must be of Auto Glow type clearly visible when
view from inside cabin.
[22] For Physically Handicapped person Full Length Handrails of hairline finish steel grade of 304 should be provided at
appropriate height on the Rear & Side Wall Panels in Lift Car.
[23] With Necessary KVA rating voltage controlled Stabilizer suitable for your controller, drive and all equipments of
[24] Necessary rating of DP Elcb and FP Elcb required for lift is in scope of work which rating is sugested by CEICED
Department (electrical Inspector)
(B) SPECIAL FEATURES DESCRIPTION OF LIFTS for PREMIUM category
1. Advanced control system dual 64 bit embedded microprocessor with CANBUS Serial Communication mode
including Regenerative power efficient operation,on site programming facility, Anti nuisance, Pte-opening, BMS/RMS
with necessary online real time monitoring system having necessary connectivity for remote monitoring & other
suitable supporting hardware & software devices to fulfil the purpose.
2. Floor Indication LCD Display with call registration & brail mark with arrival gong and hall lantern & TFT Screen in the
car with MP3 Voice Announcer.
3. CAR Panel should be Scratch resistive SS Moonrock finish / Hair Line / Honeycomb for car and all Doors, All
landing doors must have fire rating up to 2 hours and car door must have multi-level crisscross beam door protection.
4. To & fro communication system & wiring (i.e. car , control room & guard room ) and Each elevator are equipped
with remote monitoring system.agency has to provide mobile app and user id and password for monitoring
13-1 DESCRIPTION OF LIFT :
Supplying, Erecting, Testing & Commissioning the passenger / stretcher lift having following main features:
13-1-AQ 15/16 Passengers, Ground plus 3 upper floor with Rated Speed of 1.0 m/sec.,
(C) With General PLUS ADDITIONAL SPECIAL FEATURES attached herewith. Prem. Cat.
Rupees Twenty Lakh Twenty
13-1-AQ 2.00 Ea. 2023094.64 Three thousand Ninety Four
Paise Sixty Four Only
13-1-AR 15/16 Passengers, Ground plus 4 upper floor with Rated Speed of 1.0 m/sec.,
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
(C) With General PLUS ADDITIONAL SPECIAL FEATURES attached herewith. Prem. Cat. Rupees Twenty One Lakh
Fifty Five thousand Four
hundred Forty Five Paise
Design, Supply, Installation, Testing & Commissioning of Hospital Dump Lift
Unmanned material lift suitable for hospital use, electric traction / hydraulic type, complete in all respects with rated
capacity 1000 Kg (confirmable to 500 Kg), heavy duty service Hoisting Machine / Power Pack Geared traction motor /
Hydraulic power pack complete with accessories Rupees Eight Lakh Six
Motor & Drive System - 415V, 3 Phase, 50Hz, IP55 motor with VVVF drive / control Control Panel- Microprocessor thousand Seven hundred
509 RA 2.00 based controller with emergency stop, overload & phase failure protection Ea. 806777.90
Seventy Seven Paise Ninety
Landing Doors with Interlocking - SS/MS swing doors with vision panel and electro-mechanical interlock Only
Safety Devices - Upper & lower limit switches, safety brake, emergency stop switch
Testing, Load Test & Commissioning - Complete testing, trial run, handing over with O&M manuals
Supply, Installation, Testing and Commissioning of Highend Server having 16 core Xeon processor;64GB RAM,Dual
PIU Approved Rate Input Hot Swap (1+1) Redundant Power Supply, 16 Hot Swap 3 5"/2 5" SATA HDD/SSD Drive Bay (up to 18TB Rupees Seven Lakh Forty
Government Capacity), 2x 10 GbE and 2x 1 GbE LAN ports, GPU GTX1650, HW RAID Controller. Three thousand Two
ayurvedic hospital hundred Eighty Nine Paise
across Gujart state. Thirty Only
Processor: Intel i5 14th Generation
RAM: 16 GB DDR5
SSD: 1 TB NVMe Rupees Ninety Eight
511 RA 1.00 Display: ~14″ or 15.6″ laptop (choose size per preference) Ea. 98980.00 Thousand Nine hundred
Brand: HP, Dell, Lenovo(OEM) Eighty Only
OS: Windows 11 (OEM)
Additional items: Warranty, accessories, etc.
Functionality: Print / Copy / Scan (All-in-one)
Print output: Monochrome (black & white)
Paper size: A4 supported
Print speed: Often ~ 40 pages per minute (ppm).
Duplex (automatic double-sided) printing: Yes
Rupees Thirty Six Thousand
512 RA 1.00 Connectivity: WiFi, Ethernet, USB Ea. 36865.00
Eight hundred Sixty Five Only
ADF (Automatic Document Feeder) for scanning multiple pages: Yes
Monthly duty cycle: Check manufacturer spec (e.g., up to ~80,000 pages for some model listing)
Starter and recommended toner yields: Example listing shows starter yield ~3,000 pages & full cartridge ~9,700 pages
Supply, Installation, Testing and Commissioning of Control Panel suitable for automatic operation of fire fighting
pumps consisting (1 no. of Main Electric, 1no. of Standby pump & 1 no. of jockey pump)
(a) Necessary FRLS cabling, cable tray, wiring, earthing from panel to individual equipment / pump in pump room shall
be included in the quoted price. Contractor has to submit panel SLD/GA dwg for approval.
(b) Facility for more selections i.e auto or manual. Rupees One Lakh Fifty Nine
513 RA 1.00 (c) Protection failure and control cabling. Ea. 159111.36 thousand One hundred
(d) interlocking of pressure switch with pumps Eleven Paise Thirty Six Only
(e) VFD starter
& suitable arrangement for Diesel engine.
Complete in all respect as required. (Quoted Rates are for Star delta Starter)
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Supply Installation, Testing & Commissioning of modular type Variable Refrigerant Volume air cooled Outdoor units
suitable for cooling and heating, having all hermetically sealed inverter type Scroll Compressor(s), microprocessor
based Controller, top discharge type condensing unit(s), with R410 A Refrigerant (Or Eco Friendly Green Gas if any),
vibration isolators, with suitable foundation, MS Stand for Unit with necessary paint etc. complete as required. The
Rupees Twelve Lakh Five
unit shall deliver the rated capacity at AHRI Conditions and work even at 50°C ambient temperature without tripping.
514 8-6-1. 1.00 Ea. 1200589.02 hundred Eighty Nine Paise
The unit shall be suitable to work on 400V +/- 10%, 3 Phase, 50Hz AC power supply. The unit shall be filled with first
charge of the refrigerant and ready for use as required. The COP at AHRI conditions shall not be less than 3.1 and IEER
not less than 6.5. (Design should be got approval before execution from engineer in charge) (A) for 54.0 HP
(B) for 52.0 HP Rupees Eleven Lakh Fifty Six
thousand One hundred
Twenty Two Paise Seventy
(C) for 42.0 HP Rupees Nine Lakh Thirty
Three thousand Seven
hundred Ninety One Paise
(D) for 36.0 HP Rupees Eight Lakh Three
517 8-6-1. 2.00 Ea. 800392.68 hundred Ninety Two Paise
Sixty Eight Only
(E) for 20.0 HP
Rupees Four Lakh Forty Four
518 8-6-1. 1.00 Ea. 444662.60 thousand Six hundred Sixty
Two Paise Sixty Only
(F) for 16.0 HP
Rupees Three Lakh Fifty Five
519 8-6-1. 2.00 Ea. 355730.08 thousand Seven hundred
Thirty Paise Eight Only
Supply, installation, testing and commissioning of following minimum capacity 4-way/2 way/radial flow as per
approval VRV Cassette Type Indoor ceiling mounted unit equipped with synthetic washable media pre-filter, fan
section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX Copper coil,
electronic expansion valve, outer cabinet, drain pump, grill, necessary supports, vibration isolation, cord less remote Rupees Twenty Seven
control etc., suitable for operation on single phase 230 V ± 10%, 50Hz AC supply, max noise level 60dB @ 400 cfm per Thousand Four hundred
TR(minimum) complete, as required. The unit shall have automatic force shut down provision in case of fire on Nineteen Paise Forty Eight
receiving signal from BMS System. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB Only
and 19 Degree C WB temperature fresh air provision compatible for Remote Operation System (A) 1.0 TR
(B) 2.0 TR Rupees Twenty Nine
521 8-6-2. 2.00 Ea. 29010.23 Thousand Ten Paise Twenty
(C) 2.4 to 2.5 TR Rupees Twenty Nine
Thousand Six hundred
Twenty Six Paise Thirty
(D) 3.0 TR to 3.2TR Rupees Thirty Thousand
523 8-6-2. 33.00 Ea. 30764.60 Seven hundred Sixty Four
Paise Sixty Only
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
(E) 4.0 TR Rupees Thirty One Thousand
524 16.00 Ea. 31922.06 Nine hundred Twenty Two
Supply, installation, testing and commissioning of following minimum capacity VRV High wall type Indoor unit
equipped with washable synthetic media pre-filter, fan section with noise level maximum 60 dB @min 400 cfm
/dynamically balanced blower, multispeed motor, coil section with DX copper coil, electronic expansion valve, outer
cabinet, cord less remote control, drain pan, necessary accessories etc., suitable for operation on 230 V ± 10%, 50 Hz, Rupees Seventeen Thousand
525 8-6-3. 3.00 single phase AC supply, complete as required. The unit shall have automatic force shut down provision in case of fire Ea. 17254.84 Two hundred Fifty Four Paise
on receiving signal from BMS System. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C Eighty Four Only
DB and 19 Degree C WB temperature. (A) 0.8 TR
Rupees Seventeen Thousand
526 8-6-3. 9.00 Ea. 17539.66 Five hundred Thirty Nine
Paise Sixty Six Only
Rupees Eighteen Thousand
527 8-6-3. 7.00 Ea. 18941.54 Nine hundred Forty One
Paise Fifty Four Only
(D) 1.5 to 1.65 TR Rupees Nineteen Thousand
528 8-6-3. 15.00 Ea. 19407.15 Four hundred Seven Paise
Rupees Twenty Thousand
529 8-6-3. 16.00 Ea. 20695.91 Six hundred Ninety Five Paise
Ninety One Only
Supply, Installation, Testing and commissioning of factory built floor mounted chilled water double skin type
horizontal/vertical air handling units made of 25mm thick panels consisting of pre plasticized G.I. casing of
thickness 0.8mm outside layer and 0.8 mm inside layer with polyurethane foam (PUF) insulation factory injected
between them by injection moulding machine, complete with blower section with blower suitable for static
pressure as required, minimum 2 bend GSS/PVC eliminators, cooling coil section with aluminium finned
copper tubes (tubes thickness not less than 0.5mm) cooling coil of 6 row deep, filter section with 50mm thick Rupees One Lakh Thirty
metal viscous/ washable synthetic type air prefilters, belt drive package with TEFC drive motor of efficiency class Eight thousand One hundred
IE3 suitable for 415 ± 10% volts, 50Hz, 3 Phase AC supply with suitable variable frequency drive control panel, Ninety Paise Twenty Two
drain connections,stainless steel (18G) drain pan with PUF insulation, 150 mm dia. dial type pressure gauges (2 nos.) Only
and industrial type thermometers (2 nos.) at the inlet and outlet of coil, auto purge valve wherever required,
necessary vibration isolation arrangement etc. complete as per specification and of following capacities. (C.)
DX ductable Units Outdoor as per specification, each complete with Prefilter ( MREV 8/----- **) , hermatic/Semi
Hermatic , rotary /scroll Compressor/s,suitable fan and motors along with R410a /R407C /R32/Eco friendly
refrigerant ( with zero ODP ) , Corded remote,starter panel , inbuilt thermostat . The price shall include initial charging Rupees Eighty Five
531 RA 5.00 of refrigerent , Rubber pad /Vibration isolator etc. complete for indoor & outdoor unit.Cooling capacity at ARI Nos 85850.00 Thousand Eight hundred Fifty
conditions 8.5 TR ( 3 phase 415 volts ±10% V,50 ± 5% Hz) Minimum COP , side discharge, noise level shall be @ 1 / Only
3 ** meter distance
Supply & Installation of Powder coated 0.5 Hepa Filter (600X600) as per Tender specification:
Rupees Eight Thousand Five
hundred Eighty Five Only
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Supply & Installation of Powder coated Return Air Riser as per Tender specification:(24G GI) Rupees Eleven Thousand Six
hundred Fifteen Only
Supply, Installation, Testing & Commissioning of Magnehelic gauges to measure the differential pressure across the
filters with MS powder coated box and SS top cover complete with necessary tubing and SS screws. Gauges shall be on
site calibrated or shall be with valid calibration at the time of commissioning. Magnhelic gauges for differential Rupees Three Thousand Five
pressure measurement across the room. Silicon tube - 1 meter long and SS Sensor probe shoude include in the cost. hundred Thirty Five Only
Box / Plate for above gauges. MOC - SS 304 16 gauge. Box design shoude be suitable for clean room application and
Rupees Three Thousand Five
535 RA 5.00 on metalic penal installation. Lot 3535.00
hundred Thirty Five Only
Complete Validation / Documentation of entire systems (As per classification) like velocity, PAO, Particle Count, air
flow pattern, & Recovery of Classification, Temperature, RH & Differential Pressure readings will be taken as per
approved format from client manually. For B & C Class areas, Particle count required for 3 days. Submission of
documents including Design, Installation, Operational & Performance qualifications with Training. Certificates of Rupees Three Thousand Five
supplied equipments to be submitted. Also properly marked equipment identification tags (stickers) for all HVAC hundred Thirty Five Only
equipment and directional
arrows. (For AHU's)
Complete Validation / Documentation of entire systems like velocity, will be taken as per approved format from
client. Submission of documents including Design, Installation, Operational & Performance qualifications with
Rupees Thirty Five Thousand
537 RA 1.00 Training. Certificates of supplied equipments to be submitted. Also properly marked equipment identification tags Lot 35350.00
Three hundred Fifty Only
(stickers) for all HVAC equipment and directional arrows. (For FDV's)
Complete Submission of Documents for Operational & Maintenance manuals of High Side Equipments with Training.
Certificates of supplied equipments to be submitted. Also properly marked equipment identification tags (stickers) for Rupees Fifteen Thousand
all HVAC equipment and directional arrows. One hundred Fifty Only
RH Control Heater in OT S.A. Duct
Rupees Seven Thousand Five
hundred Seventy Five Only
Supplying & fixing of powder coated extruded Aluminium Return Air Grills with louvers but without volume control Rupees Seven Thousand
540 8-11-6. 25.00 dampers complete as per specifications and size & shape as per site requirement and approved design. 7073.03 Seventy Three Paise Three
Supply and installation of Canvas Connection connecting machine's outsource of cool air to ducting
Rupees Three Thousand Two
hundred Thirty Two Only
Supply, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal
sizes of soft/hard drawn copper refrigerant piping for VRV system, complete with fittings, with suitable adjustable ring
type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-0 tubular insulation/with Class-
0 closed cell elastometric nitrile rubber tubular sleeves sections of specified thickness as given below for Suction and Mtr. Rupees Two hundred Sixty
Liquid lines, all accessories as per specifications etc with necessary refrigerant joint as required :(A) 6.4 mm dia (OD) Nine Paise Sixty Seven Only
(Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation
(B) 9.5 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation Rupees Three hundred
543 8-6-5. 300.00 Mtr. 370.67 Seventy Paise Sixty Seven
(C.) 12.7 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation Rupees Five hundred Eleven
(D) 15.86 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation Rupees Six hundred Sixty
Four Paise Fifty Eight Only
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
(E) 19 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation Rupees Seven hundred
546 8-6-5. 150.00 Mtr. 783.76 Eighty Three Paise Seventy
(F) 22.2 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation
Rupees Nine hundred Sixty
Two Paise Fifty Three Only
(G) 25.4 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation Rupees One Thousand One
548 8-6-5. 20.00 Mtr. 1135.24 hundred Thirty Five Paise
Twenty Four Only
(H) 28.58 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation Rupees One Thousand Two
549 8-6-5. 100.00 Mtr. 1202.91 hundred Two Paise Ninety
(I) 31.8 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm with 19 mm thick insulation Rupees One Thousand Two
550 8-6-5. 50.00 Mtr. 1261.49 hundred Sixty One Paise
Forty Nine Only
(J) 34.9 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm with 19 mm thick insulation Rupees One Thousand Three
551 8-6-5. 50.00 Mtr. 1326.13 hundred Twenty Six Paise
(K) 38.1 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm with 19 mm thick insulation Rupees One Thousand Three
552 8-6-5. 50.00 Mtr. 1362.49 hundred Sixty Two Paise
Forty Nine Only
(L) 41.27 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm with 19 mm thick insulation Rupees One Thousand Four
553 8-6-5. 50.00 Mtr. 1441.27 hundred Forty One Paise
Twenty Seven Only
Supply installation testing commissioning Shielded Shielded Control Cables for VRV System with necessary ISI mark
Medium class rigid PVC pipes with necessary accessories with termination in machine and control equipments.. (A) 2C Rupees One hundred Forty
X 1.5 Sq mm Shielded Armoured Three Paise Forty Two Only
(B) 3C X 1.5 Sq mm Shielded Armoured
Rupees One hundred Fifty
Three Paise Fifty Two Only
(C) 4C X 1.5 Sq mm Shielded Armoured Rupees Two hundred Three
Central Control System (A) Cord type remote control with thermostat, LED Display and internal wiring for Cassette, Rupees One Thousand Eight
557 8-6-7. 46.00 FCU & CSU Nos. 1854.36 hundred Fifty Four Paise
Thirty Six Only
(B) Central wired Remote Control System Rupees One Thousand Six
558 8-6-7. 330.00 Per HP 1670.54 hundred Seventy Paise Fifty
INSULATION AND MISCELLANEOUS PIPES WORKS Supplying colourless, odourless, non-flammable gas R-22(CHF2CL) Rupees Five hundred
Fourteen Paise Nine Only
Supplying colourless non inflammable refrigerant Gas R-410 Rupees Nine hundred
560 8-7-2 50.00 Kg. 925.16 Twenty Five Paise Sixteen
S.I.T.C. OF MS FABRICATION STAND FOR VRF ODU
Rupees One hundred Twenty
One Paise Twenty Only
Rigid UPVC drain pipe of 10 Kg/cm2. rating with 9 mm thick.nitrile rubber insulation.25 mm dia. Rupees Eighty Seven Paise
Eighty Seven Only
40 mm dia. Rupees One hundred Nine
Paise Eight Only
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting
complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved Rupees One Thousand Three
564 8-11-1. 450.00 drawings and specifications of following sheet thickness complete as required.(A) Thickness 0.63 mm sheet (22 Gauge) Sq.mt 1308.96 hundred Eight Paise Ninety
(B) Thickness 0.80 mm sheet (20 Gauge) Rupees One Thousand Five
565 8-11-1. 450.00 Sq.mt 1519.04 hundred Nineteen Paise Four
Supplying, Fixing, testing and commissioning of fire dampers in supply air duct/main branch and return air path as
and where required of required sizes i/c control wiring,the damper shall be motorized and spring return so as to close
the damper in the event of power failure automatically and open the same in case of power being restored. The Rupees Twelve Thousand
566 8-11-10. 5.00 spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed Sq.Mtr. 12024.05
Twenty Four Paise Five Only
in the event of fire signal complete as required and as per specifications. (A) Fire damper
(B) Actuator Rupees Eleven Thousand
567 8-11-10. 8.00 Ea. 11264.53 Two hundred Sixty Four
Paise Fifty Three Only
Supply and fixing of acoustic lining of supply air duct and plenum with 25 mm thick resin bonded glass wool having
density of 32 kg/m³, with 25 mm X 25 mm GI section of 1.25 mm thick, at 600 mm centre to centre covered with
Reinforced Plastic tissue paper and 0.5 mm thick perforated aluminum sheet fixed to inside surface of ducts with Sq.Mtr. Rupees Seven hundred Forty
cadmium plated nuts, bolts, stick pins, CPRX compound etc. complete as required and as per specifications. Paise Thirty Three Only
Supplying and fixing of following thickness duly laminated aluminum foil of mat finish closed cell Nitrile
rubber (Class "O") insulation on existing duct after applying suitable adhesive for Nitrile rubber. The joints shall Rupees One Thousand One
569 8-11-13. 1200.00 be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specifications Sq.Mtr. 1102.92 hundred Two Paise Ninety
and as required.25 MM Two Only
Ch-4 Deduct for avallable excavated earth for disposal of stuff at any lead or lit (Earth which s stacked at any location
outside the campus non- objectionable place shall be found by the contractor) (The minimum basic Rate of Rs. Rupees One hundred Twenty
128/cum shal be deducted in contractors RA bil) Nine Paise Twenty Eight Only
Total of civil & Electrical work
Credit amount of net up set Value for including Dismantling of old existing Building following as below (i) S.S Hospital
Petlad Old Staff Quaters No. B-2 To B-10, 9 Nos, Net Upset value- Rs 1,15,600 (ii) S.S Hospital Petlad Old Staff Quaters
No. B-11 to B-16, 06 Nos, Net Upset value- Rs 1,33,850.00, (iii) S.S Hospital Petlad Old Staff Quaters No. C-3 & C-4, 02 Rupees Four Lakh Six
571 Job 1.00 Nos, Net Upset value- Rs 52,850.00, (iiii) S.S Hospital Petlad Old Staff Quaters No. D-3 & D-4, 02 Nos, Net Upset value- Job 406940.00 thousand Nine hundred
Rs 1,04,640,Total Amount = 4,06,940/- (This Item shall not quote less than as per valuation Report, Credit Value Rs. Forty Only
Rs 1,04,640,Total Amount = 4,06,940/- (This Item shall not quote less than as per valuation Report, Credit Value Rs. Forty Only
4,06,940/-. This amount shall be deducted from the Contractor' s First R.A.Bill)
Credit amount of net up set Value for including Dismantling of old existing Building following as below (i) Main
Building at S.S Hospital Petlad , Net Upset value- Rs 8,24,350.00 (ii) TB Ward Building at S.S Hospital Petlad , Net
Upset value- Rs 1,07,050.00 (iii) PM Room & Shed Building at S.S Hospital Petlad , 01 No, Net Upset value- Rs
16,700.00, (iiii) Chimney Room at S.S Hospital Petlad , Net Upset value- Rs 1000.00, (v) Special Room Building at S.S
Hospital Petlad , Net Upset value- Rs 61,200.00 (vi) Toilet (Room) Building at S.S Hospital Petlad , Net Upset value- Rs Rupees Nine Lakh Eighty Six
572 Job 1.00 5400.00 (vii) Pump Room & Over Head Water Tank (Small) at S.S Hospital Petlad , Net Upset value- Rs -2300.00 (viii) Job 986200.00
thousand Two hundred Only
Over Head Water Tank (Large) at S.S Hospital Petlad , Net Upset value- Rs -27,200.00 Total Amount = 9,86,200/- (This
Over Head Water Tank (Large) at S.S Hospital Petlad , Net Upset value- Rs -27,200.00 Total Amount = 9,86,200/- (This
Item shall not quote less than as per valuation Report, Credit Value Rs. 9,86,200/-. This amount shall be deducted
from the Contractor' s First R.A.Bill)
Sr. N.B.O. No. Net Total Tendered Rates ( SOR 2024 - 25 )
Item Description Unit Amount
No. SOR Quantity Rate In Words
Credit amount of net up set Value for including Dismantling of Fire Safety Equipment following as below (i) Fire Safety
Equipment in Hospital Main Building, TB Ward and Special Room Line at S.S Hospital Petlad , Net Upset value- Rs
10,54,600.00, Total Amount = 10,54,600/- (This Item shall not quote less than as per valuation Report, Credit Value Rupees Ten Lakh Fifty Four
10,54,600.00, Total Amount = 10,54,600/- (This Item shall not quote less than as per valuation Report, Credit Value Rupees Ten Lakh Fifty Four
Rs. 10,54,600/-. This amount shall be deducted from the Contractor' s First R.A.Bill) thousand Six hundred Only
Total Credit Amount
Estimated Amount put to tender: Rupees Forty Two Crore Thirty Lakh Forty Six thousand Three hundred Thirty Four Paise Five Only
I / We am / are willing to carry out the work at _______________________________%above/below
percent (should be written in figures And Words ) of the estimated rates mentioned.Amount of my / our tender works out as under.
* Estimated amount * Estimated amount
Put to tender Rs.____________________ Put to tender Rs.____________________
(Please strike out whichever not applicable.)
(1) All works shall be carried out as per Public Works Department Handbook and other specifications of Division or as directed.
(2) All the columns in Schedule should be fifled in ink and the total of the entries in the last column should be struck by the contractor under his
(3) Rates quoted include clearance of site (prior to commencement of work and at its close ) in all respects and hold good for work under all conditions,
(4) To be continued on additional sheets , if found necessary .
(5) Recovery Toward Cost of Dismental Material Shall be made for Rs 406940.00 from the 1st RA Bill of Contractor.
Quantity, rates & wording of items are as per estimates and calculation in the schedule " B " are arithmetically checked and found correct.
Signature of Contractor
Dy Executive Engineer Executive Engineer
PIU, Anand PIU, Anand
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
19-Special Conditions-07-02-2025.pdf
BOQ SDH Petlad.pdf
Building-Specification.pdf
Ele-List of Approved Products-FINAL.pdf
GRs and Conditions-11-06-24.pdf
Instructions for Electri works.pdf
Insurance Clause-03-11-2025.pdf
Make List Dt-15-10-25-6680.pdf
Standard Specification for Electrical Work.pdf
Tender Details-165-01.pdf
SBD SDH Petlad.pdf
Download all tender documents and submit your bid