Tender Value
₹35.3 L
EMD Value
₹70,600
Closing Date
21 Sept 2021, 6:00 pmClosed
THE GM(STPS)
ADMIN BUILDING, STPS,THE WBPDCL.
Maintenance work of 315 MVA BHEL Make Generator Transformer-5, 20 MVA UAT- 5A and 5B and 40MVA ST-3 and ST-4 during U-5 OH periods under EMO dept., STPS.
2021_WBPDC_341615_1
WBPDCL/STPS/NIT/E2506/21-22
Open Tender
ELECTRICAL WORKS M/R
Item Rate
365 days
ADMIN BUILDING, STPS, THE WBPDCL.
Please refer Tender documents.
3 documents required · 3 mandatory
₹0
₹70,600
Yes
ADMIN BUILDING, STPS,THE WBPDCL.
27 Apr 2022
26 Aug 2021
24 Sept 2021
27 Aug 2021
21 Sept 2021
1 Sept 2021
31 Aug 2021
Amount
Generator Transformer #5, Make- BHEL : MVA-189 /252/315, Voltage(HV)- 235 KV, Voltage(LV) - 16.5 KV, Current(HV) - 774.81 Amp, Current(LV) -11035.21 Amp , Sl. No:6006263
Isolation of GT #5 from both LV & HV terminal with necessary dismantling and Removing of Dropper Moose Conductor & Flexible Connector
Jobs to facilitate the Testing work of transformer along with bushing before O/H & after O/H by testing dept.
Disconnection of oil lines to conservator tank and radiator side & equalizer line & Blanking work prior oil draining at reasonable level and Conservator Tank Air Cell Heartiness checking by N2/ Dry air, MOG checking & necessary gasket replacement after lifting from base.
OCTC Diverter Chamber lifting from base after disconnection and assistance for Servicing/maintenance work (change of O-ring & Gaskets) as per recommendation of OEM personal (BHEL) and Servicing Job of Off circuit Tap changer drive mechanism for enabling smooth Operation in all taps position and job assistance to OCTC testing.
Y-phase HV turret lifting for arresting the oil leakage at bottom if possible without disconnection of Bushing.
Dismantling of HV Neutral Bushing from base for rectification oil leakage and replacement if required.
Dismantling & Lifting of all LV Bushing from base for rectification of oil leakage due to trouble in oil seal and assistance to OEM for rectification of Hotspot in LV turret area and necessary maintenance work like changes of Bolt, Stud, as per recommendation.
Disconnection of TWENTY FOUR (24) Nos Radiator bank from header for requisite Maintenance of valve by replacement of o-ring & gasket.
Dismantling of transformer pipe line from main tank, Buchholz Relay etc if required and Change of gaskets such as Man-hole gaskets, WTI & OTI Gaskets, PRV, Buchholz Relay gaskets, other flange gaskets (LV side inspection, equalizing pipe flanges, radiator flanges etc.) If required.
Twelve nos Cooler Fans dismantling & Fitting after OH of Motor, to be done by other agency at STPS premises.
Oil Filtration after completion of jobs still achieving desired parameter of oil due to exposure to air during maintenance works prior Oil Filling.
Transformer Surface cleaning, checking, oil settling, venting Jobs after completion of oil filtration & filling work
Reconnection of HV & LV Terminal after completion of maintenance work & satisfactory transformer testing.
Deputation of Skilled Manpower during Charging of GT#5 for 12 hours or more as per situation during unit synchronization.
BHEL Make UAT#5A & UAT#5A: 16.5/6.6 KV, 20/16 MVA, Current (HV)-699.81A, (LV)-1673.479A Sl. No:2017185 & 2017186
Isolation of Trf.from both LV & HV terminal and Necessary Jobs to facilitate the Testing of transformer before for both trf maint. Job
Disconnection of oil lines to conservator tank and radiator side & equalizer line & Blanking work prior oil draining at reasonable level for both
Job Assistance to OEM for OLTC Servicing / maintenance work as per recommendation of OEM personal (CTR) for both UAT.
Conservator Tank Air Cell Healthiness checking by N2/ Dry air, MOG checking & necessary gasket replacement after lifting from base.
Transformer Oil Filtration after completion of jobs as required BDV value due to exposure to air during maintenance works prior Oil Filling.
Transformer Surface cleaning, checking, oil settling, venting Jobs after completion of oil filtration & filling work and HV, LV connection.
BHEL Make ST # 3 & ST # 5: 220/6.9 KV, 40/25 MVA, Current (HV)-104.973 A, (LV)-2091.55/1255.11A YNy0d1 Sl. No: NA & 2018453
Isolation of Trf.from both LV & HV terminal and Necessary Jobs to facilitate the Testing of transformer before trf maint. Job for both
Disconnection of oil lines to conservator tank and radiator side & equalizer line & Blanking work prior oil draining at reasonable level for OLTC disconnection
Job Assistance to OEM for OLTC Servicing / maintenance work as per recommendation of OEM personal (BHEL) for both Station Transformer.
Conservator Tank Air Cell Healthiness checking by N2/ Dry air, MOG checking & necessary gasket replacement after lifting from base.
Replacement of existing Air Cell inside conservator tank by new one after lowering the main tank oil up to required level for ST#3 only if found damaged.
Transformer Oil Filtration after completion of jobs still aas required BDV value of oil due to exposure to air during maintenance works prior Oil Filling.
Transformer Surface cleaning, checking, oil settling, venting Jobs after completion of oil filtration & filling work and HV, LV connection.
SHREE ABIRAMI ENGGINEERING WORKS
MESSON ELECTRICALS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .