Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹564.8 CrAccepted-AOC GODREJ WATERSIDE TOWER NO 1 OFFICE 803 8TH FLOOR PLOT NO 5 BLOCK DP SECTOR V SALT LAKE CITY KOLKATA 700091 | KOLKATA | KOLKATA | WEST BENGAL | 700091 | ₹564.8 Cr | L1 | Accepted-AOC Work awarded to M/s. ITD Cementation India Limited, Mumbai being L1 bidder |
| 2 | L2₹588.5 CrRejected-AOC | ₹588.5 Cr | L2 | Rejected-AOC Financial bid not accepted being L2 bidder |
| 3 | L3₹614.8 CrRejected-AOC CRYSTAL TOWER 4TH FLOOR TELIBANDHA RAIPUR | RAIPUR | RAIPUR | CHHATTISGARH | ₹614.8 Cr | L3 | Rejected-AOC Financial bid not accepted being L3 bidder |
| 4 | L4₹731.9 CrRejected-AOC | ₹731.9 Cr | L4 | Rejected-AOC Financial bid not accepted being L4 bidder |
Tender Value
₹622.0 Cr
EMD Value
₹6.5 Cr
Closing Date
31 Jul 2018, 6:00 pmClosed
Sr. Manager (Engg-C)
O/o ED Engg-SR Rajiv Gandhi Bhawan, Safdarjung Airport New Delhi
Up gradation of passenger terminal building and airside facilities at Tiruchiraplli International Airport. SH. Construction of new TB, elevated road alongwith associated elect. mechanical, Airport system, IT works and comprehensive maintenance
2018_AAI_11085_1
AAI/CHQ/ED Engg-SR/Trichy/NITB/2018
Open Tender
Civil Works
1080 days
Trichy Airport
As per NIT
3 documents required · 3 mandatory
₹11,800
Airports Authority of India
₹6.5 Cr
30 Jun 2021
19 Jun 2018
7 Aug 2018
19 Jun 2018
31 Jul 2018
3 Jul 2018
19 Jun 2018 - 27 Jun 2018
Amount
Total of BoQ 2 (Civil Works)
Total of BoQ 3 (Electro Mechanical, Airport System & IT Works, including AICMC and Operations)
Description of Work / Item(s)
Amount
Stripping, storing of top soil by road side/demarketed horticulture area at 15 m internal and re-application on embankment slopes, cut slopes and other areas in complete in all respect as per direction of Engineer-In-Charge. (Note: To meet out GRHIA rating)
Excavation for basement in all kinds of soil with all lifts and leads hydraulic excavator of 0.9 cum bucket capacity including cutting and loading in tippers, transporting to embankment site within all lifts and lead upto 1000 m, trimming bottom and side slopes in accordance with requirements of lines, grades and cross sections and backfilling the excavated earth to the extent required and utilising the remaining earth locally for road work within all lifts and lead within Airport Permises.(Note: Payment for construction of embankment for road work shall be paid under Item no 6)
Excavation for basement in ordinary rock (Highly Weathered rock) with all lifts and leads hydraulic excavator of 0.9 cum bucket capacity including cutting and loading in tippers, transporting to embankment site within all lifts and lead upto 1000 m, trimming bottom and side slopes in accordance with requirements of lines, grades and cross sections and backfilling the excavated earth to the extent required and utilizing the remaining earth locally for road work within all lifts and lead within Airport Premises.(Note: Payment for construction of embankment for road work shall be paid under Item no 6)
Earth work in excavation by mechanical means in all kind of soils with all lifts of foundation of structures, pipes exceeding 600 mm dia as per drawing and technical specification, including setting out, construction of shoring and bracing, removal of stumps and other deleterious matter, dressing of sides and bottom, backfilling the excavated earth to the extent required and utilizing the remaining earth locally for road work with all leads within airport Premises(Note: Payment for construction of embankment for road work shall be paid under Item no 6)
Earth work in excavation by mechanical means in ordinary rock (Highly Weathered rock) with all lifts of foundation of structures, pipes exceeding 600 mm dia as per drawing and technical specification, including setting out, construction of shoring and bracing, removal of stumps and other deleterious matter, dressing of sides and bottom, backfilling the excavated earth to the extent required and utilizing the remaining earth locally for road work with all leads within airport Premises(Note: Payment for construction of embankment for road work shall be paid under Item no 6)
Construction of embankment with approved materials deposited at site (Obtained from cutting and excavation from basement and foundation of other structures), graded and compacted to meet requirement of technical specification complete in all respect as per direction of Engineer-In-Charge.
Supplying and filling in plinth with fine sand (Natural sand or M Sand) in pile foundations and under floors, including watering, ramming, consolidating and dressing complete.
Excavating trenches of required width for pipes, cables, etc. including excavation for sockets, and dressing of sides, ramming of bottoms, depth upto 1.5 m, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, with all leads within airport Premises. All Kinds of Soil Pipes, cables etc,From 15 mm but not exceeding 80 mm dia.
Excavating trenches of required width for pipes, cables, etc., including excavation for sockets, and dressing of sides, ramming of bottoms, depth upto 1.5m, including getting out the excavated soil, and then returning soil as required, in layers not exceeding 20cm in depth including consolidating each deposited layer by ramming, watering etc. and disposing of surplus excavated soil as directed with all leads within airport Premises. All Kinds of Soil Pipes, cables etc., exceeding 80mm dia but not exceeding 300mm dia
Excavating trenches of required width for pipes, cables, etc., including excavation for sockets, and dressing of sides, ramming of bottoms, depth upto 1.5m, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20cm in depth including consolidating each deposited layer by ramming, watering etc. and disposing of surplus excavated soil as directed with all leads within airport Premises. All Kinds of Soil Pipes, cables etc. exceeding 300 mm dia but not exceeding 600 mm
Extra for excavating trenches for pipes, cables etc. in all kinds of soil for depth exceeding 1.5 m, but not exceeding 3 m.). All Kinds of Soil Pipes, cables etc., exceeding 80mm dia but not exceeding 300mm dia
Extra for excavating trenches for pipes, cables etc. in all kinds of soil for depth exceeding 1.5 m, but not exceeding 3 m. All Kinds of Soil Pipes, cables etc., exceeding 300mm dia but not exceeding 600mm dia
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work upto plinth level 1:5:10 (1 Cement : 5 coarse sand (zone-III): 10 graded stone aggregate 40 mm nominal size)
Providing and laying in position ready mixed plain cement concrete, with cement content as per approved design mix and manufactured in fully automatic batching plant and transported to site of work in transit mixer for all leads, having continuous agitated mixer, manufactured as per mix design of specified grade for plain cement concrete work, including pumping of R.M.C. from transit mixer to site of laying and curing, excluding the cost of centering and shuttering including cost of curing, admixtures in recommended proportions as per IS : 9103 to accelerate/ retard setting of concrete, improve workability without impairing strength and durability as per direction of the Engineer-in-charge. All works above plinth level in M-15 grade plain cement concrete (cement content considered @ 240 kg/cum) Note : 1)For the purpose of tendering, the quantity of cement used for one Cum. of finished concrete may be assumed as 240 Kg. If the actual quantity of cement required as per laboratory mix design varies from the quantity assumed above, necessary cost adjustment for deviation in the quantity of cement as per mix design, if any, shall be done as per the rate of cement in actual supply voucher from manufacturer/authorized dealer at the time of execution. In the case of authorized distributor the rate may be authenticated by the manufacturer. The rate of cement exclusive of GST shall only be considered for payment.
Providing and laying in position ready mixed plain cement concrete, with cement content as per approved design mix and manufactured in fully automatic batching plant and transported to site of work in transit mixer for all leads, having continuous agitated mixer, manufactured as per mix design of specified grade for plain cement concrete work, including pumping of R.M.C. from transit mixer to site of laying and curing, excluding the cost of centering and shuttering including cost of curing, admixtures in recommended proportions as per IS : 9103 to accelerate/ retard setting of concrete, improve workability without impairing strength and durability as per direction of the Engineer-in-charge. All works up to above plinth level in M-25 grade plain cement concrete (cement content considered @ 330 kg/cum). Note : 1) For the purpose of tendering, the quantity of cement used for one Cum. of finished concrete may be assumed as 330 Kg. If the actual quantity of cement required as per laboratory mix design varies from the quantity assumed above, necessary cost adjustment for deviation in the quantity of cement as per mix design, if any, shall be done as per the rate of cement in actual supply voucher from manufacturer/authorized dealer at the time of execution. In the case of authorized distributor the rate may be authenticated by the manufacturer. The rate of cement exclusive of GST shall only be considered for payment. Note: 2) This item shall be executed below granite flooring and epoxy terrazzo flooring items only.
Providing and laying in position machine batched and machine mixed design mix M-30 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-in-charge. All works upto plinth level (Note :- For the purpose of tendering, the quantity of cement used for one Cum. of finished concrete may be assumed as 340 Kg. If the actual quantity of cement required as per laboratory mix design varies from the quantity assumed above, necessary cost adjustment for deviation in the quantity of cement as per mix design, if any, shall be done as per the rate of cement in actual supply voucher from manufacturer/authorized dealer at the time of execution. In the case of authorized distributor the rate may be authenticated by the manufacturer. The rate of cement exclusive of GST shall only be considered for payment..
Providing and laying in position machine batched and machine mixed design mix M-30 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-in-charge. All works above plinth level upto Floor Five Level. (Note :- For the purpose of tendering, the quantity of cement used for one Cum. of finished concrete may be assumed as 340 Kg. If the actual quantity of cement required as per laboratory mix design varies from the quantity assumed above, necessary cost adjustment for deviation in the quantity of cement as per mix design, if any, shall be done as per the rate of cement in actual supply voucher from manufacturer/authorized dealer at the time of execution. In the case of authorized distributor the rate may be authenticated by the manufacturer. The rate of cement exclusive of GST shall only be considered for payment.)
Providing and laying in position machine batched and machine mixed design mix M-35 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-in-charge. All works up to plinth level (Note :-For the purpose of tendering, the quantity of cement used for one Cum. of finished concrete may be assumed as 350 Kg. If the actual quantity of cement required as per laboratory mix design varies from the quantity assumed above, necessary cost adjustment for deviation in the quantity of cement as per mix design, if any, shall be done as per the rate of cement in actual supply voucher from manufacturer/authorized dealer at the time of execution. In the case of authorized distributor the rate may be authenticated by the manufacturer. The rate of cement exclusive of GST shall only be considered for payment.)
Providing and laying in position machine batched and machine mixed design mix M-35 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-in-charge. All works above plinth level upto Floor Five Level. (Note :- For the purpose of tendering, the quantity of cement used for one Cum. of finished concrete may be assumed as 350 Kg. If the actual quantity of cement required as per laboratory mix design varies from the quantity assumed above, necessary cost adjustment for deviation in the quantity of cement as per mix design, if any, shall be done as per the rate of cement in actual supply voucher from manufacturer/authorized dealer at the time of execution. In the case of authorized distributor the rate may be authenticated by the manufacturer. The rate of cement exclusive of GST shall only be considered for payment.).
Providing and laying in position machine batched and machine mixed design mix M-40 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-in-charge. All works above plinth level upto Floor Five Level. (Note :- For the purpose of tendering, the quantity of cement used for one Cum. of finished concrete may be assumed as 360 Kg. If the actual quantity of cement required as per laboratory mix design varies from the quantity assumed above, necessary cost adjustment for deviation in the quantity of cement as per mix design, if any, shall be done as per the rate of cement in actual supply voucher from manufacturer/authorized dealer at the time of execution. In the case of authorized distributor the rate may be authenticated by the manufacturer. The rate of cement exclusive of GST shall only be considered for payment)
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more. (Note : Contractor is permitted to use ready to use " cut and bend " rebars of approved make from factory/ workshop but nothing extra shall be payable for use of ready to use "cut and bend " rebars.
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete above plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more. (Note : Contractor is permitted to use ready to use " cut and bend " rebars of approved make from factory/ workshop but nothing extra shall be payable for use of ready to use "cut and bend " rebars.
Centering and shuttering including strutting, propping etc. and removal of form for :Foundations, footings, bases of columns etc. for mass concrete.
Centering and shuttering including strutting, propping etc. and removal of form for : Walls (any thickness) including attached pilasters buttresses , plinth and string courses etc.
Centering and shuttering including strutting, propping etc. and removal of form for : Suspended floors, roofs, landings, balconies and access platform.
Centering and shuttering including strutting, propping etc. and removal of form for : Lintels, beams, plinth beams, girders, bressumers and cantilevers.
Centering and shuttering including strutting, propping etc. and removal of form for : Columns, Pillars, Piers, Abutments, Posts and Struts.
Centering and shuttering including strutting, propping etc. and removal of form for: Stairs, (excluding landings) except spiral - staircases.
Centering and shuttering including strutting, propping etc. and removal of form for : Extra for shuttering in circular column, Pillars, Piers, Abutments, Posts and Struts.
Extra for additional height in centering, shuttering where ever required with adequate bracing, propping etc., including cost of de-shuttering / centering at all levels, over a height of 3.50 m, for every additional height of 1 metre or part thereof (Plan area to be measured). Suspended floors, roofs, landing, beams and balconies (Plan area to be measured)
Providing and Placing in position suitable PVC water stops conforming to IS:12200 for construction/ expansion joints between two RCC members and fixed to the reinforcement with binding wire before pouring concrete etc. complete, Kickers (320 mm wide, 5 mm thick)
Providing and fixing of expansion joint system related with floor location as per drawings and direction of Engineer-In-Charge. The joints system will be of extruded aluminum base members, self aligning / self centering arrangement and support plates etc. as per ASTM B221-02. The system shall be such that it provides floor to floor /floor to wall expansion control system for various vertical location in load application areas that accommodates multi directional seismic movement without stress to it’s components. System shall consist of metal profiles with a universal. aluminum base member designed to accommodate various project conditions and finish floor treatments. The cover plate shall be designed of width and thickness required to satisfy projects movement and loading requirements and secured to base members by utilizing manufacturer’s pre-engineered self-centering arrangement that freely rotates / moves in all directions. The Self – centering arrangement shall exhibit circular sphere ends that lock and slide inside the corresponding aluminum extrusion cavity to allow freedom of movement and flexure in all directions including vertical displacement. Provision of Moisture Barrier Membrane in the Joint System to have watertight joint is mandatory requirement all as per the manufactures design and as approved by Engineer -in- Charge . (Material shall confirm to ASTM 6063.) Floor joint 150mm gap
Providing and fixing of expansion joint system related with wall joint (internal/ external) location as per drawings and direction of Engineer-In- Charge. The joints shall be of extruded aluminum base members, self aligning / centering arrangement and support plates as per ASTM B221- 02. The material shall be such that it provides an Expansion Joints System suitable for vertical wall to wall/ wall to corner application, both new and existing construction in office Buildings & complexes with no slipping down tendency amongst the components of the Joint System. The Joint System shall utilize light weight aluminum profiles exhibiting minimal exposed aluminum surfaces mechanically snap locking the multicellular to facilitate movement. (Material shall confirm to ASTM 6063.) Wall joint of 150mm gap
Providing and fixing 150 mm thick expansion joint filler board of approved brand of Dawn colour between expansion joints, using specifically extruded high performance sheet minimum density 28 kg per cum and compression strength 0.21 Kg./Sqm when tested as per ASTM D-3575 including using double sided adhesive SIL tape (manufactured by Supreme Industries Ltd. or approved equivalent) of 25x25x2 mm at four places per Sqm to the casted surface to form the expansion joint filler board will become one side of the shuttering while the expansion joint is being created, including cost of all materials, Transportation, cutting and placing to the required size, labour charges, sundries, wastage etc.at all levels complete as per drawings and as per direction of Engineer-in-Charge.
Providing and fixing sheet covering under expansion joints with iron screws as per design.Aluminium fluted strips 3.15 mm thick. 200mm wide
Designing, providing and installing prestressed ground anchors of 25 MT capacity at foundation level in accordance with BS:8081 & specifications based on the provided data such as service life of anchor, design load using prestressing steel with minimum fixed length of 5 mts. or more depending on the pull out criteria. Rate shall include drilling through over burden, all type of soils, weathered/hard rock with either rotary/pneumatic percussion method, flushing the hole, fabrication & installing of anchors, stressing and grouting of anchors to achieve its strength to its capacity level & anchoring to the desired locking force level, providing adequate corrosion protective etc. (Note : This item shall be executed with prior approval of Engineer-In-Charge subject to site requirement and decision of Engineer-In-Charge shall be final and binding and no claim whatsoever shall be entertained)
Note: The contractor shall make at his own cost all necessary arrangements for maintaining water level, in the area where works are under execution low enough so as not to cause any harm to the work shall be considered as inclusive of pumping out or bailing out water, if required, for which no extra payment shall be made. This will include water coming from any source, such as rains, accumulated rain water, floods, leakages from sewer and water mains, subsoil water table being high or due to any other cause whatsoever. The contractor shall make necessary provisions of pumping, dredging bailing out water coming from all above sources and excavation and other works shall be kept free of water by providing suitable system approved by the Engineer-in-charge. Sub-soil water table at work site is reported to be about approx. 5.0 m. below the general ground level. In order to avoid possibility of basement floor of main building being getting uplifted/damaged due to water pressure, the contractor shall lower the ground water table below the proposed foundation level by boring tube wells all around the proposed building using well point sinking method or any suitable method as approved by Engineer-in-charge. Sub soil water table shall be maintained at least 50 cm. below the P.C.C level during excavation, laying of P.C.C., water proofing treatment, laying of basement raft and beams including filling of earth/sand under the basement floor. The water table shall not be allowed to rise above base of raft level until completion of outer retaining walls including water proofing of vertical surface of walls and back filling along the walls upto ground level and until the structure attains such height to counter balance the uplift pressure(if any). However, the contractor should inspect the site and make his own assessment about sub-soil water level likely to be encountered at the time of execution and quote his rates accordingly. Rate of all items are inclusive of pumping out or bailing out water, if required. Nothing extra on this account whatsoever shall be paid to him. The sequence of construction shall be got approved by the Engineer-in-charge.
Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in:, Cement mortar 1:6 (1 Cement : 6 coarse sand)
Brick work with non modular fly ash bricks conforming to IS:12894, class designation 10 average compressive strength in super structure above plinth level up to floor V level in :Cement mortar 1:6 (1 cement : 6 Coarse sand)
Providing and laying autoclaved aerated cement blocks masonry with 100mm/150mm/200mm/250mm thick or as desired size/ thickness AAC blocks conforming to IS 2185 Part 3 (1989) having density in oven dry condition 551 - 650 Kg/Cum, Grade -I, minimum Compressive strength 4 N/mm2, thermal conductivity in air dry condition 0.23 W/mK in super structure above plinth level up to all floor level at all heights with RCC band at sill level and lintel level with approved block laying polymer modified adhesive mortar (minimum 6 mm thick) conforming to ANSI A118.1 & ANSI A118.4-1999, all complete as per direction of Engineering-Charge. (The payment of RCC band and reinforcement shall be made for separately).
Half brick masonry with non modular fly ash bricks of class designation 10, conformingio IS :12894, in super structure above plinth and upto floor V level in Cement mortar 1 : 4 (1 cement : 4 coarse sand)
Extra for providing and placing including drilling where as required in position 2 Nos. 6 mm dia M.S. bars at every third course of half brick masonry
Providing and fixing 50 mm thick extruded polystyrene rigid insulation board of required size between cavity wall, complying with ISO4898:2008 & ASTM C 578-08b - type VI, having thermal conductivity of 0.0289 W/m K as per ASTM C 578 (measured as per IS 3346), compressive strength of > 350 kPa listed as per ASTM D 1621, density of 34-36 kg/cum as per ASTM D 1622, water absorption <1% by volume as per ASTM D 2842, oxygen index of 24.1 to 28.1listed as per ASTM D 2863, cell size 0.4 mm of dia (max) as per ASTM D 3576. Fire retardant property as per DIN 4102, Part 1 of class B2 and as per ASTM E84 class A, fixed with suitable water based adhesive and fastener, complete in all respect as per the directions of Engineer-in-Charge.
Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: Cement mortar 1:4 (1 cement : 4 coarse sand)
Providing & fixing in position 65 mm thick factory made door frame of Phenol bonded Bamboo wood (superior class, interior use), in approved colour, texture and finish.The bamboo wood shall have minimum density of 1000 Kg/cum, minimum hardness 1000 Kgf. The door frame shall have tenon & mortise interlocking system, to be fixed to the wall with 100 mm size G.I screws all complete as per directions of Engineer-in charge.
Providing & fixing in position Phenol bonded Bamboo wood panelled or panelled and glazed shutters for doors, windows, clerestorey windows with pre-molded 30mm thick planks, in approved colours, texture & finish. It shall have 10mm wide, 25mm deep groove to fit in panels.The bamboo wood shall have minimum density of 1000 Kg/cum, minimum Hardness 1000 Kgf. All styles and rails shall have profiled interlocking system locked in place by bamboo pins, all complete as per direction of Engineer in charge. (The panelling will be paid for separately).
Providing & fixing in position Phenol bonded Bamboo wood panelling of 10mm thick, in 25 to 40 mm thick panelled or panelled & glazed shutters for doors, windows, clerestorey windows, in approved colour, texture & finish. The bomboo wood planks shall have minimum density of 1000 Kg/cum & minimum Hardness 1000 Kgf. The panels shall have profiled interlocking system locked in place with bamboo pins all complete as per directions of Engineer in-charge. (Area of opening for panel inserts excluding portion inside grooves or rebates to be measured).
Providing and fixing in position single/double leaf including frames fire check doors with 120 minutes fire rating conforming to BS:476 part 22 & IS : 364 part II of approved make at all levels including all accessories like door closer,panic exit device (single/double leaf),ss ball bearings , vision panel etc., testing and complete in all respect with Prototype Test certificate for a test carried out earlier at CBRI Roorkee /NTH for fire rating of doors including manufactures test certificate as per technical specifications and direction of Engineer-In-Charge. (Note: The cost includes door frames, door shutter , vision panel ,all hardware’s, accessories and cost of fire door with frame and all hardware required for laboratory testing and any incidental additional requirements for execution of this item as per technical specifications and complete satisfaction to Engineer- In –Charge, cost of all above shall be treated as included in the item and nothing extra will be paid on this account )
Providing and fixing stainless steel (grade 304) tower bolts of approved make with necessary screws etc. complete. In stainless steel satin / polished finish 250 x10 mm
Providing and fixing stainless steel finish cylindrical keyless (with an emergency opening option from outside) lock of godrej (Product code 9843) with bolt throw 12mm and backset 60 mm or equivalent as per approved make complete in all respect as per direction of Engineer Incharge. (location: Disabled toilet)
Providing and fixing stainless steel finish cylindrical keyed (with three number of keys for each lock) lock of godrej (Product code 5329) with bolt throw 12mm and backset 60 mm or equivalent as per approved make complete in all respect as per direction of Engineer Incharge.
Providing and fixing Stainless Steel (grade 304) floor door stoppers in stainless steel satin finish (Twin) of Dorma(TZ-5000)/Hafele make (article no.937.13.53033 or equivalent as per approved make) make with necessary ss screws etc. or approved equivalent make with necessary S.S screws etc. complete as per direction of Engineer in charge.
Providing and fixing aluminium extruded section body tubular type universal hydraulic door closer (having brand logo with IS : 3564, embossed on the body, door weight upto 36 kg to 80 kg and door width from 701 mm to 1000 mm), with double speed adjustment with necessary accessories and screws etc. complete.
Providing and fixing wooden moulded beading to door and window frame with iron screws, plugs and priming coat on unexposed surface etc. complete.( 2nd class teak wood) 50x20mm or 80x12.5mm as desired
Providing and fixing Toilet cubicles (L-shape) with door, pilaster and divider of 18mm thick CGF category board (compact general purpose flame retardant) both side decorative Thermosetting Synthetic Resin Bonded Compact Laminated Sheets of required colour ,shade and sizes as per approved make and conforming to IS 2046 and BE EN 438(1):1991 including stainless steel accessories ( SS-304 grade) like square top rail. Front panel and divider wall with stripe shoe touching floor with square SS rail (No gap shall be at bottom of divider/front panel except door), knob, thumb turn and indicator, twin coat hook, door stopper, adjustable shoe, gravity hinges, and locking arrangement, SS channel, i/c I shape closing partitions where ever required to complete the cubical etc. as desired etc., all complete as per drawings. The cubical unit shall be installed in approved finish, shades and colours as per specifications and direction of Engineer in charge. Toilet cubicles of size 900mm (width) X 1500mm (depth) X 2100mm (height) with door. External Laminate finish should be of Metallic.
Providing and fixing partition upto ceiling height consisting of G.I. frame and required board, including providing and fixing of frame work made of special section power pressed/ roll form G.I. sheet with zinc coating of 120 gms/sqm(both side inclusive), consisting of floor and ceiling channel 50mm wide having equal flanges of 32 mm and 0.50 mm thick, fixed to the floor and ceiling at the spacing of 610 mm center to center with dash fastener of 12.5 mm dia meter 50 mm length or suitable anchor fastener or metal screws with nylon plugs and the studs 48 mm wide having one flange of 34 mm and other flange 36 mm and 0.50 mm thick fixed vertically within flanges of floor and ceiling channel and placed at a spacing of 610mm center to center by 6 mm dia bolts and nuts, including fixing of studs along both ends of partition fixed flush to wall with suitable anchor fastener or metal screws with nylon plugs at spacing of 450 mm centre to centre, and fixing of boards to both side of frame work by 25 mm long dry wall screws on studs, floor and ceiling channels at the spacing of 300 mm centre to centre. . The boards are to be fixed to the frame work with joints staggered to avoid through cracks, M.S. fixing channel of 99 mm width (0.9 mm thick having two flanges of 9.5 mm each) to be provided at the horizontal joints of two boards, fixed to the studs using metal to metal flat head screws, including jointing and finishing to a flush finish with recommended jointing compound, jointing tape, angle beads at corner (25 mm x 25 mm x 0.5 mm), joint finisher and two coats of primer suitable for board as per manufacture's specification and direction of engineer in charge all complete. 75 mm overall thickness full height partition with 12.5 mm thick double skin fire rated gypsum board of approved make conforming to IS: 2095: part I
Supplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked together through their entire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, the cost of providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 -part 1 and M.S. top cover of required thickness for rolling shutters. 80 x 1.20mm M.S. laths with 1.20mm thick top cover
Providing and fixing ball bearing for rolling shutters.
Extra for Providing mechanical device chain and cranks operation for operating rolling shutters exceeding 10 sqm and upto 16.80 sqm in the area
Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. In stringers, treads, landings etc. of stair cases, including use of chequered plate wherever required, all complete
Steel work welded in built up sections/framed work including cutting hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. In gratings, frames, guard bar, ladders, railings, louvers, insert ,brackets, gates etc. and similar works.
Structural steel work in single section, fixed with or without connecting plate, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. (Note: Base plates on top of column, slab etc. shall be measured under this item)
Supply, Providing, Fabricating, Assembling, erecting and placing in position Tubular Structure (terminal building Roof Trusses, MS pipe in RCC Voided slab for elevated road only) consisting of tubular structure made from MS built-up section :- plates confirming to IS 2062 Grade Yst 350,Tubular Structure:- made from Steel hollow sections, conforming to IS 1161/4923, Grade Yst 310, thickness upto 10mm ) in the profile shape as per drawings with special plate connector, pinion joints, Plates, hollow sections etc. using water jet 3-D cutting system for obtaining smooth 3-dimensional curvature with special plate connector, pinion joints, Plates, hollow sections etc. using SAW/MMAW/MIG welding process with special plate connectors, pinion joints, plates,nuts and bolts, hollow sections etc. and including transportation, cutting , threading, machining, leads and lifts upto all heights, tools and plants and necessary scaffolding etc. required for all operations involved to complete this work as per approved drawings. The tubular structure system with plate connectors, pinion joints, nuts and bolts etc. is to be provided. The complete structure shall be painted with epoxy primer of 75 micron DFT (low VOC i.e. less than 250 gm/ltr), intermediate coat with micaceous iron oxide of 100 micron DFT and finishing coat with two components high Gloss Acrylic Polyurethane Finish Paint of 75 micron DFT(low VOC i.e. less than 250 gm/ltr) on steel work at all locations prepared by sand blasting and applied with airless spray in required DFT (dry film thickness) for each coat as per technical specifications and direction of Engineer-in-Charge. The structural drawings shall be provided by AAI; however the contractor has to prepare shop drawings which have to be approved by Engineer-in-charge/PMC before start of work. The cost includes supplying, fabricating, erecting of structure including welding, sand blasting, scaffolding, cost of primer, intermediate coat and polyurethane paint application etc. complete. (Please note that rate is inclusive of erection by cranes/ scaffolding or by any other means complete in all respects.)
Supply, Providing ,Fabricating, Assembling , erecting and placing in position Tubular Structure (All Facade frame work, Aerobridge structure, electromechanical services supporting structure, walkways, Runner, Purlin of terminal building roof truss etc. or similar work) consisting of tubular structure made from MS built-up section :- rolled steel section & plates confirming to IS 2062 Grade Yst 350,Tubular Structure:- made from Steel hollow sections, conforming to IS 1161/4923, Grade Yst 310, thickness upto 10mm ) in the profile shape as per drawings with special plate connector, pinion joints, Plates, hollow sections etc. using water jet 3-D cutting system for obtaining smooth 3-dimensional curvature with special plate connector, pinion joints, Plates, hollow sections etc. using SAW/MMAW/MIG welding process with special plate connectors, pinion joints, plates,nuts and bolts, hollow sections etc. and including transportation, cutting , threading, machining, leads and lifts upto all heights, tools and plants and necessary scaffolding etc. required for all operations involved to complete this work as per approved drawings. The tubular structure system with plate connectors, pinion joints, nuts and bolts etc. is to be provided. The complete structure shall be painted with epoxy primer of 75 micron DFT (low VOC i.e. less than 250 gm/ltr), intermediate coat with micaceous iron oxide of 100 micron DFT and finishing coat with two components high Gloss Acrylic Polyurethane Finish Paint of 75 micron DFT(low VOC i.e. less than 250 gm/ltr) on steel work at all locations prepared by sand blasting and applied with airless spray in required DFT (dry film thickness) for each coat as per technical specifications and direction of Engineer-in-Charge. The structural drawings shall be provided by AAI; however the contractor has to prepare shop drawings which have to be approved by Engineer-in-charge/PMC before start of work. The cost includes supplying, fabricating, erecting of structure including welding, sand blasting, scaffolding, cost of primer, intermediate coat and polyurethane paint application etc. complete. (Please note that rate is inclusive of erection by cranes(if required)/ scaffolding or by any other means complete in all respects.)
Providing and fixing frame work for partitions/ wall lining etc. made of 50x50x1.6 mm hollow MS tube, placed along the walls, ceiling and floor in a grid pattern with spacing @ 60 cm centre to centre both ways (vertically & horizontally) or at required spacing near opening, with necessary welding at junctions and fixing the frame to wall/ ceiling/ floors with steel dash fasteners of 8 mm dia, 75 mm long bolt, including making provision for opening for doors, windows, electrical conduits, switch boards etc., including providing with two coats of approved steel primer etc. complete, all as per direction of Engineer-in-charge.
Providing and fixing 1mm thick M.S. sheet door with frame of 40x40x6mm angle iron and 3mm M.S. gusset plates at the junction and corners , all necessary fittings complete, including applying a priming coat of approved steel primer. Using M.S angles 40x40x6mm for diagonal braces.
Providing and fixing G.I. chain link fabric fencing of required width in mesh size 50x50 mm including strengthening with 2 mm dia wire or nuts, bolts and washers as required complete as per the direction of Engineer-in-charge. Made of G.I. wire of dia. 4 mm, PVC coated to achieve outer dia not less than 5 mm in required colour and shade
Kota stone slab flooring over 20mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing polishing and groove complete with base of cement mortar 1 : 4 ( 1 cement : 4 coarse sand) : 25 mm thick
Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laid on 12 mm (average) thick cement mortar 1:3 (1 cement 3 coarse sand) and jointed with grey cement slurry mixed with pigment to match the shade of the slabs, including rubbing polishing and groove complete.
Providing and laying full body / homogenous/ double charge heavy duty Vitrified tiles ( Polish / satin Finish/ anti skid/ Matt finish) in floor having water absorption less than 0.5% and confirming to IS:15622 , of approved make, in all colours and shades laid in approved design and pattern over duly cured and dried 15 mm (average) thick correction layer base of cement mortar 1:4 (1 cement: 4 coarse sand) followed by laying and fixing with high polymer modified quick set adhesive Type II IS: 15477,with average 6 mm thickness including grouting of joints of 3 mm width, using epoxy grout mix of 0.70 kg of organic coated filler of desired shade (0.10 kg of hardener and 0.20 kg of resin per kg), including filling / grouting and finishing complete as per direction of Engineer-in-charge. Size of Tile 600 x 600 mm x 16mm thick
Providing and laying Ceramic glazed floor tiles of size 300x300 mm (thickness to be specified by the manufacturer) of 1st quality conforming to IS : 15622 of approved make in colours such as White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement :4 Coarse sand), jointing with grey cement slurry @ 3.30kg/sqm including pointing the joints with white cement and matching pigment etc., complete..
Providing and laying full body / homogenous/ double charge heavy duty Vitrified tiles ( Polish / satin Finish/ anti skid/ Mate) in different sizes (thickness to be specified by the manufacturer), with water absorption less than 0.08% and conforming to IS: 15622, of approved brand & manufacturer, in all colours and shade, in skirting, riser of steps, dado , laid with cement based high polymer modified quick set tile adhesive (water based) conforming to Type II IS: 15477, in average 6 mm thickness, including grouting of joints including pointing in white cement mixed with pigment of matching shade complete. Size of Tile 600mm x 600mm / 400mm x 800mm
Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete.
Providing and laying tactile tile (for vision impaired persons as per standards) of size 300x300x9.8mm having water absorption less than 0.5% and conforming to IS: 15622, of approved make in all colours and shades in outdoor floors such as footpath, court yard, multi modals location etc., laid on 20mm thick base of cement mortar 1:4 (1 cement : 4 coarse sand) in all shapes & patterns including grouting the joints with white cement mixed with matching pigments etc. complete as per direction of Engineer-in-Charge.
Providing and fixing 18mm thick gangsaw cut mirror polished (premoulded and prepolished) machine cut for kitchen platforms, vanity counters ,window sills , facias and similar locations of required size of approved shade, colour and texture laid over 20mm thick base cement mortar 1:4 (1 cement : 4 coarse sand) with joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edge to give high gloss finish etc. complete at all levels.. Granite of any colour and shade (Area of slab over 0.50 sqm)
Extra for providing opening of required size & shape for wash basin/ kitchen sink in kitchen platform, vanity counter and similar location in marble/ granite work including necessary holes for pillar tabs etc. including moulding, rubbing & polishing of cut edges etc. complete
Providing and laying polythene sheet (white in colour) of thickness 400 micron conforming to IS: 2508, on the PCC with overlaps of not less than 300mm longitudinally and 300mm transversely over and including a base layer of 6mm thick fine sand/M-Sand complete as per specifications and as directed by Engineer‐in-charge (Note- Only plan area shall be measured for payment) (Note: This item shall be used under granite flooring on ground floor(without any RCC slab) Item no 77 & 78 and Item no 354)
Providing and laying 25 mm thick factory cut mirror polished ( pre-polished) superior granite stone tile in flooring of shade Imperial white or White pearl from Tamilnadu or Rajasthan in required design and patterns, in linear as well as curvilinear portions of the building, all complete as per the architectural drawings with tile of size 800mm x 800mm of approved shade, color and texture duly factory treated with water proof penetrating shield treatment on bottom surface and four sides of the granite stone tile with two or more coats. The treatment shall be carried out as per manufacturer's specification. The tiles shall be supplied to site in packed condition in wooden boxes and laid in approved design and pattern over duly cured and dried 15 mm (average) thick correction layer base of cement mortar 1:4 (1 cement: 4 coarse sand) followed by laying and fixing with white colour stone adhesive of category C2 TE (minimum) in compliance with ISO 13007-1 EN 12004/12002 with average 6mm thickness and jointed with 3 mm width, using epoxy grout mix of 0.70 kg of organic coated filler of desired shade (0.10 kg of hardener and 0.20 kg of resin per kg), including making provisions of expansion joints, rubbing and curing etc. complete at all levels.(As per approved samples available at AAI offices at Delhi ) After completion of all activities flooring shall be cover with polyethylene sheet of minimum 200 micron and 10 mm thick plaster of Paris to avoid damage to flooring during other works. At final stage of building work POP & Polythene sheet shall be removed and final cleaning and buffing if any shall be completed to the satisfaction of Engineer-In-Charge. Note :- (i)The process includes cost of granite stone tile including cutting& wastage due to design and patterns in linear as well as curvilinear pattern as per architectural drawings,Pre- polishing, laying with mortar, drying,adhesive , fixing, treatment with Water Proof Penetrating Shield Treatment, grouting joints with epoxy grout ,spacers & covering top surface after all treatment with POP & Polythene sheet etc. and removal of same and thereafter cleaning buffing etc. complete. (ii) At site no cutting/grinding of granite tile is permitted. Edges of the slabs shall be true, square and free from chippings and the surface shall be true and plane otherwise tile shall be rejected and nothing extra shall be payable.
Providing and laying 25 mm thick factory cut mirror polished ( pre-polished) superior granite stone tile in flooring of shade chocolate mahogany or similar dark shade in required design and patterns, in linear as well as curvilinear portions of the building, all complete as per the architectural drawings with tile of size 800mm x 800mm of approved shade, color and texture The tiles shall be supplied to site in packed condition in wooden boxes and laid in approved design and pattern over duly cured and dried 15 mm (average) thick correction layer base of cement mortar 1:4 (1 cement: 4 coarse sand) followed by laying and fixing with white colour stone adhesive of category C2 TE (minimum) in compliance with ISO 13007-1 EN 12004/12002 with average 6mm thickness and jointed with 3 mm width, using epoxy grout mix of 0.70 kg of organic coated filler of desired shade (0.10 kg of hardener and 0.20 kg of resin per kg), including making provisions of expansion joints, rubbing and curing etc. complete at all levels.(As per approved samples available at AAI offices at Delhi ) After completion of all activities flooring shall be cover with polyethylene sheet of minimum 200 micron and 10 mm thick plaster of Paris to avoid damage to flooring during other works. At final stage of building work POP & Polythene sheet shall be removed and final cleaning and buffing if any shall be completed to the satisfaction of Engineer-In-Charge. Note :- (i)The process includes cost of granite stone tile including cutting& wastage due to design and patterns in linear as well as curvilinear pattern as per architectural drawings,Pre- polishing, laying with mortar, drying,adhesive , fixing, grouting joints with epoxy grout ,spacers & covering top surface after all treatment with POP & Polythene sheet etc. and removal of same and thereafter cleaning buffing etc. complete. (ii) At site no cutting/grinding of granite tile is permitted. Edges of the slabs shall be true, square and free from chippings and the surface shall be true and plane otherwise tile shall be rejected and nothing extra shall be payable.
Providing and laying 18 mm thick gang saw cut mirror polished ( prepolished) superior granite stone in risers, steps, skirting, dado, wall cladding, column cladding etc. machine cut in required size, with all four edges 1/4 chamfered and mirror polished, approved shades, colour, texture laid over 15mm thick base cement mortar 1:3 (1 cement : 3 coarse sand followed by laying and fixing with white colour stone adhesive of category C2 TE (minimum) in compliance with ISO 13007-1 EN 12004/12002 with average 6mm thickness including rubbing and curing etc. complete at all levels.(As per approved samples available at AAI offices at Delhi ) Note :- The process includes cost of granite stone (cutting/wastage/ Pre- polishing/ laying with mortar/ drying/ adhesive / fixing/ treatment with Water Proof Penetrating Shield Treatment, cleaning buffing etc. complete
Providing and laying Polished Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the staircase treads in single length and landings, all complete as per the architectural drawings, with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand), laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade, including rubbing, curing and polishing and edge moulding with mirror polished etc. all complete as specified and as directed by the Engineer-in-Charge. Polished Granite stone slab jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent.
Extra over and above of Item no 77 & 78 for Leathered finishing of polished granite stone as per approved by Engineer in charge., complete at all levels to complete satisfaction of Engineer-In-Charge.
Providing & fixing in position Phenol bonded Bamboo wood flooring with planks of sizes 14mm thick, 1800mm length (minimum) and 130 mm wide(minimum), in approved colour, texture and finish, having Performance Appraisal Certificate (PAC) issued by Building Materials & Technology Promotion Council (BMTPC). The flooring shall be fixed with tongue and groove interlocking system, with underlayment of 4mm thick expanded poly ethylene foam sheets having density 40kg/cum, over prepared surface with necessary quarter round planks of size 1900mm x 18mm and door reducer of size 1900mm x 44mm, wherever required. The bomboowood planks shall have minimum density of 1000 Kg/cum & minimum Hardness 1000 Kgf. with Eco friendly UV coating, all complete as per direction of Engineer in-charge.
Providing & fixing in position Phenol bonded Bamboo wood in wall skirting with planks of sizes 14mm thick, 1900mm length (minimum) and 85mm wide(minimum), in approved colour, texture and finish, having Performance Appraisal Certificate (PAC) issued by Building Materials & Technology Promotion Council (BMTPC). The skirting shall be fixed with SS screws & rawl plugs, over underlayment of 4mm thick, expanded poly ethylene foam sheets having 40kg/cum density over prepared surface. The bomboowood planks shall have minimum density of 1000 Kg/cum & minimum Hardness 1000 Kgf. with Eco friendly UV coating, all complete as per direction of Engineer in-charge.
Providing and fixing at all height false ceiling of 4mm thick phenol bonded Bamboo Mat board (595x595mm) conforming to 15:13958-1994 including providing and fixing of frame work made of GI angle 25x25x0.4 mm thick all around suitably fixed to wall with the help of dash fastener and hanger frame (600x600 c/c) made GI slotted Tee having powder coating on bottom side (30x25x0.3 mm thick for main member & 25x25x0 .3 mm for cross member) connected to ceiling with 2.64mm GI wire and anchor fastener at every junction and also including cost of making openings for light fittings, grills, diffusers, cut outs made with frame of perimeter channels suitably fixed all complete as per direction of Engineer-in-charge.
Providing and laying 9mm thick resinous matrix seamless terrazzo flooring trowel finish with maximum variation 10 mm in 3meter over base concrete of 40 mm thickness of grade M 25, in all design and patterns as per drawing at all floor levels with Joint edge and termination strips , accessories like divider strips, control- and expansion-joint strips, base and border strips, abrasive strips, moisture barrier layer etc. and rubbing of the poured in place terrazzo surface by using high speed terrazzo grinders with rubbing plugs in 8 stages including filling up Pin holes appearing must be thoroughly cleaned immediately and filled during this process. The work shall be executed as per manufacture specification and to the complete satisfaction of Engineer-In-Charge.
Providing and laying in position 6mm wide expansion joint in granite flooring with stainless steel angle of grade 304 and size 50 X 10 mm and 1.0 mm thick at positions with exposed edge bullnosed as shown in drawing and fixing angle on concrete surface by 40mm long Stainless steel screws at every 450mm and filling Joints of size 4 mm wide and 10 mm deep over 5 mm dia baker/ armour rod with Polysulphide sealant of approved make conforming to BS-5212- 990 or IS: 11433-1995 , as per manufacturer’s specifications including filling the remaining portion with 4mm thick expansion joint filler board of approved brand of Dawn colour between expansion joints, using specifically extruded high performance sheet minimum density 28 kg per cum and compression strength 0.21 Kg./Sqm when tested as per ASTM D-3575 ,preparing the surface and applying masking tape along the edge of joint to prevent accidental spillage of sealant on top surface and removing the masking tape after application of sealant etc. complete as per direction of Engineer in- Charge [Note: For purpose of payment, quantity (Length x Width x Depth) of Polysulphide sealant only will be measured. SS angle shall be paid under item no 115)
Designing ,supply, fabrication, erection and installation of on-site single length color coated( in different colours shade) Standing Seam profile, double architectural insulated standing seam steel roofing system in seven layers as detailed in technical specification. The roofing system will be designed, and installed to withstand the wind pressure at Trichy in confirmation to relevant IS codes with adequate factor of safety, expansion and contraction forces resulting from an atmospheric temperature range 5 to 60 degrees Celsius. The thermal & acoustic performance shall meet the following criteria and shall be tested by independent testing facilities to the required standards or equivalent standards. The complete roofing system will meet the required thermal performance of maximum 0.261 W/m2K. Airborne Sound Transmission loss of the Galvalume /Zincalume steel shall be tested to ASTM E90-97 or equivalent approved standards and shall achieve a Sound Transmission Class (STC) of at least 39 ±3 db. The supplier and applicator shall have the necessary ISO 9001:2000, 14001:2004 &OHSAS 18001 certification. The insulation material should conform to ECBC /GRIHA recommendation. The entire Double skin roofing system is installed over the structure purlin. The measurement shall be based on finished/covered surface area. The contractor shall prepare the shop drawings based on the drawings supplied by the Engineer-in-charge for approval. (Item includes designing ,supplying, installation and fixing of profiled metal sheeting in seven layers including cost of top layer ,system accessories insulation, vapour barrier, 12mm cement board ,liner sheet, fasteners, gaskets, brackets screws rivets, sealants, inner closure fillers, fixtures, all machineries, testing charges etc. any other incidental item required to execute the work as per technical specifications and all taxes but excluding GST complete.). (Note: Flashing including fixing with all accessories etc. shall be paid separately under item no 89).
Designing, Supplying, installation and fixing of ZINC Titanium cladding SYSTEM with panels of 300 mm Centre to Centre width,panel made from Quartz pre weathered zinc titanium alloy conforming to EN 988 Specifications of the following layers: Top Layer: ZINC titanium Interlocking panels roof cladding tiles system in Quartz Aspect (thickness: :1.0 mm ) of 300 mm wide X up to 2000 mm length or in other sizes as per drawing ,in cassette form with 24mm fold on all four sides interlocking roof cladding panels fixed on double skin roof, at all heights. Interlocking panels are rainscreen system with available pan width of panels of 300 mm Centre to Centre (Max). Second Layer : 50 mm X 38 mm x 2 mm aluminium extruded tubular sections as per the architectural drawings and approved shop drawings , the aluminum quality shall be as per grade 6063 T5 or T6 as per BS 1474,including super durable powder coating of 60-80 microns conforming to AAMA 2604 of required colour and shade ,installed over the existing standing seam roof with special clips @ 04 nos in one panel of zinc cladding. These Special clips shall be made from the aluminium quality as per grade 6063 T5 or T6 as per BS 1474 and shall be specially designed and developed to suit roof profiles. The clips shall be tested for the wind uplift forces with safe design factors based on wind pressure in Trichy. Zinc Interlocking panels shall be fixed over the aluminium box section substructure using stainless screws All fasteners shall be of austenitic stainless steel 304 series or higher in order to prevent corrosion / galvanic action with the components fastened. Rates includes Designing, Supplying, installation and fixing of profiled zinc panels including specially designed clips and all accessories at all height as per approved design, technical specifications and shop drawings
Supply and fixing of 0.65 mm thick ( TCT) G 300 grade flashing in roofing system under Item no 87 in desired colours required as per detailed drawings / required size and specification including all formation, sealants accessories complete in all respect as per direction of Engineer in charge.
Supplying & Fixing of fall protection system of make Checkmate,Latchways, Capital safety, Honeywell, Kalzip over standing seam profile roof system with a seam to seam distance of 400 mm as per EN 795 Type C:2012 and TS 16415 with roof anchorage posts suitable for standing seam roof and fall protection equipment (PPE) as required, including supporting equipment such as Ladder/Elevated Works Platform (EWP) /Lifting tool/Scaffolding etc. as per Technical Specifications. The system shall be capable of taking load of minimum 3 users at a time(300 kg minimum). Six (06) Nos. Self-Rescue Device (SSD) system shall also provide along with the system. The complete system shall be planned, designed and fixed at site to cater all along the roof periphery of the roof etc., complete all, as per the direction of Engineer-in-charge and 5084 treated aluminium alloys. All complete as per direction of Engineer In charge.
Supplying & fixing of safe Walkway system of make Checkmate,Latchways, Capital safety, Honeywell, Kalzip for safe walking over the roof on standing seam profile roof system with a seam to seam distance of 400 mm. The Walkways are to be made in FRP/uPVC with aluminium accessories, SS nut-bolts and fasteners. The system must confirm BS EN 516: 2016. The rate includes supporting equipment such as Ladder/Elevated Works Platform (EWP) /Lifting tool/Scaffolding etc. and as per Technical Specifications. The walkways system shall be manufactured from FRP Pultruded Grating/uPVC. The complete system shall be planned, designed and fixed at site to cater all along the roof periphery like exhaust fan, louvers, skylights and gutters of the roof etc., complete all, as per the direction of Engineer-in charge.
Supplying & fixing of safe STEP Walkway system of make Checkmate,Latchways, Capital safety, Honeywell, Kalzip. The Adjustable steps are made in uncoated cast aluminium alloy AA 231/UPVC. The system consists of progressively adjustable 2 aluminium brackets. Size – 460mm x 250mm and thickness of aluminium tread is minimum 4mm. Minimum Angle Adjustment of brackets – 0 to 45 degrees. The system to be tested and certified to EN 516 and by BIA. The rate is including supporting equipment such as ladder/elevated works platform (EWP) /Lifting tool/Scaffolding etc. and as per Technical Specifications. The complete system shall be planned, designed and fixed at site to cater all along the roof periphery like exhaust fan, louvers, skylights and gutters of the roof etc. complete all, as per the direction of Engineer-in charge.
Supply and fixing of Roof Hatch (NYSTROM/BABENKO/BILCO/Checkmate Make) or equivalent of Aluminium Mill Finish .The specification are as under: Leaf – Single Leaf Opening Size – 914 x 914 mm Material – Aluminium Cover & Frame in 2.5mm thick Cover – Hollow 25mm, concealed with Fibreglass insulation, fully welded at all corners, internally reinforced for 40 psf live load Curb – Height 305mm with integral cap flashing, 25mm Fibre Board Insulation, fully welded at all corners, mounting flange for securing hatch to roof. EPDM Gasket – EPDM gasket fixed to the cover. Hinge – Heavy duty Pintle Hinge with SS-316. Hinge – Heavy duty Pintle Hinge with SS-316.
Providing and fixing 1.2mm thick TCT colour coated galvanized steel having minimum 240-245MPa yield strength as per IS 513 with a crest height of 44 to 51 at a pitch distance of 130 to 316mm c/c having a cover width of 760 to 960mm. The galvanization shall be minimum 275 gm per sqm as per IS 277 with colour coating of polyester quality paint of 20 microns over the primer coat of 5 microns on the exposed side and 5 microns alkyde coat over 5 microns primer coat on the inner side/ hot dipped zinc coating of 275 gm/sqm on both sides confirming to AS 1397 and BS EN 10147:2000 complete the job with all respect as desired and as per the direction of Engineer-in charge.
Providing and fixing precoated galvanized iron profile sheets (size, shape and pitch of corrugation as approved by Engineer-in-charge)0.50 mm (+ 0.05 %) total coated thickness with zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns. Sheet should have protective guard film of 25 microns minimum to avoid scratches during transportation and should be supplied in single length upto 12 metre or as desired by Engineering- charge. The sheet shall be fixed using self drilling /self tapping screws of size (5.5x 55 mm) with EPDM seal, complete upto any pitch in horizontal/ vertical or curved surfaces, excluding the cost of purlins, rafters and trusses and including cutting to size and shapen wherever required.
Providing and fixing GI Clip in Metal Ceiling System of 600x600/ 600x1200 mm module in profile as per drawing which includes providing and fixing ‘C’ wall angle of size 20x30x20 mm made of 0.5 mm thick pre painted steel along the perimeter of the room with help of nylon sleeves and wooden screws at 300 mm center to centre, suspending the main C carrier of size 10x38x10 mm made of G.I steel 0.7 mm thick from the soffit with help of soffit cleat 37x27x25x1.6 mm, rawl plugs of size 38x12 mm and C carrier suspension clip and main carrier bracket at 1000 mm c/c. Inverted triangle shaped Spring Tee having height of 24 mm and width of 34 mm made of GI steel 0.45 mm thick is then fixed to the main C carrier and in direction perpendicular to it at 600 mm centers with help of suspension brackets. Wherever the main C carrier and spring T have to join, C carrier and spring T connectors have to be used. All sections to be galvanized @ 120 gms/sqm (both side inclusive),fixing with clip in tiles into spring ‘T’ with GI Metal Ceiling Clip in plain Beveled edge global white color tiles of size 600x600/600x1200 and 0.5 mm thick with 25 mm height, made of G I sheet having galvanizing of 100 gms/ sqm (both sides inclusive) and 20% perforation area with 1.8 mm dia holes and having NRC of 0.5, electro statically polyester powder coated of thickness 60 microns (minimum), including factory painted after bending and perforation .
Providing & fixing false ceiling at all height including providing & fixing of framework made of special section, power pressed from M.S. sheets and galvanised with zinc coating of 120 gms/ sqm (both side inclusive) as per IS : 277 and consisting of angle cleat of size 25mm wide x 1.6mm thick with flanges of 27mm and 37mm, at 1200mm c/c, one flange fixed to the ceiling with dash fastener 12.5mm dia x 50mm long with 6mm dia bolts, other flange of cleat fixed to the angle hangers of 25 x10 x0.50mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I channels 45 x15 x 0.90mm running at the spacing of 1200 mm c/c, to which the ceiling section 0.5mm thick bottom wedge of 80mm with tapered flanges of 26 mm each having lips of 10.5mm, at 450mm c/c, shall be fixed in a direction perpendicular to G.I intermediate channel with connecting clip made out of 2.64mm dia x 230mm long G.I wire at every junction, including fixing perimeter channels 0.50mm thick 27mm high having flanges of 20mm and 30mm long, the perimeter of ceiling fixed to wall/partitions with the help of Rawl plugs at 450mm centre, with 25mm long dry wall screws @ 230mm interval, including fixing of Calcium Silicate Board to ceiling section and perimeter channels with the help of dry wall screws of size 3.5 x25mm at 230mm c/c, including jointing & finishing to a flush finish of tapered and square edges of the board with recommended jointing compounds, jointing tapes,finishing with jointing compounds in three layers covering up to 150mm on both sides of joints and two coats of primer suitable for boards, all as per manufacture's specification and also including the cost of making opening for light fittings, grills, diffusers, cut outs made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer in charge but excluding the cost of painting with:8 mm thick Calcium Silicate Board made with Calcareous & Siliceous materials reinforced with cellulose fiber manufactured through autoclaving process.
Providing and Fixing 15 mm thick densified tegular edged eco friendly light weight calcium silicate false ceiling tiles of approved texture of size 595 x 595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanised steel sections (galvanising @ 120 grams per sqm including both side) consisting of main ‘T’ runner suitably spaced at joints to get required length and of size 24x38 mm made from 0.33 mm thick (minimum) sheet, spaced 1200 mm centre to centre, and cross “T” of size 24x28 mm made out of 0.33 mm (Minimum) sheet, 1200 mm long spaced between main’T’ at 600 mm centre to centre to form a grid of 1200x600 mm and secondary cross ‘T’ of length 600 mm and size 24 x28 mm made of 0.33 mm thick (Minimum) sheet to be inter locked at middle of the 1200x 600 mm panel to from grid of size 600x600 mm, resting on periphery walls /partitions on a Perimeter wall angle pre-coated steel of size(24x24X3000 mm made of 0.40 mm thick (minimum) sheet with the help of rawl plugs at 450 mm centre to centre with 25 mm long dry wall screws @ 230 mm interval and laying 15 mm thick densified edges calcium silicate ceiling tiles of approved texture in the grid, including, cutting/ making opening“for services like diffusers, grills, light fittings, fixtures, smoke detectors etc., wherever required. Main ‘T’ runners to be suspended from ceiling using G.I. slotted cleats of size 25x35x1.6 mm fixed to ceiling with 12.5 mm dia and 50 mm long dash fasteners, 4 mm G.I. adjustable rods with galvanised steel level clips of size 85 x 30 x 0.8 mm, spaced at 1200 mm centre to centre along main ‘T’, bottom exposed with 24 mm of all Tsections shall be pre-painted with polyester baked paint, for all heights, as per specifications, drawings and as directed by Engineer-in-Charge.Note :- Only calcium silicate false ceiling area will be measured from wall to wall. No deduction shall be made for exposed frames/opening (cut outs) having area less than 0.30 sqm.The calcium silicate ceiling tile shall have NRC value of 0.50 (Minimum), light reflection > 85%, non- combustible as per B.S. 476 part IV, 100%humidity resistance and also having thermal conductivity <0.043 w/mK.
Providing and fixing U Baffle Aluminum panel ceiling as per approved make of approved RAL Colour finish consisting of panel size 200 mm deep X 50 mm width with closed ends using minimum 0.7 mm thick aluminum and 360 mm centre to centre as per drawings enclosed , Pure Polyester Powder Coated, Aluminum alloy AA 3105 (Al. Mg) for higher strength . Panels shall be connected using friction grip upper and lower bracket on a special carrier of 30 mm wide x 30 mm high x 2 mm thick powder coated GI member as approved colour to form as cassette based on the module of 360c/c or as per manufacturer specifications, which shall be downward accessible with a torsion springs/ or special bolted bracket hanger system in group of panel or as desired. Main Runners: All vertical baffles are attached to factory punched 30x30x2.0mm thick black Powder coated G.I member with the special baffle hangers/springs to form a module of 360mm C/C. Baffle ceiling panels according to EN 13964 and quality standards of Green pro certification /TAIM e.V.: latest version Cross Runners: 30 mm wide x 30 mm high x 2 mm thick powder coated GI member as approved colour designed to interlock baffle section on designated spacing are spaced at 1200mm Centre maximum. Suspension System : The complete frame to be suspended using special bracket with M6 threaded rod as desired length or as per detailed drawings. Paint Finish: All baffles to be Pure Polyester Powder Coated as confirmed/approved by Engineer-in-charge. The panels shall be fixed to pre installed structural M.S.frame/ RCC work at all levels including all accessories like Fasteners, Hangers, screws, washers, etc. at site complete with all respect as desired . conforming to specifications and directions of Engineer-in-Charge .Contractor shall provide 10 years guarantee for entire system including material and Pure Polyester Powder Coating. The Items includes supplying, Installation and fixing of U Baffle Aluminum panel ceiling over MS structural frame / RCC work, Labours, Scaffolding all required machineries for fixing, tools, Fasteners, Hangers, screws, washers etc. complete in all respect as desired and to the satisfaction of Engineer In Charge ( M.S. structure / frame work shall be paid separately under item no 60 ).
Providing and applying 12 mm thick (average) premixed formulated one coat gypsum lightweight plaster having additives and light weight aggregates as vermiculite/ perlite respectively conforming to IS: 2547 (Part - 1 & II) 1976, applied on hacked / uneven background such as bare brick/ block/ RCC work on walls & ceiling at all floors and locations, finished in smooth line and level etc. complete.
12 mm cement plaster finished with a floating coat of neat cement : 1:3 (1 cement : 3 fine sand)
Distempering with 1st quality acrylic distemper (ready mixed) of approved manufacturer, of required shade and colour complete, as per manufacturer's specification. Two or more coats on new work
Painting with synthetic enamel paint ,having VOC (Volatile Organic Compound) content less than 150 gms/litre, of approved brand and manufacture, including applying additional coats wherever required to achieve even shade colour. Two or more coats on new work
Providing and finishing walls at all heights with textured exterior finish of following specifications: i) One coat of priming coat of exterior primer @ 2.20 lit per 10 Sqm. ii) Application of 2mm thick Texture materials of approved pattern/finish having a minimum specific gravity of 1.9kg / liter , solid contents in the range of 82-85%. iii) Final coats (Two or more) of Exterior paint as approved and shade @3.28 liters/10sqm.all complete as per specifications and directions of Engineer-In-Charge.
Wall painting with premium acrylic emulsion paint of interior grade having VOC ( Volatile Organic Compound ) content less than 50grams/litre of approved brand and manufacturer, including applying additional coats wherever required to achieve even shade colour. Two or more coats on new work
Applying priming coats with primer of approved brand and manufacture, having low VOC ( Volatile Organic Compound) content with water thinnable cement primer on wall surface having VOC content less than 50grames/ litre.
Providing and fixing aluminum work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. aluminum sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, aluminum snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately): For fixed portion Polyester powder coated aluminum (minimum thickness of polyester powder coating 50 micron). (Note: One sample of each section shall be tested for every 5000 kg or part thereof for confirmation to IS: 733 and IS: 1285 (ii) Polyester powder coating shall be tested for every 5000 kg or part thereof for confirmation to minimum requirement of 50 micron.)
Providing and fixing aluminum work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. aluminum sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, aluminum snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately): For Openable portion For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket required (Fittings shall be paid for separately). Polyester powder coated aluminum (minimum thickness of polyester powder coating 50 micron). (Note: One sample of each section shall be tested for every 5000 kg or part thereof for confirmation to IS: 733 and IS: 1285 (ii) Polyester powder coating shall be tested for every 5000 kg or part thereof for confirmation to minimum requirement of 50 micron.)
Providing and fixing glazing in aluminum door, window, ventilator shutters and partitions etc. with PVC/neoprene gasket, aluminum snap beading, aluminum channel etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminum snap beading, channel shall be paid in basic item) With float glass panes of 5.50/6.0 mm thick .
Providing and supplying aluminum extruded tubular and other aluminum sections as per the architectural drawings and approved shop drawings , the aluminum quality as per grade 6063 T5 or T6 as per BS 1474,including super durable powder coating of 60-80 microns conforming to AAMA 2604 of required colour and shade as approved by the Engineer-in-Charge. (The item includes cost of material such as cleats, sleeves, screws etc. necessary for fabrication of extruded aluminum frame work. Nothing extra shall be paid on this account). (Note: One sample of each section shall be tested for every 5000 kg or part thereof for confirmation to aluminum quality as per grade 6063 T5 or T6 as per BS 1474 (ii) Super durable powder coating shall be tested for every 5000 kg or part thereof for confirmation to minimum requirement of 60-80 microns conforming to AAMA 2604.)
Designing, fabricating, testing, protection, installing and fixing in position Fully Unitized Curtain Wall Four sided Structural glazed system (with open joints) to withstand the Design wind pressure of 2Kpa confirming to IS-875 part-III. The curtain wall system must pass the Proof test of 1.5 times the design wind pressure without any failure. Contractor shall provide a water tight structural glazing having all the performance characteristics etc. all complete as required, as per the Architectural drawings, as per item description, as specified, as per the approved shop drawings and as directed by the Engineer-in-Charge. The system should accommodate 37.52mm DGU in vision areas (refer glazing specification mentioned as a separate BOQ item). The work shall be executed as per technical specifications and to complete satisfaction of Engineer-In-Charge.(Note :Vision panel and aluminum extruded tubular and other aluminum sections shall be paid separately under Item no 112 and 110 respectively)
Providing, assembling and supplying vision panel units of size and shape as required and specified 36.89 mm thick Laminated Insulated glass unit comprising of 12.89mm thick Heat Strengthened (HS) Laminated Outerlite (6mm thick Clear Heat Strengthened glass + 0.89 SGP + 6mm thick Heat Strengthened Performance glass) + 16mm Air Space Gap + 8mm Thick Clear Heat Soaked toughened Innerlite glass including primary seal and secondary seal (structural silicone sealant) etc. all complete for the required performances as detailed herein under, as per the Architectural drawings, as per the approved shop drawings, as specified and as directed by the Engineer-in-Charge. The IGUs shall be assembled in the factory/ workshop of the glass processor. “(Payment for fixing of IGU Panels in the curtain glazing is included item No 111). “For payment of vision glass panel, only the actual area of glass on face # 1 of the glass panels (excluding the areas of the grooves and weather silicone sealant), shall be measured in sqm. Glass Performance & Shade : Blue, Green, bronze, gold, clear substrate. Visual light Transmission (VLT) :38%(Minimum) External reflection : 10-20% Internal reflection: 10-15% Solar Heat Gain Coefficient (SHGC) : 0.22(Maximum) U value : 1.5 (W/M²K) (Maximum)
Providing and fixing Aluminum composite panel cladding around the columns including circular columns, dead walls, edges of roofs, under side of ceiling, facia as per technical data at all heights. Aluminum composite panel shall be of approved makes and shades (inclusive of 20% Quantity for stainless steel brushshade) made out of 4mm thick aluminum composite panel comprising of Aluminum Skin of Minimum 0.5mm of 5005 Alloy with KYNAR 500/Hylar 5000 PVDF based fluorocarbon resin and Lead free Coating of approved finish +3mm thick noncombustible mineral based polymer core compliance to A2, s1, d0 As per En13501-1, ASTM E119 and NBC Guidelines 2016 +0.5mm aluminum skin of 5005 Alloy with service coat bond with either Sandwich or co extrusion process. Overall weight of the panel shall not be less than 8 kg per sqm as specified using stainless steel screws, nuts, bolts, washers, cleats, weather silicone non streaking sealant, backer rods etc. The Aluminum frame work behind ACP panel shall consists of rectangular tube 2mm thick 38 mm X 50 mm as main frame, shall be fixed to existing RCC/MS structure with 5 mm MS galvanized brackets @ 600 mm C/C bothways. Nylon separators to prevent bi-metallic contacts all complete required to be provided. The Contractor shall provide aluminium composite panel cladding, having all the performance characteristics all complete , as per the Architectural drawings, as per Item description, as specified, as per the approved shop drawings and as directed by the Engineer-in-Charge. However, for the purpose of payment, only the actual area on the external face of the curtain wall with Aluminum Composite Panel Cladding (including width of groove) shall be measured in sqm up to two decimal places. Alumimum frame work behind ACP panel wall shall be paid separately under item no 107).
Providing and fixing stainless steel ( Grade 304) railing ,fender,bollords or any other item made of Hollow tubes, channels, angle ,plates etc., including , grinding, buffing, polishing and making curvature (wherever required) , making necessary arrangement for fixing of glass of 13.52 thickness and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per drawings and approval of Engineer-in-charge, (for payment purpose only weight of stainless steel members ( lowest of actual and standard weight) shall be considered excluding fixing accessories such as fasteners etc.), (Note : (i) Please note that no site welding of SS pipes will be allowed and longitudinal joints shall be made by arrangement of internal SS sleeves, in vertical pipes no joints are permitted) (ii) Rate includes preparation and submission of shop drawings by contractor. work shall be executed on the basis of approved shop drawings, nothing extra shall be payable for shop drawings. (iv) ( One sample of each section shall be tested for every 5000 kg or part thereof for confirmation to SS grade 304 )
Providing and fixing 12 mm thick frameless toughened glass door shutter of approved brand and manufacture, including providing and fixing top & bottom pivot & spring type fixing arrangement and making necessary holes etc. for fixing required door fittings, all complete as per direction of Engineer-in-charge (Door handle, lock and stopper etc.to be paid separately). Note :Top & bottom pivot & spring type fixing arrangement shall comprise double action hydraulic floor spring of approved brand and manufacture conforming to IS : 6315, having brand logo embossed on the body / plate with double spring mechanism and door weight upto 125 kg, for doors, including cost of cutting floors etc., embedding in floors etc. as required and making good the same matching to the existing floor finishing and cover plates with brass pivot and single piece M.S. sheet outer box with slide plate etc. complete as per the direction of Engineer-in-charge. With stainless steel cover plate minimum 1.25 mm thickness.
Providing and fixing Assa Abloy YEH-01A /DORMA pull Handle TGDI-H 600 or equivalent as per approved make back to back with 500mm c/c, adjustable fixing for glass, wood and metal doors in satin finish stainless steel grade 304. The pull handles should have supporting washer with raised bevelling on the outer surface. Length =600mm, 25mm dia, -SS304 etc. .complete as per direction of Engineer-in-Charge.
Extra for fritting of the glass of partitions, vestibules and façade glazing as per detailed drawing and direction of Engineer in charge.
Supply, Installation, Testing and Commissioning of Approved make Automatic Sliding Door System with clear opening 3000mm x 2400mm supplied with Intelligent Self-learning Micro-Controller Unit, DC Motor with Integrated Electro-mechanical Lock and gear assembly, Step-down transformers and power switch unit, Roller carrier assembly with Safety Anti-rise wheels, Automatic sliding track unit in Aluminium, Stainless Steel Running Track for Rollers, cover profile for track unit in Anodized aluminium finish, Concealed Glass clamping profile with hole preparation ensures positive glass holding, Digital device manager with several built in secured programmable functions which includes user setup modes such as AUTO/EXIT/LOCK/OPEN/MANUAL. Automatic operator activation by standard motion sensor and Safety of pedestrians ensured with Integrated Motion + Safety sensor. Automatic Operator tested as per International standards. Sliding Glass door shall be 11.52 mm thick ( 5mm thick Clear Toughened glass + 1.52mm PVB layer + 5mm thick Clear Toughened glass) with 40 mm wide stainless steel u beading of grade SS 304 with hole preparation to ensure safe and secure positive holding of glass. Price to include supply and installation of Automatic Sliding Door with laminated glass complete in all respect as per manufacture specification and satisfaction to Engineer In charge.
Providing and laying water proofing treatment in sunken portion of WCs, bathroom etc., by applying cement slurry mixed with water proofing cement compound consisting of applying : a) First layer of slurry of cement @ 0.488 kg/sqm mixed with water proofing cement compound @ 0.253 kg/ sqm. This layer will be allowed to air cure for 4 hours. b) Second layer of slurry of cement @ 0.242 kg/sqm mixed with water proofing cement compound @ 0.126 kg/sqm. This layer will be allowed to air cure for 4 hours followed with water curing for 48 hours. The rate includes preparation of surface, treatment and sealing of all joints, corners, junctions of pipes and masonry with polymer mixed slurry :
Providing and laying integral cement based water proofing treatment including preparation of surface as required for treatment of roofs, balconies, terraces etc. consisting of following operations: : a) Applying a slurry coat of neat cement using 2.75 kg/sqm of cement admixed with water proofing compound conforming to IS. 2645 and approved by Engineer-in-charge over the RCC slab including adjoining walls upto 300 mm height including cleaning the surface before treatment. : b) Laying brick bats with mortar using broken bricks/brick bats 25 mm to 115 mm size with 50% of cement mortar 1:5 (1 cement : 5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge over 20 mm thick layer of cement mortar of mix 1:5 (1 cement :5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge to required slope and treating similarly the adjoining walls upto 300 mm height including rounding of junctions of walls and slabs. c) After two days of proper curing applying a second coat of cement slurry using 2.75 kg/ sqm of cement admixed with water proofing compound conforming to IS : 2645 and approved by Engineering-charge. d) Finishing the surface with 20 mm thick joint less cement mortar of mix 1:4 (1 cement :4 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineering-charge including laying glass fibre cloth of approved quality in top layer of plaster and finally finishing the surface with trowel with neat cement slurry and making pattern of 300x300 mm square 3 mm deep. e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test. All above operations to be done in order and as directed and specified by the Engineer-in-Charge : With average thickness of 120 mm and minimum thickness at khurra as 65 mm. Note :- (The incase of any leakage if the injection grouting or any type processes required for stopping of leakage, the same shall be done by the Contractor free of cost with in appropriate time to avoid further damages .If the contractor fails to rectify the defects well in time, the same will be done by AAI at risk and cost of the contractor.
Providing and applying integral crystalline slurry of hydrophilic in nature for waterproofing treatment to the RCC structures like retaining walls of the basement, water tanks, roof slabs, podiums, reservoir, sewage & water treatment plant, tunnels/ subway and bridge deck etc., prepared by mixing in the ratio of 5 : 2 (5 parts integral crystalline slurry : 2 parts water) for vertical surfaces and 3 : 1 (3 parts integral crystalline slurry : 1 part water) for horizontal surfaces and applying the same from negative (internal) side with the help of synthetic fiber brush. The material shall meet the requirements as specified in ACI- 212-3R-2010 i.e. by reducing permeability of concrete by more than 90% compared with control concrete as per DIN 1048 and resistant to 16 bar hydrostatic pressure on negative side. The crystalline slurry shall be capable of self-healing of cracks up to a width of 0.50mm. The work shall be carried out all complete as per specification and the direction of the engineer-in-charge. The product performance shall carry guaranteed for 5 years against any leakage. For vertical surface two coats @0.70 kg per sqm per coat. Note-1 : The product performance shall carry guaranteed for 10 years against any leakage. Note -2:- The All Waterproofing works as above including supply and apply should be carried out by authorized / manufacturer approved applicator.
Providing and applying integral crystalline slurry of hydrophilic in nature for waterproofing treatment to the RCC structures like retaining walls of the basement, Raft slab, epoxy grouting of rock anchoring, water tanks, roof slabs, podiums, reservoir, sewage & water treatment plant, tunnels/ subway and bridge deck etc., prepared by mixing in the ratio of 5 : 2 (5 parts integral crystalline slurry : 2 parts water) for vertical surfaces and 3 : 1 (3 parts integral crystalline slurry : 1 part water) for horizontal surfaces and applying the same from negative (internal) side with the help of synthetic fiber brush. The material shall meet the requirements as specified in ACI- 212-3R-2010 i.e. by reducing permeability of concrete by more than 90% compared with control concrete as per DIN 1048 and resistant to 16 bar hydrostatic pressure on negative side. The crystalline slurry shall be capable of self-healing of cracks up to a width of 0.50mm. The work shall be carried out all complete as per specification and the direction of the engineer-in-charge. The product performance shall carry guaranteed for 10 years against any leakage. For horizontal surface one coat @1.10 kg per sqm. Note-1 : The product performance shall carry guaranteed for 10 years against any leakage. Note -2:- The All Waterproofing works as above including supply and apply should be carried out by authorized / manufacturer approved applicator.
Providing and fixing 6mm thick bevelled edge mirror of superior glass of approved quality and approved make with 12mm thick waterproof plywood backing fixed properly, and with 25mm dia stainless steel stud and 10mm brush finish stainless steel trims machine cut in required size and shape as approved shade colour etc. complete at all levels as per detailed drawings and direction of Engineer in Charge.
Providing & fixing Urinal Modesty Panels made of 12 mm thick VGS category board both side decorative Thermosetting Synthetic Resin Bonded Compact Laminated Sheets of required colour ,shade and sizes as per approved make and conforming to IS 2046 and BE EN 438(1):1991 as per approved make of approved texture/shade having standard dimension of 1200 mm Height x 450 -500 mm Width and should be heat, bacteria, water, chemical, scratch and impact resistant . The product should have Green Guard Certificate, including all accessories as per manufacturer's specifications and direction of Engineer-in-Charge . Modesty panels will be fixed to the wall at an appropriate height from the floor with 304 grade SS right angle bracket, 304 grade SS Screws with satin finish & Wall Plugs . The work includes all accessories, machineries, tools etc., complete as per direction of Engineer-in-charge
Providing and placing in position Check in Counter of size 1000 x 892 x 1200 mm as per approved Drawing , made of 19 mm thick Boiling water proof block board of approved make, with complete exterior finish surface of 12 mm thick solid acrylic in any colour combination and interior finish with 1 mm thick suede/gloss finish laminate of approved colour and pattern with all necessary frames works /stainless steel screws/ SS hinges/telescopic channels for drawers/ handles /locks/bottom support /necessary cutouts /wire manager etc. all complete as per drawing and direction of engineer in charge. The complete work includes construction of frame work with 19mm Boiling water proof block board (BWP) , fixing of solid acrylic with necessary moulding of edges ,fixing of laminate , drawers, shutters and all necessary hardware and placing in position of complete counter inclusive of all taxes but exclusive of GST. Shop drawings to be got approved from Engineer-In-Charge before execution.
Providing and placing in position Information/Boarding gate counter of size 950 x 750 x 1150 mm as per approved drawing made of 19 mm thick Boiling water proof block board of approved make with complete exterior finish surface of 12 mm thick solid acrylic with combination of different colour shade and interior finish with 1 mm thick laminate with all necessary frames works /stainless steel screws/ SS hinges/telescopic channels for drawers/ handles /locks/bottom support /necessary cutouts /wire manager etc. all complete as per drawing and direction of engineer in charge. The complete work includes construction of frame work , fixing of solid acrylic with necessary moulding of edges ,fixing of laminate , drawers, shutters and all necessary hardware and placing in position of complete counter . Shop drawings to be got approved from Engineer-In-Charge before execution.
Providing and placing in position Immigration counter of size 2400 x 1800 x 1300 mm as per approved drawing , made of 19 mm thick Boiling water proof block board of approved make with complete exterior finish surface of 12 mm thick solid acrylic in any other colour combination and interior finish with 1 mm thick laminate in suede /gloss finish of approved colour and pattern with all necessary frames works of block board /stainless steel screws/ SS hinges/telescopic channels for drawers/ handles /locks/bottom support /necessary cutouts /wire manager etc. all complete as per drawing and direction of Engineer In Charge. The complete work includes construction of frame work , fixing of solid acrylic with necessary moulding of edges ,fixing of laminate , drawers, shutters and all necessary hardware and placing in position of complete in all respect as per direction of Engineer-In-Charge. Shop drawings to be got approved from Engineer-In-Charge before execution.
Providing and placing in position Custom Counter of size 1000 x 892 x 1200 mm as per approved Drawing , made of 19 mm thick Boiling water proof block board of approved make with complete exterior finish surface of 12 mm thick solid acrylic in any colour combination and interior finish with 1 mm thick suede/gloss finish laminate of approved colour and pattern with all necessary frames works /stainless steel screws/ SS hinges/telescopic channels for drawers/ handles /locks/bottom support /necessary cutouts /wire manager etc. all complete as per drawing and direction of engineer in charge. The complete work includes construction of frame work with 19mm Boiling water proof block board , fixing of solid acrylic with necessary moulding of edges ,fixing of laminate , drawers, shutters and all necessary hardware and placing in position of complete counter including inclusive of all taxes but exclusive of GST . Shop drawings to be got approved from Engineer-In-Charge before execution.
Providing and placing in position stamping table and pedestal as per approved Drawing , made of 19 mm thick Boiling water proof block board of approved make having stamping table exterior exposed surface finished with 12 mm thick solid acrylic in any approved equivalent colour combination and pedestal sides having 12 mm thick solid acrylic in any colour combination along with 20 mm thick flamed granite of approved color/shade at top of pedestal, all complete as per drawing and directions of Engineer In charge .The rate should be inclusive of making complete frame work all necessary screws , accessories , fixing or solid acrylic necessary moulding of edges of granite , and solid acrylic , flaming of granite with inclusive of all taxes but exclusive of GST . Shop drawings to be got approved from Engineer-In-Charge before execution.
Providing and fixing table for inspection table as per approved drawing near security check of size 1250 x 750 x 800 mm made with19 mm thick Boiling water proof block board of approved make with12 mm thick acrylic solid surface of make in any colour combination on three sides and suitable opening in the fourth side with shutters and shelves as approved by Engineer -In -Charge .The openable shutter of the table in should to be finished with with 1 mm thick laminate of approved colour and pattern. The top of the table to be provided with 20mm thick mirror polish granite of approved shade and color as per approved drawing and directions of Engineer In charge. Shop drawings to be got approved from Engineer-In-Charge before execution.
Providing and placing in position Custom Inspection table of size 2400 x 800 x 600 mm as per approved drawing , made of 19 mm thick Boiling water proof block board of approved make with complete exterior finish surface of 12 mm thick solid acrylic in any colour combination in all sides and top with 20 mm thick mirror polished chocolate mahogany or other similar dark shade granite slab(sample to be approved before fixing) supported on suitable supporting members of wooden battens(2nd class teak) of size 50 mm x 50 mm with chamfering of edges /moulding of granite slab along with bottom 175 mm stainless steel cladding with 18 gauge 304 grade , with all necessary frames works /stainless steel screws/bottom support /wire manager etc. all complete as per drawing and direction of Engineer in Charge. The complete work includes construction of frame work , fixing of solid acrylic with necessary moulding of edges of solid acrylic and granite , and all necessary hardware and placing in position of complete table in all respect as per direction of Engineer-In-Charge.
Providing and fixing concertina coil fencing with punched tape concertina coil 600 mm dia 10 metre openable length ( total length 90 m), having 50 nos rounds per 6 metre length, upto 3 m height of wall with existing angle iron 'Y' shaped placed 2.4 m or 3.00 m apart and with 9 horizontal R.B.T. reinforced barbed wire, stud tied with G.I. staples and G.I. clips to retain horizontal, including necessary bolts or G.I.barbed wire tied to angle iron, all complete as per direction of Engineer-in-charge, with reinforced barbed tape(R.B.T.) / Spring core (2.5mm thick) wire of high tensile strength of 165 kg/ sq.mm with tape (0.52 mm thick) and weight 43.478 gm/ metre (cost of M.S. angle, C.C. blocks shall be paid separately)
Providing and erecting 3.00 metre high temporary barricading at site; each panel of size 2.50mx3.00m made of 40x40x6mm angle iron or 50x50x3mm hollow MS tube posts/horizontal members/bracings covered with 1.63 mm thick MS sheet/pre coated sheets. The sheet shall be fixed with 30x5mm MS flat by suitable welding/riveting. MS channel ISLC 75 @ 5.70 kg/m, 50cm long shall be provided at the bottom having oval shaped holes of size 50x25mm at both ends with 50cm long MS angle 40x40x6mm bracing. Suitable arrangement shall be made to fix the barricading to avoid from overturning by providing 250mm long expansion fasteners at both ends. The work shall be executed as per drawing/direction of Engineer-in-Charge which includes writing and painting with synthetic enamel paint in two or more coats,, arrangement for traffic diversion such as traffic signals during construction at site for day and night glow lamps as per site requirement , reflective signs, marking, flags, caution tape as directed by the Engineer-in-Charge. The barricading provided shall be retained in position at site continuously i/c shifting of barricading from one location to another location as many times as required during the execution of the entire work till its completion. Rate include its maintenance for damages, painting, all incidentals, labour materials, equipment’s and works required to execute the job and shifting as per site requirement. The barricading shall not be removed without prior approval of Engineer-in Charge. (Note: - Onetime payment shall be made for providing barricading from start of work till completion of work i/c shifting as per site requirement. The barricading provided shall remain to be the property of the contractor on completion of the work).
Providing & fixing 1st Quality white vitreous china wall hung type European type water closet with C.P. bolts, nuts, C.I. chair or other hanging arrangement, with white solid plastic seat and cover with lid including concealed slim line low level dual - flushing cistern, including flush pipe Health faucet, CP Brass bib cock, Toilet paper holder , C.P. brass hinge rubber buffers, with accessories,C.I/M.S. brackets painted with two coats of enamel paint of approved shade over a coat of primer (Fixing shall be as per manufacturer's specifications). C.P. brass screws and wooden cleats, including cutting and making good the wall and floors wherever required. a) EWC Make: (Kohler 18131IN-S-0), (Hindware Enigma Slim 92502), (Jaquar : SLS-WHT-6951) b) Cistern Make: (Kohler 77027IN-P-NA + 5413IN-P-CP), (Hindware Concealo), (Jaquar JCS-WHT-2400S) c) Health Faucet Make: (Kohler Cat No:12927IN-CP), (Hindware "F160068"), (Jaquar ALD-CHR-577) d) Bib cock Make: (Kohler Cat No:16093IN-4-CP), (Hindware Contessa F330041), (Jaquar FLR-CHR-5047N) e) Toilet paper holder Make: (Kohler 5633INCP, Jaqur ACNCHR 1153N, CERA F5004110)
Providing and fixing 1st Quality water closet squatting pan (Indian type W.C. pan) with 100 mm sand cast Iron P or S trap, conselled slim line low level dual - flushing cistern, including flush pipe, with all fittings and fixtures including Health faucet, CP Brass bib cock, Toilet Paper holder complete, including cutting and making good the walls and floors wherever required a) White Vitreous china Orissa pattern W.C. pan of size 580x440 mm with integral type foot rests, b) Cistern Make: (Kohler 77027IN-P-NA + 5413IN-P-CP), (Hindware Concealo), (Jaquar JCS-WHT-2400S) C) Bib cock Make: (Kohler Cat No:16093IN-4-CP), (Hindware Contessa F330041), (Jaquar FLR-CHR-5047N) d)Health Faucet Make: (Kohler Cat No:12927IN-CP), (Hindware "F160068"), (Jaquar ALD-CHR-577), e) Toilet paper holder Make: (Kohler 5633INCP, Jaqur ACNCHR 1153N,
Providing and Fixing 32 mm bottle trap for waste connection pipe and sensor faucet for cold water for Wash basin complete including CP brass waste and CP waste pipe in all respects as per direction of the Engineer-In-Charge. a) Bottle trap (Kohler Cat No: 7314IN-CP), (Hindware F850015), (Jaquar ALD CHR-769L300X190) b) Sensor faucet (Kohler Cat No: 18057IN-ND-CP), (Hindware F240001), (Jaquar SNR-CHR-51021)
Providing and fixing 1st Quality white vitreous china battery based infrared sensor operated urinal pre & post flushing with water (250 ml & 500 ml consumption), having water inlet from back side, including fixing to wall with suitable brackets, 40 mm CP Brass bottle trap, CP Brass waste all as per manufacturers specification and direction of Engineer-in-charge. a) Urinal Make: (Kohler Cat No: 5017IN-ER-0), (Hindware Senso art 60018), Jaquar URS-WHT-132530) b) Automatic flushing system for urinal Make: (Kohler 8791T-C01-CP), (Hindware 500964), Jaquar SNR-CHR-51097) c) Bottle trap Make: (Kohler Cat No: 7314IN-CP), (Hindware F850015), (Jaquar ALD CHR-769L300X190)
Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per IS: 13983 with C.I. brackets and stainless steel plug 40 mm,including painting of fitting and braackets, cutting and making good the walls wherever required. kitchen sink with drain board Size 510x1040mm bowl depth 250 mm
Providing and Fixing 15 mm nominal bore CP Brass long body bib cock complete including cutting and making good the walls wherever required Make: (Hindware Immacula F110002), (Jaquar CON-CHR-107KN), (CERA F2006152)
Providing and fixing Strainless Steel (SS) liquid soap dispenser with push lever assembly with soap refill fixed in wall with Screws complete in all respect as per direction of the engineer-in-charge Make: (CERA: F5002111), (Jaquar ACN-CHR-1137N)
Providing and fixing C.P. brass angle valve quarter turn of approved quality conforming to IS:8931 15mm nominal bore Make: (Kohler Cat No: 80154IN-4-CP), (Hindware Cat No: F310003), (Jaquar FLR-CHR-5053N)
Providing and fixing S.S. body tissue paper dispenser complete including cutting and making good the walls wherever required Make: (Jaquar Cat No: PTD SAPDT0106CS)
Providing and Fixing complete system of Bath and shower including CP Single lever concealed divertor, O.H. Rose shower with shower arm, CP Bath spout, Towel rail and concealed stop cock complete including C.P. brass screws and wooden cleats, including cutting and making good the wall and floors wherever required. a) C.P Single lever concealed diverter (CERA F1014702 F4010103), (Hindware Divertor F850090 & F110042), (Jaquar ALD-CHR-065 & FLR-CHR-5065K) b) Over head Rose shower with Shower arm Make: (Kohler 16347IN-CP & 73037T-CL-CP), (Hindware F160039), (Jaquar SHA-CHR-477 & OHS-CHR-1709) c) CP Bath spout Make: (Kohler Cat No: 8160IN-CP), (Hindware Immacula Series F110023), (Jaquar SPJ-CHR-429) d) CP Towel Rail Make: (Kohler K-97495T-CP) , (Jaquar ACN 1111NM), (Cera F5003103) e) CP Brass stop cock 15 mm nominal bore
Providing and Fixing complete sysytem for Handicapt Toilet of Hindwarematrix/ cerara course comparsing of 1st Quality white vitreous china floor mounted European type water closet including exposed cistern, Health faucet, CP Brass bib cock, Toilet paper holder ,Flat Back wash basin with one pair of mounting brackets , complete with fittings and seat cover, two no hinged rail 76 cms and five nos of grab bar 60 cms, including 32 mm bottle trap for waste connection, 15 mm automatic sensor faucet for cold water for Handicaped Toilet complete in all respest as per direction of the engineer-in-charge. (Make: Hindware Matrix, CERA Cruse) Health Faucet Make: (Kohler Cat No:12927IN-CP), (Hindware "F160068"), (Jaquar ALD-CHR-577) Bib cock Make: (Kohler Cat No:16093IN-4-CP), (Hindware Contessa F330041), (Jaquar FLR-CHR-5047N) e) Toilet paper holder Make: (Kohler 5633INCP, Jaqur ACNCHR 1153N, CERA F5004110) Bottle trap (Kohler Cat No: 7314IN-CP), (Hindware F850015), (Jaquar ALD CHR-769L300X190) Sensor faucet Make: (Kohler Cat No: 18057IN-ND-CP), (Hindware F240001), (Jaquar SNR-CHR-51021).
Providing and Fixing straight / offset type flexible single body push fit type WC pan connector with inlet ring and integral single mould sealing fins made of flexible EVA body to be fixed with manufacture supplied grease, including rubber bush / adaptor for use with C.I pipe as supplied with the pan connector complete as directed by Engineer-in-charge Make: (Geberit make)/(Viega make)
Providing and Fixing C.P brass Aerosol perfume dispenser, fixed to wooden cleats / Rawl Plug with C.P brass screws, complete including cutting and making good the walls wherever required Make: (HINDWARE Cat No: AP-B168NIA)
Providing on Fixing 200/400 mm diameter Mild Steel pipes conforming to IS-3589 of thickness 6.3 mm including cutting, welding, nut-bolts, gasket, fitting viz. bends, tees, reducers, crosses, flanges etc. and fixing the pipes on wall / ceiling / beam / floor with suitable MS clamps / structural supports/PCC block and external painting with two coats of red oxide primer and two coats of synthetic enamel paint of approved shade and internal Epoxy coating complete as required and as specified. ( Payment shall be made on the basis of actual weight of pipe or standrand weight as per IS3589, which ever is less For terrace rain water system)
Providing and Fixing soil, waste and vent pipes 100 mm dia Hubless centrifugally cast (spun) iron pipes epoxy coated inside & outside IS:15905
Providing and fixing 100mm dia. M.S. holder-bat clamps of approved design to Sand Cast iron/cast iron (spun) pipe embedded in and including cement concrete blocks 10X10X10cm of 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size) including cost of cutting holes and making good the walls etc.
Providing and fixing bend of required degree with access door, insertion rubber washer 3 mm thick, bolts and nuts complete. 100mm dia Bend of required degree with access door of Hubless centrifugally cast (spun) iron epoxy coated inside & outside as per IS:15905 , insertion rubber washer 3mm thick, bolts and nuts complete
Providing and fixing 100mm dia Plain Bend of required degree for Hubless centrifugally cast (spun) iron pipes epoxy coated inside & outside IS:15905
Providing and fixing single equal plain junction of required degree of Hubless centrifugally cast (spun) iron epoxy coated inside & outside as per IS:15905 :
Providing and Fixing double equal plain junction of 100x100x100x100 mm size of Hubless centrifugally cast (spun) iron pipes epoxy coated inside & outside IS:15905
Providing and fixingdoor piece, insertion rubber washer 3mm thick, bolts & nuts complete. 100mm dia door piece, Sand cast iron S&S as per IS - 3989.
Providing and fixing trap of self cleansing design with screwed down or hinged grating with or without vent arm complete, including cost of cutting and making good the walls and floors. 100 mm inlet and 100 mm outlet. Hubless centrifugally cast (spun) iron epoxy coated inside & outside as per IS:15905
Providing and fixing shielded coupling of Hubless centrifugally cast iron pipe 100 mm dia for SS 304 grade coupling with EPDM rubber gasket
Providing and fixing M.S. stays and clamps for sand cast iron/centrifugally cast (spun) iron pipes of diameter: 100mm
Providing and Fixing 100 mm inlet and 100 mm outlet for Hubless centrifugally cast (spun) iron epoxy coated inside & outside as per IS:15905 trap of self cleansing design with screwed down or hinged grating with or without vent arm complete, including cost of cutting and making good the walls and floors.
Providing and Fixing G.I. Reducing elbow of 100 x 50 mm in cement concrete 1:2:4 at all levels for floor drains (exlcuding cost of grating) for connection to floor traps in sunken portions, complete as per drawings and as per approval of the engineer-in-charge.
Providing and fixing G.I. pipes complete with G.I. fittings and clamps, i/c cutting and making good the walls etc.Internal work - Exposed on wall, 32 mm dia nominal bore
Providing and fixing G.I. pipes complete with G.I. fittings and clamps, i/c cutting and making good the walls etc.Internal work - Exposed on wall, 40 mm dia nominal bore
Providing and fixing G.I. pipes complete with G.I. fittings and clamps, i/c cutting and making good the walls etc.Internal work - Exposed on wall, 50 mm dia nominal bore
Painting of 32 mm dia G.I. Pipes and fittings with two coats of anti-corrosive bitumastic paint of approved quality.
Painting of 40 mm dia G.I. Pipes and fittings with two coats of anti-corrosive bitumastic paint of approved quality.
Painting of 50 mm dia G.I. Pipes and fittings with two coats of anti-corrosive bitumastic paint of approved quality.
Providing and fixing G.I. Inlet fittings with maximum 3 inlets 32,40 & 50 mm size fabricated from 100 mm dia G.I. pipes and welded G.I. sockets, fixed to C.I. Trap with lead caulked joints and set in cement concrete(1:2:4) complete as directed by Engineer-in-charge.
Providing and Fixing SS Grating with frame and SS Screws casted heavy 125 mm dia complete as directed by Engineer-in-charge.
Providing and fixing 100 mm dia cast brass cleanout plug / floor cleanout with suitable insert keys for opening, male threaded joint with G.I. socket caulked to spun soil pipe including cost of joint etc.complete as directed by Engineer-in-charge.
Providing and fixing 150 mm dia cast brass cleanout plug / floor cleanout with suitable insert keys for opening, male threaded joint with G.I. socket caulked to spun soil pipe including cost of joint etc.complete as directed by Engineer-in-charge.
Providing and fixing 150 mm dia cast iron soil, waste and vent pipes as per IS:15905 (Hubless pipes) including all fittings with or without access of any degree i.e bends, junctions, branches, end caps, reducers, cowls, offsets, access pieces, G.I. holder bats and clamps, stays, etc and jointing with stainless steel 304 couplings with EPDM rubber gasket, including cutting holes in walls and floors and making good the same wherever required, all structural supports as per approved specifications, complete, as per instructions of the Engineer-in-charge.
Providing and fixing 20mm dia. Nominal bore G.I. Pipe complete with G.I. Fittings and clamps, including cutting and making good the walls etc. (internal work - Exposed on wall)
Providing and fixing 25mm dia. Nominal bore G.I. Pipe complete with G.I. Fittings and clamps, including cutting and making good the walls etc. (internal work - Exposed on wall)
Providing and fixing 32mm dia. Nominal bore G.I. Pipe complete with G.I. Fittings and clamps, including cutting and making good the walls etc. (internal work - Exposed on wall)
Providing and fixing 40mm dia. Nominal bore G.I. Pipe complete with G.I. Fittings and clamps, including cutting and making good the walls etc. (internal work - Exposed on wall)
Providing and fixing 50mm dia. Nominal bore G.I. Pipe complete with G.I. Fittings and clamps, including cutting and making good the walls etc. (internal work - Exposed on wall)
Providing and fixing class B 65mm dia. Nominal bore G.I. Pipe complete with G.I. Fittings and clamps, including cutting and making good the walls etc. (internal work - Exposed on wall)
Providing and fixing class B 80mm dia. Nominal bore G.I. Pipe complete with G.I. Fittings and clamps, including cutting and making good the walls etc. (internal work - Exposed on wall)
Providing and fixing class B 100mm dia. Nominal bore G.I. Pipe complete with G.I. Fittings and clamps, including cutting and making good the walls etc. (internal work - Exposed on wall)
Providing and fixing class B 150mm dia. Nominal bore G.I. Pipe complete with G.I. Fittings and clamps, including cutting and making good the walls etc. (internal work - Exposed on wall)
Providing and fixing 32 mm dia nominal bore G.I pipes Class "B" complete with G.I fittings including trenching and refilling etc. (External work)
Providing and fixing 40 mm dia nominal bore G.I pipes Class "B" complete with G.I fittings including trenching and refilling etc. (External work)
Providing and fixing 50 mm dia nominal bore G.I pipes Class "B" complete with G.I fittings including trenching and refilling etc. (External work)
Providing and fixing 65 mm dia nominal bore G.I pipes Class "B" complete with G.I fittings including trenching and refilling etc. (External work)
Providing and fixing 80 mm dia nominal bore G.I pipes Class "B" complete with G.I fittings including trenching and refilling etc. (External work)
Providing and fixing 100 mm dia nominal bore G.I pipes Class "B" complete with G.I fittings including trenching and refilling etc. (External work)
Providing and fixing 150 mm dianominal bore G.I pipes Class "B" complete with G.I fittings including trenching and refilling etc. (External work)
Providing and fixing 15 mm dia Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Concealed work, including cutting chases and making good the walls etc.
Providing and fixing 20 mm dia Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Concealed work, including cutting chases and making good the walls etc.
Providing and fixing 25 mm dia Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Concealed work, including cutting chases and making good the walls etc.
Providing and fixing 32 mm dia Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Concealed work, including cutting chases and making good the walls etc.
Providing and fixing 40 mm dia Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Concealed work, including cutting chases and making good the walls etc.
Providing and fixing 50 mm dia Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Concealed work, including cutting chases and making good the walls etc.
Providing and fixing 65 mm dia Chlorinated Polyvinyl Chloride (CPVC Schedule 40) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Concealed work, including cutting chases and making good the walls etc.
Providing and fixing Stainless Steel pipe and fitting of grade AISI 304as per JIS standard 3448 complete with press type fitting (fittingshall be paid for separately) i/c fixing of the pipe with clamps at 1.00m spacing including cutting and making good the walls includingtesting of joints complete as per direction of Engineer-in-charge.(The pipe length inserted in the fitting shall not be measured forpayment) internal Work Exposed on wall 22.22 mm outer dia Pipe
Providing and fixing Stainless Steel pipe and fitting of grade AISI 304as per JIS standard 3448 complete with press type fitting (fittingshall be paid for separately) i/c fixing of the pipe with clamps at 1.00m spacing including cutting and making good the walls includingtesting of joints complete as per direction of Engineer-in-charge.(The pipe length inserted in the fitting shall not be measured forpayment) internal Work Exposed on wall 28.58 mm outer dia Pipe
Providing and fixing Stainless Steel pipe and fitting of grade AISI 304as per JIS standard 3448 complete with press type fitting (fittingshall be paid for separately) i/c fixing of the pipe with clamps at 1.00m spacing including cutting and making good the walls includingtesting of joints complete as per direction of Engineer-in-charge.(The pipe length inserted in the fitting shall not be measured forpayment) internal Work Exposed on wall 34 mm outer dia Pipe
Providing and fixing Stainless Steel pipe and fitting of grade AISI 304as per JIS standard 3448 complete with press type fitting (fittingshall be paid for separately) i/c fixing of the pipe with clamps at 1.00m spacing including cutting and making good the walls includingtesting of joints complete as per direction of Engineer-in-charge.(The pipe length inserted in the fitting shall not be measured forpayment) internal Work Exposed on wall 42.70 mm outer dia Pipe
Providing and fixing required Stainless Steel Fitting of press fit design of grade AISI 304 conforming to JWWA G116 standard with V-profile or Mprofile and with O-ring sealing gasket of EPDM material of required dia as per dirction of Engineer-in-charge. Coupling / Socket For 22.22 mm outer dia pipe
Providing and fixing required Stainless Steel Fitting of press fit design of grade AISI 304 conforming to JWWA G116 standard with V-profile or Mprofile and with O-ring sealing gasket of EPDM material of required dia as per dirction of Engineer-in-charge. Coupling / Socket For 28.58 mm outer dia pipe
Providing and fixing required Stainless Steel Fitting of press fit design of grade AISI 304 conforming to JWWA G116 standard with V-profile or Mprofile and with O-ring sealing gasket of EPDM material of required dia as per dirction of Engineer-in-charge. Coupling / Socket For 34.00 mm outer dia pipe
Providing and fixing required Stainless Steel Fitting of press fit design of grade AISI 304 conforming to JWWA G116 standard with V-profile or Mprofile and with O-ring sealing gasket of EPDM material of required dia as per dirction of Engineer-in-charge. Coupling / Socket For 42.70 mm outer dia pipe
Providing and fixing required Stainless Steel Fitting of press fit design of grade AISI 304 conforming to JWWA G116 standard with V-profile or Mprofile and with O-ring sealing gasket of EPDM material of Providing and fixing required Stainless Steel Fitting of press fit design of grade AISI 304 conforming toJWWA G116 standard with V-profile or M-profile and with O-ring sealing gasket of EPDM material of required dia as per dirction of Engineer-in-charge. Reducer For 22.22 mm x 15.88 mm outer dia pipe
Providing and fixing required Stainless Steel Fitting of press fit design of grade AISI 304 conforming to JWWA G116 standard with V-profile or Mprofile and with O-ring sealing gasket of EPDM material of Providing and fixing required Stainless Steel Fitting of press fit design of grade AISI 304 conforming toJWWA G116 standard with V-profile or M-profile and with O-ring sealing gasket of EPDM material of required dia as per dirction of Engineer-in-charge. Reducer For 28.58 mm x 15.88 mm outer dia pipe
Providing and fixing required Stainless Steel Fitting of press fit design of grade AISI 304 conforming to JWWA G116 standard with V-profile or Mprofile and with O-ring sealing gasket of EPDM material of Providing and fixing required Stainless Steel Fitting of press fit design of grade AISI 304 conforming toJWWA G116 standard with V-profile or M-profile and with O-ring sealing gasket of EPDM material of required dia as per dirction of Engineer-in-charge. Reducer For 34.00 mm x 22.22 mm outer dia pipe
Providing and fixing required Stainless Steel Fitting of press fit design of grade AISI 304 conforming to JWWA G116 standard with V-profile or Mprofile and with O-ring sealing gasket of EPDM material of Providing and fixing required Stainless Steel Fitting of press fit design of grade AISI 304 conforming toJWWA G116 standard with V-profile or M-profile and with O-ring sealing gasket of EPDM material of required dia as per dirction of Engineer-in-charge. Reducer For 42.70 mm x 15.88 mm outer dia pipe
Providing and fixing required Stainless Steel Fitting of press fit design of grade AISI 304 conforming to JWWA G116 standard with V-profile or Mprofile and with O-ring sealing gasket of EPDM material of required dia as per dirction of Engineer-in-charge.elbow 22.22 mm outer dia pipe
Providing and fixing required Stainless Steel Fitting of press fit design of grade AISI 304 conforming to JWWA G116 standard with V-profile or Mprofile and with O-ring sealing gasket of EPDM material of required dia as per dirction of Engineer-in-charge.elbow 28.58 mm outer dia pipe
Providing and fixing required Stainless Steel Fitting of press fit design of grade AISI 304 conforming to JWWA G116 standard with V-profile or Mprofile and with O-ring sealing gasket of EPDM material of required dia as per dirction of Engineer-in-charge.elbow 34.00 mm outer dia pipe
Providing and fixing required Stainless Steel Fitting of press fit design of grade AISI 304 conforming to JWWA G116 standard with V-profile or Mprofile and with O-ring sealing gasket of EPDM material of required dia as per dirction of Engineer-in-charge.elbow 42.70 mm outer dia pipe
Providing and fixing required Stainless Steel Fitting of press fit design of grade AISI 304 conforming to JWWA G116 standard with V-profile or Mprofile and with O-ring sealing gasket of EPDM material of required dia as per dirction of Engineer-in-charge.Equal Tee 22.22 mm outer dia pipe
Providing and fixing required Stainless Steel Fitting of press fit design of grade AISI 304 conforming to JWWA G116 standard with V-profile or Mprofile and with O-ring sealing gasket of EPDM material of required dia as per dirction of Engineer-in-charge.Equal Tee 28.58 mm outer dia pipe
Providing and fixing required Stainless Steel Fitting of press fit design of grade AISI 304 conforming to JWWA G116 standard with V-profile or Mprofile and with O-ring sealing gasket of EPDM material of required dia as per dirction of Engineer-in-charge.Equal Tee 34.00 mm outer dia pipe
Providing and fixing required Stainless Steel Fitting of press fit design of grade AISI 304 conforming to JWWA G116 standard with V-profile or Mprofile and with O-ring sealing gasket of EPDM material of required dia as per dirction of Engineer-in-charge.Equal Tee 42.70 mm outer dia pipe
Providing and fixing required Stainless Steel Fitting of press fit design of grade AISI 304 conforming to JWWA G116 standard with V-profile or Mprofile and with O-ring sealing gasket of EPDM material of required dia as per dirction of Engineer-in-chargeValve Connector 22.22 mm outer dia pipe x 15 mm nominal dia threaded.
Providing and fixing required Stainless Steel Fitting of press fit design of grade AISI 304 conforming to JWWA G116 standard with V-profile or Mprofile and with O-ring sealing gasket of EPDM material of required dia as per dirction of Engineer-in-chargeValve Connector 28.58 mm outer dia pipe x 25 mm nominal dia threaded.
Providing and fixing required Stainless Steel Fitting of press fit design of grade AISI 304 conforming to JWWA G116 standard with V-profile or Mprofile and with O-ring sealing gasket of EPDM material of required dia as per dirction of Engineer-in-charge.Valve Connector 34.00 mm outer dia pipe x 32 mm nominal dia threaded.
Providing and fixing required Stainless Steel Fitting of press fit design of grade AISI 304 conforming to JWWA G116 standard with V-profile or Mprofile and with O-ring sealing gasket of EPDM material of required dia as per dirction of Engineer-in-chargeValve Connector 42.70 mm outer dia pipe x 40 mm nominal dia threaded.
Providing and fixing required Stainless Steel Fitting of press fit design of grade AISI 304 conforming to JWWA G116 standard with V-profile or Mprofile and with O-ring sealing gasket of EPDM material of required dia as per dirction of Engineer-in-Cap Connector 22.22 mm outer dia pipe
Providing and fixing required Stainless Steel Fitting of press fit design of grade AISI 304 conforming to JWWA G116 standard with V-profile or Mprofile and with O-ring sealing gasket of EPDM material of required dia as per dirction of Engineer-in-chargeCap 28.58 mm outer dia pipe
Providing and fixing required Stainless Steel Fitting of press fit design of grade AISI 304 conforming to JWWA G116 standard with V-profile or Mprofile and with O-ring sealing gasket of EPDM material of required dia as per dirction of Engineer-in-charge.Cap 34.00 mm outer dia pipe
Providing and fixing required Stainless Steel Fitting of press fit design of grade AISI 304 conforming to JWWA G116 standard with V-profile or Mprofile and with O-ring sealing gasket of EPDM material of required dia as per dirction of Engineer-in-chargeCap 42.70 mm outer dia pipe
Providing and Fixing 54 mm od stainless steel pipe (Gradr SS-316) confirming to JIS 3448 standrad complete with press type fitting with SC-Contur in accordance with DVGW regulations JWWA G116 such as sockets, bends, elbows, tees, reducers, unions, flagnes, clamps/Structural steel supports, hangers ets. necessary adapters for GI to SS/ other metals and for connections to CP fitting, Jointing,Sundries, Cutting holes in walls/floors/slabs & making good, complete in all respects.(pipe length included in fitting shall not be measured in payment) Internal work - Exposed on wall.
Providing and Fixing 76mm od stainless steel pipe (Gradr SS-316) confirming to JIS 3448 standrad complete with press type fitting with SC-Contur in accordance with DVGW regulations JWWA G116 such as sockets, bends, elbows, tees, reducers, unions, flagnes, clamps/Structural steel supports, hangers ets. necessary adapters for GI to SS/ other metals and for connections to CP fitting, Jointing,Sundries, Cutting holes in walls/floors/slabs & making good, complete in all respects.(pipe length included in fitting shall not be measured in payment) Internal work - Exposed on wall.
Providing and Fixing 88 mm od stainless steel pipe (Gradr SS-316) confirming to JIS 3448 standrad complete with press type fitting with SC-Contur in accordance with DVGW regulations JWWA G116 such as sockets, bends, elbows, tees, reducers, unions, flagnes, clamps/Structural steel supports, hangers ets. necessary adapters for GI to SS/ other metals and for connections to CP fitting, Jointing,Sundries, Cutting holes in walls/floors/slabs & making good, complete in all respects.(pipe length included in fitting shall not be measured in payment) Internal work - Exposed on wall.
Providing and laying S & S Ductile Iron Pipes conforming to IS :8329: 100 mm dia Ductile Iron Class K-9 pipes
Providing and laying S & S Ductile Iron Pipes conforming to IS :8329: 150 mm dia Ductile Iron Class K-9 pipes
Providing push-on-joints of 100 mm dia for Ductile Iron Pipes including testing of joints and the cost of rubber gasket :
Providing push-on-joints of 150 mm dia for Ductile Iron Pipes including testing of joints and the cost of rubber gasket :
Providing and laying D.I. specials of class K-12 suitable for push-on jointing as per IS : 9523 : Up to 600 mm dia
Providing and fixing 25 mm dia G.I. Union in G.I. Pipe including cutting and threading the pipe and making long screws etc. complete (new work)
Providing and fixing 32 mm dia nominal bore G.I. Union in G.I. Pipe including cutting and threading the pipe and making long screws etc. complete (new work)
Providing and fixing 40 mm dia nominal bore G.I. Union in G.I. Pipe including cutting and threading the pipe and making long screws etc. complete (new work)
Providing and fixing 50 mm dia nominal bore G.I. Union in G.I. Pipe including cutting and threading the pipe and making long screws etc. complete (new work)
Providing and fixing 65 mm dia nominal bore G.I. Union in G.I. Pipe including cutting and threading the pipe and making long screws etc. complete (new work)
Providing and fixing 80 mm dia nominal bore G.I. Union in G.I. Pipe including cutting and threading the pipe and making long screws etc. complete (new work)
Providing and fixing 100 mm dia nominal bore G.I. Union in G.I. Pipe including cutting and threading the pipe and making long screws etc. complete (new work)
Providing and fixing 150 mm dia nominal bore G.I. Union in G.I. Pipe including cutting and threading the pipe and making long screws etc. complete (new work)
Painting of 32 mm dia G.I. pipes and fittings with two coats of anti-corrosive bitumastic paint of approved quality :
Painting of 40 mm dia G.I. pipes and fittings with two coats of anti-corrosive bitumastic paint of approved quality :
Painting of 50 mm dia G.I. pipes and fittings with two coats of anti-corrosive bitumastic paint of approved quality :
Painting of 65 mm dia G.I. pipes and fittings with two coats of anti-corrosive bitumastic paint of approved quality :
Painting of 80 mm dia G.I. pipes and fittings with two coats of anti-corrosive bitumastic paint of approved quality :
Providing and filling sand of grading zone V or coarser grade, allround the G.I. pipes in external work, 25 mm diameter pipe.
Providing and filling sand of grading zone V or coarser grade, allround the G.I. pipes in external work, 32 mm diameter pipe.
Providing and filling sand of grading zone V or coarser grade, allround the G.I. pipes in external work, 40 mm diameter pipe.
Providing and filling sand of grading zone V or coarser grade, allround the G.I. pipes in external work, 50 mm diameter pipe.
Providing and filling sand of grading zone V or coarser grade, allround the G.I. pipes in external work, 65 mm diameter pipe.
Providing and filling sand of grading zone V or coarser grade, allround the G.I. pipes in external work, 80 mm diameter pipe.
Providing and filling sand of grading zone V or coarser grade, allround the G.I. pipes in external work, 100 mm diameter pipe.
Providing and filling sand of grading zone V or coarser grade, allround the G.I. pipes in external work, 150 mm diameter pipe.
Painting 20 mm dia G.I. pipes and fittings with synthetic enamel white paint with two coats over a ready mixed priming coat, both of approved quality for new work :
Painting 25 mm dia G.I. pipes and fittings with synthetic enamel white paint with two coats over a ready mixed priming coat, both of approved quality for new work :
Painting 32 mm dia G.I. pipes and fittings with synthetic enamel white paint with two coats over a ready mixed priming coat, both of approved quality for new work :
Painting 40 mm dia G.I. pipes and fittings with synthetic enamel white paint with two coats over a ready mixed priming coat, both of approved quality for new work :
Painting 50 mm dia G.I. pipes and fittings with synthetic enamel white paint with two coats over a ready mixed priming coat, both of approved quality for new work :
Providing and fixing 20 mm dia forged brass lever operated ball valve of full flow with forged brass ball (Machined to mirror smooth finsh with hard chrome plated) and spindle with setting and gland of superior quality having minimum working pressure of 10 kg/cm2 etc. complete in all respect.
Providing and fixing 25 mm dia forged brass lever operated ball valve of full flow with forged brass ball (Machined to mirror smooth finsh with hard chrome plated) and spindle with setting and gland of superior quality having minimum working pressure of 10 kg/cm2 etc. complete in all respect.
Providing and fixing 32 mm dia forged brass lever operated ball valve of full flow with forged brass ball (Machined to mirror smooth finsh with hard chrome plated) and spindle with setting and gland of superior quality having minimum working pressure of 10 kg/cm2 etc. complete in all respect.
Providing and fixing 40 mm dia forged brass lever operated ball valve of full flow with forged brass ball (Machined to mirror smooth finsh with hard chrome plated) and spindle with setting and gland of superior quality having minimum working pressure of 10 kg/cm2 etc. complete in all respect.
Providing and fixing 50 mm dia forged brass lever operated ball valve of full flow with forged brass ball (Machined to mirror smooth finsh with hard chrome plated) and spindle with setting and gland of superior quality having minimum working pressure of 10 kg/cm2 etc. complete in all respect.
Providing and fixing 65 mm dia C.I. butterfly valves of approved make , wafer end type class PN 1.6 as per I.S:13095 or with integrally moulded linear of nitrile or EPDM, SS Disc and steam lever operated including necessary nuts, bolts, gaskets, flanges etc., complete as directed by Engineer-in-charge.
Providing and fixing 80 mm dia C.I. butterfly valves of approved make , wafer end type class PN 1.6 as per I.S:13095 or with integrally moulded linear of nitrile or EPDM, SS Disc and steam lever operated including necessary nuts, bolts, gaskets, flanges etc., complete as directed by Engineer-in-charge.
Providing and fixing 100 mm dia C.I. butterfly valves of approved make , wafer end type class PN 1.6 as per I.S:13095 or with integrally moulded linear of nitrile or EPDM, SS Disc and steam lever operated including necessary nuts, bolts, gaskets, flanges etc., complete as directed by Engineer-in-charge.
Providing and fixing 150 mm dia C.I. butterfly valves of approved make , wafer end type class PN 1.6 as per I.S:13095 or with integrally moulded linear of nitrile or EPDM, SS Disc and steam lever operated including necessary nuts, bolts, gaskets, flanges etc., complete as directed by Engineer-in-charge.
Providing & fixing 65 mm dia Non return valve of approved make CI body for PN 1.6 rating, conforming to IS:5312 complete in all respects. Vertical
Providing & fixing 100 mm dia Non return valve of approved make CI body for PN 1.6 rating, conforming to IS:5312 complete in all respects. Vertical
Providing & fixing 150 mm dia Non return valve of approved make CI body for PN 1.6 rating, conforming to IS:5312 complete in all respects. Vertical
Providing and Fixing 20 mm dia Pressure Reducing station for cold water supply comprising of 2 Nos. of brass ball valves on outlet and bye-pass and ball valve with inbuilt strainers and a PRV (Diaphram type) unit with out going pressure gauge with flanged or union connection including safety valve. The complete system is tested to a pressure not less than 15 Kg/Cm2 and suitable to reduce the pressure as per requirement including flanges/unions, nuts, bolts and washers complete as required for applications. (Horizontal or vertical as applicable).
Providing and Fixing 25 mm dia Pressure Reducing station for cold water supply comprising of 2 Nos. of brass ball valves on outlet and bye-pass and ball valve with inbuilt strainers and a PRV (Diaphram type) unit with out going pressure gauge with flanged or union connection including safety valve. The complete system is tested to a pressure not less than 15 Kg/Cm2 and suitable to reduce the pressure as per requirement including flanges/unions, nuts, bolts and washers complete as required for applications. (Horizontal or vertical as applicable).
Providing and Fixing 32 mm dia Pressure Reducing station for cold water supply comprising of 2 Nos. of brass ball valves on outlet and bye-pass and ball valve with inbuilt strainers and a PRV (Diaphram type) unit with out going pressure gauge with flanged or union connection including safety valve. The complete system is tested to a pressure not less than 15 Kg/Cm2 and suitable to reduce the pressure as per requirement including flanges/unions, nuts, bolts and washers complete as required for applications. (Horizontal or vertical as applicable).
Providing and Fixing 40 mm dia Pressure Reducing station for cold water supply comprising of 2 Nos. of brass ball valves on outlet and bye-pass and ball valve with inbuilt strainers and a PRV (Diaphram type) unit with out going pressure gauge with flanged or union connection including safety valve. The complete system is tested to a pressure not less than 15 Kg/Cm2 and suitable to reduce the pressure as per requirement including flanges/unions, nuts, bolts and washers complete as required for applications. (Horizontal or vertical as applicable).
Providing and Fixing 50 mm dia Pressure Reducing station for cold water supply comprising of 2 Nos. of brass ball valves on outlet and bye-pass and ball valve with inbuilt strainers and a PRV (Diaphram type) unit with out going pressure gauge with flanged or union connection including safety valve. The complete system is tested to a pressure not less than 15 Kg/Cm2 and suitable to reduce the pressure as per requirement including flanges/unions, nuts, bolts and washers complete as required for applications. (Horizontal or vertical as applicable).
Providing and Fixing 65 mm dia Pressure Reducing station for cold water supply comprising of 2 Nos. of brass ball valves on outlet and bye-pass and ball valve with inbuilt strainers and a PRV (Diaphram type) unit with out going pressure gauge with flanged or union connection including safety valve. The complete system is tested to a pressure not less than 15 Kg/Cm2 and suitable to reduce the pressure as per requirement including flanges/unions, nuts, bolts and washers complete as required for applications. (Horizontal or vertical as applicable).
Providing and Laying 25 OD uPVC water pipes (I.S:4985) of 8 Kg/cm2 including all fittings e.g. bends, junctions, elbow, f-tee, m-tee, offsets, access pieces etc. jointing with solvent cement complete. Rates includes any type of fittings required for the provision of Garden Hydrant point in main ring of the Hydrant pipe in different location complete in with trenching, refilling and testing of joints complete as per direction of the engineer in charge.
Providing and Laying 32 OD uPVC water pipes (I.S:4985) of 8 Kg/cm2 including all fittings e.g. bends, junctions, elbow, f-tee, m-tee, offsets, access pieces etc. jointing with solvent cement complete. Rates includes any type of fittings required for the provision of Garden Hydrant point in main ring of the Hydrant pipe in different location complete in with trenching, refilling and testing of joints complete as per direction of the engineer in charge.
Providing and Laying 40 OD uPVC water pipes (I.S:4985) of 6 Kg/cm2 including all fittings e.g. bends, junctions, elbow, f-tee, m-tee, offsets, access pieces etc. jointing with solvent cement complete. Rates includes any type of fittings required for the provision of Garden Hydrant point in main ring of the Hydrant pipe in different location complete in with trenching, refilling and testing of joints complete as per direction of the engineer in charge.
Providing and Laying 50 OD uPVC water pipes (I.S:4985) of 6 Kg/cm2 including all fittings e.g. bends, junctions, elbow, f-tee, m-tee, offsets, access pieces etc. jointing with solvent cement complete. Rates includes any type of fittings required for the provision of Garden Hydrant point in main ring of the Hydrant pipe in different location complete in with trenching, refilling and testing of joints complete as per direction of the engineer in charge.
Providing and Laying 63 OD uPVC water pipes (I.S:4985) of 6 Kg/cm2 including all fittings e.g. bends, junctions, elbow, f-tee, m-tee, offsets, access pieces etc. jointing with solvent cement complete. Rates includes any type of fittings required for the provision of Garden Hydrant point in main ring of the Hydrant pipe in different location complete in with trenching, refilling and testing of joints complete as per direction of the engineer in charge.
Providing and Laying 75 OD uPVC water pipes (I.S:4985) of 6 Kg/cm2 including all fittings e.g. bends, junctions, elbow, f-tee, m-tee, offsets, access pieces etc. jointing with solvent cement complete. Rates includes any type of fittings required for the provision of Garden Hydrant point in main ring of the Hydrant pipe in different location complete in with trenching, refilling and testing of joints complete as per direction of the engineer in charge.
Providing and Laying 90 OD uPVC water pipes (I.S:4985) of 6Kg/cm2 including all fittings e.g. bends, junctions, elbow, f-tee, m-tee, offsets, access pieces etc. jointing with solvent cement complete. Rates includes any type of fittings required for the provision of Garden Hydrant point in main ring of the Hydrant pipe in different location complete in with trenching, refilling and testing of joints complete as per direction of the engineer in charge
Constructing masonry chamber 30x30x50 cm with FPS bricks, inside with brick work in cement mortar 1:4 (1 cement : 4 Coarse sand) for stop cock, with C.I. surface box 100x100x75 mm (inside) with hinged cover fixed in cement concrete slab1:2:4 mix (1 cement: 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) necessary excavation foundation concrete 1:5:10 mix (1 cement : 5 fine sand and 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick finished with a floating coat of neat cement complete as per standard design. With common burnt clay FPS (non modular) bricks of class designation 7.5
Constructing masonry Chamber 60x60x75 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with C.I. surface box 100mm. top diameter, 160 mm bottom diameter and 180 mm deep (inside) with chained lid and RCC top slab 1:2:4 mix (1 cement :2 coarse sand : 4 graded stone aggregate 20mm nominal size), i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick finished with a floating coat of neat cement complete as per standard design : With common burnt clay F.P.S.(non modular) bricks of class designation 7.5.
Constructing masonry Chamber 90x90x100 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with C.I. surface box 100 mm top diameter, 160 mm bottom diameter and 180 mm deep (inside) with chained lid and RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ), i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size ) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design : With common burnt clay F.P.S.(non modular) bricks of class designation 7.5.
Constructing masonry Chamber 120x120x100 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with C.I. surface box 100 mm top diameter, 160 mm bottom diameter and 180 mm deep ( inside) with chained lid and RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) , i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design : With common burnt clay F.P.S.(non modular) bricks of class designation 7.5
Providing and fixing 15 mm dia thermal insulation over hot water pipes in chase having Japanese Red Oxide Primer Coat with 6mm thick Kaiflex, nitrile or approved equivalent thermal insulation tubing, a elastomeric flexible material having hermetic blister closed cell structure of expanded synthetic rubber having density of 60-90 Kg/m3 over pipes of following sizes including all required accessories complete as per Manufacture's specifications and finishing complete in all respect as directed by Engineer-in-charge.
Providing and fixing 20 mm dia thermal insulation over hot water pipes in chase having Japanese Red Oxide Primer Coat with 6mm thick Kaiflex, nitrile or approved equivalent thermal insulation tubing, a elastomeric flexible material having hermetic blister closed cell structure of expanded synthetic rubber having density of 60-90 Kg/m3 over pipes of following sizes including all required accessories complete as per Manufacture's specifications and finishing complete in all respect as directed by Engineer-in-charge.
Providing and fixing 25 mm dia thermal insulation over hot water pipes in chase having Japanese Red Oxide Primer Coat with 6mm thick Kaiflex, nitrile or approved equivalent thermal insulation tubing, a elastomeric flexible material having hermetic blister closed cell structure of expanded synthetic rubber having density of 60-90 Kg/m3 over pipes of following sizes including all required accessories complete as per Manufacture's specifications and finishing complete in all respect as directed by Engineer-in-charge.
Providing and fixing 32 mm dia 750 mm long hot dipped G.I. Puddle flanges for water tanks as per I.S. 1239 (Class C) with 6mm thick M.S. Plate of suitable size and welded alround the pipe fixed in walls, beams and top slab of R.C.C tanks, complete with all details in all respects and as per drawing.
Providing and fixing 40 mm dia 750 mm long hot dipped G.I. Puddle flanges for water tanks as per I.S. 1239 (Class C) with 6mm thick M.S. Plate of suitable size and welded alround the pipe fixed in walls, beams and top slab of R.C.C tanks, complete with all details in all respects and as per drawing.
Providing and fixing 50 mm dia 750 mm long hot dipped G.I. Puddle flanges for water tanks as per I.S. 1239 (Class C) with 6mm thick M.S. Plate of suitable size and welded alround the pipe fixed in walls, beams and top slab of R.C.C tanks, complete with all details in all respects and as per drawing.
Providing and fixing 65 mm dia 750 mm long hot dipped G.I. Puddle flanges for water tanks as per I.S. 1239 (Class C) with 6mm thick M.S. Plate of suitable size and welded alround the pipe fixed in walls, beams and top slab of R.C.C tanks, complete with all details in all respects and as per drawing.
Providing and fixing 80 mm dia 750 mm long hot dipped G.I. Puddle flanges for water tanks as per I.S. 1239 (Class C) with 6mm thick M.S. Plate of suitable size and welded alround the pipe fixed in walls, beams and top slab of R.C.C tanks, complete with all details in all respects and as per drawing.
Providing and fixing 100 mm dia 750 mm long hot dipped G.I. Puddle flanges for water tanks as per I.S. 1239 (Class C) with 6mm thick M.S. Plate of suitable size and welded alround the pipe fixed in walls, beams and top slab of R.C.C tanks, complete with all details in all respects and as per drawing.
Providing and fixing 150 mm dia 750 mm long hot dipped G.I. Puddle flanges for water tanks as per I.S. 1239 (Class C) with 6mm thick M.S. Plate of suitable size and welded alround the pipe fixed in walls, beams and top slab of R.C.C tanks, complete with all details in all respects and as per drawing.
Providing and fixing 50 mm dia C.I. double acting air valve of approved quality with bolts, nuts, rubber insertions etc. complete (The tail pieces, tapers etc if required will be paid separately) :
Providing and fixing 80 mm dia insect-proof coupling to vent pipes of underground tank/overhead tank with threaded or flanged joints, including M.S. flanges, nuts, bolts, 3mm thick rubber insertions complete.
Providing, laying and jointing 150 MM Dia glazed stoneware pipes class SP-1 with stiff mixture of cement mortar in the proportion of 1:1 (1 cement : 1 fine sand) including testing of joints etc. complete :
Providing, laying and jointing 200 MM Dia glazed stoneware pipes class SP-1 with stiff mixture of cement mortar in the proportion of 1:1 (1 cement : 1 fine sand) including testing of joints etc. complete :
Providing, laying and jointing 250 MM Dia glazed stoneware pipes class SP-1 with stiff mixture of cement mortar in the proportion of 1:1 (1 cement : 1 fine sand) including testing of joints etc. complete :
Providing, laying and jointing 300 MM Dia glazed stoneware pipes class SP-1 with stiff mixture of cement mortar in the proportion of 1:1 (1 cement : 1 fine sand) including testing of joints etc. complete :
Providing and laying non-pressure 200 mm dia NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete :
Providing and laying non-pressure 250 mm dia NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete :
Providing and laying non-pressure 300 mm dia NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete :
Providing and laying non-pressure 450 mm dia NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete :
Providing and laying non-pressure 600 mm dia NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete :
Providing and laying non-pressure 700 mm dia NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete :
Providing and laying non-pressure 800 mm dia NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete :
Providing and laying non-pressure 900 mm dia NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete :
Providing and laying non-pressure 1000 mm dia NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete :
Providing and laying non-pressure 600 mm dia NP3 class R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete :
Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 40 mm nominal size) all-round S.W. pipes including bed concrete as per standard design : - 100mm diameter S.W Pipe
Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 40 mm nominal size) all-round S.W. pipes including bed concrete as per standard design : - 150mm diameter S.W Pipe
Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 40 mm nominal size) all-round S.W. pipes including bed concrete as per standard design : - 200mm diameter S.W Pipe
Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 40 mm nominal size) all-round S.W. pipes including bed concrete as per standard design : - 250mm diameter S.W Pipe
Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 40 mm nominal size) all-round 300 MM Dia S.W./RCC/NP2/NP3 pipes including bed concrete as per standard design :
Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 40 mm nominal size) all-round 450 MM Dia S.W./RCC/NP2/NP3 pipes including bed concrete as per standard design :
Providing and fixing square-mouth S.W. gully trap class SP-1 complete with C.I. grating brick masonry chamber with water tight C.I. cover with frame of 300 x300 mm size (inside) the weight of cover to be not less than 4.50 kg and frame to be not less than 2.70 kg as per standard design: 150 x 100 mm size P type With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
Providing and fixing square-mouth S.W. gully trap class SP-1 complete with C.I. grating brick masonry chamber with water tight C.I. cover with frame of 450 x450 mm size (inside) the weight of cover to be not less than 4.50 kg and frame to be not less than 2.70 kg as per standard design: 180 x 150 mm size P type With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement : 4 coarse sand ) with R.C.C. top slab with 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), foundation concrete 1:4:8 mix (1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size), inside plastering 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with floating coat of neat cement and making channels in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement complete as per standard design : Inside size 90x80 cm and 45 cm deep including C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover and frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg) : With common burnt clay FPS(non modular) bricks of class designation 7.5
Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement : 4 coarse sand ) with R.C.C. top slab with 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), foundation concrete 1:4:8 mix (1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size), inside plastering 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with floating coat of neat cement and making channels in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement complete as per standard design : Inside size 120x90 cm and 90 cm deep including C.I. cover with frame (medium duty) 500 mm internal diameter, total weight of cover and frame to be not less than 116 kg (weight of cover 58 kg and weight of frame 58 kg) : With common burnt clay FPS(non modular) bricks of class designation 7.5
Extra depth of manholes Size 90x80cms with common burnt clay FPS Bricks with class designation75
Extra depth of manholes Size 120x90cms with burnt clay FPS Bricks with class designation75
Constructing brick masonry circular type manhole 0.91 m internal dia at bottom and 0.56m dia at top in cement mortar 1:4 (1 cement : 4 coarse sand), inside cement plaster 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with a floating coat of neat cement, foundation concrete 1:3:6 mix (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size), and making necessary channel in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement, all complete as per standard design : 0.91 m deep with SFRC cover and frame (heavy duty, HD-20 grade designation) 560 mm internal diameter conforming to I.S. 12592, total weight of cover and frame to be not less than 182 kg., fixed in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) including centering, shuttering all complete. (Excavation, foot rests and 12mm thick cement plaster at the external surface shall be paid for separately) : With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
Extra depth for circular type Manhole 0.91 internal dia with F.P.S. Bricks class designation 75, depth beyond 0.91 m to 1.67 m
Constructing brick masonry circular manhole 1.22 m internal dia at bottom and 0.56 m dia at top in cement mortar 1:4 (1 cement :4 coarse sand) inside cement plaster 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with a floating coat of neat cement foundation concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) and making necessary channel in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement, all complete as per standard design : 1.68 m deep with SFRC Cover and frame (heavy duty HD- 20 grade designation) 560 mm internal diameter conforming to I.S. 12592, total weight of cover and frame to be not less than 182 kg. fixed in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) including centering, shuttering all complete. (Excavation, foot rests and 12 mm thick cement plaster at the external surface shall be paid for separately) : With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
Extra depth for Circular type Manhole 1.22 m internal dia (at Bottom) With F.P.S bricks class designation 75, Depth beyond 1.68 to 2.29 m.
Constructing brick masonry circular manhole 1.52 m internal dia at bottom and 0.56 m dia at top in cement mortar 1:4 (1 cement : 4 coarse sand) inside cement plaster 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with a floating coat of neat cement, foundation concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) and making necessarychannel in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement, all complete as per standard design : 2.30 m deep with SFRC Cover and frame (heavy duty HD-20 grade designation) 560 mm internal diameter conforming to I.S. 12592, total weight of cover and frame to be not less than 182 kg. fixed in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) including centering, shuttering all complete.(Excavation, foot rests and 12 mm thick cement plaster at the external surface shall be paid for separately) : With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
Extra depth for circular type manhole 1.52 m internal dia (at bottom) beyond 2.30 m : With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
Constructing brick masonry chamber for underground C.I. inspection chamber and bends with bricks in cement mortar 1:4 (1 cement : 4 coarse sand) C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover with frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg), R.C.C. top slab with 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), foundation concrete 1:5:10 (1 cement : 5 coarse sand (Zone III) : 10 graded stone aggregate 40 mm nominal size), inside plastering 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand), finished smooth with a floating coat of neat cement on walls and bed concrete etc. complete as per standard design: Inside dimensions 600x 850 mm and 45 cm deep for pipe line with three or more inlets : With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
Extra for depth beyond 45 cm of brick masonry chamber : For 600x850 mm size With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
Providing & fixing orange colour safety foot rest of minimum 6mm thick plastic encapsulated as per I.S:10910 on 12 mm dia steel bar conforming to I.S:1786 having minimum cross section as 23mm x 25mm and over all minimum length 263mm and width as 165mm with minimum 165 mm space between protruded legs having 2mm tread on top surface by ribbing or chequering besides necessary and adequate anchoring projections on tail length on 138mm as per standard drawing and suitable to with stand the bend test and chemical resistance test as per specifications and having manufacturer's permanent identification mark to be visible even after fixing, including fixing in manholes with 30x20x15cm cement concrete block 1:3:6 (1 cement: 3 coarse sand: 6 graded stone aggregate 20mm nominal size) complete as per design.
Constructing brick masonry road gully chamber 45x45x77.5 cm with bricks in cement mortar 1:4 (1 cement : 4 coarse sand ) with precast R.C.C. vertical grating complete as per standard design : With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
Constructing brick masonry road gully chamber 50x45x60 cm with bricks in cement mortar 1:4 (1 cement : 4 coarse sand) including 500x450 mm pre-cast R.C.C. horizontal grating with frame complete as per standard design : With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
Constructing brick masonry road gully chamber 110x50x77.5 cm with bricks in cement mortar 1:4 (1 cement : 4 coarse sand) including 500x450 mm precast R.C.C. horizontal grating with frame and vertical grating complete as per standard design : With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
Providing and fixing in position pre-cast R.C.C. manhole cover and frame of required shape and approved quality, EHD-35, Circular shape 560 mm internal dia
Boring/drilling bore well of required dia for casing/ strainer pipe, by suitable method prescribed in IS: 2800 (part I), including collecting samples from different strata, preparing and submitting strata chart/ bore log, including hire & running charges of all equipments, tools, plants & machineries required for the job, all complete as per direction of Engineer -in-charge, upto 150 metre depth below ground level. All types of soil 500 mm dia
Supplying, assembling, lowering and fixing in vertical position in bore well, unplasticized PVC medium well casing (CM) pipe of required dia, conforming to IS: 12818, including required hire and labour charges, fittings & accessories etc. all complete, for all depths, as per direction of Engineer -in-charge For 200 mm nominal size dia
Supplying, assembling, lowering and fixing in vertical position in borewell unplasticized PVC medium well screen (RMS) pipes with ribs, conforming to IS: 12818, including hire &labour charges, ittings & accessories etc. all complete, for all depths, as per direction of Engineer-in charge. For 200mm nominal size dia
Gravel packing in tube well construction in accordance with IS: 4097, including providing gravel fine/ medium/ coarse, in required grading & sizes as per actual requirement, all complete as per direction of Engineer-in- charge.
Development of Tubewell in accordance with IS : 2800 (part I) and IS: 11189, to establish maximum rate of usable water yield without sand content (beyond permissible limit), with required capacity air compressor, running the compressor for required time till well is fully developed, measuring yield of well by “V” notch method or any other approved method, measuring static level & draw down etc. by step draw down method, collecting water samples & getting tested in approved laboratory, i/c disinfection of tubewell, all complete, including hire & labour charges of air compressor, tools & accessories etc., all as per requirement and direction of Engineer-in-charge.
Providing and fixing suitable size threaded mild steel cap or spot welded plate to the top of bore well housing/ casing pipe, removable as per requirement, all complete for borewell of 200 mm dia
Providing and fixing 200 mm dia M.S. clamp of required dia to the top of casing/housing pipe of tubewell as per IS: 2800 (part I), including necessary bolts & nuts of required size complete.
Providing and fixing 200 mm dia Bail plug/ Bottom plug of required dia to the bottom of pipe assembly of tubewell as per IS:2800 (part I).
Supplying, filling, spreading & leveling stone boulders of size range 5 cm to 20 cm, in recharge pit, in the required thickness, for all leads & lifts, all complete as per direction of Engineer-in-charge.
Supplying, filling, spreading & leveling gravels of size range 5 mm to 10 mm, in the recharge pit, over the existing layer of boulders, in required thickness, for all leads & lifts, all complete as per direction of Engineer-incharge.
Supplying, filling, spreading & leveling coarse sand of size range 1.5 mm to 2 mm in recharge pit, in required thickness over gravel layer, for all leads & lifts, all complete as per direction of Engineer -in-charge.
Providing and fixing factory made precast RCC perforated drain covers,having concrete of strength not less than M-25, of size 1000 x 450x50 mm, reinforced with 8 mm dia four nos longitudinal & 9 nos cross sectional T.M.T. hoop bars, including providing 50 mm dia perforations @ 100 to 125 mm c/c, including providing edge binding with M.S. flats of size 50 mm x 1.6 mm complete, all as per direction of Engineer-in-charge.
Construction of brick masonry desilting chamber of size 200x100x60cm (effective depth) before rainy well with 75 class designation bricks in cement mortar 1:4 (1 cement : 4 coarse sand) , foundation concrete 1:4:8 mix (1 cement : 4 coarse sand; 8 graded stone aggregate 40mm nominal size), inside and outside plastering 12mm thick with cement mortar 1:3 (1 cement : 3 coarse sand), finished with a floating coat of neat cement inside and rough plaster on outside, including fixing of grating , neatly finished complete in all respects including neccessary excavation, refilling and disposal of surplus earth, complete as per attached Sketch.
Preparation of granular sub-base by providing close graded material, conforming to specifications mixing in a mechanical mix plant at OMC, carriage of mixed material by mechanical transport to work site, for all leads and lifts, spreading in uniform layers of specified thickness with mechanical means including neatly leveling & dressing on prepared surface and compacting with vibratory power roller to achieve the desired density, complete and as per direction of Engineer-in-charge. with confirming to grading-1 of table 1 of particular specifications.
Providing, laying, spreading and compacting graded stone aggregate (size range 53 mm to 0.075mm) to wet mix macadam(WMM) specification including premixing the material with water at OMC in mechanical mix plant, carriage of mixed material by mechanical transport to site, for all leads & lifts, laying in uniform layers with mechanical paver finisher in sub-base/ base course on well prepared surface and compacting with vibratory roller of 8 to 10 tonne capacity to achieve the desired density, complete as per specifications and directions of Engineer-in-charge
Providing and laying dry lean cement concrete with coarse and fine aggregate conforming to IS:383, the size of coarse aggregate not exceeding 26.5 mm, aggregate cement ratio not exceed 15:1, aggregate gradation after blending to be as per specification, cement content not to be less than 150 kg/cum, optimum moisture content to be determined during trial length construction, concrete strength not to be less than 10 MPa at 7 days, mixed in a batching plant as per mix design, transported to site, laid with a paver with electronic sensor, compacting with 8-10 tonne vibratory roller, finishing and curing etc complete as per specification and direction of the Engineer-in-Charge
Providing and laying Pavement Quality Concrete (PQC) produced in a batching plant having a Characteristic flexural strength i.e. minimum flexural strength of 4.1 MPa at 28 days using 350 Kg of ordinary Portland cement of 43 grad , fine aggregate, graded stone aggregates of 40 mm nominal size in appropriate proportion as per specification and job mix formula, laid in panels as per drawings/design as approved by the Engineer-In-Charge using Slip form paver/Manual method) including making necessary provision for expansion joint, curing, etc. complete as per direction of Engineer-in-Charge and particular specifications. The item for execution shall also include the following operations: Mechanically cutting dummy joints 3mm wide x 1/3rd thickness of slab which is subsequently widened to 10mm for the top 25mm depth and construction joints 10mm wide x 25mm deep as per specification. Filling Polysulphide sealant in dummy, construction and expansion joints including providing closed-cell Polyethylene foam back-up rod, and painting side of joints with Polysulphide primer, etc. complete (to be paid separately) Note: For the purpose of tendering, the quantity of cement used for one Cum. of finished concrete may be assumed as 350 Kg. If the actual quantity of cement required as per laboratory mix design varies from the quantity assumed above, necessary cost adjustment for deviation in the quantity of cement as per mix design, if any, shall be done as per the rate of cement in actual supply voucher from manufacturer/authorized dealer at the time of execution. In the case of authorized distributor the rate may be authenticated by the manufacturer. The rate of cement exclusive of GST shall only be considered for payment.
Providing and laying in position for expansion joint, 25mm thick pre-cut Synthetic joint filler board of approved make conforming to IS:1838(part 3)-2011, 45 mm from top (to be removed at the time of filling of Polysulphide sealant), complete as per particular specifications and directions of Engineer-in-charge. (Note: Mode of measurement shall be length of joint multiplied by depth of filler board including precut portion.)-unit m2
Providing and laying in position Polysulphide sealant of approved make conforming to BS-5212- 990 or IS: 11433-1995. In expansion/ construction / dummy joints including rounding off edges, applying 2 coats of approved primer compatible with the brand of Polysulphide and preparing the surface and applying masking tape along the edge of joint to prevent accidental spillage of sealant on top surface and to give neat finish to the sealant and removing the masking tape after application of sealant etc. complete as per direction of Engineer in- Charge & particular specifications. [Note: For purpose of payment, quantity (Length x Width x Depth) of Polysulphide sealant only will be measured.] : Expansion Joints of size 25 mm wide and 10 mm deep over 30mm dia closed-cell Polyethylene foam back-up rod, as per manufacturers specifications and sketch at Appendix-‘A’.
Providing and laying in position Polysulphide sealant of approved make conforming to BS-5212- 990 or IS: 11433-1995. In expansion/ construction / dummy joints including rounding off edges, applying 2 coats of approved primer compatible with the brand of Polysulphide and preparing the surface and applying masking tape along the edge of joint to prevent accidental spillage of sealant on top surface and to give neat finish to the sealant and removing the masking tape after application of sealant etc. complete as per direction of Engineer in- Charge & particular specifications. [Note: For purpose of payment, quantity (Length x Width x Depth) of Polysulphide sealant only will be measured.] : Construction Joints of size 10 mm wide and 10 mm deep over 12mm dia closed-cell Polyethylene foam back-up rod, as per manufacturers specifications and sketch at Appendix-‘A’. Dummy Joints of size 10 mm wide and 10 mm deep over 12 mm dia closed-cell Polyethylene foam back-up rod, as per manufacturer’s specifications and sketch at Appendix-‘A’.
Providing and applying 2.5 mm thick road marking strips (retro reflective) of specified shade/ colour using hot thermoplastic material by fully/ semi automatic thermoplastic paint applicator machine fitted with profile shoe, glass beads dispenser, propane tank heater and profile shoe heater, driven by experienced operator on road surface including cost of material, labour, T&P, cleaning the road surface of all dirt, seals, oil, grease and foreign material etc. complete as per direction of Engineer-in-charge and accordance with applicable specifications.
Providing and laying of Filter media with granular materials/stone crushed aggregates satisfying the requirements laid down in clause 2504.2.2. of MoRTH specifications to a thickness of not less than 600 mm with smaller size towards the soil and bigger size towards the wall and provided over the entire surface behind abutment, wing wall and return wall to the full height compacted to a firm condition complete as per drawing and Technical Specification.
Designing and construction of Reinforced Earth Structure(RE Wall) including excavation of foundation, foundation concrete, cement concrete grooved sealing in the foundation for facing elements(facia material), placement of facia element , assembling , joining of facia elements providing complete drainage system for disposal of rain water during the service conditions as well as water added during rising of embankment, covering external drainage pipes with precast cover facia, internal perforated drainage pipes wrapped with geotextile fabric as per approved drawings , providing geotextile filter fabric and 600 mm thick filter media along the base and sides behind the facia wall, sealing of joints EPDM Pad and geotextile etc. as per approved drawing, providing and laying in position galvanized steel strips of approved section and length and connecting with precast facia panels as per design, anchoring in filled up material with nails etc. as per approved design including all materials, Labour, lead and lift, plants, machinery, complete as per directions of Engineer-in Charge complete in all respect as per approved design, MoRTH specification section 3100 and satisfaction to Engineer-In-Charge.( Note:1 The measurement for payment for reinforced soil wall shall be in square meters of work of each face and shall be measured in the plane of final inclination specified in approved drawings. The measurement of length shall be the finished work along the length of road. The measurement of height along the slope shall be done from the top level of the footing on which the the facia element is placed to the top of the capping beam. 2. The cost include design, drawings ,cost of all material , Labour & plant required as mentioned in item and any incidental additional requirements for execution of this item as per MoRTH specifications section 3100 and approved design shall also be treated as included in the item and nothing extra will be paid for such extra work), but excluding the cost of RCC facia element , friction slab ,RCC crash barrier, excavation of foundation , foundation concrete, filter media and 110mm dia PVC perforated pipe and these items shall be paid under respective items.)
Providing & Laying 160mm dia, 10 kg pressure PVC Perforated pipe having outlets of 110 mm dia at every 30 metre intervals as per drawings and direction of Engineer In charge.
Providing and fixing in position single strip seal expansion joint catering to maximum movement of 80mm , comprising two monolithic edge beams with loop anchorage and "V" shape Elastromeric sealing element conforming to MORTH specifications 2013 and IRC : SP-69-2005( guidelines & specifications for expansion joints) as applicable for horizontal joints in the slab including cost of all materials, transportation, labour charges, Neoprene Elastomeric Seal, sundries etc. complete as per drawings with warranty of trouble free maintenance of 10 years and as directed by Engineer-in-Charge.
Supplying, fitting and fixing in position true to line and level POT-PTFE bearing consisting of a metal piston supported by a disc or unreinforced elastomer confined within a metal cylinder, sealing rings, dust seals, PTFE surface sliding against stainless steel mating surface, complete assembly to be of cast steel/fabricated structural steel, metal and elastomer elements to be as per IRC: 83 part-I & II respectively and other parts conforming to BS: 5400, section 9.1 & 9.2 and clause 2006 of MoRTH Specifications complete as per drawing and approved Technical Specifications. 250 MT Capacity
Providing and transporting to work location(s) precast reinforced cement concrete facia panels for Reinforced Soil Structure ( RE wall) made from machine batched and machine mixed design mix M-35 grade cement concrete , using cement content as per approved design mix, pumping of concrete to fabrication yard including design and finishing with approved architectural features and AAI logo, cost of centering, shuttering, finishing ,curing, admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability, improve workability without impairing strength and durability but excluding cost of reinforcement as per direction of Engineer-in-charge.
Providing and laying at or near ground level factory made kerb stone of M-25 grade cement concrete in position to the required line, level and curvature, jointed with cement mortar 1:3 (1 cement: 3 coarse sand), including making joints with or without grooves (thickness of joints except at sharp curve shall not to more than 5mm), including making drainage opening wherever required complete etc. as per direction of Engineer-in-charge (length of finished kerb edging shall be measured for payment). (Precast C.C. kerb stone shall be approved by Engineer-in-charge).
Description of Work / Item(s)
Amount
PART - A - SITC
POINT WIRING
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLSH PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLSH PVC insulated copper conductor single core cable etc. as required. - Group C
Wiring for MCB control primary light point/ fan point/ exhaust fan point/ call bell point with 2.5 sq.mm FRLSH PVC insulated copper conductor single core cable in surface / recessed steel conduit and earthing the point with 2.5 sq.mm FRLSH PVC insulated copper conductor single core cable etc. as required. - (MCB cost is included in the DB)
Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLSH PVC insulated copper conductor single core cable in surface/ recessed steel conduit, and earthing the point with 1.5 sq. mm FRLSH PVC insulated copper conductor single core cable etc. as required. - Group C
Wiring for light plug with 2X2.5 sq. mm FRLSH PVC insulated copper conductor single core cable in surface/ recessed steel conduit along with 1 No. 2.5 sq. mm FRLSH PVC insulated copper conductor single core cable for loop earthing as required.
Wiring for power plug with 2X4 sq. mm FRLSH PVC insulated copper conductor single core cable in surface/ recessed steel conduit along with 1 No. 4 sq. mm FRLSH PVC insulated copper conductor single core cable for loop earthing as required.
Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLSH PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required.
2 x 1.5 sq. mm + 1 x 1.5 sq. mm earth wire
2 x 2.5 sq. mm + 1 x 2.5 sq. mm earth wire.
2 X 6 sq. mm + 1 X 6 sq. mm earth wire (for industrial sockets and SPNDB)
4 X 6 sq. mm + 2 X 6 sq. mm earth wire (for industrial sockets)
4 X 10 sq. mm + 2 X 6 sq. mm earth wire
4 x 16 sq. mm + 2 x 6 sq. mm earth wire
Supply and wiring for circuit/sub main wiring with the following sizes of FRLSH PVC insulated copper conductor unarmoured power cable on existing surface /raceways etc. as required, complying to IS - 7098 and relevant standards.
3 x 2.5 sq. mm
3 x 4 sq. mm
Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. (For ELV Services)
Supplying and fixing of following sizes of Heavy class FR PVC (ISI marked) conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 2 Nos. 3 pin 5/6 amps modular socket outlet and 1 No. 16 amps modular switch, connection etc. as required.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.( for hand dryer)
Supplying and fixing 32 A, 240 V, SPN Industrial type socket outlet (IP-65), with 2 pole and earth, plug top along with 32 A, “C” curve, SP, MCB, in Polycarbonate enclosure, on surface or in recess, with cover for the socket out let and complete with connections, testing and commissioning etc. as required.
Supplying and fixing 32 A, 415 V, TPN Industrial type socket outlet (IP-65), with 4 pole and earth, plug top along with 32 A, “C” curve, TPMCB, in polycarbonate enclosure, on surface or in recess, with cover for the socket out let and complete with connections, testing and commissioning etc. as required.
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
5/6 amp switch
15/16 amp switch
3 pin 5/6 amp socket
6 pin 15/16 amp socket
Supplying and fixing following size / modules, GI box along with modular base & cover plate for modular switches in recess etc. as required.
1 or 2 Module (75mm X 75mm)
3 Module (100mm X 75mm)
4 Module (125mm X 75mm)
6 Module (200mm X 75mm)
8 Module (200mmX125mm)
Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required
DISTRIBUTION BOARDS, MCBs & MCCBs
S/F TP MCB DB: Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB PPI distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/ Isolator)
4 way (4 + 6 +12), Double door, horizontal type
6 way (4 +6+18), Double door, horizontal type
8 way (4 +6+ 24), Double door, horizontal type
12 Way ( 4 + 6 + 36 ) Double Door
S/F prewired SP MCB DB: Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 12 way, Double door
S/F 4P MCB: Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.
S/F DP MCB: Supplying and fixing following rating, double pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.
S/F 'C' series, SP MCB: Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
S/F 'B' series, SP MCB blanking plate: Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
Supplying and fixing following rating, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
40 amps (double pole)
63 amps (TPN)
Supplying and fixing following rating, double pole, 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.
40 amps (double pole)
63 amps (double pole)
All Em. Lighting DB's shall be IP-55/66,UV resistant as per IEC 61439,flame retardant, self extinguishing material for outdoor/harsh environment like resistant to weather influences (humidity, temperature, water sprays)
6 way TPN DB (Flame retardant enclosure as per specs.) INCOMER 1 No. 40A 4 pole MCB (10 KA) OUTGOINGS 18nos. 16A / 20A / 25A /32A SP MCB's (10KA) as required DB as described above
8 way TPN DB (Flame retardant enclosure as per specs.) INCOMER 1 No. 40A 4 pole MCB (10 KA) OUTGOINGS 24 nos. 16A / 20A / 25A /32A SP MCB's (10KA) as required DB as described above
12 way TPN DB (Flame retardant enclosure as per specs.) INCOMER 1 No. 40A 4 pole MCB (10 KA) OUTGOINGS 24 nos. 16A / 20A / 25A /32A SP MCB's (10KA) as required DB as described above
All VTPN DB's, shall be pre assembled with vertical bus bars & IP-55/66,UV resistant as per IEC 61439 ,suitable for outdoor/harsh environment like resistant to weather influences (humidity, temperature, water sprays), chemical resistance etc.
12 way VTPN DB INCOMER 1 No. 100A 4 pole MCCB (16 KA) with earth fault protection OUTGOINGS 36 nos. modules 25A /32A/63A SP/TP MCB's (10KA) as required DB as described above
Providing and fixing 40/63 Amps DP contactors for switching operation of lighting circuit through BMS including providing and fixing sheet steel enclosure and interconnecting with Daylight/lux sensor earthing etc. as required.
Supplying , installation, testing & commissioning of junctions box for D.B outgoings/cables, wires etc. complete with interconnection/bus bars & made of same material & finishes as per specifications of DB's.
Cable End box for 4 way TPN DB
Cable End box for 6 way TPN DB
Cable End box for 8 way TPN DB
Cable End box for 12 way TPN DB
INTERNAL LIGHTING FIXTURES SUPPLY & INSTALLATION
Supply, Installation, testing and commissioning of Recess LED 600x600mm fitting made of CRCA/Extruded Aluminium fixture should have minimum efficacy at System level (Not Chip Level) ≥=120lumens/watt, 3000lm, Life of fixture 50000hrs@L70B50 Lumen maintenance, CCT up to 4000, CRI ≥80, PF ≥0.95, and an operating Voltage Range of 150 - 270 V. Minimum Internal Surge Protection 2.5KV. The fixture should comply with the parameters as per IS10322. Minimum system Lumens 3000. Philips Models RC600B LED30S840 PSU W60L60 /Trilux Model Troffer X Panel-NW ET01 / Wipro-LM29-451XXX-40-TA or equivalent complying to the specifications.(It should not be a simple flat panel with full diffuser of 600mmX600mm/tile type luminaire). Luminaire shall be submitted with certificates consisting of LM79 from NABL accredited lab and LM80 issued by LED manufacturer.
Supply, Installation, testing and commissioning of Recess LED 600x600mm fitting made of CRCA/Extruded Aluminium , fixture should have minimum efficacy at System level (Not Chip Level) ≥=120lumens/watt, 4000lm, Life of fixture 50000hrs@L70B50 Lumen maintenance, CCT up to 4000, CRI ≥80, PF ≥0.95, and an operating Voltage Range of 150 - 270 Internal Surge Protection 2.5KV. The fixture should comply with the parameters as per IS10322 . Minimum system Lumens 4000. Philips Models RC600B LED40S840 PSU W60L60 / Trilux Model Troffer X Panel -NW ET01/Wipro-LM38-461XXX-40-TA or equivalent complying to the specifications. (It should not be a simple flat panel with full diffuser of 600mmX600mm/tile type luminaire).Luminaire shall be submitted with certificates consisting of LM79 from NABL accredited lab and LM80 issued by LED manufacturer.
Supply, Installation, testing and commissioning of Recess LED DALI (Dimmable)600x600mm fitting made of CRCA/Extruded Aluminium fixture should have minimum efficacy at System level (Not Chip Level) ≥=120lumens/watt, 4000lm, Life of fixture 50000hrs@L70B50 Lumen maintenance, CCT up to 4000, CRI ≥80, PF ≥0.95, and an operating Voltage Range of 150 - 270 Internal Surge Protection 2.5KV. The fixture should comply with the parameters as per IS10322.Minimum system Lumens 4000. Philips Models RC600B LED40S840 PSD W60L60 / Trilux Model Troffer X Panel -NW ETDD 01 / Wipro LM38-461-XXX40DATA or equivalent complying to the specifications. (It should not be a simple flat panel with full diffuser of 600mmX600mm/tile type luminaire). Luminaire shall be submitted with certificates consisting of LM79 from NABL accredited lab and LM80 issued by LED manufacturer.
Supply, Installation, testing and commissioning of LED Recessed Down lighter with a nominal system lumen output of 2200 lumens and a minimum system efficacy of 110 lm/W. The luminaire should have a colour temperature of 4000K and CRI≥80. The luminaire shall meet IP20 rating with THD≤10% and PF ≥ 0.95. The luminaire housing should made of die-cast aluminium with polycarbonate/ PMMA/Polystyrene diffuser. The fixture should comply with the parameters as per IS10322. Philips Make DN470B C LED20S/840 PSU / Trilux Orion LED ET/Wipro-CRDL11R023HP40TA or equivalent complying to the specifications. Luminaire shall be submitted with certificates consisting of LM79 from NABL accredited lab and LM80 issued by LED manufacturer.
Supply, Installation, testing and commissioning of LED Recessed Down lighter with a nominal system lumen output of 1200 lumens and a minimum system efficacy of 110 lm/W. The luminaire should have a colour temperature of 4000K and CRI≥80. The luminaire shall meet IP20 rating with THD≤10% and PF ≥ 0.95. The luminaire housing should made of die-cast aluminium with polycarbonate/PMMA/Polystyrene diffuser. The fixture should comply with the parameters as per IS10322. Philips Make DN460B C LED11S/840 PSU / Trilux Ambiella Plus IND G3 LED 1000-840 ET/Wipro - CRDL11R017HP40TA or equivalent complying to the specifications. Luminaire shall be submitted with certificates consisting of LM79 from NABL accredited lab and LM80 issued by LED manufacturer.
Supply, Installation, testing and commissioning of LED Recessed Down lighter with a nominal system lumen output of 800 lumens and a minimum system efficacy of 110 lm/W. The luminaire should have a colour temperature of 4000K and CRI≥80. The luminaire shall meet IP20 rating with THD≤10% and PF ≥ 0.95. The luminaire housing should made of pressure die-cast aluminium with a high efficiency diffuser. The fixture should comply with the parameters as per IS10322. Philips Make Green perform series / Trilux Ambiella IND G3 LED 640-840 ET /Wipro- CRDL11R013HP40LA or equivalent complying to the specifications. Luminaire shall be submitted with certificates consisting of LM79 from NABL accredited lab and LM80 issued by LED manufacturer.
Supply, Installation, testing and commissioning of LED 4ft Batten with a nominal system lumen output of 4000 lumens and a minimum system efficacy of 100 lm/W. The luminaire shall have a rated system lifetime of 40,000 burning hours at L70. The luminaire should have a colour temperature of 5700/6500K and CRI≥80. The luminaire shall meet IP20 rating with THD ≤ 10% and PF ≥ 0.95. The luminaire housing should made of CRCA with diffuser. Philips Make ENDURALED BATTEN "BN 108C LED 40S PSU CDL WH" / Trilux TRL OTA 3600 - 860 ET IP 20/Wipro- LE10-491-XXX57TA or equivalent complying to the specifications. Luminaire shall be submitted with certificates consisting of LM79 from NABL accredited lab and LM80 issued by LED manufacturer.
Supply, Installation, testing and commissioning of LED 4ft Batten with a nominal system lumen output of 2000 lumens and a minimum system efficacy of 100 lm/W. The luminaire shall have a rated system lifetime of 40,000 burning hours at L70. The luminaire should have a colour temperature of 5700 /6500K and CRI≥80. The luminaire shall meet IP20 rating with THD ≤ 10% and PF ≥ 0.95. The luminaire housing should made of CRCA with a PC glossy diffuser. Philips Make ENDURALED BATTEN "BN 108C LED 20S PSU CDL WH" / Trilux TRL OTA 1800 - 860 ET IP 20/Wipro- LE10-251-XXX57TA or equivalent complying to the specifications. Luminaire shall be submitted with certificates consisting of LM79 from NABL accredited lab and LM80 issued by LED manufacturer.
Supply, Installation, testing and commissioning of High Pressure Die Cast Aluminium Alloy housing LED High Bay Luminaire of 9000 system lumen & system efficacy of ≥ 120lm/w specially designed heat sinks dust free. For high ceiling heights having beam Angle 60 deg. / 90Degree, proper Lenses for effective light distribution & polycarbonate cover/toughened glass, Luminous flux (Lumen)9000. Correlated Colour Temp 4000/5000/6500k, CRI≥70, Maintenance of lumen L70 (Hrs.) 50K@L70,Ambient temperature (Ta) 45Degree. Protection of Fixture:- IP65, power factor ≥0.95, Surge protection 4KV, Voltage range 150-270V AC, the fixture should comply other parameters as per IS:10322. LM 79 and LM80 reports need to be submitted from a NABL Approved Laboratory. Philips Maxoled BY415 LED90S FG PSU / Trilux LBL 10400 ET 120D / Wipro - LH17-132-090-50-PU/ LH17-132-060-50-PU / LH17-132-090-40-PU/ LH17-132-060-40-PU or equivalent complying to the specifications. The fixtures shall be supplied with the painting and finishings similar to the baffles/ceiling colour pattern required at site. (Fixtures shall also be supplied with polycarbonate junction box suitable for loop in loop out of 3x4 sq. mm power cable and 2x1.5 sq.mm wire for automation controls.) Luminaire shall be submitted with certificates consisting of LM79 from NABL accredited lab and LM80 issued by LED manufacturer.
Supply, Installation, testing and commissioning of High Pressure Die Cast Aluminium Alloy housing LED High Bay Luminaire of 16500 system & system efficacy of ≥ 120lm/w lumen specially designed heat sinks dust free. For high ceiling heights having beam Angle 60 deg. / 90Deg, proper Lenses for effective light distribution & polycarbonate cover/toughened glass, Luminous flux (Lumen)16500.Corelated Colour Temp 4000/5000/6500k, CRI≥70, Maintenance of lumen L70 (Hrs.) 50K@L70,Ambient temperature (Ta) 45Degree, Protection of Fixture:- IP65, power factor ≥0.95, Surge protection 4KV,Votage range 150-270V AC, the fixture should comply other parameters as per IS:10322. LM 79 and LM80 reports needs to be submitted from a NABL Approved Laboratory. Similar to Philips Maxoled BY415 LED160S FG PSU / Trilux LBL 15600 ET 120D / Wipro- LH17-192-090-50-PU/ LH17-192-060-50-PU / LH17-192-090-40-PU/ LH17-192-060-40-PU or equivalent complying to the specifications. The fixtures shall be supplied with the painting and finishings similar to the baffles/ceiling colour pattern required at site. (Fixtures shall also be supplied with polycarbonate junction box suitable for loop in loop out of 3x4 sq. mm power cable and 2x1.5 sq.mm wire for dimming automation controls.) Luminaire shall be submitted with certificates consisting of LM79 from NABL accredited lab and LM80 issued by LED manufacturer.
Supply, Installation, testing and commissioning of Surface Mounted Linear LED maximum 60 mm wide fitting with housing made of Extruded Aluminium and anodized finish. The diffuser should be Extruded Polycarbonate/PMMA/Polystyrene. The luminaire should have options for standalone (4ft) unit lengths and should also have provision for continuous mounting. LED Used shall be SMD type and fixture should have minimum efficacy at System level (Not Chip Level) ≥=110lumens/watt, Life of fixture 50000hrs@L70, CCT choice available in 4000K and 5700/6500K, CRI ≥80, PF ≥0.95, THD≤10%, an operating Voltage Range of 150 - 270 V, 50Hz,IP-20 . Minimum Internal Surge Protection 2.5KV. The fixture should comply with the parameters as per IS10322. Minimum system Lumens 2600 for a 4ft luminaire. Philips Model Pure line Slim SP780 X LED26S-4000/6500 PSU W6L112 OD SI / Trilux LCL H 1200 OTA 52 LED 2000-840 ET /Wipro-LM34-401XXX-57SMTA / LM34-401XXX-40SMTA or equivalent complying to the specifications. The fixtures shall be supplied with the painting and finishing similar to the baffles/ceiling colour pattern required at site. (Fixtures shall also be supplied with polycarbonate junction box suitable for loop in loop out of 3x4 sq. mm power cable and 2x1.5 sq.mm wire for automation controls.) ( For lighting fixtures in non A.C areas 5700/6500 k to be provided). Luminaire shall be submitted with certificates consisting of LM79 from NABL accredited lab and LM80 issued by LED manufacturer.
Supply, Installation, testing and commissioning of Surface/ceiling suspended Linear LED maximum 60 mm wide fitting with housing made of Extruded Aluminium and anodized finish. The diffuser should be Extruded Polycarbonate/PMMA/Polystyrene. The luminaire should have options for standalone (8ft) unit lengths and should also have provision for continuous mounting. LED Used shall be SMD type and fixture should have minimum efficacy at System level (Not Chip Level) ≥=110lumens/watt, Life of fixture 50000hrs@L70, CCT choice available in 4000/ 5700 / 6500K, CRI minimum 80, PF ≥0.95, THD≤10%, an operating Voltage Range of 150 - 270 V, 50Hz,IP-20 . Minimum Internal Surge Protection 2.5KV. The fixture should comply with the other parameters as per IS10322 and specifications. Minimum system Lumens 5200 for a 8ft luminaire. Wipro-LM34-501XXX-57SMTA / LM34-501XXX-40SMTA / Philips Model Pure line Slim SP780 X LED52S PSU W6L224 OD SI / Trilux LCL H 2400 OTA 75 LED 5200-840 ETD 01 / and complying to the specifications. The fixtures shall be supplied with the painting and finishing similar to the baffles/ceiling colour pattern required at site. (Fixtures shall also be supplied with polycarbonate junction box suitable for loop in loop out of 3x4 sq. mm power cable and suitable wire for automation controls.) Luminaire shall be submitted with certificates consisting of LM79 from NABL accredited lab and LM80 issued by LED manufacturer.
Supply, Installation, testing and commissioning of Linear profiles for cove lighting with Low profile housing height of 21 mm (.86 in), including mounting clips. The housing should be of Extruded polycarbonate, white finish. The lens should be of clear polycarbonate. The luminaire should have options for standalone (4ft) unit lengths and should also have provision for continuous mounting with 110 degrees beam angle. LED Used shall be SMD type and fixture should have minimum efficacy at System level (Not Chip Level) ≥=100lumens/watt, Life of fixture 50000hrs@L70B50 Lumen maintenance, CCT choice available in 4000K and 3000K, CRI ≥80, PF ≥0.9, THD≤10%, an operating Voltage Range of 150 - 270 V, 50Hz. The luminaire should be suitable to work in damp location, IP40 and IK08 rated. The fixture should comply with the parameters as per IS10322 Minimum system Lumens 1100 for a 4ft luminaire. Philips Model Vaya cove LP G2, 1219mm / Trilux LED Cove 1200/ Wipro-4ft COVE LIGHT or equivalents. Luminaire shall be submitted with certificates consisting of LM79 from NABL accredited lab and LM80 issued by LED manufacturer.
Supply, Installation, testing and commissioning of LED bulkhead suitable for surface/wall mounting, powder coated extruded aluminium/standard alloy housing, comprising of LED’s of approved makes with Constant current output Switchable electronic driver with THD≤10%, Power factor 0.95 or higher, having a system level lumen of 600 lumens with luminaire efficacy of not less than 95 lm/W, CRI≥80, IP rating - IP65 or higher, Service Life of luminaire minimum L70, 50,000 burning hours).& as per specifications as required. (Similar to Philips Catalogue No WT202W LED6S XX PSU S2 PC / Trilux OPTIMA LED BULKHEAD / Wipro - LW03-850-XXX-57-TA or equivalents. Luminaire shall be submitted with certificates consisting of LM79 from NABL accredited lab and LM80 issued by LED manufacturer.
Supply, Installation, testing and commissioning of 1200mm ceiling fans complete with double ball bearing, motor, blades, canopies, capacitor etc. suitable for operation on 230 volts, 50 Hz., 1 phase, AC supply complete as required. ceiling fan, including wiring the down rods of length (upto 100 cm) with 1.5 sq. mm FR PVC insulated, copper conductor, single core cable, including providing and fixing phenolic laminated sheet cover on the fan box etc. as required.
Supplying, installation, testing and commissioning of Passive Infrared(PIR) technology based occupancy sensor having high performance, non regulating programmable type, suitable for connected load upto 10 A, for mounting height up to 2.8 meter and for 5-7 meter diameter coverage area along with necessary fixing arrangements i/c programming at site etc. complete as required. Similar to Wipro Catalogue No.: CRPS10R010A
Supplying, installation, testing and commissioning of networkable on KNX dual technology based occupancy sensor having high performance, non regulating programmable type, suitable for connected load upto 10 A, for mounting height up to 2.6 meter and for 5m X 15m coverage area along with necessary fixing arrangements i/c programming at site etc. complete as required.
Supplying, installation, testing and commissioning of Astronomical time switch of following configuration to be mounted in feeder pillars / Lighting DBs for automatic switching On & OFF of street lights at sun set & sun rise or twilight(Auto ON, Auto OFF, Auto modes) with manual override facility with 12/24 hour display format with suitable battery and indication for relay status i/c programming at site complete as required.
Supplying, installation, testing and commissioning of Lighting Automation system complete with Relays, controllers, sensors required as per number of fixtures as per site requirement & consisting of the followings.
Supply, installation, testing & commissioning of 12 channel KNX switching Actuator with 10A on each channel having the capability to control Delay function, staircase lighting function, with or without manual On/off function. , central function, disable function, logic operation or priority control. status feedback function for each channel & behaviour on bus voltage recovery etc. as required and as per technical specification. It should Also Include Din Rail mount Power supply Unit for KNX devices generating the bus voltage of 30VDC with 640mA of current for a Line , which have the Capability of supporting 64 KNX devices with integrated choke and short circuit protection etc. as required and as per technical specification.
Supply, Installation, Testing & Commissioning of Astronomical timer for the timer application. Network power supply to feed the power to the network complete in all respect as required per site.
Supply, Installation, Testing & Commissioning of Networked Daylight Sensors for the detection of ambient lux level and maintain the required lux level accordingly complete in all respect as required per site.
Supply, installation, testing & commissioning of IP Gateway or interface between KNX networks and BMS IP networks. This gateway should be from the same OEM who also manufactures above will be supplying the above mentioned products like the actuator & power supplies for seamless connectivity & operation as data can thereby be exchanged between system devices and devices on the IP network(Router) giving BMS control of Lighting alongwith Area Control. Further ensuring the linkages of Metering (Modbus offer, Smart link RTU and IP) on the same device and connect to BMS including Modbus /Banet or RS485 port built onto it etc. as required and as per technical specification. It should be Complete with power Supply and required enclosure.
Supply, installation, testing & commissioning of Communication Cable (2x2x0.8) 4 Core to connect Relay Actuator, Time Clock, BMS Gateway, Automation Sensor. It should comply EIBA guideline with DIN VDE 0207 & VDE 0815 etc. as required and as per technical specification.
Supply, Installation, Testing & Commissioning of Local Enclosure to contain relays and MCB's complete in all respect as required per site.
Supplying, installation, testing & commissioning of LED Aviation light luminaries including required driver/ control box, protections, above the highest point of terrace level and making good the same. It should switch ON automatically as required in night time & OFF in day time including FRLS copper control wiring etc. complete in all respect as required & as approved by the Engineer Incharge. (Cat . No. Bajaj BGAV 302 LED or equivalent from approved makes/ CLIENT). (fixing height may please be considered as per the site requirement).
LIGHTNING PROTECTION SYSTEM
Supply, Installation, and Fixing of Air Terminal 2mtr.Trapezoidal Dia. (Ø16 / 10 mm), Material Al, Complying to standard EN 62561-2 complete in all respect as required.
Supply, Installation, and Fixing of Clamp for connecting air terminal rod to 8mm Conductor, Material Al, Clamping Range 16 mm & 2x8-10 mm, Complied to standard EN 62561-1 complete in all respect as required.
Supply, Installation, and Fixing of Universal Clamp, Material Stainless steel, Clamping range Rd 8-10 mm, Complied to standard EN 62561-2 complete in all respect as required.
Supply, Installation, and Fixing of Al Round Conductor on roof (Ø 8mm), Diameter 8 mm, Material AlMgSi, Complied to standard EN 62561-2 complete in all respect as required.
Supply, Installation, and Fixing of Al Down Conductor Holder for Metal / Roof Sheet with accessories Stainless Steel Self-Threaded Screw With washer, Complying to standard EN 62561-1 complete in all respect as required.
Supply, Installation, and Fixing of Al Round Conductor for Down Conductor (Ø 8mm), Material AlMgSi, Complying to standard EN 62561-2 complete in all respect as required.
Supply, Installation, and Fixing of Al Down Conductor Holder for Metal / Roof Sheet with accessories Stainless Steel Self-Threaded Screw With washer, Complying to standard EN 62561-1 complete in all respect as required.
Supply, Installation, and Fixing of Test Clamp, Material StSt, Complying to standard EN 62561-1 complete in all respect as required.
Supply, Installation, and Fixing of GI Strip for Down Conductor to earth (25x6 mm) complete in all respect as required.
Supply, Installation, and Fixing of GI Strip holder (25x6 mm) complete in all respect as required.
Supply, Installation, and Fixing of 17.2 mm Copper bonded UL listed rod of 3 mtr. length complete in all respect as required.
Supply, Installation, and Fixing of Environment friendly, RoHS certified, low resistivity Ground Enhancement material in 22.6 Kg pack to fill the bore area around the rod complete in all respect as required.
Supply, Installation, and Fixing of StSt 316 grade clamp to terminate the load on earth electrode complete in all respect as required.
Supply, Installation, and Fixing of Poly Plastic Pit Cover complete in all respect as required.
Supply, Installation, and Fixing of GI Strip 25x6mm for Interconnecting Earth Pits complete in all respect as required.
EXTERNAL ROAD LIGHTING
Supply, assembly, erection, connecting, testing & commissioning of standard 10.0 metre high (above ground) GRP Pole (Pressures as per IS 875 Part-3), with stiffeners, chain, Allen bolt, single arm bracket, foundation bolts, pre fabricated plate, template, accessories, nut and washers, factory finish, Base plate. The column shall also be provided with flush door at the bottom with proper strengthening to the cut-out of the door opening, an outdoor IP-66 rated junction/ looping box with Heavy duty 3 phase & Neutral, 32 Amp connector with 10A DP MCB, double earthing arrangements, including all accessories complete as required as per specifications & approved by the Engineer Incharge.
Supply, Installation, testing and commissioning of Epoxy powder coated pressure die-cast aluminium housing with weatherproof gasket for LED including 135 W LED sand control gear compartments, frame with heat resistant toughened clear glass fixed with SS screws. Colour temp. – 5700K/6500K with 10kV external surge protector, Input voltage range: 150–270V AC. Side entry mounting for 50 to 60 mm OD pipe bracket. Philips BRP322 LED 138 CW HE NR PC S3 XT or Trilux Endora 15000 or Wipro LR-02-182-xxx-57-TA or equivalents.
Supply, Installation, Testing and Commissioning of LED Post Top having Top Red Illuminated for Aesthetic & Night Lilly Appearance with a system lumen output of 7000 lumens in symmetric distribution, and a minimum system efficacy of 100 lm/W, Along with 0.7m Standard Pole, The luminaire shall have a rated system lifetime of 50,000 burning hours at L70. System wattage 70W, The luminaire should have a colour temperature of 5700K and CRI > 70 and IK10 with IEC 60598 certification. The luminaire shall meet IP66 with THD < 10% and PF > 0.9. Operating Voltage 140-270VAC,The luminaire shall have closed diffused optics with polycarbonate diffuser board. The total power consumption should not exceed 70W (including driver). Similar to Philips City cube post top series 70W/ Trilux Tx Publisca 67 W or equivalent (Including 5 Meter Pole as per OEM/Lighting manufacturer)
Supply, Installation, Testing and Commissioning of LED Post Top having Top Red Illuminated for Aesthetic & Night Lilly Appearance with a system lumen output of 7000 lumens in symmetric distribution, and a minimum system efficacy of 100 lm/W, Along with 0.7m Standard Pole, The luminaire shall have a rated system lifetime of 50,000 burning hours at L70. System wattage 35W, The luminaire should have a colour temperature of 5700K and CRI > 70 and IK10 with IEC 60598 certification. The luminaire shall meet IP66 with THD < 10% and PF > 0.9. Operating Voltage 140-270VAC,The luminaire shall have closed diffused optics with polycarbonate diffuser board. The total power consumption should not exceed 35W (including driver). Similar to Philips City cube post top series 35W / Trilux Tx Publisca 40 W or equivalent (Including 3 Meter Pole as per OEM/Lighting manufacturer)
Supply, Installation, Testing and Commissioning of 20M high mast shaft in two sections suitable for wind speed as per specifications, with raising lowering system comprising, head frame, luminaries carriage suitable to install 12 nos. luminaries in symmetrical arrangement, double drum winch, 6mm diameter SS wire rope, trailing cable, connector, integral power tool motor, manual handle, junction box, lightening finial. (Wiring material from JB to individual luminaire & MCB in base compartment are not included and are a part of installation).
Drum winch, 6mm diameter SS wire rope, trailing cable, connector, integral power tool motor, manual handle, junction box, lightening finial. (Wiring material from JB to individual luminaire & MCB in base compartment are not included and are a part of installation).
Supply, Installation, Testing and Commissioning of foundation bolts manufactured from special steel along with nuts, washers, anchor plate and common template.
Supply, Installation, Testing and Commissioning of LED floodlight type 350 Watt outdoor type complete with fixing arrangement etc. complete as required.
Supply, Installation, Testing and Commissioning of LED type single dome aviation obstruction light outdoor type complete with fixing arrangement etc. complete as required.
Supply, Installation, Testing and Commissioning of outdoor stand mounted feeder pillar with 63A TPN MCB incomer, single dial time switch, 45A TP contactor for the automatic switching of luminaries, power tool control with 2 no 9A contactors and raise lower push button, Incoming 35 sq. mm and out going 16 & 2.5 sq. mm terminals etc. complete as required.
Providing, laying, fixing, connecting and testing of undernoted sizes of GI strip/GI wire from earth electrode to equipment loop and earthing system, in trenches, on surfaces, along pole or along M.S. support, etc. including excavation where required for laying the copper strip/ GI strip and filling back complete, conforming to relevant IS and all as specified.
GI wire 8 SWG
GI wire 6 SWG
Hot dip GI strip 25mmx 5mm on surface or in recess
Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia. including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required.
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required.
63 mm dia. (OD-63 mm & ID-51 mm nominal)
90 mm dia. (OD-90 mm & ID-76 mm nominal)
120 mm dia. (OD-120 mm & ID-103 mm nominal)
160 mm dia. (OD-160 mm & ID-135 mm nominal)
EXTERNAL ELECTRICAL WORKS
HT PANELS
33 KV HT MAIN PANEL BOARD - MAIN RECEIVING SUBSTATION (LOC: SERVICE YARD)
Supply, Installation, Testing and Commissioning of indoor type floor mounted metal clad, fabricated of 2 mm thick CRCA/Aluzinc sheet, 33 KV, VCB Panel with (07) Nos. VCBs, totally enclosed & electrically interlocked, horizontal drawout on floor, horizontal isolation type VCB as per IEC62271-100 for breakers and 200 for panels/ IS3247 of switch board, as per specifications, having capacities as mentioned below, single break, trip free mechanism, electrical and manually charged and closing breaker suitable for use on 33 KV, 3Phase, 50Hz A.C. supply , complete with self contained electrically interlocked rack in and rack out mechanism, air insulated and encapsulated copper bus bars , breaker featured with mechanical ON/ OFF indicator with hand trip device, spring release coil, shunt trip coil and auxiliary switch of 4NO + 4NC and equipped with following switchgears and accessories i/c connections suitable for 2 R X 3C X 300 sq.mm. XLPE 33 kV cable as incomer as well as outgoing feeder. STC 26.3 kA for 3 sec , Internal Arc Test for AFLR 26.3 kA for 1 sec. at individual compartments i.e. Busbar, VCB and cable compartment. All major sub-components (switchgear, relays & vacuum interrupters) shall be of same make. Separate earthing truck shall be required for each bus earthing & cable earthing. Earthing truck shall be so designed that it is impossible to earth a live. It shall be provided with capacitive voltage divider and complete with audio visual annunciation, one for each panel. (noted: cost of end termination are not included in this Item s & cable entry from bottom considered).
The panel shall be complete with suitable surge protection device required for the suitable voltage level and withstanding current.
02nos. Incomer VCB Panels, each comprising of
33kV, 630A, Vacuum Circuit Breaker
Set of 03nos. Cast resin insulated Dual core dual ratio CT, 33kV, 200-100/5-5A, Core1: Class 5P10, 10VA, Core2: Class 0.5, 10VA
Breaker control switch 240 V AC, spring charging motor 24 V, DC Shunt/tripping coil/closing coil Lockable type, Trip/Neutral/Close (TNC) Switch, Set of ON/OFF/TRIP indicating, Set of R/Y/B Phase indicating lamps, Clear lamp for Trip Circuit healthy supply & Trip Circuit fails, DC Control Supply healthy & fails, indicating lamps. LED Illumination lamp ON / OFF with limit Switch, space heater with switch 6/16 amps 5 Pin switch socket outlet, control terminal as required. Auxiliary contact for Aux. relays for Anti Pumping & indication, electrically/Mechanically interlocking etc. as required, 8 window alarm annunciator with windows and buzzer, rest push button for electrical faults in incomer panel, complete with FRLS wiring, Terminal Blocks, cable-ducts, protection MCBs.
01 No. for each breaker:- Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port and protection MCBs. and required accessories to complete the system.
Numerical Protection Relay, modular design , confirming to IEC 60255, protection scheme for detecting, indicating and tripping the breaker on critical faults like (i) over current & short circuit 51,51N & one earth fault element in the three phases, (ii) negative sequence currents due to line-to-line or conductor-break faults, (iii) residual and three-phase under-voltages/over-voltages, (iv) circuit-breaker-failure alarm, (v) tripping-circuit-failures and interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (vi) Master-Trip and Trip-Circuit Supervision The relay shall be integrated with the feeder, capturing status like Breaker On/Off/Spring. Charged/Test/Service/AC-Fail, Line-Current, Line-Voltage etc. and display the same on graphical display (MIMIC), remote communication on IEC61850 platform on Ethernet. Arc Flash Protection Shall be provided: Sensing of any ARC produced in any of the 3 chambers i.e. Breaker, Cable and Busbar apart from Protection features, along with arc sensors , fibre cables etc. along with other accessories to complete the system.
03nos. Outgoing VCB Panels as Trafo Feeders, each comprising of
33kV, 630A, Vacuum Circuit Breaker
Set of 03nos. Cast resin insulated Dual core dual ratio CT, 33kV, 100-50/5-5A, Core1: Class 5P10, 10VA, Core2: Class 0.5, 10VA
Breaker control switch 240 V AC, spring charging motor 24 V, DC Shunt/tripping coil/closing coil Lockable type, Trip/Neutral/Close (TNC) Switch, Set of ON/OFF/TRIP indicating, Set of R/Y/B Phase indicating lamps, Clear lamp for Trip Circuit healthy supply & Trip Circuit fails, DC Control Supply healthy & fails, indicating lamps. LED Illumination lamp ON / OFF with limit Switch, space heater with switch 6/16 amps 5 Pin switch socket outlet, control terminal as required. Auxiliary contact for Aux. relays for Anti Pumping & indication, electrically/Mechanically interlocking etc. as required, 12 window alarm annunciator with windows and buzzer, rest push button for electrical faults in incomer panel, complete with FRLS wiring, Terminal Blocks, cable-ducts, protection MCBs.
01 No. for each breaker:- Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port and protection MCBs. and required accessories to complete the system.
Numerical Protection Relay, modular design , confirming to IEC 60255, protection scheme for detecting, indicating and tripping the breaker on critical faults like (i) Differential/Unit protection of Transformer (ii) Restricted Earth Fault for solidly grounded transformer on Secondary side (iii) Over-Current & Earth-Fault detection for both Transformer primary and secondary (iv) Negative sequence faults due to line-to-line or conductor break (v) Three-phase under/over-voltage protection (vi) Transformer auxiliary protections (vii) circuit-breaker-failure alarm, (viii)OTI/WTI Alarm (ix)Master-Trip and Trip-Circuit Supervision (x) tripping-circuit-failures and interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. The relay shall be integrated with the feeder, capturing status like Breaker On/Off/Spring. Charged/Test/Service/AC-Fail, Line-Current, Line-Voltage etc. and display the same on graphical display (MIMIC), remote communication on IEC61850 platform on Ethernet. Arc Flash Protection Shall be provided: Sensing of any ARC produced in any of the 3 chambers i.e. Breaker, Cable and Busbar apart from Protection features, along with arc sensors , fibre cables etc. along with other accessories to complete the system.
02nos. Bus Coupler Panels, each comprising of
33kV, 630A, Vacuum Circuit Breaker including associated Bus riser PT panels consisting of suitable burden & class of PT's.
Set of 03nos. Cast resin insulated Dual core dual ratio CT, 33KV, 200-100/5-5A, Core1: Class 5P10, 10VA, Core2: Class 0.5, 10VA
Breaker control switch 240 V AC, spring charging motor 24 V, DC Shunt/tripping coil/closing coil Lockable type, Trip/Neutral/Close (TNC) Switch, Set of ON/OFF/TRIP indicating, Set of R/Y/B Phase indicating lamps, Clear lamp for Trip Circuit healthy supply & Trip Circuit fails, DC Control Supply healthy & fails, indicating lamps. LED Illumination lamp ON / OFF with limit Switch, space heater with switch 6/16 amps 5 Pin switch socket outlet, control terminal as required. Auxiliary contact for Aux. relays for Anti Pumping & indication, electrically/Mechanically interlocking etc. as required, 8 window alarm annunciator with windows and buzzer, rest, rest push button for electrical faults in incomer panel, complete with FRLS wiring, Terminal Blocks, cable-ducts, protection MCBs
Numerical Protection Relay, modular design , confirming to IEC 60255, protection scheme for detecting, indicating and tripping the breaker on critical faults like (i) Synchro-Check and Energizing Check b/w bus-voltages on either side of coupler (ii) circuit-breaker-failure alarm, (iii) tripping-circuit-failures and interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (iv) Master-Trip and Trip-Circuit Supervision
01no. Bus PT Panels comprising of
The Bus PT panel shall be installed in the remaining bus-section(s) which does not have any other Bus PT connected to it.
LEDs for R-Y-B
The panel shall be complete with FRLS wiring, Terminal Blocks, cable-trays, isolation MCBs, CFL illumination, power-socket and space-heater with thermostat as per requirement.
Busbars
800 amps TP,36 KV air insulated and encapsulated copper Bus bar of suitable size as per panel configuration.
230V, single phase 2 wire AC to 24V DC Batteries ,charger with semiconductor/IGBT full wave rectifier with auto /manual float cum boost facility complete with 24V DC, 120 AH sealed maintenance free batteries including one no. distribution board having 32 Amps DP MCB as incomer and 8 Nos. 20/16A DP MCB's (D.C. duty) as outgoing complete as required and as per technical specifications.
11 KV MAIN HT PANEL BOARD (LOC: SERVICE YARD)
Supply, Installation, Testing and Commissioning of indoor type floor mounted metal clad, fabricated of 2 mm thick CRCA/Aluzinc sheet, 11 kV, VCB Panel with (12) Nos. VCBs, totally enclosed & electrically interlocked, horizontal drawout on floor, horizontal isolation type VCB as per IEC62271-100 for breakers and 200 for panels/ IS3247 of switch board, as per specifications, having capacities as mentioned below, single break, trip free mechanism, electrical and manually charged and closing breaker suitable for use on 11 kV, 3Phase, 50Hz A.C. supply , complete with self contained electrically interlocked rack in and rack out mechanism, air insulated and encapsulated copper bus bars, breaker featured with mechanical ON/ OFF indicator with hand trip device, spring release coil, shunt trip coil and auxiliary switch of 4NO + 4NC and equipped with following switchgears and accessories i/c connections suitable for 2 R X 3C X 300 sq.mm. XLPE 11 kV cable as incomer as well as outgoing feeder. STC 26.3 kA for 3 sec , Internal Arc Test for AFLR 26.3 kA for 1 sec. at individual compartments i.e. Busbar, VCB and cable compartment. All major sub-components (switchgear, relays & vacuum interrupters) shall be of same make. Separate earthing truck shall be required for each bus earthing & cable earthing. Earthing truck shall be so designed that it is impossible to earth a live. It shall be provided with capacitive voltage divider and complete with audio visual annunciation, one for each panel. (noted: cost of end termination are not included in this Item s & cable entry from bottom considered).
The panel shall be complete with suitable surge protection device required for the suitable voltage level and withstanding current.
03nos. Incomer VCB Panels each comprising of
11kV, 630A, Vacuum Circuit Breaker
Set of 03nos. Cast resin insulated Dual core dual ratio CT, 11kV, 300-150/5-5A, Core1: Class 5P10, 10VA, Core2: Class 0.5, 10VA
Set of 03nos. Cast resin Current Transformers 11kV, 300/5, Class PS, 5VA for REF Protection
Breaker control switch 240 V AC, spring charging motor 24 V, DC Shunt/tripping coil/closing coil Lockable type, Trip/Neutral/Close (TNC) Switch, Set of ON/OFF/TRIP indicating, Set of R/Y/B Phase indicating lamps, Clear lamp for Trip Circuit healthy supply & Trip Circuit fails, DC Control Supply healthy & fails, indicating lamps. LED Illumination lamp ON / OFF with limit Switch, space heater with switch 6/16 amps 5 Pin switch socket outlet, control terminal as required. Auxiliary contact for Aux. relays for Anti Pumping & indication, electrically/Mechanically interlocking etc. as required, 8 window alarm annunciator with windows and buzzer, ack, rest, rest push button for electrical faults in incomer panel, complete with FRLS wiring, Terminal Blocks, cable-ducts, protection MCBs.
01 No. for each breaker:- Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port and protection MCBs. and required accessories to complete the system.
Numerical Protection Relay, modular design , confirming to IEC 60255, protection scheme for detecting, indicating and tripping the breaker on critical faults like (i)over current & short circuit 51,51N & one earth fault element in the three phases, (ii) negative sequence currents due to line-to-line or conductor-break faults, (iii) residual and three-phase under-voltages/over-voltages, (iv) circuit-breaker-failure alarm, (v) tripping-circuit-failures and interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (vi) Master-Trip and Trip-Circuit Supervision The relay shall be integrated with the feeder, capturing status like Breaker On/Off/Spring. Charged/Test/Service/AC-Fail, Line-Current, Line-Voltage etc. and display the same on graphical display (MIMIC), remote communication on IEC61850 platform on Ethernet. Arc Flash Protection Shall be provided: Sensing of any ARC produced in any of the 3 chambers i.e. Breaker, Cable and Busbar apart from Protection features, along with arc sensors , fibre cables etc. along with other accessories to complete the system.
07 nos. Outgoings VCB Panel each comprising of
11kV, 630A, Vacuum Circuit Breaker
2 Set of 03nos. Cast resin insulated Dual core dual ratio CT, 11kV, 300-150/5-5A, Core1: Class 5P10, 10VA, Core2: Class 0.5, 10VA ;
5 Set of 03nos. Cast resin insulated Dual core dual ratio CT, 11kV, 200-100/5-5A, Core1: Class 5P10, 10VA, Core2: Class 0.5, 10VA ;
Breaker control switch 240 V AC, spring charging motor 24 V, DC Shunt/tripping coil/closing coil Lockable type, Trip/Neutral/Close (TNC) Switch, Set of ON/OFF/TRIP indicating, Set of R/Y/B Phase indicating lamps, Clear lamp for Trip Circuit healthy supply & Trip Circuit fails, DC Control Supply healthy & fails, indicating lamps. LED Illumination lamp ON / OFF with limit Switch, space heater with switch 6/16 amps 5 Pin switch socket outlet, Control terminal as required. Auxiliary contact for Aux. relays for Anti Pumping & indication, electrically/Mechanically interlocking etc. as required, 8 window alarm annunciator with windows and buzzer, rest, rest push button for electrical faults in incomer panel, complete with FRLS wiring, Terminal Blocks, cable-ducts, protection MCBs
01 No. for each breaker:- Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port and protection MCBs. and required accessories to complete the system.
Numerical Protection Relay, modular design , confirming to IEC 60255, protection scheme for detecting, indicating and tripping the breaker on critical faults like (i)over current & short circuit 51,51N & one earth fault element in the three phases, (ii) negative sequence currents due to line-to-line or conductor-break faults, (iii) residual and three-phase under-voltages/over-voltages, (iv) circuit-breaker-failure alarm, (v) tripping-circuit-failures and interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (vi) Master-Trip and Trip-Circuit Supervision The relay shall be integrated with the feeder, capturing status like Breaker On/Off/Spring. Charged/Test/Service/AC-Fail, Line-Current, Line-Voltage etc. and display the same on graphical display (MIMIC), remote communication on IEC61850 platform on Ethernet. Arc Flash Protection Shall be provided: Sensing of any ARC produced in any of the 3 chambers i.e. Breaker, Cable and Busbar apart from Protection features, along with arc sensors , fibre cables etc. along with other accessories to complete the system.
02nos. Bus Coupler Panels, each comprising of
11kV, 630A, Vacuum Circuit Breaker Panel
Numerical Protection Relay, modular design, confirming to IEC 60255, protection scheme for detecting, indicating and tripping the breaker on critical faults like (i) Synchro-Check and Energizing Check b/w bus-voltages on either side of coupler (ii) circuit-breaker-failure alarm, (iii) tripping-circuit-failures and tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. The relay shall be integrated with the feeder, capturing status like Breaker On/Off/Spring. Charged/Test/Service/AC-Fail, Line-Current, Line-Voltage etc. and display the same on graphical display (MIMIC), remote communication on IEC61850 platform on Ethernet. Arc Flash Protection Shall be provided: Sensing of any ARC produced in any of the 3 chambers i.e. Breaker, Cable and Busbar apart from Protection features, along with arc sensors , fibre cables etc. along with other accessories to complete the system.
Breaker control switch 240 V AC, spring charging motor 24 V, DC Shunt/tripping coil/closing coil Lockable type, Trip/Neutral/Close (TNC) Switch, Set of ON/OFF/TRIP indicating, Set of R/Y/B Phase indicating lamps, Clear lamp for Trip Circuit healthy supply & Trip Circuit fails, DC Control Supply healthy & fails, indicating lamps. LED Illumination lamp ON / OFF with limit Switch, space heater with switch 6/16 amps 5 Pin switch socket outlet, control terminal as required. Auxiliary contact for Aux. relays for Anti Pumping & indication, electrically/Mechanically interlocking etc. as required, 8 window alarm annunciator with windows and buzzer, ack, rest, rest push button for electrical faults in incomer panel, complete with FRLS wiring, Terminal Blocks, cable-ducts, protection MCBs
Busbars
800 amps TP,12 KV air insulated and encapsulated copper Bus bar of suitable size as per panel configuration.
11 KV MAIN HT PANEL BOARD (LOC: SERVICE YARD) AS ABOVE
11 KV HT PANEL BOARD HVAC YARD (LOC: SERVICE YARD)
Supply, Installation, Testing and Commissioning of indoor type floor mounted metal clad, fabricated of 2 mm thick CRCA/Aluzinc sheet, 11 kV, VCB Panel with (11) Nos. VCBs, totally enclosed & electrically interlocked, horizontal drawout on floor, horizontal isolation type VCB as per IEC62271-100 for breakers and 200 for panels/ IS3247 of switch board, as per specifications, having capacities as mentioned below, single break, trip free mechanism, electrical and manually charged and closing breaker suitable for use on 11 kV, 3Phase, 50Hz A.C. supply , complete with self contained electrically interlocked rack in and rack out mechanism, air insulated and encapsulated copper bus bars , breaker featured with mechanical ON/ OFF indicator with hand trip device, spring release coil, shunt trip coil and auxiliary switch of 4NO + 4NC and equipped with following switchgears and accessories i/c connections suitable for 2 R X 3C X 300 sq.mm. XLPE 11 kV cable as incomer as well as outgoing feeder. STC 18.4 kA for 3 sec , Internal Arc Test for AFLR 18.4 kA for 1 sec. at individual compartments i.e. Busbar, VCB and cable compartment. All major sub-components (switchgear, relays & vacuum interrupters) shall be of same make. Separate earthing truck shall be required for each bus earthing & cable earthing. Earthing truck shall be so designed that it is impossible to earth a live. It shall be provided with capacitive voltage divider and complete with audio visual annunciation, one for each panel. (noted: cost of end termination are not included in this Item s & cable entry from bottom considered).
The panel shall be complete with suitable surge protection device required for the suitable voltage level and withstanding current.
04nos. Incomer VCB Panels each comprising of
11kV, 630A, Vacuum Circuit Breaker
Set of 03nos. Cast resin insulated Dual core dual ratio CT, 11kV, 300-150/5-5A, Core1: Class 5P10, 10VA, Core2: Class 0.5, 10VA
Breaker control switch 240 V AC, spring charging motor 24 V, DC Shunt/tripping coil/closing coil Lockable type, Trip/Neutral/Close (TNC) Switch, Set of ON/OFF/TRIP indicating, Set of R/Y/B Phase indicating lamps, Clear lamp for Trip Circuit healthy supply & Trip Circuit fails, DC Control Supply healthy & fails, indicating lamps. LED Illumination lamp ON / OFF with limit Switch, space heater with switch 6/16 amps 5 Pin switch socket outlet, Control terminal as required. Auxiliary contact for Aux. relays for Anti Pumping & indication, electrically/Mechanically interlocking etc. as required, 8 window alarm annunciator with windows and buzzer, ack, rest, rest push button for electrical faults in incomer panel, complete with FRLS wiring, Terminal Blocks, cable-ducts, protection MCBs.
01 No. for each breaker:- Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port and protection MCBs. and required accessories to complete the system.
Numerical Protection Relay, modular design, confirming to IEC 60255, protection scheme for detecting, indicating and tripping the breaker on critical faults like (i)over current & short circuit 51,51N & one earth fault element in the three phases, (ii) negative sequence currents due to line-to-line or conductor-break faults, (iii) residual and three-phase under-voltages/over-voltages, (iv) circuit-breaker-failure alarm, (v) tripping-circuit-failures and interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (vi) Master-Trip and Trip-Circuit Supervision The relay shall be integrated with the feeder, capturing status like Breaker On/Off/Spring. Charged/Test/Service/AC-Fail, Line-Current, Line-Voltage etc. and display the same on graphical display (MIMIC), remote communication on IEC61850 platform on Ethernet. Arc Flash Protection Shall be provided: Sensing of any ARC produced in any of the 3 chambers i.e. Breaker, Cable and Busbar apart from Protection features, along with arc sensors , fibre cables etc. along with other accessories to complete the system.
05nos. Outgoings VCB Panel
11kV, 630A,Vacuum Circuit Breaker Panel
Set of 03nos. Cast resin insulated Dual core dual ratio CT, 11KV, 150-80/5-5A, Core1: Class 5P10, 10VA, Core2: Class 0.5, 10VA ;
Breaker control switch 240 V AC, spring charging motor 24 V, DC Shunt/tripping coil/closing coil Lockable type, Trip/Neutral/Close (TNC) Switch, Set of ON/OFF/TRIP indicating, Set of R/Y/B Phase indicating lamps, Clear lamp for Trip Circuit healthy supply & Trip Circuit fails, DC Control Supply healthy & fails, indicating lamps. LED Illumination lamp ON / OFF with limit Switch, space heater with switch 6/16 amps 5 Pin switch socket outlet, Control terminal as required. Auxiliary contact for Aux. relays for Anti Pumping & indication, electrically/Mechanically interlocking etc. as required, 12 window alarm annunciator with windows and buzzer, ack, rest, rest push button for electrical faults in incomer panel, complete with FRLS wiring, Terminal Blocks, cable-ducts, protection MCBs.
01 No. for each breaker:- Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port and protection MCBs. and required accessories to complete the system.
Numerical Protection Relay, modular design , confirming to IEC 60255, protection scheme for detecting, indicating and tripping the breaker on critical faults like (i) Restricted Earth Fault for solidly grounded transformer on Secondary side (ii) Over-Current & Earth-Fault detection for both Transformer primary and secondary (iii) Negative sequence faults due to line-to-line or conductor break (iv) Three-phase under/over-voltage protection (v) Transformer auxiliary protections (vi) circuit-breaker-failure alarm, (vii)OTI/WTI Alarm (viii)Master-Trip and Trip-Circuit Supervision (ix) tripping-circuit-failures and interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. The relay shall be integrated with the feeder, capturing status like Breaker On/Off/Spring. Charged/Test/Service/AC-Fail, Line-Current, Line-Voltage etc. and display the same on graphical display (MIMIC), remote communication on IEC61850 platform on Ethernet. Arc Flash Protection Shall be provided: Sensing of any ARC produced in any of the 3 chambers i.e. Breaker, Cable and Busbar apart from Protection features, along with arc sensors , fibre cables etc. along with other accessories to complete the system.
02nos. Bus Coupler Panels, each comprising of
11kV, 630A, Vacuum Circuit Breaker Panel , including associated Bus riser PT panels consisting of suitable burden & class of PT's.
Numerical Protection Relay, modular design , confirming to IEC 60255, protection scheme for detecting, indicating and tripping the breaker on critical faults like (i) Synchro-Check and Energizing Check b/w bus-voltages on either side of coupler (ii) circuit-breaker-failure alarm, (iii) tripping-circuit-failures and tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. The relay shall be integrated with the feeder, capturing status like Breaker On/Off/Spring. Charged/Test/Service/AC-Fail, Line-Current, Line-Voltage etc. and display the same on graphical display (MIMIC), remote communication on IEC61850 platform on Ethernet. Arc Flash Protection Shall be provided: Sensing of any ARC produced in any of the 3 chambers i.e. Breaker, Cable and Busbar apart from Protection features, along with arc sensors , fibre cables etc. along with other accessories to complete the system.
Breaker control switch 240 V AC, spring charging motor 24 V, DC Shunt/tripping coil/closing coil Lockable type, Trip/Neutral/Close (TNC) Switch, Set of ON/OFF/TRIP indicating, Set of R/Y/B Phase indicating lamps, Clear lamp for Trip Circuit healthy supply & Trip Circuit fails, DC Control Supply healthy & fails, indicating lamps. LED Illumination lamp ON / OFF with limit Switch, space heater with switch 6/16 amps 5 Pin switch socket outlet, Control terminal as required. Auxiliary contact for Aux. relays for Anti Pumping & indication, electrically/Mechanically interlocking etc. as required, 8 window alarm annunciator with windows and buzzer, ack, rest, rest push button for electrical faults in incomer panel, complete with FRLS wiring, Terminal Blocks, cable-ducts, protection MCBs
Bus PT Panel, each comprising of
The Bus PT panel shall be installed in the remaining bus-section(s) which does not have any other Bus PT connected to it.
LEDs for R-Y-B
The panel shall be complete with FRLS wiring, Terminal Blocks, cable-trays, isolation MCBs, led illumination, power-socket and space-heater with thermostat as per requirement.
Busbars
630 amps TP, 12 KV air insulated and encapsulated copper Bus bar of suitable size as per panel configuration.
11 KV MAIN HT PANEL BOARD (LOC: SERVICE YARD) AS ABOVE
11 KV HT PANEL BOARD HVAC YARD (LOC:PTB ESS)
Supply, Installation, Testing and Commissioning of indoor type floor mounted metal clad, fabricated of 2 mm thick CRCA/Aluzinc sheet, 11 KV, VCB Panel with (11) Nos. VCBs, totally enclosed & electrically interlocked, horizontal drawout on floor, horizontal isolation type VCB as per IEC62271-100 for breakers and 200 for panels/ IS3247 of switch board, as per specifications, having capacities as mentioned below, single break, trip free and manually charged and closing breaker suitable for use on 11 kV, 3Phase, 50Hz A.C. supply , complete with self contained electrically interlocked rack in and rack out mechanism, air insulated and encapsulated copper bus bars , breaker featured with mechanical ON/ OFF indicator with hand trip device, spring release coil, shunt trip coil and auxiliary switch of 4NO + 4NC and equipped with following switchgears and accessories i/c connections suitable for 2 R X 3C X 300 sq.mm. XLPE 11 KV cable as incomer as well as outgoing feeder. STC 18.4 kA for 3 sec , Internal Arc Test for AFLR 18.4 kA for 1 sec. at individual compartments i.e. Busbar, VCB and cable compartment. All major sub-components (switchgear, relays & vacuum interrupters) shall be of same make. Separate earthing truck shall be required for each bus earthing & cable earthing. Earthing truck shall be so designed that it is impossible to earth a live. It shall be provided with capacitive voltage divider and complete with audio visual annunciation, one for each panel. (noted: cost of end termination are not included in this Item s & cable entry from bottom considered).
The panel shall be complete with suitable surge protection device required for the suitable voltage level and withstanding current.
04nos. Incomer VCB Panels each comprising of
11kV, 630A, Vacuum Circuit Breaker
Set of 03nos. Cast resin insulated Dual core dual ratio CT, 11KV, 300-150/5-5A, Core1: Class 5P10, 10VA, Core2: Class 0.5, 10VA
Breaker control switch 240 V AC, spring charging motor 24 V, DC Shunt/tripping coil/closing coil Lockable type, Trip/Neutral/Close (TNC) Switch, Set of ON/OFF/TRIP indicating, Set of R/Y/B Phase indicating lamps, Clear lamp for Trip Circuit healthy supply & Trip Circuit fails, DC Control Supply healthy & fails, indicating lamps. LED Illumination lamp ON / OFF with limit Switch, space heater with switch 6/16 amps 5 Pin switch socket outlet, Control terminal as required. Auxiliary contact for Aux. relays for Anti Pumping & indication, electrically/Mechanically interlocking etc. as required, 8 window alarm annunciator with windows and buzzer, ack, rest, rest push button for electrical faults in incomer panel, complete with FRLS wiring, Terminal Blocks, cable-ducts, protection MCBs.
01 No. for each breaker:- Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port and protection MCBs. and required accessories to complete the system.
Numerical Protection Relay, modular design, confirming to IEC 60255, protection scheme for detecting, indicating and tripping the breaker on critical faults like (i)over current & short circuit 51,51N & one earth fault element in the three phases, (ii) negative sequence currents due to line-to-line or conductor-break faults, (iii) residual and three-phase under-voltages/over-voltages, (iv) circuit-breaker-failure alarm, (v) tripping-circuit-failures and interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (vi) Master-Trip and Trip-Circuit Supervision The relay shall be integrated with the feeder, capturing status like Breaker On/Off/Spring. Charged/Test/Service/AC-Fail, Line-Current, Line-Voltage etc. and display the same on graphical display (MIMIC), remote communication on IEC61850 platform on Ethernet. Arc Flash Protection Shall be provided: Sensing of any ARC produced in any of the 3 chambers i.e. Breaker, Cable and Busbar apart from Protection features, along with arc sensors , fibre cables etc. along with other accessories to complete the system.
05nos. Outgoings VCB Panel
11kV, 630A,Vacuum Circuit Breaker Panel
Set of 03nos. Cast resin insulated Dual core dual ratio CT, 11KV, 150-80/5-5A, Core1: Class 5P10, 10VA, Core2: Class 0.5, 10VA ;
Breaker control switch 240 V AC, spring charging motor 24 V, DC Shunt/tripping coil/closing coil Lockable type, Trip/Neutral/Close (TNC) Switch, Set of ON/OFF/TRIP indicating, Set of R/Y/B Phase indicating lamps, Clear lamp for Trip Circuit healthy supply & Trip Circuit fails, DC Control Supply healthy & fails, indicating lamps. LED Illumination lamp ON / OFF with limit Switch, space heater with switch 6/16 amps 5 Pin switch socket outlet, Control terminal as required. Auxiliary contact for Aux. relays for Anti Pumping & indication, electrically/Mechanically interlocking etc. as required, 12 window alarm annunciator with windows and buzzer, ack, rest, rest push button for electrical faults in incomer panel, complete with FRLS wiring, Terminal Blocks, cable-ducts, protection MCBs.
01 No. for each breaker:- Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port and protection MCBs. and required accessories to complete the system.
Numerical Protection Relay, modular design , confirming to IEC 60255, protection scheme for detecting, indicating and tripping the breaker on critical faults like (i) Restricted Earth Fault for solidly grounded transformer on Secondary side (ii) Over-Current & Earth-Fault detection for both Transformer primary and secondary (iii) Negative sequence faults due to line-to-line or conductor break (iv) Three-phase under/over-voltage protection (v) Transformer auxiliary protections (vi) circuit-breaker-failure alarm, (vii)OTI/WTI Alarm (viii)Master-Trip and Trip-Circuit Supervision (ix) tripping-circuit-failures and interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. The relay shall be integrated with the feeder, capturing status like Breaker On/Off/Spring. Charged/Test/Service/AC-Fail, Line-Current, Line-Voltage etc. and display the same on graphical display (MIMIC), remote communication on IEC61850 platform on Ethernet. Arc Flash Protection Shall be provided: Sensing of any ARC produced in any of the 3 chambers i.e. Breaker, Cable and Busbar apart from Protection features, along with arc sensors , fibre cables etc. along with other accessories to complete the system.
02nos. Bus Coupler Panels, each comprising of
11kV, 630A, Vacuum Circuit Breaker Panel, including associated Bus riser PT panels consisting of suitable burden & class of PT's.
Numerical Protection Relay, modular design , confirming to IEC 60255, protection scheme for detecting, indicating and tripping the breaker on critical faults like (i) Synchro-Check and Energizing Check b/w bus-voltages on either side of coupler (ii) circuit-breaker-failure alarm, (iii) tripping-circuit-failures and tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. The relay shall be integrated with the feeder, capturing status like Breaker On/Off/Spring. Charged/Test/Service/AC-Fail, Line-Current, Line-Voltage etc. and display the same on graphical display (MIMIC), remote communication on IEC61850 platform on Ethernet. Arc Flash Protection Shall be provided: Sensing of any ARC produced in any of the 3 chambers i.e. Breaker, Cable and Busbar apart from Protection features, along with arc sensors , fibre cables etc. along with other accessories to complete the system.
Breaker control switch 240 V AC, spring charging motor 24 V, DC Shunt/tripping coil/closing coil Lockable type, Trip/Neutral/Close (TNC) Switch, Set of ON/OFF/TRIP indicating, Set of R/Y/B Phase indicating lamps, Clear lamp for Trip Circuit healthy supply & Trip Circuit fails, DC Control Supply healthy & fails, indicating lamps. LED Illumination lamp ON / OFF with limit Switch, space heater with switch 6/16 amps 5 Pin switch socket outlet, Control terminal as required. Auxiliary contact for Aux. relays for Anti Pumping & indication, electrically/Mechanically interlocking etc. as required, 8 window alarm annunciator with windows and buzzer, ack, rest, rest push button for electrical faults in incomer panel, complete with FRLS wiring, Terminal Blocks, cable-ducts, protection MCBs.
Bus PT Panel, each comprising of
The panel shall be installed in the remaining bus-section(s) which does not have any other Bus PT connected to it.
LEDs for R-Y-B
The panel shall be complete with FRLS wiring, Terminal Blocks, cable-trays, isolation MCBs, led illumination, power-socket and space-heater with thermostat as per requirement.
Busbars
630 amps TP, 12 KV air insulated and encapsulated copper Bus bar of suitable size as per panel configuration.
11 KV MAIN HT PANEL BOARD (LOC: PTB ESS) AS ABOVE
11 KV MAIN HT DISTRIBUTION PANEL BOARD (LOC: SERVICE YARD)
Supply, Installation, Testing and Commissioning of indoor type floor mounted metal clad, fabricated of 2 mm thick CRCA/Aluzinc sheet, 11 kV, VCB Panel with (09) Nos. VCBs, totally enclosed & electrically interlocked, horizontal drawout on floor, horizontal isolation type VCB as per IEC62271-100 for breakers and 200 for panels/ IS3247 of switch board, as per specifications, having capacities as mentioned below, single break, trip free and manually charged and closing breaker suitable for use on 11 kV, 3Phase, 50Hz A.C. supply , complete with self contained electrically interlocked rack in and rack out mechanism, air insulated and encapsulated copper bus bars , breaker featured with mechanical ON/ OFF indicator with hand trip device, spring release coil, shunt trip coil and auxiliary switch of 4NO + 4NC and equipped with following switchgears and accessories i/c connections suitable for 2 R X 3C X 300 sq.mm. XLPE 11 kV cable as incomer as well as outgoing feeder. STC 18.4 kA for 3 sec , Internal Arc Test for AFLR 18.4 kA for 1 sec. at individual compartments i.e. Busbar, VCB and cable compartment. All major sub-components (switchgear, relays & vacuum interrupters) shall be of same make. Separate earthing truck shall be required for each bus earthing & cable earthing. Earthing truck shall be so designed that it is impossible to earth a live. It shall be provided with capacitive voltage divider and complete with audio visual annunciation, one for each panel. (noted: cost of end termination are not included in this Item s & cable entry from bottom considered).
The panel shall be complete with suitable surge protection device required for the suitable voltage level and withstanding current.
02nos. Incomer VCB Panels each comprising of
11kV, 630A, Vacuum Circuit Breaker
Set of 03nos. Cast resin insulated Dual core dual ratio CT, 11kV, 200-100/5-5A, Core1: Class 5P10, 10VA, Core2: Class 0.5, 10VA
Breaker control switch 240 V AC, spring charging motor 24 V, DC Shunt/tripping coil/closing coil Lockable type, Trip/Neutral/Close (TNC) Switch, Set of ON/OFF/TRIP indicating, Set of R/Y/B Phase indicating lamps, Clear lamp for Trip Circuit healthy supply & Trip Circuit fails, DC Control Supply healthy & fails, indicating lamps. LED Illumination lamp ON / OFF with limit Switch, space heater with switch 6/16 amps 5 Pin switch socket outlet, Control terminal as required. Auxiliary contact for Aux. relays for Anti Pumping & indication, electrically/Mechanically interlocking etc. as required, 8 window alarm annunciator with windows and buzzer, ack, rest, rest push button for electrical faults in incomer panel, complete with FRLS wiring, Terminal Blocks, cable-ducts, protection MCBs
01 No. for each breaker:- Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port and protection MCBs. and required accessories to complete the system.
Numerical Protection Relay, modular design , confirming to IEC 60255, protection scheme for detecting, indicating and tripping the breaker on critical faults like (i)over current & short circuit 51,51N & one earth fault element in the three phases, (ii) negative sequence currents due to line-to-line or conductor-break faults, (iii) residual and three-phase under-voltages/over-voltages, (iv) circuit-breaker-failure alarm, (v) tripping-circuit-failures and interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (vi) Master-Trip and Trip-Circuit Supervision The relay shall be integrated with the feeder, capturing status like Breaker On/Off/Spring. Charged/Test/Service/AC-Fail, Line-Current, Line-Voltage etc. and display the same on graphical display (MIMIC), remote communication on IEC61850 platform on Ethernet. Arc Flash Protection Shall be provided: Sensing of any ARC produced in any of the 3 chambers i.e. Breaker, Cable and Busbar apart from Protection features, along with arc sensors , fibre cables etc. along with other accessories to complete the system.
06 nos. Outgoings VCB Panel each comprising of
11kV, 630A,Vacuum Circuit Breaker Panel.
Set of 03nos. Cast resin insulated Dual core dual ratio CT, 11kV, 300-150/5-5A, Core1: Class 5P10, 10VA, Core2: Class 0.5, 10VA ;
Breaker control switch 240 V AC, spring charging motor 24 V, DC Shunt/tripping coil/closing coil Lockable type, Trip/Neutral/Close (TNC) Switch, Set of ON/OFF/TRIP indicating, Set of R/Y/B Phase indicating lamps, Clear lamp for Trip Circuit healthy supply & Trip Circuit fails, DC Control Supply healthy & fails, indicating lamps. LED Illumination lamp ON / OFF with limit Switch, 60 watts space heater with switch 6/16 amps 5 Pin switch socket outlet, Control terminal as required. Auxiliary contact for Aux. relays for Anti Pumping & indication, electrically/Mechanically interlocking etc. as required, 8 window alarm annunciator with windows and buzzer, ack, rest, rest push button for electrical faults in incomer panel, complete with FRLS wiring, Terminal Blocks, cable-ducts, protection MCBs
01 No. for each breaker:- Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port and protection MCBs. and required accessories to complete the system.
Numerical Protection Relay, modular design , confirming to IEC 60255, protection scheme for detecting, indicating and tripping the breaker on critical faults like (i)over current & short circuit 51,51N & one earth fault element in the three phases, (ii) negative sequence currents due to line-to-line or conductor-break faults, (iii) residual and three-phase under-voltages/over-voltages, (iv) circuit-breaker-failure alarm, (v) tripping-circuit-failures and interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (vi) Master-Trip and Trip-Circuit Supervision The relay shall be integrated with the feeder, capturing status like Breaker On/Off/Spring. Charged/Test/Service/AC-Fail, Line-Current, Line-Voltage etc. and display the same on graphical display (MIMIC), remote communication on IEC61850 platform on Ethernet. Arc Flash Protection Shall be provided: Sensing of any ARC produced in any of the 3 chambers i.e. Breaker, Cable and Busbar apart from Protection features, along with arc sensors , fibre cables etc. along with other accessories to complete the system.
1nos. Bus Coupler Panels, each comprising of
11kV, 630A, Vacuum Circuit Breaker Panel
Numerical Protection Relay, modular design , confirming to IEC 60255, protection scheme for detecting, indicating and tripping the breaker on critical faults like (i) Synchro-Check and Energizing Check b/w bus-voltages on either side of coupler (ii) circuit-breaker-failure alarm, (iii) tripping-circuit-failures and tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. The relay shall be integrated with the feeder, capturing status like Breaker On/Off/Spring. Charged/Test/Service/AC-Fail, Line-Current, Line-Voltage etc. and display the same on graphical display (MIMIC), remote communication on IEC61850 platform on Ethernet. Arc Flash Protection Shall be provided: Sensing of any ARC produced in any of the 3 chambers i.e. Breaker, Cable and Busbar apart from Protection features, along with arc sensors , fibre cables etc. along with other accessories to complete the system.
Breaker control switch 240 V AC, spring charging motor 24 V, DC Shunt/tripping coil/closing coil Lockable type, Trip/Neutral/Close (TNC) Switch, Set of ON/OFF/TRIP indicating, Set of R/Y/B Phase indicating lamps, Clear lamp for Trip Circuit healthy supply & Trip Circuit fails, DC Control Supply healthy & fails, indicating lamps. LED Illumination lamp ON / OFF with limit Switch, 60 watts space heater with switch 6/16 amps 5 Pin switch socket outlet, Control terminal as required. Auxiliary contact for Aux. relays for Anti Pumping & indication, electrically/Mechanically interlocking etc. as required, 12 window alarm annunciator with windows and buzzer, ack, rest, rest push button for electrical faults in incomer panel, complete with FRLS wiring, Terminal Blocks, cable-ducts, protection MCBs
Busbars
630 amps TP,12 KV air insulated and encapsulated copper Bus bar to withstand full short circuit currents upto 18.4 kA for three second of suitable size as per panel configuration.
11 KV DISTRIBUTION HT PANEL BOARD AS ABOVE
11 KV (18.4KA) HT PANEL 1 No. INCOMING/OUTGOING BOARD 18.4KA FOR DG SETS IN DG ROOM
Supply, Installation, Testing and Commissioning of indoor type floor mounted metal clad, fabricated of 2 mm thick CRCA/Aluzinc sheet, 11 kV, (IC/OG) one incomer & one outgoing VCBs Panel . VCBs, totally enclosed & electrically interlocked, horizontal drawout on floor, horizontal isolation type VCB as per IEC62271-100 for breakers and 200 for panels/ IS3247 of switch board, as per specifications, having capacities as mentioned below, single break, trip free and manually charged and closing breaker suitable for use on 11 kV, 3Phase, 50Hz A.C. supply , complete with self contained electrically interlocked rack in and rack out mechanism, air insulated and encapsulated copper bus bars , breaker featured with mechanical ON/ OFF indicator with hand trip device, spring release coil, shunt trip coil and auxiliary switch of 4NO + 4NC and equipped with following switchgears and accessories i/c connections suitable for 2 R X 3C X 300 sq.mm. XLPE 11 kV cable as incomer as well as outgoing feeder. STC 18.4 kA for 3 sec , Internal Arc Test for AFLR 18.4 kA for 1 sec. at individual compartments i.e. Busbar, VCB and cable compartment. All major sub-components (switchgear, relays & vacuum interrupters) shall be of same make. Separate earthing truck shall be required for each bus earthing & cable earthing. Earthing truck shall be so designed that it is impossible to earth a live. It shall be provided with capacitive voltage divider and complete with audio visual annunciation, one for each panel. (noted: cost of end termination are not included in this Item s & cable entry from bottom considered).
The panel shall be complete with suitable surge protection device required for the suitable voltage level and withstanding current.
01 nos. Incomer/Outgoing VCB Panels each comprising of
11kV, 630A, Vacuum Circuit Breaker.
Set of 03nos. Cast resin insulated Dual core dual ratio CT, 11kV, 150-100/5-5A, Core1: Class 5P10, 10VA, Core2: Class 0.5, 10VA
Breaker control switch 240 V AC, spring charging motor 24 V, DC Shunt/tripping coil/closing coil Lockable type, Trip/Neutral/Close (TNC) Switch, Set of ON/OFF/TRIP indicating, Set of R/Y/B Phase indicating lamps, Clear lamp for Trip Circuit healthy supply & Trip Circuit fails, DC Control Supply healthy & fails, indicating lamps. LED Illumination lamp ON / OFF with limit Switch, space heater with switch 6/16 amps 5 Pin switch socket outlet, Control terminal as required. Auxiliary contact for Aux. relays for Anti Pumping & indication, electrically/Mechanically interlocking etc. as required, 12 window alarm annunciator with windows and buzzer, ack, rest, rest push button for electrical faults in incomer panel, complete with FRLS wiring, Terminal Blocks, cable-ducts, protection MCBs.
01 No. for each breaker:- Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port and protection MCBs. and required accessories to complete the system.
Numerical Protection Relay, modular design , confirming to IEC 60255, protection scheme for detecting, indicating and tripping the breaker on critical faults like (i)over current & short circuit 51,51N & one earth fault element in the three phases, (ii) negative sequence currents due to line-to-line or conductor-break faults, (iii) residual and three-phase under-voltages/over-voltages, (iv) circuit-breaker-failure alarm, (v) tripping-circuit-failures and interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (vi) Master-Trip and Trip-Circuit Supervision The relay shall be integrated with the feeder, capturing status like Breaker On/Off/Spring. Charged/Test/Service/AC-Fail, Line-Current, Line-Voltage etc. and display the same on graphical display (MIMIC), remote communication on IEC61850 platform on Ethernet. Arc Flash Protection Shall be provided: Sensing of any ARC produced in any of the 3 chambers i.e. Breaker, Cable and Busbar apart from Protection features, along with arc sensors , fibre cables etc. along with other accessories to complete the system.
11 KV (18.4KA) HT PANEL 1 No. INCOMING/OUTGOING BOARD 18.3KA FOR DG SETS IN DG ROOM WITH SPECS. SAME AS ABOVE
Battery & Battery Charger 230V, single phase 2 wire AC to 24V DC Batteries charger with semiconductor/IGBT full wave rectifier with auto /manual float cum boost facility complete with 24V DC, 180 AH sealed maintenance free batteries including one no. distribution board having 63 Amps DP MCCB as incomer and 16 Nos. 20/16A DP MCB's (D.C. duty) as outgoing complete as required and as per technical specifications.
11 KV HT PANEL BOARD - DG SYNC PANEL. (LOC: Service Yard)
Supply, Installation, Testing and Commissioning of indoor type floor mounted metal clad, fabricated of 2 mm thick CRCA/Aluzinc sheet, 11 kV, 12 Nos. VCBs Panel . VCBs, totally enclosed & electrically interlocked, horizontal drawout on floor, horizontal isolation type VCB as per IEC62271-100 for breakers and 200 for panels/ IS3247 of switch board, as per specifications, having capacities as mentioned below, single break, trip free and manually charged and closing breaker suitable for use on 11 kV, 3Phase, 50Hz A.C. supply , complete with self contained electrically interlocked rack in and rack out mechanism, air insulated and encapsulated copper bus bars , breaker featured with mechanical ON/ OFF indicator with hand trip device, spring release coil, shunt trip coil and auxiliary switch of 4NO + 4NC and equipped with following switchgears and accessories i/c connections suitable for 2 R X 3C X 300 sq.mm. XLPE 11 kV cable as incomer as well as outgoing feeder. STC 18.4 kA for 3 sec , Internal Arc Test for AFLR 18.4 kA for 1 sec. at individual compartments i.e. Busbar, VCB and cable compartment. All major sub-components (switchgear, relays & vacuum interrupters) shall be of same make. Separate earthing truck shall be required for each bus earthing & cable earthing. Earthing truck shall be so designed that it is impossible to earth a live. It shall be provided with capacitive voltage divider and complete with audio visual annunciation, one for each panel. (noted: cost of end termination are not included in this Items & cable entry from bottom considered).
The panel shall be complete with suitable surge protection device required for the suitable voltage level and withstanding current.
05nos. Incomer VCB Panels each comprising of
11kV, 630A, Vacuum Circuit Breaker ,as described above.
Set of 03nos. Cast resin insulated Dual core dual ratio CT, 11kV, 150-75/5-5A, Core1: Class 5P10, 10VA, Core2: Class 0.5, 10VA
Breaker control switch 240 V AC, spring charging motor 24 V, DC Shunt/tripping coil/closing coil Lockable type, Trip/Neutral/Close (TNC) Switch, Set of ON/OFF/TRIP indicating, Set of R/Y/B Phase indicating lamps, Clear lamp for Trip Circuit healthy supply & Trip Circuit fails, DC Control Supply healthy & fails, indicating lamps. LED Illumination lamp ON / OFF with limit Switch, space heater with switch 6/16 amps 5 Pin switch socket outlet, Control terminal as required. Auxiliary contact for Aux. relays for Anti Pumping & indication, electrically/Mechanically interlocking etc. as required, 12 window alarm annunciator with windows and buzzer, ack, rest, rest push button for electrical faults in incomer panel, complete with FRLS wiring, Terminal Blocks, cable-ducts, protection MCBs
01 No. for each breaker:- Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port and protection MCBs. and required accessories to complete the system.
Numerical Protection Relay, modular design , confirming to IEC 60255, protection scheme for detecting, indicating and tripping the breaker on critical faults like (i)over current & short circuit 51,51N & one earth fault element in the three phases, (ii) negative sequence currents due to line-to-line or conductor-break faults, (iii) residual and three-phase under-voltages/over-voltages, (iv) circuit-breaker-failure alarm, (v) tripping-circuit-failures and interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (vi) Master-Trip and Trip-Circuit Supervision The relay shall be integrated with the feeder, capturing status like Breaker On/Off/Spring. Charged/Test/Service/AC-Fail, Line-Current, Line-Voltage etc. and display the same on graphical display (MIMIC), remote communication on IEC61850 platform on Ethernet. Arc Flash Protection Shall be provided: Sensing of any ARC produced in any of the 3 chambers i.e. Breaker, Cable and Busbar apart from Protection features, along with arc sensors , fibre cables etc. along with other accessories to complete the system.
05nos. Outgoing VCB Panels , each comprising of
11kV, 630A, Vacuum Circuit Breaker Panel , as prescribed above.
Set of 03nos. Cast resin insulated Dual core dual ratio CT, 11kV, 250-125/5-5A, Core1: Class 5P10, 10VA, Core2: Class 0.5, 10VA ;
Breaker control switch 240 V AC, spring charging motor 24 V, DC Shunt/tripping coil/closing coil Lockable type, Trip/Neutral/Close (TNC) Switch, Set of ON/OFF/TRIP indicating, Set of R/Y/B Phase indicating lamps, Clear lamp for Trip Circuit healthy supply & Trip Circuit fails, DC Control Supply healthy & fails, indicating lamps. LED Illumination lamp ON / OFF with limit Switch, space heater with switch 6/16 amps 5 Pin switch socket outlet, Control terminal as required. Auxiliary contact for Aux. relays for Anti Pumping & indication, electrically/Mechanically interlocking etc. as required, 12 window alarm annunciator with windows and buzzer, ack, rest, rest push button for electrical faults in incomer panel, complete with FRLS wiring, Terminal Blocks, cable-ducts, protection MCBs
01 No. for each breaker:- Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port and protection MCBs. and required accessories to complete the system.
Numerical Protection Relay, modular design , confirming to IEC 60255, protection scheme for detecting, indicating and tripping the breaker on critical faults like (i)over current & short circuit 51,51N & one earth fault element in the three phases, (ii) negative sequence currents due to line-to-line or conductor-break faults, (iii) residual and three-phase under-voltages/over-voltages, (iv) circuit-breaker-failure alarm, (v) tripping-circuit-failures and interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (vi) Master-Trip and Trip-Circuit Supervision The relay shall be integrated with the feeder, capturing status like Breaker On/Off/Spring. Charged/Test/Service/AC-Fail, Line-Current, Line-Voltage etc. and display the same on graphical display (MIMIC), remote communication on IEC61850 platform on Ethernet. Arc Flash Protection Shall be provided: Sensing of any ARC produced in any of the 3 chambers i.e. Breaker, Cable and Busbar apart from Protection features, along with arc sensors , fibre cables etc. along with other accessories to complete the system.
02nos. Bus Coupler Panels, each comprising of
11kV, 800A, Vacuum Circuit Breaker Panel, including associated Bus riser PT panels consisting of suitable burden & class of PT's.
Numerical Protection Relay, modular design , confirming to IEC 60255, protection scheme for detecting, indicating and tripping the breaker on critical faults like (i) Synchro-Check and Energizing Check b/w bus-voltages on either side of coupler (ii) circuit-breaker-failure alarm, (iii) tripping-circuit-failures and tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. The relay shall be integrated with the feeder, capturing status like Breaker On/Off/Spring. Charged/Test/Service/AC-Fail, Line-Current, Line-Voltage etc. and display the same on graphical display (MIMIC), remote communication on IEC61850 platform on Ethernet. Arc Flash Protection Shall be provided: Sensing of any ARC produced in any of the 3 chambers i.e. Breaker, Cable and Busbar apart from Protection features, along with arc sensors , fibre cables etc. along with other accessories to complete the system.
Breaker control switch 240 V AC, spring charging motor 24 V, DC Shunt/tripping coil/closing coil Lockable type, Trip/Neutral/Close (TNC) Switch, Set of ON/OFF/TRIP indicating, Set of R/Y/B Phase indicating lamps, Clear lamp for Trip Circuit healthy supply & Trip Circuit fails, DC Control Supply healthy & fails, indicating lamps. LED Illumination lamp ON / OFF with limit Switch, space heater with switch 6/16 amps 5 Pin switch socket outlet, Control terminal as required. Auxiliary contact for Aux. relays for Anti Pumping & indication, electrically/Mechanically interlocking etc. as required, 12 window alarm annunciator with windows and buzzer, ack, rest, rest push button for electrical faults in incomer panel, complete with FRLS wiring, Terminal Blocks, cable-ducts, protection MCBs
01nos. Panels for each bus section , each comprising of
The panel shall be installed in the remaining bus-section(s) which does not have any other connected to it.
LEDs for R-Y-B
The panel shall be complete with FRLS wiring, Terminal Blocks, cable-trays, isolation MCBs, led illumination, power-socket and space-heater with thermostat as per requirement.
Busbars
800 Amps, TP, 12KV air insulated and encapsulated copper Bus bar to withstand full short circuit currents upto 18.4 KA for three second of suitable size as per panel configuration
11 KV HT PANEL BOARD - DG SYNC PANEL. (LOC: Service Yard) AS ABOVE
METERING, RELAY & CONTROL PANEL FOR 11 kV DG SYNCHRONIZING PANELS
Supply, installation, testing and commissioning of 11KV relay & remote control panel indoor type for incoming feeder and outgoing feeder. The panel shall be with back access double door arrangement, dust and vermin proof, Minimum IP-42 class protection and fabricated from CRCA sheet steel of 2 mm thick for frame work and covers, 3 mm thick for gland, plates i/c cleaning & finishing complete with 9 tank process for powder coating in approved shade,, including internal wiring using 1.1kV FRLS insulated multistrand cable (2.5sqmm for CT/PT circuit, 1.5sqmm for Control circuit), numbered and colour coded as per IS-5578 having suitable entry for cable consisting of the following:-
5 Nos. Incoming feeder for DG Synch. Panel and each incoming comprises of the following :
Digital multi function meter , accuracy class 0.5 facility with following parameters maximum demand load, Kilo Watt Hour (KWh), kVA, kW, along with Current, Power factor, Voltage, Frequency and including RS-485 communication port for SCADA/BMS connectivity. .
Control & Push Button
Lockable type, Trip/Neutral/Close (TNC) Switch
Lockable type local/Remote Switch
Main Protection Relay should have provision of tripping of breaker in case of failure of TNC switch.
Push buttons for DC fail accept and test
LED Indicating lamp
Breaker - On/Off/Trip/Spring Charged
R/Y/B Phase
Trip circuit healthy & Trip Circuit fails alarm
DC Control Supply healthy & fails alarm
AC Supply Available
Other items
Hooter with audible alarm with Bell
LED Illumination lamp ON / OFF with limit Switch
Space heater with thermostat / RCBO, 30 mA
6/16 amps 5 Pin switch socket outlet
Control terminal as required
Tripping and Control circuit operating at 24 VDC, Spring charging, space heater, CFL illumination circuit, operating at 230VAC, suitably isolated and protected via fuses/MCBs
Excitation Ammeter & Voltmeter
Temperature scanner
Multi function numeric relay with RS-485 communication ports for the following:
Check synchronizing Relay
Under Voltage relay
Reverse power relay
Loss of excitation relay
Current unbalance
Thermal over load
Breaker failure protection
Voltage restrained instantaneous over current protection (50V) , high set shall be provided on all phases.
Voltage restrained IDMT over current protection (51V) , low set shall be provided on all phases.
Ground fault protection Device No., high set shall be provided and Device No.51 N, low set shall be provided.
Over Voltage Relay
Under / Over frequency
Trip Supervision relay
Numeric generator differential Bias % with dual adjustable slop protection relay (87G)
Lockout relay
Engine cranking relay
Emergency Push Button.
Control wiring for Synchronizing Module (for Synchronizing System)
Audio visual annunciation windows with, accept, reset & test, start stop push buttons.
16 Window Solid state Annunciator for each DG sets
Set fails to start (only alarm), Over current (breaker trip), Earth Fault (Breaker trip), Excitation Failure (Engine should be stop with breaker trip), Reverse Power (Breaker trip), Over speed (Breaker will trip with engine stop command), Low Lube Oil pressure (Breaker will trip with engine stop command), High Water Temperature (Breaker will trip with engine stop command, Over / Under Voltage (Breaker trip), Bearing Temperature high (breaker will trip with engine stop command), Under / Over Frequency (Breaker trip), Winding Temperature High Breaker with trip with engine stop command), Differential Fault (Engine / Alternator field shall cut off)
2 No. Bus Coupler (each comprises of the following :)
Digital ammeter, accuracy class 0.5 facility with following parameters and including RS-485 communication port for SCADA/BMS connectivity for monitoring with following measuring parameter:
Control & Push Button
Lockable type, Trip/Neutral/Close (TNC) Switch
Lockable type local/Remote Switch
Main Protection Relay should have provision of tripping of breaker in case of failure of TNC switch.
Push buttons for DC fail accept and test
LED Indicating lamp
Breaker - On/Off/Trip/Spring Charged
R/Y/B Phase
Trip circuit healthy & Trip Circuit fails alarm
DC Control Supply healthy & fails alarm
AC Supply Available
Other items
Hooter with audible alarm with Bell
LED Illumination lamp ON / OFF with limit Switch
Space heater with switch / RCBO, 30 mA
6/16 amps 5 Pin switch socket outlet
Control terminal as required
Tripping and Control circuit operating at 24 VDC, Spring charging, space heater, LED illumination circuit, operating at 230VAC, suitably isolated and protected via fuses/MCBs
Lock out relay ( 86) with manual reset facility
5 Nos. Outgoings (each comprises of the following :)
Digital ammeter , accuracy class 0.5 facility with following parameters and including RS-485 communication port for SCADA/BMS connectivity for monitoring with following measuring parameter:
Control & Push Button
Lockable type, Trip/Neutral/Close (TNC) Switch
Lockable type local/Remote Switch
Main Protection Relay should have provision of tripping of breaker in case of failure of TNC switch.
Push buttons for DC fail accept and test
LED Indicating lamp
Breaker - On/Off/Trip/Spring Charged
R/Y/B Phase
Trip circuit healthy & Trip Circuit fails alarm
DC Control Supply healthy & fails alarm
AC Supply Available
Other items
Hooter with audible alarm with Bell
LED Illumination lamp ON / OFF with limit Switch
space heater with switch / RCBO, 30 mA
6/16 amps 5 Pin switch socket outlet
Control terminal as required
Tripping and Control circuit operating at 24 VDC, Spring charging, space heater, LED illumination circuit, operating at 230VAC, suitably isolated and protected via fuses/MCBs
Flush-Mounted, Numerical based, 3 Over Current+ 1 Earth Fault Feeder Protection Relay, providing Over Current (Low Set: 10 to 250% and High Set: 20 to 2500%), Earth-Fault (Low Set: 10 to 200% and High Set: 50 to 1250%), Circuit breaker Control, Trip Circuit Supervision, Local HMI and user-programmable 4DI/6DO for future deployment of interlocking/changeover scheme. Relay should be communicable on MODBUS protocol. 1 Set
Lock out relay ( 86) with manual reset facility
6 window annunciation for Audio visual with including Accept, Test & reset PB’s for Over current protection & earth fault trip.
METERING, RELAY & CONTROL PANEL FOR 11 kV DG SYNCHRONIZING PANELS AS ABOVE
Neutral Isolation Panel for 11 kV DG sets: 5 No. Neutral Isolating Switch for I/c & 3 No. Bus Section Each comprising of following : 1 No. 400 amps single Pole 11 KV vacuum contactor for neutral isolation for each DG set One set of Al. bus bars On/Off indicating lamps including all accessories Auto/Manual switch NIS Panel described as above complete as per specification
Neutral Grounding Panel for DG Set comprising of the following: The register element shall be made of un breakable corrosion proof. Punched stainless steel grid of Ferro chrome aluminium alloy. The resistor shall be suitable for the DG sets as required and for the 60 Amps neutral to earth current with temperature rise not exceeding 760 deg. C for 10 sec. The resistance element shall be supported on suitable insulating base housed in 2 mm thick galvanized sheet steel self-supporting, free standing cubical with louvers on sides. The unit shall be complete with connection, terminals glands plates etc. The register element shall be made of un breakable corrosion proof. Punched stainless steel grid of Ferro chrome aluminium alloy. NGR Panel described as above complete as per specification
Neutral Grounding Panel (NGR) for 33/11 kV, 5.0 MVA TR Set comprising of the following: The register element shall be made of un breakable corrosion proof. Punched stainless steel grid of Ferro chrome aluminium alloy. The resistor shall be suitable for the Transformers as required and for the 50 Amps neutral to earth current with temperature rise not exceeding 760 deg. C for 10 sec. The resistance element shall be supported on suitable insulating base housed in 2 mm thick galvanized sheet steel self-supporting, free standing cubical with louvers on sides. The unit shall be complete with connection, terminals glands plates etc. The register element shall be made of un breakable corrosion proof. Punched stainless steel grid of Ferro chrome aluminium alloy. NGR Panel described as above complete as per specification
TRANSFORMERS
OIL TYPE OUTDOOR TYPE TRANSFORMER (Location Service Yard)
Supply, Installation, Testing & Commissioning of 5.0 MVA 3 phase, 33KV/ 11 kV outdoor, ester oil filled type Power Transformer, Dyn 11 vector group connection, having impedance as per IS, Transformer winding & Insulation : CRGO type Prime grade core, 99.9% pure copper winding and neutral brought out for earthing/NGR, paper insulated Insulation & cooling : Class E insulation(or as per manufacturer i.e. thermal upgraded paper), Ester Oil natural, Air Natural, (KNAN) type cooling. Suitable for continuously rated for full load, temperature rise not exceeding 55 deg. C by thermometer in oil or 65 deg. C by resistance. ON load tap changer on HT side with 1.25% step each, range (–) 15% and (+) 5% along with RTCC Panel. Primary side cable termination box shall be suitable for 33 KV, 3C X 300 Sqmm XLPE cable and 11 kV side terminal box shall be suitable for termination of 11 kV, 2 x 3C x 300 sq.mm XLPE AL. cables. Losses of the transformers shall be as per IS:2026 as well as loading as per IS 6600 and as per best industry engineering standards.
The transformer shall be supplied with following Fitting & Accessories:
All standard fitting viz Humidistat for Alarm and Trip
Transformer Oil Temperature Alarm & Tripping
Winding temperature relay unit with Alarm and trip
Oil Level Low Alarm with trip
Electronic temperature controlled with RTD.
Gas Pressure Relays
OLTC Oil Surge Relay
3 No. 1 phase, 30 kV, 10 kA discharge current, class-II Surge arresting device for protection against lightning including Structural support for mounting lightning arrestor on the body above HT bushing.
Buchholz relay of double float type with high gas pressure alarm & trip suitable for 24 volts DC supply. With wiring upto marshalling Box & RTCC Panel
1 No. 600/5A, 5P10,10 VA, Protection class, CT after Neutral trifurcation point for backup earth fault protection (51S).
Outdoor type Marshalling box with RS-485 communication port for BMS integration to monitor all transformer parameters or having 4 No. potential free contact for alarm, trip & annunciation (one for BMS and one for control system).
The transformers shall have bi-directional rollers, winding temperature indicator, oil temperature indicator and Buchholz relay with wiring up to the marshalling box and RTCC Panel complete. The transformers shall have first filling of oil, weather proof HT cable box. The transformer shall have suitable disconnecting chamber at the ends with min 8mm thick non-magnetic gland plate, including M. S. channel and suitable size foundation complete with earth terminals / lifting lugs and other standard accessories as required, as per relevant IS to successfully test & commission the Power Transformer as described above and technical specification.
OIL TYPE OUTDOOR TYPE TRANSFORMER ( Location Service Yard) AS ABOVE
DRY TYPE INDOOR TYPE TRANSFORMER (Location- NEAR PTB) Supply, Installation, Testing & Commissioning of Cast resin Dry type 2000 kVA, 11/0.433 kV 3 Phase, 50Hz, Dyn 11 vector group copper wound class F insulation or higher, having impedance as per IS, associated with winding temperature indicator / controller temperature detector indoor type Transformer with impedance as per IS, The transformer shall be provided with +10% to -10% in steps of 2.5 % each Off load tap changer on HT side, having cable end boxes on HV side suitable for 3 x 300 sq.mm. XLPE cable of 11kV grade and 4000 Amp. bus trunking arrangement of LV side with neutral brought out separately , supplying and grouting of suitable MS channels and suitable size foundation with all accessories for mounting arrangement and confirming to IS 2026 & 11171 : 1985 & as per specification attached complete in all respects as required at site. Losses of the transformers shall be as per ECBC-2017(ECBC +) and as well as equivalent BEE star rated amended upto date. The transformers shall have bi-directional rollers, winding temperature indicator with wiring up to the marshalling box complete. . The transformer shall have 8mm thick non-magnetic gland plate, including M. S. channel and suitable size foundation complete with earth terminals / lifting lugs and other standard accessories as required, as per relevant IS to successfully test & commission the transformer as described above and technical specification DRY TYPE INDOOR TYPE TRANSFORMER AS ABOVE
OIL TYPE OUTOOR TYPE TRANSFORMER (Location- Service Yard)
Supply, installation assembling, transporting, Loading, testing and commissioning of Outdoor oil type 2500 kVA 11/0.433 KV, 3 Phase, 50Hz, Dyn11 vector group, BEE star rated, copper wound, class A or higher insulation level, associated with Oil and winding temperature indicator/ controller actuated by means of resistance temperature detector embedded in LV windings Associated buccholz protection arrangement, Oil conservator as per IS 2026 and losses as per IS 1180 Level-3, Outdoor type transformer with approximately impedance as per IS with updation, tappings for off load operation on HV side in steps of -10 to 10 % in steps of 2.5 %.The transformer shall be provided with winding temperature alarm & trip protection, having cable end boxes on HV side suitable for 3cx 300 Sqmm XLPE cable of 11KV grade and arrangement on LV side suitable for 3200A sandwiched type bus duct with neutral brought out separately and including all control wiring as per specification attached complete in all respects as required at site.) (Location services yard).
The transformer shall be supplied with following Fitting & Accessories:
All standard fitting viz Humidistat for Alarm and Trip
Transformer Oil Temperature Alarm & Tripping
Winding temperature relay unit with Alarm and trip
Oil Level Low Alarm with trip
Electronic temperature controlled with RTD.
Gas Pressure Relays
Buchholz relay of double float type with high gas pressure alarm & trip suitable for 24 volts DC supply. With wiring upto marshalling Box
1 No. 150/5A, 5P10,10 VA, Protection class, CT after Neutral trifurcation point for backup, Restricted earth fault protection(51S).
Outdoor type Marshalling box with RS-485 communication port for SCADA/BMS integration to monitor all transformer parameters or having 2 No. potential free contact for alarm, trip & annunciation (one for BMS and one for control system).
The transformers shall have bi-directional rollers, winding temperature indicator, oil temperature indicator and Buchholz relay with wiring up to the marshalling box complete. The transformers shall have first filling of oil, weather proof HT cable box. The transformer shall have suitable disconnecting chamber at the ends with min 8mm thick non-magnetic gland plate , including M. S. channel and suitable size foundation complete with earth terminals / lifting lugs and other standard accessories as required, as per relevant IS to successfully test & commission the transformer as described above and technical specification
OIL TYPE OUTOOR TYPE TRANSFORMER (Location- Service Yard) AS ABOVE
HSD STORAGE SYSTEM
HSD TANK Design, Supply, unloading, placement, Testing & Commissioning of 20 KL capacity HSD underground storage tank (Mild Steel horizontal cylindrical) with MS shell made out of 6mm thick and end plate 10mm thick suitable for under ground application complete with provision for filling, delivery and vent pipe, Dip Gauge, Float & Board Type Level Indicator, Man Hole and bucket filter including all accessories etc. as per IS 10987, Tar Epoxy anti rust coating on the entire outer surface of the tank including excavation, making suitable civil structure & filling of sand etc. complete as required. Tank shall be tested at works under hydrostatic pressure of 5 PSI before being painted with two coats of Red Oxide primer as required as per specifications and obtaining all the required statutory approvals including from Chief Explosive Authority.
Supply, erection, testing & commissioning of Float & Board Type Level Indicator with all accessories etc. complete as required.
Supply, installation, testing & commissioning of Flame Proof positive displacement type HSD Supply Gear pump with flameproof electric motor duly approved by CCE. HSD pump set suitable for operation on 415V, 50Hz AC supply having capacity of 50 lpm @ 20 mtr. head with manufacturers recommended HP/ KW capacity with flameproof electric motor, coupling, coupling guard, companion flange, MS base frame, foundation, foundation bolts, nut-bolts with flame proof emergency push buttons etc. including earthing complete as required.
Supply, installation, testing and commissioning of emergency MS epoxy box containing isolation valve for fuel line (65 NB plug valve) and also containing remote switch for disabling operation of the fuel oil pump outside. The box shall have breakable glass cover with pad lock arrangement. The box size shall be 200 x 400 x 150 mm deep. The cost shall be inclusive of isolation valve complete including providing & fixing of flame proof 2 set of ON/OFF push button station.
Supply, installation, testing & commissioning of Calibrated HSD buffer/ service tank, rectangular MS (IS:226) construction with 990 liters capacity complete with flanged inlet & outlet, overflow, drain, vent, mechanical level indicator, 450mm dia. Access hole on top with cover, flame arrestor. Tank will be made out of 3mm MS sheet and will be provided with structural support to keep tank base at (Approx. 1500mm) above FFL with access ladder arrangement, painting etc. complete as required as per the system requirement.
Supplying, installation, testing & commissioning of MS pipes of heavy class ERW piping (Class-C) conforming to IS 1239 of following sizes and materials cut to required lengths and installed with necessary bends, supports and clamps, anti-vibration mounting, etc. but excluding valves, strainers and gauges etc. adequately supported on rigid supports/ concealed on floor, painting with two coats of synthetic enamel paint after primer coat etc. complete as required.
80 mm dia.
65 mm dia.
50 mm dia.
40 mm dia.
25 mm dia.
Supply, erection, testing & commissioning of underground piping MS pipes of heavy class ERW piping (Class-C) conforming to IS 1239 of following sizes and materials cut to required lengths and installed with necessary bends, supports and clamps, including anti rust, corrosion proof 4mm thick tape wrapping, complete in all respect including digging & back filling if required etc. complete.
80 NB App.
65 NB App.
50 NB App.
VALVES, STRAINERS & Pressure Gauge, Flow meter
Supply , installation, testing & commissioning of following sizes of Ball Valve of CS Ball Valve Flanged End 150Lbs, Fire Safe antistic, Teflon sealing, with matching flanges, G.I. nuts-bolts & gaskets etc. complete as required.
80 mm dia.
65 mm dia.
50 mm dia.
40 mm dia.
25 mm dia.
Providing, Fixing, Testing and Commissioning of Non - Return Valve with Dual Plate of C I body, SS plates, flanged ends & PN 16 pressure rating for HSD system complete etc. as required.
65 mm dia.
50 mm dia.
Providing, Fixing, Testing and Commissioning Foot Valve of 65mm dia., CI body, flanged ends with required accessories etc. complete as required.
Providing, Fixing, Testing and Commissioning of HSD Oil Pot-Strainer, CI body, SS strainer, flanged ends etc. complete as required.
80 mm dia.
65 mm dia.
25 mm dia.
Providing, Fixing, Testing and Commissioning of dial type SS construction glycerine filled Pressure gauge (0 - 07 kg/cm2 range, dial size 100 mm) with isolating valve and accessories etc. complete as required.
Providing, Fixing, Testing and Commissioning of HSD Oil Flow Meter of CI body, flanged ends with Totalizer etc. complete as required.
80 mm dia.
50 mm dia.
25 mm dia.
Providing and Fixing of 80mm dia. GM collection assembly fitted with lockable brass cap suitable for local oil tanker including necessary supports, Flexible Hose Pipe (Standard Length of 3.75Mtr) etc. complete as required.
Providing & fixing level indicators, controllers for UG oil storage tanks, including wiring, cabling, probes with all other accessories ready for working complete as required. Level indication shall be compatible for BMS system. Complete interface, logic controls for two UGT HSD storage tanks, one Buffer tank & six day oil tanks complete. Providing and fixing flame proof level controllers (suitable for upper ,medium and lower stages) for day oil storage tanks, buffer tank, UG tanks, solenoid valves, automation controls, including wiring, copper FRLS cabling, probes with all other accessories ready for automatic operation of fuel oil pump/s complete as system requirement.
Providing & fixing pressure switch online to start/ stop the pump at set pressure complete with all associated work.
Providing, Fixing of NO SMOKING / Danger sign boards of size 300mm x 250mm made of 2mm thick MS Sheet including painting / sign writing etc. complete as required
Pressure testing to 150 P.S.I. and flushing HSD oil pipe, manifold and pressure gauge with nitrogen before commissioning etc. as required by Engineer in charge.
Providing, Fixing, Testing and Commissioning of Foot Valve, angle check valves with required accessories for HSD tanks etc. complete as required.
65 mm dia. (foot valve)
65 mm dia. (angle check valve)
Statutory fees towards obtaining statutory approval license, NOC, etc. for 2 no. 20 KL U.G fuel tank & for complete fuel pipe line scheme from concerned local Authority/ departments shall be born by the contractor.
DG SETS & EQUIPMENTS
Supplying of Diesel Generating set having Prime Power Rating of 2000 KVA, Silent type with acoustic enclosure, water cooled, 11000 volts at 1500 RPM, 0.8 lagging power factor suitable for 50 HZ, 3 phase system and as per Latest amendments of MOEF and CPCB. The DG sets shall be suitable for being overloaded upto 10% of the rated capacity for 1 hour in every 12 hours and consisting of the followings: The DG set shall be suitable for above 0.8 loading factor with net output shall be 2000kVA as per site conditions.
A. DIESEL ENGINE:
Diesel engine 4 stroke water cooled, electric start, of suitable BHP at 1500 RPM suitable for above output of alternator at 50 Degree C, 50%RH & at 1000 MSL and conforming to BS 5514, BS 649, IS 10000, capable of taking 10% over loading for one hour after 12 hours of continuous operation. The engine will be fitted complete with all the required accessories
Type: Multi-cylinder water cooled with heat exchanger (Air Cooled Fluid Cooler), Turbo charged with charge air cooling.
Fuel injection :As per manufacturer
Engine Starting : Battery starting.
Starting position : Universal. Auto/Manual
The Engines shall include: • Flywheel with guard. • Flexible connection. • Bellow / expansion joints • Air cleaner • Blower fan • Electronic governor with electronic fuel injection system • Fuel and lube oil filters and pumps • Day Fuel tank with visual level indicators etc. • Silencer as per latest amendments of MOEF/CPCB • Safety controls • Instrument panel • Exhaust piping to let out the exhaust at mandatory height above the canopy including support arrangement and insulation with cladding inside the canopy etc.
B. ALTERNATOR;
Synchronous alternator rated at 2000 KVA, 11000 volts at 1500 RPM, 3 phase 50 HZ, AC supply with 0.8 lagging power factor at 50 Degree C, 50% RH & at 1000 Meter MSL. The alternator shall be having SPDP enclosure, brushless, continuous duty, self excited & self-regulated through AVR conforming to IS:4722/BS 2613 suitable for tropical condition and with class-H insulation.
Type : Brushless.
Actual Power 2000 KVA at 50 deg. C.
Frequency : 50 Cycles/sec.
Supply system :3 phases & neutral
Connection : Star.
Rated rpm. : 1500 rpm.
Casing protection : As per IP-23
Insulation : Class `H / F, as per OEM
Power factor : 0.8.
Controller : Type Woodward/EMCP/DEIF for synch. operations
C. ACCESSORIES:
The Diesel Engine shall be equipped with minimum following/ as indicated in the specifications, devices/ accessories built-in type including all standard fittings.
Fuel supply pump with manual venting pump.
Turbo charger with air filter (dry/oil bath type) and damper.
Charge air cooler.
Suction fuel filter
Lube oil filter.
Hour meter and RPM indicator.
Battery Starting Mechanism.
Instrument/Indication panel complete with the followings;
a) Starting Switch with key.
b) Lub. Oil Temp. gauge.
c) Lub. Oil pressure gauge.
d) Water Temp. gauge.
Control devices for safety and monitoring along with indicators.
Common base/foundation frame.
Automatic voltage regulator (AVR).
Daily service fuel tank of 990 liters capacity(as per manufacturers) fabricated out of CRC 3 mm thick MS sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine with MS Class C pipe of suitable dia. complete with valves, level indication, flow switch & twin fuel filters with fuel injectors with potential free contacts for giving signal to existing BMS/Digital system and accessories as required as per specifications.
Anti vibration pads
12/24V DC Starting system comprising of starter motors: Voltage regulator and arrangement for initial excitation complete with suitable nos. of batteries (-nos. x, --Amp. Hour capacity maintenance free as per manufacturer standards ) for minimum 5 no. consecutive starts as required as per specifications.
The cost of initial charge of lubricants, coolant etc.
Dry exhaust manifold of suitable dia., welded blank MS C Class pipe confirming to IS:3589 cut to required lengths (max. 2 mtrs.) and installed with necessary bends, supports and clamps, anti-vibration mountings, insulation of exhaust system with mineral wool/Rockwool, 50mm thick wire mesh and aluminium cladding etc. Flexible stainless steel below as required as per specifications with critical grade type exhaust silencer.
The DG sets shall include the cost of all accessories, Acoustic enclosure as per CPCB ,Fuel system and Emission as per latest MOEF guidelines, fittings, protections, instruments, safety controls, alarms, indications etc. complete as per specifications, as required
Diesel Generating set (2000 KVA) as described above.
Installation, testing commissiong, Loading and unloading of 2000 KVA Diesel Generating set as mentioned above, specification and as per requiment.
Providing and fixing in position mild steel exhaust pipe complete with fittings, supports (angels & channels), cutting, bending, welding, 75 mm thick 96 kg/ cu.m density, mineral wool or equal insulation covered with 24 SWG. Aluminium sheet cladding etc. complete as required & approved by the Engineer Incharge.
450 mm dia. "5.2mm thick"
250 mm dia. "5.2mm thick"
Providing and fixing in position following size of heavy duty stainless steel flanged expansion bellows with G.I. nut bolt washers for DG fume piping complete with GI nut bolt washers etc. complete as required.
450 mm dia.
Providing & fixing for MS support structure for exhaust fume pipes from DG Sets (Exhaust pipe to be measured and paid for separately) along horizontal and vertical runs upto the height (as per CPCB norms) including cutting, welding etc. and applying two coats of red oxide and two coats of synthetic enamelled paint of colour and shade as directed by consultant. The design of the support structure shall be done by the contractor and shall be as per CPCB norms approved , also to get the approval from the client/ consultant before execution etc. as required.
DG AIR COOLED FLUID COOLERS, PUMPS & ACCESSORIES
Supply, installing, testing & commissioning of Air cooled fluid cooler for DG set (2000 kVA) consisting of Heat transfer coil made of Copper tubes, sine wave high efficiency Aluminium fins with Here site phenolic coating. Headers shall be made of Copper OR Carbon steel with vent and drain sockets. The unit shall be complete with axial flow fans with motors having internal wiring up to electrical junction box, electrostatic powder coated G. I. sheet casing and heavy duty base frame for floor mounting. The fans used shall be Axial fans of aerofoil design. The fans shall be of variable angle glass reinforced Poly Amide (PAG) blades and pressure die cast silumin alloy hub. The fan blades shall be very light weight, spark & corrosion resistant and shall be of high strength. Fans shall be directly mounted on the motor shaft .The motors shall be totally enclosed (TEFC) for protection against dust / moisture and class F insulated with IP-55 protection. The motors shall be foot mounted and shall be designed for 415 ± 10% Volts, 3 Phase and 50 Hz. Base frame shall be made up of heavy gauge steel section. The entire unit shall be assembled on this heavy-duty channel iron base frame and can be mounted on rooftop depending upon the job site requirement. Air purging valves shall be mounted on the top of coil headers to make sure that the cooler is completely filled with water and no Air pockets in the system. The Air and drain valves shall have ball valves with dummy plugs. Fluid cooler suitable for 2000 KVA DG set having flow rate @ 9 deg. F Delta T and 45 deg. C DB Temperature. Fluid cooler water outlet temperature shall be 88degF and inlet temperature of water to the Cooling Tower shall be 93degF. Item shall include all required accessories as per site requirement and as desired to make system functional.
FLUID COOLER PUMPS Supply, installing, testing & commissioning of Monobloc centrifugal pumps, having factory fitted mechanical seal mounted on a common base with electric motor for circulation of Engine cooling water between engine and fluid cooler. The pump motor shall be suitable for 415±10% volts, 50 cycles, 3 phase power supply having efficiency class IE3. The quoted price shall include cost of vibration isolation pads at each cooling tower water pump performance characteristics shall be as follows: Water Flow Rate : 1440 LPM Pump Head : 20 M WG Cooling Tower Pumps as described above including 1 No standby.
CONDENSING WATER PIPING Providing and fixing in position the following MS class ‘C’ pipes cut to required lengths and installed with all welded joints. Providing and fixing in position the necessary fittings like expansion bellow, elbows, tees and reducers, sockets, supports and including all accessories complete as required
400 mm dia. MS pipes
250 mm dia. MS pipes
200 mm dia. MS pipes
150 mm dia. MS pipes
100 mm dia. MS pipes
80 mm dia. MS pipes
50 mm dia. MS pipes
Providing and fixing in position the following butterfly valves :
400 mm dia. MS Valves.
250 mm dia. MS Valves.
200 mm dia. MS Valves.
150 mm dia. MS Valves.
100 mm dia. MS valves
50 mm dia. MS valves
Providing and fixing in position the following check valves :
150 mm dia. valves
100 mm dia. valves
Providing and fixing in position the following balancing valves
150 mm dia. MS Valves.
100 mm dia. MS valves.
Providing and fixing in position following ‘Y’ strainer :
150 mm dia. strainers
100 mm dia. strainers.
Supporting and fixing in position following pot strainer
400 mm dia.
150 mm dia.
Providing and fixing in position following ball valves 50 mm dia.
Providing and fixing in position the industrial type pressure gauges with gun metal valves.
Providing and fixing in position the mercury-in- glass industrial type thermometers.
Providing and fixing in position flexible connections of suitable pressure rating to be installed at Heat Exchanger, pump suction and discharge. 150 mm dia.
PROTECTIVE EARTHING
Earthmat
Supply, laying, testing and commissioning of 30 mm dia. Copper cladded MS rod, laying of vertical earth electrodes 3 m deep from earth mat including weld joints with earth mat as per approved drawings and specifications. The weld joints to be provided with bitumen coats.
Supply and creating of advance maintenance free Chemical Gel Earthing of Dual Pipe Technology (GI) of 3mtr long 50mm dia. of outer shell (MS) with the 25mm dia. of inner shell (MS) of 80-100 microns galvanized earth electrode filled with highly conducting metallic compounds with the permanent sealing’s at both the ends with the lead terminal of 32x10mm size at the top along with 50 Kgs of chemical mixture of Resistance Lowering Grounding Minerals. The loss on ignition by mass of the chemical compound shall be less than 20%. The chemical compound should be tested and certified by any International accredited and BIS (Bureau of Indian Standards) accredited laboratory. The earth electrode shall be duly tested & certified by CPRI (Central Power Research Institute), Govt. of India. The chemical earth electrode manufacturer shall be an ISO 9001:2008 & ISO 14001:2004 certified organization. The Earth pit should be covered with heavy duty polyplastic weather proof chamber etc. as required & approved by the Engineer In charge.
Supply and creating of advance maintenance free Chemical Gel Earthing of Dual Pipe Technology (GI) of 3mtr long 80mm dia. of outer shell (MS) with the 50mm dia. of inner shell (MS) of 80-100 microns galvanized earth electrode filled with highly conducting metallic compounds with the permanent sealings at both the ends with the lead terminal of 50 x 10mm size at the top along with 50 Kgs of chemical mixture of Resistance Lowering Grounding Minerals. The loss on ignition by mass of the chemical compound shall be less than 20%. The chemical compound should be tested and certified by any International accredited and BIS (Bureau of Indian Standards) accredited laboratory. The earth electrode shall be duly tested & certified by CPRI (Central Power Research Institute), Govt. of India. The chemical earth electrode manufacturer shall be an ISO 9001: 2008 & ISO 14001: 2004 certified organization. The Earth pit should be covered with heavy duty polyplastic weather proof chamber etc. as required & approved by the Engineer In charge.
Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia. including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required.
Supply and fixing of following Cu wire including all necessary fixing accessories and effecting connections, jointing with brazing etc. complete as required & approved by the Engineer Incharge.
1 x 10 Sq.mm PVC insulated copper flexible cable
1 x 35 Sq.mm PVC insulated copper flexible cable
1 x 50 Sq.mm PVC insulated copper flexible cable
Supply and laying, Testing and commissioning of copper/GI Strips/wire for interconnecting the earthing stations ,panels, DBs etc. of the following sizes in built up trenches /surface/wall/ground complete with holes & fixing, jointing / terminating accessories as per specifications & drawing as required. (Quantity shall be paid as per the actual measurement as executed, however direct measurement shall not exceed the quantity indicated in drawing approved) Note-1: In case of non-availability of any of the sizes mentioned above, next higher size available in market shall be provided at the same rate. Note-2: No additional payment will be made for providing Main Earth Terminals (made out of GI/Cu strips from within the above sizes). The METs will required to be fixed on walls as required and will be required to be provided with 12/16/20mm holes for connections of individual equipments including of other contractors'.
50mmx 6mm Copper strip on surface or in recess
50mmx 6mm G.I. strip on surface or in recess
32mmx 5mm G.I. strip on surface or in recess
25mmx 5 mm GI strip on surface or in recess
6 SWG G.I wire on surface or in recess
75mmx 10mm G.I. strip below ground for Earth Mat (at 750 mm or deeper or as per the final approved design as per the site condition) as per specifications including lap (of not less than 150mm) & cross weld joints and providing bitumen coat at every joint as required. Risers from earth mat to be brought out as per approved drawings and specifications and on surface or in recess for other application.
H.T. CABLE LAYING & TERMINATIONS
Supplying of the following sizes of 33/11KV KV Alum. (E), Armoured XLPE HT power cable as per IS7098(part-2)-1985 amended up-to-date, as per specifications.
33 KV (E), 3C x 300 Sq. mm XLPE Aluminium Armoured cable
11 KV (E), 3C x 300 Sq. mm XLPE Aluminium Armoured cable
11 KV (E), 3C x 240 Sq. mm XLPE Aluminium Armoured cable
Laying of one number XLPE power cable of 33 kV grade of following size in the existing masonry open duct as required. Above 120 sq. mm and upto 400 sq. mm
Laying of one number XLPE power cable of 33 kV grade of following size in the existing RCC/ HUME/ METAL/ Cable tray pipe as required. Above 120 sq. mm and upto 400 sq. mm
Laying of one number additional XLPE power cable of 33 kV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc. as required. Above 120 sq. mm and upto 400 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 kV grade of following size in the existing masonry open duct as required. Above 120 sq. mm and upto 400 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 kV grade of following size in the existing RCC/ HUME/ METAL/ Cable Tray pipe as required. Above 120 sq. mm and upto 400 sq. mm
Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 11 kV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc. as required. Above 120 sq. mm and upto 400 sq. mm
supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 kV grade as required.
Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 kV grade as required.
Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 33 kV grade as required.
Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 33 kV grade as required. 300 sq. mm
Providing, laying and fixing of following dia. R.C.C. pipe NP3 class complete with R.C.C. collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) for road crossings including excavation and refilling etc. complete as required.
150 mm dia.
300 mm dia.
Constructing brick masonry manhole in cement mortar 1:4 (1 cement : 4 coarse sand) with R.C.C. top slab with 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), foundation concrete 1:4:8 mix (1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size), inside plastering 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with floating coat of neat cement and making channels in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement complete as per standard design : Inside size 150 x 150 cm and 150 cm deep including RCC cover with frame (heavy duty). With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
BUS TRUNKING SYSTEM
SANDWITCH TYPE RISING MAIN
Supplying, installing by suspension on ceiling/along the wall, testing and commissioning of following capacity Sandwich Type Rising Mains for use on 3 phase 4 wire 415 V, 50Hz A.C. supply with metal clad enclosure having IP- rating as per followings and all accessories, made of 1.6mm thick steel sheet duly powder coated in convenient sections complete with 4 Nos. aluminium bus bars having current density as per standards at nominal current rating, necessary joints, elbow joints & expansion joints and bends, fire barrier at each floor, provision of tapping at every meter, adopter box and copper flexible for joints, continuous earthing with 2 Nos. aluminium strip of suitable size (one on each side) including, G.I. clamping brackets, suspenders, angle iron bracket, steel fasteners, connecting to earthing system etc. as required. Note: The bus trunking shall be measured along the length of enclosure. The Aluminium strips which will go inside L.T. panels & end termination boxes of transformers shall not be into measurement of bus trunking quantity.
800 Amp. Indoor (IP-42) (4P) Aluminium bus trunking having Neutral =100% + 2 nos. of 50x6 mm external Aluminium earth strip
1000 Amp. Indoor (IP-42) (4P) Aluminium bus trunking having Neutral =100% + 2 nos. of 50x6 mm external Aluminium earth strip
1250 Amp. Indoor (IP-42) (4P) Aluminium bus trunking having Neutral =100% + 2 nos. of 50x6 mm external Aluminium earth strip
2000 Amp. Indoor (IP-42) (4P) Aluminium bus trunking having Neutral =100% + 2 nos. of 50x 6 mm external Aluminium earth strip.
3200 Amp. outdoor (IP-65) (4P) Aluminium bus trunking having Neutral =100% + 2 nos. of 50x 6 mm external Aluminium earth strip.
4000 Amp. outdoor (IP-65) (4P) Aluminium bus trunking having Neutral =100% + 2 nos. of 50x 6 mm external Aluminium earth strip.
LT CABLES & EARTHING
Supply of following size of 1.1 kv grade FRLS multicore aluminium conductor XLPE insulated and PVC sheathed armoured cable as per IS: 7098:1988 (Part-I) with upto date amendments.
4 core, 35 Sq.mm.
4 core, 25 Sq.mm.
4 core, 16 Sq.mm.
4 core, 10 Sq.mm.
4 core, 6 Sq.mm.
3½ core X 300 Sq.mm.
3½ core X 240 Sq.mm.
3½ core X 185 Sq.mm.
3½ core X 150 Sq.mm.
3½ core X 120 Sq.mm.
3½ core X 95 Sq.mm.
3½ core X 70 Sq.mm.
3½ core, 50 Sq.mm.
3 core, 120 Sq.mm.
3 core, 95 Sq.mm.
3 core, 35 Sq.mm.
3 core, 25 Sq.mm.
3 core, 16 Sq.mm.
3 core, 10 Sq.mm.
3 core, 6 Sq.mm.
Supply of following size of 1.1kv grade FRLS multicore copper conductor XLPE insulated and PVC sheathed armoured cable as per IS : 7098:1988 with upto date amendments.
4 core, 25 Sq.mm.
4 core, 10 Sq.mm.
4 core, 6 Sq.mm.
3 core, 6 Sq.mm.
Supply of following size of 1.1kv grade FRLS copper conductor XLPE insulated and PVC sheathed unarmoured cable as per IS : 7098:1988 with upto date amendments.
1 core, 185 Sq.mm. unarm cable
1 core, 16 Sq.mm. unarm cable
3 core, 6 Sq.mm. unarm cable
3 core, 4 Sq.mm. unarm cable
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. Tagging on both the ends will be done with aluminium tags etc. complete as required.
Upto 35 sq. mm (clamped with 1mm thick saddle)
Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)
Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp)
Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp)
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc. as required. Tagging on both the ends will be done with aluminium tags etc. complete as required.
Upto 35 sq. mm
Above 35 sq. mm and upto 95 sq. mm
Above 95 sq. mm and upto 185 sq. mm
Above 185 sq. mm and upto 400 sq. mm
Supplying and making indoor end termination with brass single compression gland (Heavy duty type) and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor armoured cable of 1.1 KV grade as required.
4 core, 35 Sq.mm.
4 core, 25 Sq.mm.
4 core, 16 Sq.mm.
4 core, 10 Sq.mm.
4 core, 6 Sq.mm.
3½ core X 300 Sq.mm.
3½ core X 240 Sq.mm.
3½ core X 185 Sq.mm.
3½ core X 150 Sq.mm.
3½ core X 120 Sq.mm.
3½ core X 95 Sq.mm.
3½ core X 70 Sq.mm.
3½ core, 50 Sq.mm.
3 core, 120 Sq.mm.
3 core, 95 Sq.mm.
3 core, 35 Sq.mm.
3 core, 25 Sq.mm.
3 core, 16 Sq.mm.
3 core, 10 Sq.mm.
3 core, 6 Sq.mm.
Supply and making end termination with double brass compression gland and Copper thimbles for XLPE insulated and PVC sheathed copper conductor cable of 1.1kv grade of the following sizes as required.
4 core, 25 Sq.mm.
4 core, 10Sq.mm.
4 core, 6 Sq.mm.
3 core, 6 Sq.mm.
1 core, 185 Sq.mm. unarm cable
1 core, 16 Sq.mm. unarm cable
3 core, 6 Sq.mm. unarm cable
3 core, 4 Sq.mm. unarm cable
Supply, laying, testing and commissioning of following FRLS PVC Copper armoured shielded/ unshielded control cable in trenches /on existing cable trays/ walls including the cost of saddles, gutties, clamps, lugs etc.as required.
12C x 2.5 sq.mm shielded cable
6C x 2.5 sq.mm
3C x 2.5 sq.mm
3C x 1.5 sq.mm
Supplying and making indoor end termination with brass double compression gland (flame proof type) and copper lugs for following size of PVC insulated and PVC sheathed copper conductor armoured cable of 1.1 KV grade as required.
12 Core x 2.5 Sqmm.
6 Core x 2.5 Sqmm.
3 Core x 2.5 Sq.mm
3 core X 1.5 sq. mm
Supplying, laying, connecting, terminating on both side testing & commissioning of following size of 1.1 kv grade single/multicore copper conductor Fire Survival Cables, as per BS7846, Mica Tape Insulated overall shielded, XLPE Insulated, Armoured, Halogen Free Sheathed, LPCB Certified for required sizes‐ as per specifications including complete ,on existing cable trays, ducts, over bed of sand, clamped to wall with suitable clamps including, saddles fixing bolts, complete on as required. Tagging on both the ends will be done with aluminium tags etc. complete as required. (For fire fighting main panel and smoke fans)
4 core X 25 Sq.mm. cooper conductor armoured cable
4 core X 16 Sq.mm. cooper conductor armoured cable
4 core X 10 Sq.mm. cooper conductor armoured cable
3 core X 35 Sq.mm. cooper conductor armoured cable
3 core X 25 Sq.mm. cooper conductor armoured cable
3 core X 16 Sq.mm. cooper conductor armoured cable
3 core X 10 Sq.mm. cooper conductor armoured cable
3 core X 6 Sq.mm. cooper conductor armoured cable
Cable Tray
Supply and installation of following size of (Hot dip) GI Ladder type cable trays in convenient sections, joined with connectors including horizontal and vertical bends, reducers, tees, cross members, clamps, connection pieces and other accessories as required, duly suspended from the ceiling with GI suspenders including GI bolts & GI nuts, etc. complete as required.
300mm 50mm 1.6mm thickness
450mm 50mm 1.6mm thickness
600mm 60mm 2mm thickness
1000mm 75mm 2.0mm thickness
Supply and installing of following size of (Hot dip) GI Perforated type cable trays in convenient sections, joined with connectors including horizontal and vertical bends, reducers, tees, cross members, clamps, connection pieces and other accessories as required, duly suspended from the ceiling GI suspenders including GI bolts & GI nuts including fabrication, etc. complete as required.
150mm 50mm 1.6mm thickness
300mm 50mm 1.6mm thickness
450mm 50mm 1.6mm thickness
600mm 60mm 2mm thickness
750mm 75mm 2mm thickness
Fabricating, Supply and installing of following size of FRP Ladder type cable trays in convenient sections, joined with connectors including horizontal and vertical bends, reducers, tees, cross members, clamps, connection pieces and other accessories as required, duly fixed on existing angle iron brackets including GI bolts & nuts, including fabrication, powder coated etc. as per specification as required. (For Tunnel)
450 mm widthx100mm depth
600 mm widthx100mm depth
1000mm widthx100mm depth
Supply and fixing of Wire mesh Cable tray shall be designed and tested as per IEC 61537.The Mesh cable tray shall be of Electro Galvanised confirming to DIN E 12329 for Indoor closed and dry atmospheric application. Wire mesh cable tray should be of self interlocking system for connecting the consecutive length of 3mtr tray without additional connectors. The Diameter of the steel wire shall be minimum 3.5 mm for trays upto 150 mm and minimum 4.5 mm for trays up to 600 mm Width. The Wire mesh cable tray shall be supplied with the standard length of 3 Mtr including suspending from ceiling with full threaded GI rods, connection pieces, G.I. nut bolts, G.I. washers, fasteners etc. complete as required. (supports / suspenders will be from same make of cable tray).
300 mm width x 55mm Height
150 mm width x 35mm Height
GI Raceway & Junction boxes
Supply, assembly and laying of under floor trunking made out of 1.6mm thick GI sheet complete with jointing sleeve, horizontal bends, vertical bends, level adjustment components and closer, vertical elbow, covers, access outlet. etc. complete with all other accessories under floor installation including cutting and chasing the floor/ or on surface, making good the same, placing in position and cleaning from inside complete etc. as required.
300 mm x 38 mm (3 compartment)
150 mm x 38 mm (2 compartment)
100 mm x 38 mm (2 compartment)
50 mm x 38 mm (1 compartment)
Providing and fixing 400 x 400 x 50 mm deep GI (hot dip galvanized) floor raceways junction box made out of 1.6 mm thick sheet steel as per specification.
Providing and fixing 250 x 250 x 50 mm deep GI (hot dip galvanized) raceways made out of 1.6 mm thick sheet steel junction box as per specification.
Providing and fixing 150 x 150 x 50 mm deep GI (hot dip galvanized) raceways made out of 1.6 mm thick sheet steel junction box as per specification.
Providing and fixing 100 x 100 x 50 mm deep GI (hot dip galvanized) raceways made out of 1.6 mm thick sheet steel junction box as per specification.
Supply and fixing of 8 modules floor pop up box including providing and fixing of 2 nos. 6 Amp Socket and Switches with steel finish for under floor trunking on floor including connection & accessories etc. as required.
LT PANELS
ALL LT PANELS SPECIFIC INCLUSIONS:
The outgoing feeders as indicated in SLD shall have suitable range of followings (except capacitor feeders).
ALL Digital electronic MFM and KWH meter shall be provided with RS 485 port/RJ-45 communication port compatible for BMS & Three phase indicating lamps protected by 2 amps SP MCBs.
All ACB's shall be EDO type, suitable for minimum 65/50 kA as specified in the items (Icu=Ics=Icw for 1 sec.)
All MCCB's shall be suitable for (Icu=Ics=100% at 415/433Volts, fault level as specified in the BOQ)
Wiring with space heater, thermostat and control MCB's shall be provided for all vertical sections of main LT panel.
All breakers shall be interlocked as per schematic diagram through PLC with auto load management control. Necessary required Under voltage relay needs to be considered for the same even though if not being mentioned in detailed BOQ..
All incoming as well as outgoing feeders shall have pad locking facility.
Suitable danger board shall be provided.
All MCCB in Main LT Panel should be Plugin/Drawout Type.
All MCCB’s shall be provided with front rotary handle and operating mechanism for door interlock with Pad locking of MCCB’s handles in “OFF” Position.
The Panel fabricator shall provide Al./ Copper Bus-bars link from Breakers wherever more than two nos. of cables are terminated in the breakers.
Additional set of C.T.s, potential free contacts, connectors, contactors with wiring etc. are to be provided for BMS including space required for various transducers in Main Switch Board sections. Only transducers shall be supplied by BMS contractor.
All hinged door shall be earthed through 2.5 sq mm tinned braided copper wire.
All the panels including 800A and above shall be type tested assembly as per IEC:61439 1&2
All the panels including 630A and below shall be Partial type tested assembly as per IEC:60439/IS 8623
All motor feeders MCCBs shall be of motor duty icu=ics=433v=1 sec..
Supporting/Base rigid steel framework.
TPN ACB’s / MCCB’s shall mean 3 pole ACB’s / MCCB’s with adequate size of neutral link.
All Back access panel shall be housed with encapsulated Spark gap based class-1/type-1 SPD with in built fuse for each incomer at each Bus Section of 100kA 10/350mS as per IS/IEC 62305-3 LPL-I. All front operated panel/Sub panels shall be housed with Mov based class-2/type-2 SPD with in built fuse for each incomer at each Bus Section of In 10kA & Irms 20kA 5/20mS as per IS/IEC 62305-3 LPL-I.
BACK ACCESS PANELS WITH ACB's
Design, fabrication, assembly, wiring and supply, erection , testing and commissioning of cubicle type compartmentalised as per Form 4B, rear access free standing, dust and vermin proof (Minimum IP 42 ingress protection) main switchboards conforming to IEC-61439 1&2 suitable for use at 433 volts, 3 phase 4 wire 50 Hertz system suitable for a symmetrical fault level of --kA (specified with the panel) at 433 volts, fabricated from 2 mm outer thick CRCA sheets with hinged, gasketted (metal based neoprene) and lockable doors having structural reinforcement with suitable angle/channel/T/flat sections including 3 mm thick gland plates on top and bottom including lifting hooks and earth bus of required size with 2 nos. earthing terminals, coating, paint finish of approved shade over metal surface cleaned and treated with nine tank process complete with interconnections etc. as per specifications, as required and as below. The incoming and outgoing feeders shall be accommodated in a modular arrangement, detachable gland plates, adequate size cable alley, Sign writing, Painting, Earthing, Numbering, Danger plate, including PVC insulated copper FRLS wires of minimum 1.5sq.mm & 2.5sq.mm for CT's etc. complete as required as per specifications and drawing attached.
MAIN LT PANEL Service Yard
Incomers:
i) 4000 Amp. 4 Pole ACB - 3 set (For 3 nos. transformers)
Air Circuit Breaker Horizontal drawout type of fault breaking capacity 65KA, Electrical Draw Out Motorised operated, fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/ test/isolated position indicators and frame earthing contact, conforming to IS/IEC-60947 as amended up-to-date complete with Independent Electrical & manual spring closing mechanism, Microprocessor release (EMI & EMC certified) for over current, earth fault & short circuit protection, Shunt trip coil 24V D.C / 220V A.C, Breaker Control Switch - 16A, Test terminal block set, circuits as per standard practice, auxiliary contactors with contacts (minimum 4NO+4NC) for positive interlocking of the breakers, necessary electrical interlocking with PLC auto controls etc. as required including accessories and suitable terminals to receive bus duct connections. Microprocessor based digital display with measurements, Current : phase / neutral / earth, average, max, Voltage : Phase, Line, Average; % loading of each phases in LED/LCD bargraph, on/ off, trip & ready to close breaker status communication on BMS.
LED indication lamps for RYB, breaker 'ON/ OFF/ TRIP', spring charged, DC control supply healthy etc. with 2Amp control MCBs
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Microprocessor release/s based relay/s (EMI & EMC certified) for over current, earth fault & short circuit protection, Under voltage relay with definite time, along with dual core CT of current transformers of 4000/5A ratio, 15 VA class-5P10 protection - 1 set.
Suitable size & set of CT's for APFC Relay (class 1.0, 15VA) & a set of neutral CT's for REF protection
Terminals to receive 4000A Al. Bus duct suitable & complete required as per site
Bus Bar :
3 Sections of Electrolytic high conductivity Aluminium extensible three phase and neutral busbars rated at 5000 amps , & auxiliary Bus Bars of suitable capacity insulated with heat shrinkable coloured PVC sleeves & suitable to with stand symmetrical fault level of 65 kA at 433 volts, i/c DMC/SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc.
Bus couplers
4000 Amp 4 pole ACB - 2 set.
a)Air Circuit Breaker Horizontal drawout type of fault breaking capacity 65KA Electrical Draw Out Motorised operated, fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/ test/isolated position indicators and frame earthing contact, conforming to IS/IEC-60947 as amended up-to-date complete with following accessories for each ACB
b) Independent Electrical / manual spring closing mechanism - I No.
c) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF' indicating light with 2A MCB, test terminal block set, circuits as per standard practice, auxiliary contacts for positive interlocking of the breakers as required.
Interlocking:
Electrical Interlocking through advance contacts / contactors in MCCB/ACB's (Incomers & Bus couplers) should be provided to ensure that only one supply is available at a time on each section of bus and to eliminate any possibility of accidentally approaching two supplies at one bus section as per single line diagram enclosed.
Outgoings:
All ACB (Ics=lcu=Icw=1s ) with microprocessor release with O/L, S/C & earth fault protection & followings shall be applicable to each.
a) Air Circuit Breaker Horizontal drawout type of fault breaking capacity 65KA, EDO type, fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/ test/isolated position indicators and frame earthing contact, conforming to IS/IEC-60947 as amended up-to-date complete with following accessories for each ACB with solid neutral link.
b) Independent manual spring closing mechanism
c) Microprocessor release(EMI & EMC certified) for with O/C S/C & earth fault protection - I set.
d)Set of Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
e) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF/TRIP' indicating light with 2A MCB, test terminal block set, circuits as per standard practice, auxiliary contacts for positive interlocking of the breakers as required.
f) Shunt trip coil 24VDC/220V A.C.
g) Terminals to receive suitable Al. Bus duct/cabling arrangement complete required as per site.
i) 2 Nos. - 2500 Amp. TP+N ACB with suitable terminals to receive bus duct connections for each. (2 Nos. Capacitor Banks)
ii) 2 Nos. - 2000 Amp. 4P ACB (1 No. LT Ring + 1 Spare)
iii) 5 Nos. - 1600 Amp. TP+N ACB with suitable terminals to receive bus duct connections for each.( 4 Nos. Chillers + 1 spare )
iv) 3 Nos. - 1600 Amp. 4P ACB with suitable terminals to receive bus duct connections for each. ( 2 Nos. Pump panels + 1 spare)
iv) 1 No. - 1000 Amp. TP+N ACB with suitable terminals to receive bus duct connections for each. (1 No. Capacitor Bank)
All MCCB (Ics=lcu) with microprocessor release with O/L, S/C& earth fault protection & followings shall be applicable to each.
All outgoing with microprocessor based release MCCB for O/C, S/C (with ON, off trip indications) of following capacity and rating, 65 KA (Ics=Icu =100% at 433 V ) with Set of Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system. Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
i) 2 Nos. - 630 Amp. 4P MCCB ( Spares )
ii) 6 Nos. - 400 Amp. 4P MCCB ( 2-PHE, 2-F.F, 1 STP, 1 spare )
iii) 12 Nos. - 250 Amp. 4P MCCB ( 2 Nos. HVAC Service yard, External development , 2 Nos. L&P panel , Project Office panel ,2 DG aux. 1 Borewell + 3 spare )
1 no. 32-bit microprocessor based PLC with MMI for auto load Management of Main LT Panel as required with, Transformer incomers ACB's and Bus couplers ACB's, electrical interlocking etc. as required and complete interfacing with DG Panel.
Necessary interlocking with PLC auto controls such that 3 Nos. T/F incomer, 2 No Bus couplers shall be successfully operational in all possible combinations.
The Switchboard with Logic control panel shall be complete with all interconnections, risers, internal wiring, labels, control/circuit fuses etc. complete as required.
Battery & Battery Charger
MAIN LT PANEL (HVAC/SERVICE YARD) AS ABOVE
HVAC PUMP PANEL
Incomers:
i) 1600 Amp. 4 Pole ACB - 2 set
LED indication lamps for RYB, breaker 'ON/ OFF/ TRIP', spring charged, DC control supply healthy etc. with 2Amp control MCBs
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Under voltage relays - Qty. as required to achieve PLC interlocking
Terminals to receive 1600A Al. Bus duct suitable & complete required as per site
Bus Bar :
2 Sections of Electrolytic high conductivity Aluminium extensible three phase and neutral busbars rated at 2000 amps , & auxiliary Bus Bars of suitable capacity insulated with heat shrinkable coloured PVC sleeves & suitable to with stand symmetrical fault level of 50 kA at 433 volts, i/c DMC/SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc.
Interlocking:
Electrical Interlocking through advance contacts / contactors in MCCB's (Incomers & Bus couplers) should be provided to ensure that only one supply is available at a time on each section of bus and to eliminate any possibility of accidentally approaching two supplies at one bus section as per single line diagram enclosed.
Outgoings:
All MCCB (Ics=lcu) with O/L, S/C,E,F protection & followings shall be applicable to each.
All outgoing with motor duty MCCB with O/C, and suitable release for S/C,E/F protection (with ON, off trip indications) of following capacity and rating, 50kA (Ics=Icu =1s upto 433 V ) with Set of Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.. , Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
i) 5 Nos. - 250 Amp. TPN MCCB ( 4 Nos. CDW Pump, 1 spare )
ii) 5 Nos. - 200 Amp. TPN MCCB ( 4 Nos. CHWSP ,1 spare)
iii) 5 Nos. - 100 Amp. TPN MCCB ( 4 Nos. CHWPP, 1 spare)
iv) 9 Nos. - 125 Amp. TPN MCCB ( 8 Nos. CT fans, 1 spare)
v) 2 Nos. - 63 Amp. TPN MCCB ( 1 Nos. filtration system, 1 spare)
vi) 5 Nos. - 32 Amp. TPN MCCB ( 2 Nos. PMS pumps, 2 CT treatment system, 1 spare)
HVAC PUMP PANEL (HVAC/SERVICE YARD) AS ABOVE
MAIN LT PANEL TERMINAL BUILDING ESS
Incomers:
i) 3200 Amp. 4 Pole ACB - 3 set (For 3 nos. transformers)
LED indication lamps for RYB, breaker 'ON/ OFF/ TRIP', spring charged, DC control supply healthy etc. with 2Amp control MCBs
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Under voltage relays - Qty. as required to achieve PLC interlocking
Suitable size & set of CT's for APFC Relay (class 1.0, 15VA) & a set of neutral CT's for REF protection
Terminals to receive 3200A Al. Bus duct suitable & complete required as per site
Bus Bar :
3 Sections of Electrolytic high conductivity Aluminium extensible three phase and neutral busbars rated at 4000 amps , & auxiliary Bus Bars of suitable capacity insulated with heat shrinkable coloured PVC sleeves & suitable to with stand symmetrical fault level of 50 kA at 433 volts, i/c DMC/SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc.
Bus couplers
3200 Amp 4 pole ACB - 2 set.
a)Air Circuit case design, Horizontal drawout type of fault breaking capacity 50KA (Ics=lcu =Icw) upto 433V) Electrical Draw Out Motorised operated, fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/ test/isolated position indicators and frame earthing contact, conforming to IS/IEC-60947 as amended up-to-date complete with following accessories for each ACB.
b) Independent Electrical / manual spring closing mechanism - I No.
c) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF' indicating light with 2A MCB, test terminal block set, circuits as per standard practice, auxiliary contacts for positive interlocking of the breakers as required.
Interlocking:
Electrical Interlocking through advance contacts / contactors in MCCB/ACB's (Incomers & Bus couplers) should be provided to ensure that only one supply is available at a time on each section of bus and to eliminate any possibility of accidentally approaching two supplies at one bus section as per single line diagram enclosed.
Outgoings:
All ACB (Ics=lcu=Icw=1s ) with microprocessor release with O/L, S/C & earth fault protection & followings shall be applicable to each.
b) Independent manual spring closing mechanism
c) Microprocessor release(EMI & EMC certified) for with O/C S/C & earth fault protection - I set.
d)Set of Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
e) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF/TRIP' indicating light with 2A MCB, test terminal block set, circuits as per standard practice, auxiliary contacts for positive interlocking of the breakers as required.
f) Shunt trip coil 24VDC/220V A.C.
g) Terminals to receive suitable Al. Bus duct/cabling arrangement complete required as per site.
i) 2 Nos. - 2000 Amp. 4P ACB with suitable terminals to receive bus duct connections for each. (2 Smoke Ext. Main Panels )
ii) 4 Nos. - 2000 Amp. TP+N ACB with suitable terminals to receive bus duct connections for each. (2 Capacitor Banks + 1 LT Ring + 1 Spare )
iii) 1 No. - 1000 Amp. TP+N ACB with suitable terminals to receive bus duct connections for each. (1 Capacitor Bank)
iv) 3 Nos. - 1250 Amp. 4P ACB with suitable terminals to receive bus duct connections for each. (2 Em. Panels, 1 spare)
v) 7 Nos. - 1000 Amp. 4P ACB with suitable terminals to receive bus duct connections for each. ( Main AHU Panel,1,2,Main Power Panel,1,2, Main Lift & Esc. Panel,1,2, 1 Spare )
vi) 7 Nos. - 800 Amp. 4P ACB with suitable terminals to receive bus duct connections for each. (2 Nos. Main Lighting Panel + 2 Nos. BHS panels + 2 Nos. Retail M.B,1 Spare)
All MCCB (Ics=lcu) with O/L, S/C,E/F followings shall be applicable to each.
All outgoing MCCB for O/C, S/C,E/F protection (with ON, off trip indications) of following capacity and rating, 50 KA (Ics=Icu upto 433 V for 1s ) with Set of Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system. , Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
i) 3 Nos. -Microprocessor based 630 Amp. TPN MCCB ( 2 Nos. PBB panels + 1 Spare)
ii) 4 Nos. - Microprocessor based 400 Amp. TPN MCCB ( 2 Nos. PBB panels + 2 Spare)
iii) 7 Nos. - Thermal magnetic 250 Amp. TPN MCCB (1 External Dev. Panel, 2 Pump Panel, 2 Nos. ELV services, 1 Borewell panel ,1 spare)
1 no. 32-bit microprocessor based PLC with MMI for auto load Management of Main LT Panel as required with , Transformer incomers ACB's and Bus couplers ACB's, electrical interlocking etc. as required and complete interfacing with DG Panel.
Necessary interlocking with PLC auto controls such that 3 Nos. T/F incomer, 2 No Bus couplers shall be successfully operational in all possible combinations.
The Switchboard with Logic control panel shall be complete with all interconnections, risers, internal wiring, labels, control/circuit fuses etc. complete as required.
Battery & Battery Charger
MAIN LT PANEL AS ABOVE
MAIN EMERGENCY PANEL
Incomers:
i) 1250 Amp. 4 Pole ACB - 2 set
LED indication lamps for RYB, breaker 'ON/ OFF/ TRIP', spring charged, DC control supply healthy etc. with 2Amp control MCBs
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Under voltage relays - Qty. as required to achieve interlocking
Bus Bar :
2 Sections of Electrolytic high conductivity Aluminium extensible three phase and neutral busbars rated at 1600 amps , & auxiliary Bus Bars of suitable capacity insulated with heat shrinkable coloured PVC sleeves & suitable to with stand symmetrical fault level of 50 kA at 433 volts, i/c DMC/SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc.
Bus couplers
1250 Amp 4 pole ACB - 1 set.
a)Air Circuit case design, Horizontal drawout type of fault breaking capacity 50KA (Ics=lcu =Icw) upto 433V) Electrical Draw Out Motorised operated, fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/ test/isolated position indicators and frame earthing contact, conforming to IS/IEC-60947 as amended up-to-date complete with following accessories for each ACB.
b) Independent Electrical / manual spring closing mechanism
c) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF' indicating light with 2A MCB, test terminal block set, circuits as per standard practice, auxiliary contacts for positive interlocking of the breakers as required.
Interlocking:
Electrical Interlocking through advance contacts / contactors in MCCB/ACB's (Incomers & Bus couplers) should be provided to ensure that only one supply is available at a time and to eliminate any possibility of accidentally approaching two supplies at one bus section as per single line diagram enclosed.
All MCCB (Ics=lcu) with O/L, S/C,E/F protection & followings shall be applicable to each.
All outgoing MCCB for O/C, S/C,E/F protection (with On, Off, Trip indications) of following capacity and rating, 35 KA (Ics=Icu upto 433 V ) with Set of Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system. , Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
i) 4 Nos. - Microprocessor based 400 Amp. TPN MCCB (3 Nos. UPS, 1 spare)
ii) 7 Nos. - Thermal Magnetic 250 Amp. TPN MCCB (3 Nos. Ventilation panels with 2 feeders , 2 spare)
iii) 3 Nos. - Thermal Magnetic 100 Amp. TPN MCCB (2 Nos. F.F P panels, 1 spare)
Necessary interlocking with micro PLC auto controls such that 3 Nos. incomers, 2 No Bus couplers shall be successfully operational in all possible combinations.
The Switchboard with Logic control panel shall be complete with all interconnections, risers, internal wiring, labels, control/circuit fuses etc. complete as required.
MAIN EMERGENCY PANEL AS ABOVE
MAIN LIGHTING PANEL
Incomers:
i) 800 Amp. 4 Pole ACB - 2 set
LED indication lamps for RYB, breaker 'ON/ OFF/ TRIP', spring charged, DC control supply healthy etc. with 2Amp control MCBs
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Microprocessor release/s based relay/s (EMI & EMC certified) for over current, earth fault & short circuit protection, Under voltage relay with definite time , along with dual core CT of current transformers of 800/5A ratio, 15 VA class-5P10 protection - 1 set.
Terminals to receive 800A Al. Bus duct suitable & complete required as per site
Bus Bar :
2 Sections of Electrolytic high conductivity Aluminium extensible three phase and neutral busbars rated at 1000 amps , & auxiliary Bus Bars of suitable capacity insulated with heat shrinkable coloured PVC sleeves & suitable to with stand symmetrical fault level of 50 kA at 433 volts, i/c DMC/SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc.
Bus couplers
800 Amp 4 pole ACB - 1 set.
a)Air Circuit case design, Horizontal drawout type of fault breaking capacity 50KA (Ics=lcu =Icw) upto 433V) Electrical Draw Out Motorised operated, fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/ test/isolated position indicators and frame earthing contact, conforming to IS/IEC-60947 as amended up-to-date complete with following accessories for each ACB.
b) Independent Electrical / manual spring closing mechanism
c) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF' indicating light with 2A MCB, test terminal block set, circuits as per standard practice, auxiliary contacts for positive interlocking of the breakers as required.
Interlocking:
Electrical Interlocking through advance contacts / contactors in MCCB/ACB's (Incomers & Bus couplers) should be provided to ensure that only one supply is available at a time and to eliminate any possibility of accidentally approaching two supplies at one bus section as per single line diagram enclosed.
Outgoings:
All MCCB (Ics=lcu) with O/L, S/C,E/F protection & followings shall be applicable to each.
All outgoing with MCCB for O/C, S/C,E/F protection with On, off trip indications of following capacity and rating, 50KA (Ics=Icu=100% ) with Set of Digital flush type calibrated Intelligent multifunction meters (with communication port) suitable rating class - 1.0 accuracy , showing V, A, KW with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 5 VA Class 1.0 metering. , Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
i) 6 Nos. Thermal Magnetic 125 Amp. TPN 35kA MCCB ( Floor Lighting Panels & spares )
ii) 20 Nos. - Thermal Magnetic 100 Amp. TPN 35kA MCCB ( Floor Lighting Panels & spares )
Necessary interlocking 2 Nos. Incomers shall be successfully operational in all possible combinations.
The Switchboard with Logic control panel shall be complete with all interconnections, risers, internal wiring, labels, control/circuit fuses etc. complete as required.
MAIN LIGHTING PANEL AS ABOVE
MAIN POWER PANEL
Incomers:
i) 1000 Amp. 4 Pole ACB - 2 set
LED indication lamps for RYB, breaker 'ON/ OFF/ TRIP', spring charged, DC control supply healthy etc. with 2Amp control MCBs
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Microprocessor release/s based relay/s (EMI & EMC certified) for over current, earth fault & short circuit protection, Under voltage relay with definite time, along with dual core CT of current transformers of 1000/5A ratio, 15 VA class-5P10 protection - 1 set.
Terminals to receive 1250A Al. Bus duct suitable & complete required as per site
Bus Bar :
2 Sections of Electrolytic high conductivity Aluminium extensible three phase and neutral busbars rated at 1250 amps , & auxiliary Bus Bars of suitable capacity insulated with heat shrinkable coloured PVC sleeves & suitable to with stand symmetrical fault level of 35 kA at 433 volts, i/c DMC/SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc.
Bus couplers
1000 Amp 4 pole ACB - 1 set.
a)Air Circuit case design, Horizontal drawout type of fault breaking capacity 50KA (Ics=lcu =Icw) upto 433V) Electrical Draw Out Motorised operated, fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/ test/isolated position indicators and frame earthing contact, conforming to IS/IEC-60947 as amended up-to-date complete with following accessories for each ACB.
b) Independent Electrical / manual spring closing mechanism
c) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF' indicating light with 2A MCB, test terminal block set, circuits as per standard practice, auxiliary contacts for positive interlocking of the breakers as required.
Interlocking:
Electrical Interlocking through advance contacts / contactors in MCCB/ACB's (Incomers & Bus couplers) should be provided to ensure that only one supply is available at a time and to eliminate any possibility of accidentally approaching two supplies at one bus section as per single line diagram enclosed.
Outgoings:
MCCB (Ics=lcu) with O/L, S/C,E/F protection & followings shall be applicable to each.
All outgoing with MCCB for O/C, S/C,E/F protection with On, off trip indications of following capacity and rating, 50 KA (Ics=Icu=100% ) with Set of Digital flush type calibrated Intelligent multifunction meters (with communication port) suitable rating class - 1.0 accuracy , showing V, A, KW with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 5 VA Class 1.0 metering. , Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
i) 2 Nos. - Thermal Magnetic 250 Amp. TPN 35kA MCCB
i) 10 Nos. - Thermal Magnetic 160 Amp. TPN 35kA MCCB ( Floor Power Panels & spares )
ii) 16 Nos. - Thermal Magnetic 100 Amp. TPN 35kA MCCB ( Floor Power Panels & spares )
Necessary interlocking 2 Nos. Incomers shall be successfully operational in all possible combinations.
The Switchboard with Logic control panel shall be complete with all interconnections, risers, internal wiring, labels, control/circuit fuses etc. complete as required.
MAIN POWER PANEL AS ABOVE
MAIN AHU PANEL
Incomers:
i) 1000 Amp. 4 Pole ACB - 2 set
LED indication lamps for RYB, breaker 'ON/ OFF/ TRIP', spring charged, DC control supply healthy etc. with 2Amp control MCBs
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Microprocessor release/s based relay/s (EMI & EMC certified) for over current, earth fault & short circuit protection, Under voltage relay with definite time , along with dual core CT of current transformers of 1250/5A ratio, 15 VA class-5P10 protection - 1 set.
Terminals to receive 1250A Al. Bus duct suitable & complete required as per site
Bus Bar :
2 Sections of Electrolytic high conductivity Aluminium extensible three phase and neutral busbars rated at 1250 amps , & auxiliary Bus Bars of suitable capacity insulated with heat shrinkable coloured PVC sleeves & suitable to with stand symmetrical fault level of 35 kA at 433 volts, i/c DMC/SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc.
Bus couplers
1000 Amp 4 pole ACB - 1 set.
a)Air Circuit case design, Horizontal drawout type of fault breaking capacity 50KA (Ics=lcu =Icw) upto 433V) Electrical Draw Out Motorised operated, fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/ test/isolated position indicators and frame earthing contact, conforming to IS/IEC-60947 as amended up-to-date complete with following accessories for each ACB.
b) Independent Electrical / manual spring closing mechanism
c) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF' indicating light with 2A MCB, test terminal block set, circuits as per standard practice, auxiliary contacts for positive interlocking of the breakers as required.
Interlocking:
Electrical Interlocking through advance contacts / contactors in MCCB/ACB's (Incomers & Bus couplers) should be provided to ensure that only one supply is available at a time and to eliminate any possibility of accidentally approaching two supplies at one bus section as per single line diagram enclosed.
Outgoings:
All MCCB (Ics=lcu) with O/L, S/C,E/F followings shall be applicable to each.
All outgoing with MCCB for O/C, S/C,E/F protection with On, off trip indications of following capacity and rating, 50 KA (Ics=Icu=100% ) with Set of Digital flush type calibrated Intelligent multifunction meters (with communication port) suitable rating class - 1.0 accuracy , showing V, A, KW with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 5 VA Class 1.0 metering. , Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
i) 8 Nos. - Thermal Magnetic 250 Amp. TPN MCCB ( Floor AHU Panels & spares )
ii) 7 Nos. - Thermal Magnetic 160 Amp. TPN MCCB ( Floor AHU Panels & spares )
iii) 2 Nos. - Thermal Magnetic125 Amp. TPN MCCB ( Floor AHU Panels )
iv) 5 Nos. - Thermal Magnetic 100 Amp. TPN MCCB ( Floor AHU Panels & spares )
Necessary interlocking 2 Nos. Incomers shall be successfully operational in all possible combinations.
The Switchboard panel shall be complete with all interconnections, risers, internal wiring, labels, control/circuit fuses etc. complete as required.
MAIN AHU PANEL AS ABOVE
MAIN SMOKE EXT. PANEL
Incomers:
2000 Amp. 4 Pole ACB - 2 set
LED indication lamps for RYB, breaker 'ON/ OFF/ TRIP', spring charged, DC control supply healthy etc. with 2Amp control MCBs
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Microprocessor release/s based relay/s (EMI & EMC certified) for over current, earth fault & short circuit protection, Under voltage relay with definite time , along with dual core CT of current transformers of 2000/5A ratio, 15 VA class-5P10 protection - 1 set.
Terminals to receive 2000A Al. Bus duct suitable & complete required as per site
Bus Bar :
2 Sections of Electrolytic high conductivity Aluminium extensible three phase and neutral busbars rated at 2500 amps , & auxiliary Bus Bars of suitable capacity insulated with heat shrinkable coloured PVC sleeves & suitable to with stand symmetrical fault level of 50 kA at 433 volts, i/c DMC/SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc.
Bus couplers
2000 Amp 4 pole ACB - 1 set.
a)Air Circuit case design, Horizontal drawout type of fault breaking capacity 50KA (Ics=lcu =Icw) upto 433V) Electrical Draw Out Motorised operated, fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/ test/isolated position indicators and frame earthing contact, conforming to IS/IEC-60947 as amended up-to-date complete with following accessories for each ACB.
b) Independent Electrical / manual spring closing mechanism
c) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF' indicating light with 2A MCB, test terminal block set, circuits as per standard practice, auxiliary contacts for positive interlocking of the breakers as required.
Interlocking:
Electrical Interlocking through advance contacts / contactors in MCCB/ACB's (Incomers & Bus couplers) should be provided to ensure that only one supply is available at a time and to eliminate any possibility of accidentally approaching two supplies at one bus section as per single line diagram enclosed.
Outgoings:
MCCB (Ics=lcu) with O/L, S/C & earth fault protection & followings shall be applicable to each.
All outgoing with MCCB for O/C, S/C & earth fault protection as specified below with On, off trip indications of following capacity and rating, 50 KA (Ics=Icu=100% ) with Set of Digital flush type calibrated Intelligent multifunction meters (with communication port) suitable rating class - 1.0 accuracy , showing V, A, KW with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 5 VA Class 1.0 metering. , Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
i) 4 Nos. - Microprocessor based release 630 Amp. TPN MCCB ( Floor Smoke ext. Panels & spares )
ii) 8 Nos. - Microprocessor based 250 Amp. TPN MCCB ( Floor Smoke ext. Panels & spares )
iii) 1 Nos. - Microprocessor based 200 Amp. TPN MCCB ( Floor Smoke ext. Panels & spares )
iv) 1 No. - Microprocessor based 160 Amp. TPN MCCB ( Floor Smoke ext. Panels & spares )
v) 1 No. - Microprocessor based 100 Amp. TPN MCCB ( Floor Smoke ext. Panels & spares )
The Switchboard panel shall be complete with all interconnections, risers, internal wiring, labels, control/circuit fuses etc. complete as required.
MAIN SMOKE EXT. PANEL AS ABOVE
UPS OUTPUT PANEL
Incomers:
i) 400 Amp. 4 Pole MCCB - 3 set
i) 3 No. 400Amps. 4P MCCB '35ka, Icu=Ics with micro processor based release having O/L ,S/C, earth fault protection equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF/TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus Bar :
3 Sections of Electrolytic high conductivity Copper extensible 4P rated at 800 amps , & auxiliary Bus Bars of suitable capacity insulated with heat shrinkable coloured PVC sleeves & suitable to with stand symmetrical fault level of 35 kA at 433 volts, i/c DMC/SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc.
Bus couplers
800 Amp 4 pole ACB - 2 set.
a)Air Circuit case design, Horizontal drawout type of fault breaking capacity 50KA (Ics=lcu =Icw) upto 433V) Electrical Draw Out Motorised operated, fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/ test/isolated position indicators and frame earthing contact, conforming to IS/IEC-60947 as amended up-to-date complete with following accessories for each ACB.
b) Independent Electrical / manual spring closing mechanism - I No.
c) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF' indicating light with 2A MCB, test terminal block set, circuits as per standard practice, auxiliary contacts for positive interlocking of the breakers as required.
Interlocking:
Electrical Interlocking through advance contacts / contactors in MCCB/ACB's (Incomers & Bus couplers) should be provided to ensure that only one supply is available at a time and to eliminate any possibility of accidentally approaching two supplies at one bus section as per single line diagram enclosed.
Outgoings:
All ACB (Ics=lcu=Icw=1s ) with microprocessor release with O/L, S/C & earth fault protection & followings shall be applicable to each.
a) Air Circuit case design, Horizontal drawout type of fault breaking capacity 50KA, EDO type, fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/ test/isolated position indicators and frame earthing contact, conforming to IS/IEC-60947 as amended up-to-date complete with following accessories for each ACB with solid neutral link.
b) Independent manual spring closing mechanism
c) Microprocessor release(EMI & EMC certified) for with O/C S/C & earth fault protection - I set.
d) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF/TRIP' indicating light with 2A MCB, test terminal block set, circuits as per standard practice, auxiliary contacts for positive interlocking of the breakers as required.
e) Shunt trip coil 24VDC/220V A.C.
f) Terminals to receive suitable Al. Bus duct/cabling arrangement complete required as per site.
i) 3 Nos. - 800 Amp. 4P ACB with suitable terminals to receive bus duct connections for each.
All MCCB (Ics=lcu) with thermal magnetic with O/L, S/C & earth fault protection & followings shall be applicable to each.
i) 2 Nos. - 100 Amp. TPN MCCB ( Floor Panels & spares )
The Switchboard panel shall be complete with all interconnections, risers, internal wiring, labels, control/circuit fuses etc. complete as required.
UPS OUTPUT PANEL AS ABOVE
UPS DISTRIBUTION PANEL
Incomers:
800 Amp. 4 Pole ACB - 2 set
LED indication lamps for RYB, breaker 'ON/ OFF/ TRIP', spring charged, DC control supply healthy etc. with 2Amp control MCBs
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Microprocessor release/s based relay/s (EMI & EMC certified) for over current, earth fault & short circuit protection, Under voltage relay with definite time , along with dual core CT of current transformers of 800/5A ratio, 15 VA class-5P10 protection - 1 set.
Terminals to receive 1000A Al. Bus duct suitable & complete required as per site
Bus Bar :
2 Sections of Electrolytic high conductivity copper extensible 4P busbars rated at 1000 amps & auxiliary Bus Bars of suitable capacity insulated with heat shrinkable coloured PVC sleeves & suitable to with stand symmetrical fault level of 50 kA at 433 volts, i/c DMC/SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc.
Bus couplers
800 Amp 4 pole ACB - 1 set.
a)Air Circuit case design, Horizontal drawout type of fault breaking capacity 50KA (Ics=lcu =Icw) upto 433V) Electrical Draw Out Motorised operated, fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/ test/isolated position indicators and frame earthing contact, conforming to IS/IEC-60947 as amended up-to-date complete with following accessories for each ACB.
b) Independent Electrical / manual spring closing mechanism.
c) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF' indicating light with 2A MCB, test terminal block set, circuits as per standard practice, auxiliary contacts for positive interlocking of the breakers as required.
Interlocking:
Electrical Interlocking through advance contacts / contactors in MCCB/ACB's (Incomers & Bus couplers) should be provided to ensure that only one supply is available at a time and to eliminate any possibility of accidentally approaching two supplies at one bus section as per single line diagram enclosed.
Outgoings:
All MCCB (Ics=lcu) with thermal magnetic based with O/L, S/C & earth fault protection & followings shall be applicable to each.
All outgoing with MCCB for O/C, S/C & earth fault protection with On, off trip indications of following capacity and rating, 35 KA (Ics=Icu=100% ) with Set of Digital flush type calibrated Intelligent multifunction meters (with communication port) suitable rating class - 1.0 accuracy , showing V, A, KW with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 5 VA Class 1.0 metering. , Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
i) 24 Nos. - 100 Amp. 4P MCCB ( Floor UPS Panels & spares )
The Switchboard panel shall be complete with all interconnections, risers, internal wiring, labels, control/circuit fuses etc. complete as required.
UPS DISTRIBUTION PANEL AS ABOVE
MAIN Lifts & Esc. PANEL
Incomers:
1000 Amp. 4 Pole ACB - 2 set
LED indication lamps for RYB, breaker 'ON/ OFF/ TRIP', spring charged, DC control supply healthy etc. with 2Amp control MCBs
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Terminals to receive 1000A Al. Bus duct suitable & complete required as per site
Under voltage relays - Qty. as required to achieve interlocking
Bus Bar :
2 Sections of Electrolytic high conductivity Aluminium extensible three phase and neutral busbars rated at 1250 amps , & auxiliary Bus Bars of suitable capacity insulated with heat shrinkable coloured PVC sleeves & suitable to with stand symmetrical fault level of 50 kA at 433 volts, i/c DMC/SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc.
Bus couplers
1000 Amp 4 pole ACB - 1 set.
a)Air Circuit case design, Horizontal drawout type of fault breaking capacity 50KA (Ics=lcu =Icw) upto 433V) Electrical Draw Out Motorised operated, fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/ test/isolated position indicators and frame earthing contact, conforming to IS/IEC-60947 as amended up-to-date complete with following accessories for each ACB.
b) Independent Electrical / manual spring closing mechanism - I No.
c) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF' indicating light with 2A MCB, test terminal block set, circuits as per standard practice, auxiliary contacts for positive interlocking of the breakers as required.
Interlocking:
Electrical Interlocking through advance contacts / contactors in MCCB/ACB's (Incomers & Bus couplers) should be provided to ensure that only one supply is available at a time and to eliminate any possibility of accidentally approaching two supplies at one bus section as per single line diagram enclosed.
Outgoings:
All MCCB (Ics=lcu) with O/L, S/C & earth fault protection & followings shall be applicable to each.
All outgoing with MCCB for O/C, S/C & earth fault protection with On, off trip indications of following capacity and rating, 50 KA (Ics=Icu=100% ) with Set of Digital flush type calibrated Intelligent multifunction meters (with communication port) suitable rating class - 1.0 accuracy , showing V, A, KW with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 5 VA Class 1.0 metering. , Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
i) 8 Nos. - 400 Amp. TPN MCCB Microprocessor Based ( Floor Panels & spares )
The Switchboard panel shall be complete with all interconnections, risers, internal wiring, labels, control/circuit fuses etc. complete as required.
MAIN Lifts & Esc. PANEL AS ABOVE
MAIN METER BOARD PANEL
Incomers:
800 Amp. 4 Pole ACB - 2 set
LED indication lamps for RYB, breaker 'ON/ OFF/ TRIP', spring charged, DC control supply healthy etc. with 2Amp control MCBs
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Terminals to receive 800A Al. Bus duct suitable & complete required as per site
Under voltage relays - Qty. as required to achieve interlocking
Bus Bar :
2 Sections of Electrolytic high conductivity Aluminium extensible three phase and neutral busbars rated at 1000 amps , & auxiliary Bus Bars of suitable capacity insulated with heat shrinkable coloured PVC sleeves & suitable to with stand symmetrical fault level of 50 kA at 433 volts, i/c DMC/SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc.
Bus couplers
800 Amp 4 pole ACB - 1 set.
a)Air Circuit case design, Horizontal drawout type of fault breaking capacity 50KA (Ics=lcu =Icw) upto 433V) Electrical Draw Out Motorised operated, fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/ test/isolated position indicators and frame earthing contact, conforming to IS/IEC-60947 as amended up-to-date complete with following accessories for each ACB.
b) Independent Electrical / manual spring closing mechanism - I No.
c) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF' indicating light with 2A MCB, test terminal block set, circuits as per standard practice, auxiliary contacts for positive interlocking of the breakers as required.
Interlocking:
Electrical Interlocking through advance contacts / contactors in MCCB/ACB's (Incomers & Bus couplers) should be provided to ensure that only one supply is available at a time and to eliminate any possibility of accidentally approaching two supplies at one bus section as per single line diagram enclosed.
Outgoings:
All MCCB (Ics=lcu) with O/L, S/C & earth fault protection & followings shall be applicable to each.
All outgoing with MCCB for O/C, S/C & earth fault protection with On, off trip indications of following capacity and rating, 50 KA (Ics=Icu=100% ) with Set of Digital flush type calibrated Intelligent multifunction meters (with communication port) suitable rating class - 1.0 accuracy , showing V, A, KW with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 5 VA Class 1.0 metering. , Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
i) 4 Nos. - 400 Amp. TPN MCCB with microprocessor based release ( Retail Meter Board Panels & spare)
ii) 4 No. - 200 Amp. TPN MCCB with thermal magnetic based release ( Retail Meter Board Panels & spare)
The Switchboard panel shall be complete with all interconnections, risers, internal wiring, labels, control/circuit fuses etc. complete as required.
MAIN METER BOARD PANEL AS ABOVE
MAIN BHS PANEL
Incomers:
800 Amp. 4 Pole ACB - 2 set
LED indication lamps for RYB, breaker 'ON/ OFF/ TRIP', spring charged, DC control supply healthy etc. with 2Amp control MCBs
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Microprocessor release/s based relay/s (EMI & EMC certified) for over current, earth fault & short circuit protection, Under voltage relay with definite time, along with dual core CT of current transformers of 800/5A ratio, 15 VA class-5P10 protection - 1 set.
Terminals to receive 1000A Al. Bus duct suitable & complete required as per site
Bus Bar :
2 Sections of Electrolytic high conductivity Aluminium extensible three phase and neutral busbars rated at 1000 amps , & auxiliary Bus Bars of suitable capacity insulated with heat shrinkable coloured PVC sleeves & suitable to with stand symmetrical fault level of 50 kA at 433 volts, i/c DMC/SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc.
Bus couplers
800 Amp 4 pole ACB - 1 set.
a)Air Circuit case design, Horizontal drawout type of fault breaking capacity 50KA (Ics=lcu =Icw) upto 433V) Electrical Draw Out Motorised operated, fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/ test/isolated position indicators and frame earthing contact, conforming to IS/IEC-60947 as amended up-to-date complete with following accessories for each ACB.
b) Independent Electrical / manual spring closing mechanism - I No.
c) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF' indicating light with 2A MCB, test terminal block set, circuits as per standard practice, auxiliary contacts for positive interlocking of the breakers as required.
Interlocking:
Electrical Interlocking through advance contacts / contactors in MCCB/ACB's (Incomers & Bus couplers) should be provided to ensure that only one supply is available at a time and to eliminate any possibility of accidentally approaching two supplies at one bus section as per single line diagram enclosed.
Outgoings:
All MCCB (Ics=lcu) with thermal magnetic based release O/L, S/C & earth fault protection & followings shall be applicable to each.
All outgoing with MCCB for O/C, S/C & earth fault protection with On, off trip indications of following capacity and rating, 50 KA (Ics=Icu=100% ) with Set of Digital flush type calibrated Intelligent multifunction meters (with communication port) suitable rating class - 1.0 accuracy , showing V, A, KW with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 5 VA Class 1.0 metering. , Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
i) 4 No. - 250 Amp. TPN MCCB ( BHS DISTRIBUTION PANELS )
ii) 4 No. - 160 Amp. TPN MCCB ( BHS DISTRIBUTION PANELS )
The Switchboard panel shall be complete with all interconnections, risers, internal wiring, labels, control/circuit fuses etc. complete as required.
MAIN BHS PANEL AS ABOVE
CAPACITOR PANELS
The capacitor units shall be rated at 525 V.
1000 kVAR HYBRID PANEL
The Hybrid Solution should comprise of Active filter i.e. 700A and Passive i.e.( 500kVAr ). Incomer should be 2000A, 50kA ACB. The Active harmonic filter shall be 2 nos. of 350A with IGBT's (or as per manufacturer). The Passive part shall comprise of Thyristors with suitable rating fast active semi conductor fuse, de-tuned with series reactor 14% and capacitor bank should have the following step ratings: 9 x 50 + 2 x 15 + 2 x 10kVAr. Capacitor shall be as per MPP low loss as per standards. · Each stage of the capacitor bank should have suitable overload and short circuit protection. · The Solution should have surge arrestors and over temperature protection.
The system should be with compatible with Grid Power OR D.G. Power Supply.
The manufacturer / supplier should prove through submission of software simulations that the Total Demand Distortion (TDD) is within the limits as specified in IEEE Std 519-2014, standards on IEEE recommended practices and requirements for Harmonic Control in Electric Power System. The simulation software should take into consideration the performance of the detuned capacitor bank. The capacitor bank shall not amplify the existing system harmonics.
The capacitor banks should be of type tested design and temperature rise test report of the capacitor bank performed at an independent laboratory should be submitted along with the offer. Third party type test certificate from an organization of international repute must be submitted along with the tender document for technical approval for Hybrid filter. The international laboratory should be accredited according to ISO/IEC 17025:2005.
The Hybrid PQ Solution should be designed, manufactured and supplied by the Original Equipment Manufacturer ( OEM ) only. The Manufacturer should have ISO 9001, 14001, OHAS 18001, ENMS 50001 certification, ROHS compliance.
The Hybrid Solution described as above complete in all respect as per specification enclosed, up to the entire satisfaction of engineer In Charge. To ensure safety, reliability and accountability of component co ordination, all the major capacitor bank components such as capacitor units, de tuning reactors, PF controllers, circuit breakers, contactors and the enclosure system called for in this specification should preferably be from a single manufacturer. The OEM shall preferably manufacturer PFC components . The APFC panel manufactured by OEM's only will be accepted & factory acceptance test ( FAT ) will be carried out at OEM's factory only.
i) 2000 Amp.TP ACB - 1 set
Air Circuit case design, Horizontal drawout type of fault breaking capacity 50KA (Ics=lcu=Icw) Electrical Draw Out Motorised operated, fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/ test/isolated position indicators and frame earthing contact, conforming to IS/IEC-60947 as amended up-to-date complete with Independent Electrical & manual spring closing mechanism, Microprocessor release (EMI & EMC certified) for over current, earth fault & short circuit protection, Shunt trip coil 24V D.C / 220V A.C, Breaker Control Switch - 16A, Test terminal block set, circuits as per standard practice, auxiliary contactors with contacts (minimum 4NO+4NC) for positive interlocking of the breakers, necessary electrical interlocking with PLC auto controls etc. as required including following accessories and suitable to receive bus duct connections.
LED indication lamps for RYB, breaker 'ON/ OFF/ TRIP', spring charged, DC control supply healthy etc. with 2Amp control MCBs
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Microprocessor release/s based relay/s (EMI & EMC certified) for over current, earth fault & short circuit protection, Under voltage relay with definite time, along with dual core CT of current transformers of 2000/5A ratio, 15 VA class-5P10 protection - 1 set.
Terminals to receive 2000A Al. Bus duct suitable & complete required as per site.
Bus Bar :
Electrolytic high conductivity Aluminium extensible three phase and neutral busbars rated at 2000 amps , & auxiliary Bus Bars of suitable capacity insulated with heat shrinkable coloured PVC sleeves & clip on shrouds for joints having a maximum current density as per Indian standards suitable to with stand symmetrical fault level of 50 kA at 433 volts i/c DMC/SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc. The neutral busbar is to be of full capacity.
ii) ACB 800A
ACB (Ics=lcu=Icw=1s ) with microprocessor release with O/L, S/C & earth fault protection & followings shall be applicable to each.
a) Air Circuit case design, Horizontal drawout type of fault breaking capacity 50KA, EDO type, fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/ test/isolated position indicators and frame earthing contact, conforming to IS/IEC-60947 as amended up-to-date complete with following accessories for each ACB with solid neutral link.
b) Independent manual spring closing mechanism
c) Microprocessor release(EMI & EMC certified) for with O/C S/C & earth fault protection - I set.
d) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF/TRIP' indicating light with 2A MCB, test terminal block set, circuits as per standard practice, auxiliary contacts for positive interlocking of the breakers as required.
e) Shunt trip coil 24VDC/220V A.C.
f) Terminals to receive suitable Al. Bus duct/cabling arrangement complete required as per site.
i)1 Nos. - 800 Amp. 4P ACB with suitable terminals to receive bus duct connections for each.
CAPACITOR PANEL (HVAC/SERVICE YARD) AS ABOVE
400kVAR CAPACITOR PANEL For Stand by Transformers
The Solution should comprise (400 kVAr including Thyristors with fast acting semiconductor fuse ,Detuned filter reactors 14%) Incomer should be 1000A, 50kA, ACB. · The capacitor bank should have the following step ratings: 6 x 50 + 2 x 25 +2 x 15 +2 x 10kVAr. Capacitor shall be as per MPP low loss as per standards. · Each stage of the capacitor bank should have suitable overload and short circuit protection. · The Solution should have surge arrestors and over temperature protection.
The system should be with compatible with Grid Power OR D.G. Power Supply.
The capacitor banks should be of type tested design and temperature rise test report of the capacitor bank performed at an independent laboratory should be submitted along with the offer. The Manufacturer should have ISO 9001, 14001, OHAS 18001, ENMS 50001 certification, ROHS compliance.
The Solution described as above complete in all respect as per specification enclosed, up to the entire satisfaction of engineer In Charge. To ensure safety, reliability and accountability of component co ordination, all the major capacitor bank components such as capacitor units, de tuning reactors, PF controllers, circuit breakers, contactors and the enclosure system called for in this specification should preferably be from a single manufacturer. The OEM shall preferably manufacturer PFC components . The APFC panel manufactured by OEM's only will be accepted & factory acceptance test ( FAT ) will be carried out at OEM's factory only.
i) 1000 Amp.TP ACB - 1 set
Air Circuit case design, Horizontal drawout type of fault breaking capacity 50KA (Ics=lcu=Icw) Electrical Draw Out Motorised operated, fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/ test/isolated position indicators and frame earthing contact, conforming to IS/IEC-60947 as amended up-to-date complete with Independent Electrical & manual spring closing mechanism, Microprocessor release (EMI & EMC certified) for over current, earth fault & short circuit protection, Shunt trip coil 24V D.C / 220V A.C, Breaker Control Switch - 16A, Test terminal block set, circuits as per standard practice, auxiliary contactors with contacts (minimum 4NO+4NC) for positive interlocking of the breakers, necessary electrical interlocking with PLC auto controls etc. as required including following accessories and suitable to receive bus duct connections.
LED indication lamps for RYB, breaker 'ON/ OFF/ TRIP', spring charged, DC control supply healthy etc. with 2Amp control MCBs
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Microprocessor release/s based relay/s (EMI & EMC certified) for over current, earth fault & short circuit protection, Under voltage relay with definite time , along with dual core CT of current transformers of 1000/5A ratio, 15 VA class-5P10 protection - 1 set.
Terminals to receive 1000A Al. Bus duct suitable & complete required as per site.
Bus Bar :
Electrolytic high conductivity Aluminium extensible three phase and neutral busbars rated at 1000 amps, & auxiliary Bus Bars of suitable capacity insulated with heat shrinkable coloured PVC sleeves & clip on shrouds for joints having a maximum current density as per Indian standards suitable to with stand symmetrical fault level of 50 kA at 433 volts i/c DMC/SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc. The neutral busbar is to be of full capacity.
CAPACITOR PANEL AS ABOVE
FRONT OPERATED PANELS
Design, fabrication, assembly, wiring and supply, erection , testing and commissioning of cubicle type compartmentalised as per Form 4B free standing, dust and vermin proof (Minimum IP 42 ingress protection) front operated switchboards conforming to IS 8623/IEC-60439 suitable for use at 433 volts, 3 phase 4 wire 50 Hertz system suitable for a symmetrical fault level of --kA (specified with the panel) at 433 volts, fabricated from 2 mm outer thick CRCA sheets with hinged, gasketted (metal based neoprene) and lockable doors having structural reinforcement with suitable angle/channel/T/flat sections including 3 mm thick gland plates on top and bottom including lifting hooks and earth bus of required size for prospective fault level at that panel with 2 nos. earthing terminals, coating, paint finish of approved shade over metal surface cleaned and treated with nine tank process complete with interconnections etc. as per specifications, as required and as below. The incoming and outgoing feeders shall be accommodated in a modular arrangement, detachable gland plates, adequate size cable alley, Sign writing, Painting, Earthing, Numbering, Danger plate, including PVC insulated copper FRLS wires of minimum 1.5sq.mm & 2.5sq.mm for CT's etc. complete as required as per specifications and drawing attached.
SERVICE YARD L&P PANEL
Incomers:
i) 2 No. 250Amps. 4P MCCB 50KA , Icu=Ics with micro processor based release having O/L ,S/C earth fault protection & necessary interlocking arrangement between two nos. incomers & one no. bus coupler and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF/TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 250Amps. 4P MCCB 50 ka, Icu=Ics with Thermal Magnetic based release having O/L ,S/C protection.
Bus Bar :
2 sections of TPN aluminium extensible type main bus bars of minimum of 300 Amp 50kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with thermal magnetic based MCCB with front operating handle for O/C, S/C protections of following capacity and rating minimum 50kA (Ics=Icu =1 sec. upto 433 V ) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
i) 5 Nos. - 40 Amp. TPN MCCB with ON indications
ii) 1 Nos. - 63 Amp. TPN MCCB with ON indications
iii) 2 Nos. - 32 Amp. DP MCB's
Service L&P panel as above
DG AUX. PANEL
Incomers:
i) 2 No. 250Amps. 4P MCCB 50ka, Icu=Ics with micro processor based release having O/L ,S/C earth fault protection & necessary interlocking arrangement between two nos. incomers & one no. bus coupler and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF/TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 250Amps. 4P MCCB 50.ka, Icu=Ics with Thermal Magnetic based release having O/L ,S/C protection.
2 sections of TPN aluminium extensible type main bus bars of minimum of 300 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with motor duty MCCB with front operating handle for O/C, S/C protection of following capacity and rating minimum 50kA (Ics=Icu =1 433 V ) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
i) 5 Nos. - 40 Amp , 19 Nos.32 Amp. TPN Motor duty MCCB with ON indications
DG AUX. panel as above
SERVICE YARD VENTILATION PANEL
Incomers:
i) 2 No. 250Amps. 4P MCCB '25ka, Icu=Ics with micro processor based release having O/L ,S/C earth fault protection & necessary interlocking arrangement between two nos. incomers & one no. bus coupler and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF/TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 250Amps. 4P MCCB '25ka, Icu=Ics with Thermal Magnetic based release having O/L ,S/C protection.
Bus Bar :
2 sections of TPN aluminium extensible type main bus bars of minimum of 300 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with motor duty MCCB with front operating handle for O/C, S/C protection of following capacity and rating minimum 25kA (Ics=Icu =1 433 V ) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
i) 10 Nos. - 40 Amp. TPN Motor duty MCCB with ON indications
ii) 6 Nos. - 32 Amp. TPN Motor duty MCCB with ON indications
iii) 2 Nos. - 63 Amp. TPN Motor duty MCCB with ON indications
iv) 2 Nos. - 100 Amp. TPN thermal magnetic based MCCB with O/C,S.C protections with ON indications
Service Yard Ventilation panel as above
STP VENTILATION PANEL
Incomers:
i) 1 No. 100Amps. 4P MCCB 25ka, Icu=Ics with M.P based release having O/L ,S/C earth fault protection equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF/TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus Bar :
TPN aluminium extensible type main bus bars of minimum of 150 Amp 25 kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with motor duty MCCB with front operating handle for O/C, S/C protection of following capacity and rating 25kA (Ics=Icu =1 sec. upto 433 V ) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
i) 6 Nos. - 32 Amp. TPN Motor duty MCCB with ON indications for each
ii) 1 Nos. - 63 Amp. TPN Motor duty MCCB with ON indications for each
iii) 2 Nos. - 32 Amp. double pole, MCB 'C' (10ka)
STP Ventilation panel as above
SERVICE YARD EXT. DEV. PANEL
Incomers:
i) 1 No. 250Amps. 4P MCCB '25ka, Icu=Ics with micro processor based release having O/L ,S/C, earth fault protection equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF/TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus Bar :
TPN aluminium extensible type main bus bars of minimum of 300 Amp, 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with thermal magnetic based adjustable release MCCB with front operating handle for O/C, S/C protection of following capacity and rating,25 KA (Ics=Icu upto 433 V ) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
i) 1 Nos. - 100 Amp. 25 kA TPN, thermal release MCCB (Ics=lcu) with following accessories for each MCCB.
ii) 3 Nos. - 63 Amp. 25kA four pole, thermal release MCCB (Ics=lcu) with following accessories for each MCCB.
iii) 2 Nos. - 40 Amp. four pole, MCB 'C' (10ka)
Service Yard Ext. panel as above
PBB Panel-1
Incomers:
i) 2 No. 630Amps. 4P MCCB 36ka, Icu=Ics with micro processor based release having O/L ,S/C earth fault protection & necessary interlocking arrangement between two nos. incomers & one no. bus coupler and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF/TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 630Amps. 4P MCCB 36ka, Icu=Ics with M.P based release having O/L ,S/C protection.
Bus Bar :
2 sections of TPN aluminium extensible type main bus bars of minimum of 700 Amp 36kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with thermal magnetic based adjustable release MCCB with front operating handle for O/C, S/C protection of following capacity and rating, 36 KA (Ics=Icu upto 433 V ) with Set of Digital flush type calibrated MFM meters suitable rating class - 1.0 accuracy , showing V,A,KW with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 5 VA Class 1.0 metering. , Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
8 Nos. - 125 Amp. TPN, MCCB with 'ON' LED indication lamps
PBB panel-1 as above
PBB Panel-2
Incomers:
i) 2 No. 400Amps. 4P MCCB '25ka, Icu=Ics with micro processor based release having O/L ,S/C & earth fault protection & necessary interlocking arrangement between two nos. incomers & one no. bus coupler and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF/TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 400Amps. 4P MCCB '25ka, Icu=Ics with M.P based release having O/L ,S/C protection.
Bus Bar :
2 sections of TPN aluminium extensible type main bus bars of minimum of 500 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with thermal magnetic based adjustable release MCCB with front operating handle for O/C, S/C protection of following capacity and rating,25 KA (Ics=Icu upto 433 V ) with Set of Digital flush type calibrated MFM meters suitable rating class - 1.0 accuracy , showing V,A,KW with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 5 VA Class 1.0 metering. , Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
6 Nos. - 125 Amp. TPN, MCCB with 'ON' LED indication lamps
PBB panel-2 as above
BASEMENT LIGHTING POWER PANEL (Location- Basement)
Incomers:
i) 2 Nos. 160Amps. 4P MCCB '25ka, Icu=Ics with M.P based release having O/L ,S/C,E/F protection & necessary mechanical interlocking arrangement between two nos. incomers & one no. bus coupler and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON,OFF,TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 160Amps. 4P MCCB '25ka, Icu=Ics with Thermal magnetic based release having O/L ,S/C protection.
Bus Bar :
2 sections of TPN aluminium extensible type main bus bars of minimum of 200 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with thermal magnetic based adjustable release MCCB with front operating handle for O/C, S/C protection of following capacity and rating,25 KA (Ics=Icu upto 433 V ) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
1 Nos. - 40 Amp., 4 Nos.-63Amp., 5 Nos. -32Amp. TPN, MCCB 25kA with 'ON' LED indication lamps backed up with 2Amp back up control MCB with MFM meter & required CT's.
Lighting Power panel as above
AR. LEVEL LIGHTING PANEL-1,2 ( Location Electrical Room AR-1,3)
Incomers:
i) 2 Nos. 100Amps. 4P MCCB '25ka, Icu=Ics with micro processor based release having O/L ,S/C,E/F protection & necessary mechanical interlocking arrangement between two nos. incomers & one no. bus coupler and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON,OFF,TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 100Amps. 4P MCCB '25ka, Icu=Ics with Thermal Magnetic based release having O/L ,S/C protection.
Bus Bar :
2 sections of TPN aluminium extensible type main bus bars of minimum of 150 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with thermal magnetic based adjustable release MCCB with front operating handle for O/C, S/C protection of following capacity and rating,25 KA (Ics=Icu upto 433 V ) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
6 Nos. - 40 Amp. TPN, MCCB 25kA with 'ON' LED indication lamps backed up with 2Amp back up control MCB with MFM meter & required CT's
Lighting panel as above
AR. LEVEL LIGHTING PANEL-3 ( Location Electrical Room AR-5)
Incomers:
i) 2 Nos. 125Amps. 4P MCCB '25ka, Icu=Ics with micro processor based release having O/L ,S/C,E/F protection & necessary mechanical interlocking arrangement between two nos. incomers & one no. bus coupler and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON,OFF,TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 125Amps. 4P MCCB '25ka, Icu=Ics with Thermal magnetic based release having O/L ,S/C protection.
Bus Bar :
2 sections of TPN aluminium extensible type main bus bars of minimum of 150 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with thermal magnetic based adjustable release MCCB with front operating handle for O/C, S/C protection of following capacity and rating,25 KA (Ics=Icu upto 433 V ) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
6 Nos. - 40 Amp. TPN, MCCB 25kA with 'ON' LED indication lamps backed up with 2Amp back up control MCB with MFM meter & required CT's
Lighting panel as above
MZ. LEVEL LIGHTING PANEL-1,3 ( Location Electrical Room MZ-2,7)
Incomers:
i) 2 Nos. 100Amps. 4P MCCB '25ka, Icu=Ics with micro processor based release having O/L ,S/C,E/F protection & necessary mechanical interlocking arrangement between two nos. incomers & one no. bus coupler and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON,OFF,TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 100Amps. 4P MCCB '25ka, Icu=Ics with Thermal Magnetic based release having O/L ,S/C protection.
Bus Bar :
2 sections of TPN aluminium extensible type main bus bars of minimum of 150 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with thermal magnetic based adjustable release MCCB with front operating handle for O/C, S/C protection of following capacity and rating,25 KA (Ics=Icu upto 433 V ) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
6 Nos. - 40 Amp. TPN, MCCB 25kA with 'ON' LED indication lamps backed up with 2Amp back up control MCB with MFM meter & required CT's
Lighting panel as above
MZ. LEVEL LIGHTING PANEL-2 ( Location Electrical Room MZ-6)
Incomers:
i) 2 Nos. 100Amps. 4P MCCB '25ka, Icu=Ics with micro processor based release having O/L ,S/C,E/F protection & necessary mechanical interlocking arrangement between two nos. incomers & one no. bus coupler and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON,OFF,TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 100Amps. 4P MCCB '25ka, Icu=Ics with Thermal Magnetic based release having O/L ,S/C protection.
Bus Bar :
2 sections of TPN aluminium extensible type main bus bars of minimum of 150 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with thermal magnetic based adjustable release MCCB with front operating handle for O/C, S/C protection of following capacity and rating,25KA (Ics=Icu upto 433 V) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
8 Nos. - 40 Amp. TPN, MCCB 25kA with 'ON' LED indication lamps backed up with 2Amp back up control MCB with MFM meter & required CT's
Lighting panel as above
DEPARTURE LEVEL LIGHTING PANEL-1 ( Location Electrical Room DP-1)
Incomers:
i) 2 Nos. 100Amps. 4P MCCB '25ka, Icu=Ics with micro processor based release having O/L ,S/C,E/F protection & necessary mechanical interlocking arrangement between two nos. incomers & one no. bus coupler and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON,OFF,TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 100Amps. 4P MCCB '25ka, Icu=Ics with Thermal Magnetic based release having O/L ,S/C protection.
Bus Bar :
2 sections of TPN aluminium extensible type main bus bars of minimum of 150 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with thermal magnetic based adjustable release MCCB with front operating handle for O/C, S/C protection of following capacity and rating,25 KA (Ics=Icu upto 433 V) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
8 Nos. - 40 Amp. TPN, MCCB 25kA with 'ON' LED indication lamps backed up with 2Amp back up control MCB with MFM meter & required CT's
Lighting panel as above
DEPARTURE LEVEL LIGHTING PANEL-2( Location Electrical Room DP-3)
Incomers:
i) 2 Nos. 100Amps. 4P MCCB '25ka, Icu=Ics with micro processor based release having O/L ,S/C,E/F protection & necessary mechanical interlocking arrangement between two nos. incomers & one no. bus coupler and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON,OFF,TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 100Amps. 4P MCCB '25ka, Icu=Ics with Thermal Magnetic based release having O/L ,S/C protection.
Bus Bar :
2 sections of TPN aluminium extensible type main bus bars of minimum of 150 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with thermal magnetic based adjustable release MCCB with front operating handle for O/C, S/C protection of following capacity and rating,25 KA (Ics=Icu upto 433 V) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
8 Nos. - 40 Amp. TPN, MCCB 25kA with 'ON' LED indication lamps backed up with 2Amp back up control MCB with MFM meter & required CT's
Lighting panel as above
DEPARTURE LEVEL LIGHTING PANEL-3( Location Electrical Room DP-4)
Incomers:
i) 2 Nos. 100Amps. 4P MCCB '25ka, Icu=Ics with micro processor based release having O/L ,S/C,E/F protection & necessary mechanical interlocking arrangement between two nos. incomers & one no. bus coupler and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON,OFF,TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 100Amps. 4P MCCB '25ka, Icu=Ics with Thermal Magnetic based release having O/L ,S/C protection.
Bus Bar :
2 sections of TPN aluminium extensible type main bus bars of minimum of 150 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with thermal magnetic based adjustable release MCCB with front operating handle for O/C, S/C protection of following capacity and rating,25 KA (Ics=Icu upto 433 V) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
6 Nos. 40 Amp. TPN, MCCB 25kA with 'ON' LED indication lamps backed up with 2Amp back up control MCB with MFM meter & required CT's
Lighting panel as above
WALKWAY LEVEL LIGHTING PANEL (Location Electrical Room UDP)
Incomers:
i) 2 Nos. 100Amps. 4P MCCB '25ka, Icu=Ics with micro processor based release having O/L ,S/C,E/F protection & necessary mechanical interlocking arrangement between two nos. incomers & one no. bus coupler and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON,OFF,TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 100Amps. 4P MCCB '25ka, Icu=Ics with Thermal Magnetic based release having O/L ,S/C protection.
Bus Bar :
2 sections of TPN aluminium extensible type main bus bars of minimum of 150 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with thermal magnetic based adjustable release MCCB with front operating handle for O/C, S/C protection of following capacity and rating,25 KA (Ics=Icu upto 433 V) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
6 Nos. - 40 Amp. TPN, MCCB 25kA with 'ON' LED indication lamps backed up with 2Amp back up control MCB with MFM meter & required CT's and 6 Nos. 4P AC contactors of suitable rating with NO/NC contacts for BMS.
Lighting panel as above
ARRIVAL LEVEL POWER PANEL-1 (Location Electrical Room AR-1 )
Incomers:
i) 2 Nos. 160Amps. 4P MCCB '25ka, Icu=Ics with micro processor based release having O/L ,S/C,E/F protection & necessary mechanical interlocking arrangement between two nos. incomers & one no. bus coupler and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON,OFF,TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 160Amps. 4P MCCB '25ka, Icu=Ics with Thermal Magnetic based release having O/L ,S/C protection.
Bus Bar :
2 sections of TPN aluminium extensible type main bus bars of minimum of 200 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with thermal magnetic based adjustable release MCCB with front operating handle for O/C, S/C protection of following capacity and rating,25 KA (Ics=Icu upto 433 V) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
6 Nos. - 63 Amp. TPN, MCCB 25kA with 'ON' LED indication lamps backed up with 2Amp back up control MCB.
Power panel as above
ARRIVAL LEVEL POWER PANEL-2,3 (Location Electrical Room AR-4,5 )
Incomers:
i) 2 Nos. 100Amps. 4P MCCB '25ka, Icu=Ics with micro processor based release having O/L ,S/C,E/F protection & necessary mechanical interlocking arrangement between two nos. incomers & one no. bus coupler and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON,OFF,TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 100Amps. 4P MCCB '25ka, Icu=Ics with Thermal Magnetic based release having O/L ,S/C protection.
Bus Bar :
2 sections of TPN aluminium extensible type main bus bars of minimum of 150 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with thermal magnetic based adjustable release MCCB with front operating handle for O/C, S/C protection of following capacity and rating, 25 KA (Ics=Icu upto 433 V) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
5 Nos. - 63 Amp. TPN, MCCB 25kA with 'ON' LED indication lamps backed up with 2Amp back up control MCB.
Power panel as above
MZ. LEVEL POWER PANEL-1 (Location Electrical Room MZ-3 )
Incomers:
i) 2 Nos. 100Amps. 4P MCCB '25ka, Icu=Ics with micro processor based release having O/L ,S/C,E/F protection & necessary mechanical interlocking arrangement between two nos. incomers & one no. bus coupler and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON,OFF,TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 100Amps. 4P MCCB '25ka, Icu=Ics with Thermal Magnetic based release having O/L ,S/C protection.
Bus Bar :
2 sections of TPN aluminium extensible type main bus bars of minimum of 150 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with thermal magnetic based adjustable release MCCB with front operating handle for O/C, S/C protection of following capacity and rating,25 KA (Ics=Icu upto 433 V) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
5 Nos. - 63 Amp. TPN, MCCB 25kA with 'ON' LED indication lamps backed up with 2Amp back up control MCB.
Power panel as above
MZ. LEVEL POWER PANEL-2,3 (Location Electrical Room MZ-6,7 )
Incomers:
i) 2 Nos. 100Amps. 4P MCCB '25ka, Icu=Ics with micro processor based release having O/L ,S/C,E/F protection & necessary mechanical interlocking arrangement between two nos. incomers & one no. bus coupler and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON,OFF,TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 100Amps. 4P MCCB '25ka, Icu=Ics with Thermal Magnetic based release having O/L ,S/C protection.
Bus Bar :
2 sections of TPN aluminium extensible type main bus bars of minimum of 150 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with thermal magnetic based adjustable release MCCB with front operating handle for O/C, S/C protection of following capacity and rating,25 KA (Ics=Icu upto 433 V) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
5 Nos. - 63 Amp. TPN, MCCB 25kA with 'ON' LED indication lamps backed up with 2Amp back up control MCB.
Power panel as above
DEPARTURE LEVEL POWER PANEL-1,2 (Location Electrical Room DEP.-1,3)
Incomers:
i) 2 Nos. 160Amps. 4P MCCB '25ka, Icu=Ics with micro processor based release having O/L ,S/C,E/F protection & necessary mechanical interlocking arrangement between two nos. incomers & one no. bus coupler and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON,OFF,TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 160Amps. 4P MCCB '25ka, Icu=Ics with Thermal Magnetic based release having O/L ,S/C protection.
Bus Bar :
2 sections of TPN aluminium extensible type main bus bars of minimum of 200 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with thermal magnetic based adjustable release MCCB with front operating handle for O/C, S/C protection of following capacity and rating,25 KA (Ics=Icu upto 433 V=1s) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
6 Nos. - 63 Amp. TPN, MCCB 25kA with 'ON' LED indication lamps backed up with 2Amp back up control MCB.
Power panel as above
DEPARTURE LEVEL POWER PANEL-3,4 (Location Electrical Room DEP.-4,6)
Incomers:
i) 2 Nos. 100Amps. 4P MCCB '25ka, Icu=Ics with micro processor based release having O/L ,S/C,E/F protection & necessary mechanical interlocking arrangement between two nos. incomers & one no. bus coupler and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON,OFF,TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 100Amps. 4P MCCB '25ka, Icu=Ics with Thermal Magnetic based release having O/L ,S/C protection.
Bus Bar :
2 sections of TPN aluminium extensible type main bus bars of minimum of 150 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with thermal magnetic based adjustable release MCCB with front operating handle for O/C, S/C protection of following capacity and rating,25 KA (Ics=Icu upto 433 V=1s) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
6 Nos. - 63 Amp. TPN, MCCB 25kA with 'ON' LED indication lamps backed up with 2Amp back up control MCB.
Power panel as above
BASEMENT UPS PANEL
Incomers:
i) 2 Nos. 100Amps. 4P MCCB '25ka, Icu=Ics with micro processor based release having O/L ,S/C,E/F protection & necessary mechanical interlocking arrangement between two nos. incomers & one no. bus coupler and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON,OFF,TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 100Amps. 4P MCCB '25ka, Icu=Ics with Thermal Magnetic based release having O/L ,S/C protection.
Bus Bar :
2 sections of 4P copper extensible type main bus bars of minimum of 150 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with thermal magnetic based adjustable release MCCB with front operating handle for O/C, S/C protection of following capacity and rating,25 KA (Ics=Icu upto 433 V=1s) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
9 Nos. - 40 Amp. TPN, MCCB 25kA with 'ON' LED indication lamps backed up with 2Amp back up control MCB.
Basement UPS panel as above
ARRIVAL LEVEL UPS PANEL-1 ( Location Electrical Room AR-2)
Incomers:
i) 2 Nos. 100Amps. 4P MCCB '25ka, Icu=Ics with micro processor based release having O/L ,S/C,E/F protection & necessary mechanical interlocking arrangement between two nos. incomers & one no. bus coupler and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON,OFF,TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 100Amps. 4P MCCB '25ka, Icu=Ics with Thermal Magnetic based release having O/L ,S/C protection.
Bus Bar :
2 sections of 4P copper extensible type main bus bars of minimum of 150 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with thermal magnetic based adjustable release MCCB with front operating handle for O/C, S/C protection of following capacity and rating, 25 KA (Ics=Icu upto 433 V=1s) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
13 Nos. - 40 Amp. TPN, MCCB 25kA with 'ON' LED indication lamps backed up with 2Amp back up control MCB.
ARRIVAL LEVEL UPS PANEL UPS panel as above
ARRIVAL LEVEL UPS PANEL-2 ( Location Electrical Room AR-6)
Incomers:
i) 2 Nos. 100Amps. 4P MCCB '25ka, Icu=Ics with micro processor based release having O/L ,S/C,E/F protection & necessary mechanical interlocking arrangement between two nos. incomers & one no. bus coupler and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON,OFF,TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 100Amps. 4P MCCB '25ka, Icu=Ics with Thermal Magnetic based release having O/L ,S/C protection.
Bus Bar :
2 sections of 4P copper extensible type main bus bars of minimum of 150 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with thermal magnetic based adjustable release MCCB with front operating handle for O/C, S/C protection of following capacity and rating,25 KA (Ics=Icu upto 433 V=1s) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
9 Nos. - 40 Amp. TPN, MCCB 25kA with 'ON' LED indication lamps backed up with 2Amp back up control MCB.
ARRIVAL LEVEL UPS PANEL UPS panel as above
MZ. LEVEL UPS PANEL-1 ( Location Electrical Room MZ-3)
Incomers:
i) 2 Nos. 100Amps. 4P MCCB '25ka, Icu=Ics with micro processor based release having O/L ,S/C,E/F protection & necessary mechanical interlocking arrangement between two nos. incomers & one no. bus coupler and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON,OFF,TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 100Amps. 4P MCCB '25ka, Icu=Ics with Thermal Magnetic based release having O/L ,S/C protection.
Bus Bar :
2 sections of 4P copper extensible type main bus bars of minimum of 150 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with thermal magnetic based adjustable release MCCB with front operating handle for O/C, S/C protection of following capacity and rating,25 KA (Ics=Icu upto 433 V=1s) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
8 Nos. - 40 Amp. TPN, MCCB 25kA with 'ON' LED indication lamps backed up with 2Amp back up control MCB.
MZ. LEVEL UPS PANEL UPS panel as above
MZ. LEVEL UPS PANEL-2,3 ( Location Electrical Room MZ-7,MZ-8)
Incomers:
i) 2 Nos. 100Amps. 4P MCCB '25ka, Icu=Ics with micro processor based release having O/L ,S/C,E/F protection & necessary mechanical interlocking arrangement between two nos. incomers & one no. bus coupler and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON,OFF,TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 100Amps. 4P MCCB '25ka, Icu=Ics with Thermal magnetic based release having O/L ,S/C protection.
Bus Bar :
2 sections of 4P copper extensible type main bus bars of minimum of 150 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with thermal magnetic based adjustable release MCCB with front operating handle for O/C, S/C protection of following capacity and rating,25 KA (Ics=Icu upto 433 V=1s) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
6 Nos. - 40 Amp. TPN, MCCB 25kA with 'ON' LED indication lamps backed up with 2Amp back up control MCB.
MZ. LEVEL UPS PANEL UPS panel as above
DEP. LEVEL UPS PANEL-1 ( Location Electrical Room DP-1)
Incomers:
i) 2 Nos. 100Amps. 4P MCCB '25ka, Icu=Ics with micro processor based release having O/L ,S/C,E/F protection & necessary mechanical interlocking arrangement between two nos. incomers & one no. bus coupler and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON,OFF,TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 100Amps. 4P MCCB '25ka, Icu=Ics with Thermal Magnetic based release having O/L ,S/C protection.
Bus Bar :
2 sections of 4P copper extensible type main bus bars of minimum of 150 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with thermal magnetic based adjustable release MCCB with front operating handle for O/C, S/C protection of following capacity and rating,25 KA (Ics=Icu upto 433 V=1s) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
10 Nos. - 40 Amp. TPN, MCCB 25kA with 'ON' LED indication lamps backed up with 2Amp back up control MCB.
DEP. LEVEL UPS PANEL UPS panel as above
DEP. LEVEL UPS PANEL-2 ( Location Electrical Room DP-3)
Incomers:
i) 2 Nos. 100Amps. 4P MCCB '25ka, Icu=Ics with micro processor based release having O/L ,S/C,E/F protection & necessary mechanical interlocking arrangement between two nos. incomers & one no. bus coupler and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON,OFF,TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 100Amps. 4P MCCB '25ka, Icu=Ics with Thermal Magnetic based release having O/L ,S/C protection.
Bus Bar :
2 sections of 4P copper extensible type main bus bars of minimum of 150 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with thermal magnetic based adjustable release MCCB with front operating handle for O/C, S/C protection of following capacity and rating,25 KA (Ics=Icu upto 433 V=1s) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
11 Nos. - 40 Amp. TPN, MCCB 25kA with 'ON' LED indication lamps backed up with 2Amp back up control MCB.
DEP. LEVEL UPS PANEL UPS panel as above
DEP. LEVEL UPS PANEL-3 ( Location Electrical Room DP-4)
Incomers:
i) 2 Nos. 100Amps. 4P MCCB '25ka, Icu=Ics with micro processor based release having O/L ,S/C,E/F protection & necessary mechanical interlocking arrangement between two nos. incomers & one no. bus coupler and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON,OFF,TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 100Amps. 4P MCCB '25ka, Icu=Ics with Thermal Magnetic based release having O/L ,S/C protection.
Bus Bar :
2 sections of 4P copper extensible type main bus bars of minimum of 150 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with thermal magnetic based adjustable release MCCB with front operating handle for O/C, S/C protection of following capacity and rating,25 KA (Ics=Icu upto 433 V=1s) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
6 Nos. - 40 Amp. TPN, MCCB 25kA with 'ON' LED indication lamps backed up with 2Amp back up control MCB.
DEP. LEVEL UPS PANEL UPS panel as above
DEP. LEVEL UPS PANEL-4 ( Location Electrical Room -Services room)
Incomers:
i) 2 Nos. 100Amps. 4P MCCB '25ka, Icu=Ics with micro processor based release having O/L ,S/C,E/F protection & necessary mechanical interlocking arrangement between two nos. incomers & one no. bus coupler and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON,OFF,TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 100Amps. 4P MCCB '25ka, Icu=Ics with Thermal Magnetic based release having O/L ,S/C protection.
Bus Bar :
2 sections of 4P copper extensible type main bus bars of minimum of 150 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with thermal magnetic based adjustable release MCCB with front operating handle for O/C, S/C protection of following capacity and rating,25 KA (Ics=Icu upto 433 V=1s) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
7 Nos. - 40 Amp. TPN, MCCB 25kA with 'ON' LED indication lamps backed up with 2Amp back up control MCB.
DEP. LEVEL UPS PANEL UPS panel as above
BASEMENT AHU PANEL
Incomers:
i) 2 No. 250Amps. 4P MCCB '25ka, Icu=Ics with micro processor based release having O/L ,S/C earth fault protection & necessary interlocking arrangement between two nos. incomers & one no. bus coupler and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF/TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 250Amps. 4P MCCB '25ka, Icu=Ics with Thermal Magnetic based release having O/L ,S/C protection.
Bus Bar :
2 sections of TPN aluminium extensible type main bus bars of minimum of 300 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with motor duty MCCB with front operating handle for O/C, S/C protection of following capacity and rating minimum 25kA (Ics=Icu =1 433 V ) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
i) 2 Nos. - 32 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB with MFM meter & required CT's.
ii) 8 Nos. - 40 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB with MFM meter & required CT's.
AHU panel as above
ARRIVAL AHU PANEL-1 (Electrical Room AR-2)
Incomers:
i) 2 No. 160Amps. 4P MCCB '25ka, Icu=Ics with micro processor based release having O/L ,S/C earth fault protection & necessary interlocking arrangement between two nos. incomers & one no. bus coupler and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF/TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 160Amps. 4P MCCB '25ka, Icu=Ics with Thermal Magnetic based release having O/L ,S/C protection.
Bus Bar :
2 sections of TPN aluminium extensible type main bus bars of minimum of 200 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with motor duty MCCB with front operating handle for O/C, S/C protection of following capacity and rating minimum 25kA (Ics=Icu =1 433 V ) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
i) 3 Nos. - 32 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB with MFM meter & required CT's.
ii) 2 Nos. - 100 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB with MFM meter & required CT's.
ii) 2 Nos. - 63 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB with MFM meter & required CT's.
iii) 1 Nos. - 32 Amp. double pole, MCB 'C' (10ka)
AHU panel as above
ARRIVAL AHU PANEL-2 (Electrical Room AR-5)
Incomers:
i) 2 No. 100Amps. 4P MCCB '25ka, Icu=Ics with micro processor based release having O/L ,S/C earth fault protection & necessary interlocking arrangement between two nos. incomers & one no. bus coupler and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF/TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 100Amps. 4P MCCB '25ka, Icu=Ics with Thermal Magnetic based release having O/L ,S/C protection.
Bus Bar :
2 sections of TPN aluminium extensible type main bus bars of minimum of 150 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with motor duty MCCB with front operating handle for O/C, S/C protection of following capacity and rating minimum 25kA (Ics=Icu =1 433 V ) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
i) 2 Nos. - 32 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB with MFM meter & required CT's.
ii) 2 Nos. - 40 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB with MFM meter & required CT's.
ii) 1 Nos. - 63 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB with MFM meter & required CT's.
iv) 5 Nos. - 32/63 Amp. double pole, MCB 'C' (10ka)
AHU panel as above
MZ. AHU PANEL-1 (Electrical Room MZ-3)
Incomers:
i) 2 No. 250Amps. 4P MCCB '25ka, Icu=Ics with M.P based release having O/L ,S/C earth fault protection & necessary interlocking arrangement between two nos. incomers & one no. bus coupler and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF/TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 250Amps. 4P MCCB '25ka, Icu=Ics with Thermal Magnetic based release having O/L ,S/C protection.
Bus Bar :
2 sections of TPN aluminium extensible type main bus bars of minimum of 300 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with motor duty MCCB with front operating handle for O/C, S/C protection of following capacity and rating minimum 25kA (Ics=Icu =1 433 V ) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
i) 5 Nos. - 32 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB with MFM meter & required CT's.
ii) 11 Nos. - 40 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB with MFM meter & required CT's.
AHU panel as above
MZ. AHU PANEL-2 (AHU Room Near Departure corridor)
Incomers:
i) 2 No. 250Amps. 4P MCCB '25ka, Icu=Ics with M.P based release having O/L ,S/C earth fault protection & necessary interlocking arrangement between two nos. incomers & one no. bus coupler and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF/TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 250Amps. 4P MCCB '25ka, Icu=Ics with Thermal Magnetic based release having O/L ,S/C protection.
Bus Bar :
2 sections of TPN aluminium extensible type main bus bars of minimum of 300 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with motor duty MCCB with front operating handle for O/C, S/C protection of following capacity and rating minimum 25kA (Ics=Icu =1 433 V ) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
i) 4 Nos. - 32 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB with MFM meter & required CT's.
ii) 4 Nos. - 40 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB with MFM meter & required CT's.
iii) 3 Nos. - 63 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB with MFM meter & required CT's.
iv) 1 Nos. - 100 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB with MFM meter & required CT's.
v) 4 Nos. - 32 Amp. double pole, MCB 'C' (10ka)
AHU panel as above
DEP. AHU PANEL-1 (Electrical room DP-1)
Incomers:
i) 2 No. 160Amps. 4P MCCB '25ka, Icu=Ics with micro processor based release having O/L ,S/C earth fault protection & necessary interlocking arrangement between two nos. incomers & one no. bus coupler and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF/TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 160Amps. 4P MCCB '25ka, Icu=Ics with Thermal Magnetic based release having O/L ,S/C protection.
Bus Bar :
2 sections of TPN aluminium extensible type main bus bars of minimum of 200 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with motor duty MCCB with front operating handle for O/C, S/C protection of following capacity and rating minimum 25kA (Ics=Icu =1 433 V ) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
i) 3 Nos. - 32 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB with MFM meter & required CT's.
i) 4 Nos. - 40 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB with MFM meter & required CT's.
ii) 1 Nos. - 63 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB with MFM meter & required CT's.
iii) 4 Nos. - 32 Amp. double pole, MCB 'C' (10ka)
AHU panel as above
DEP. AHU PANEL-2 (AHU Room)
Incomers:
i) 2 No. 160Amps. 4P MCCB '25ka, Icu=Ics with micro processor based release having O/L ,S/C earth fault protection & necessary interlocking arrangement between two nos. incomers & one no. bus coupler and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF/TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 160Amps. 4P MCCB '25ka, Icu=Ics with Thermal Magnetic based release having O/L ,S/C protection.
Bus Bar :
2 sections of TPN aluminium extensible type main bus bars of minimum of 200 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with motor duty MCCB with front operating handle for O/C, S/C protection of following capacity and rating minimum 25kA (Ics=Icu =1 433 V ) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
i) 6 Nos. - 40 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB with MFM meter & required CT's.
ii) 3 Nos. - 63 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB with MFM meter & required CT's.
iii) 3 Nos. - 32 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB with MFM meter & required CT's.
AHU panel as above
DEP. AHU PANEL-3 (Service Room)
Incomers:
i) 2 No. 100Amps. 4P MCCB '25ka, Icu=Ics with micro processor based release having O/L ,S/C earth fault protection & necessary interlocking arrangement between two nos. incomers & one no. bus coupler and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF/TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 100Amps. 4P MCCB '25ka, Icu=Ics with Thermal Magnetic based release having O/L ,S/C protection.
Bus Bar :
2 sections of TPN aluminium extensible type main bus bars of minimum of 150 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with motor duty MCCB with front operating handle for O/C, S/C protection of following capacity and rating minimum 25kA (Ics=Icu =1 433 V ) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
i) 7 Nos. - 40 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB with MFM meter & required CT's.
ii) 3 Nos. - 32 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB with MFM meter & required CT's.
AHU panel as above
BASEMENT VENT. PANEL-1 (ZONE-1,2)
Incomers:
i) 2 No. 250Amps. 4P MCCB '25ka, Icu=Ics with M.P based release having O/L ,S/C earth fault protection & necessary interlocking arrangement between two nos. incomers & one no. bus coupler and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF/TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 250Amps. 4P MCCB '25ka, Icu=Ics with Thermal Magnetic based release having O/L ,S/C protection.
Bus Bar :
2 sections of TPN aluminium extensible type main bus bars of minimum of 300 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with motor duty MCCB with front operating handle for O/C, S/C protection of following capacity and rating minimum 25kA (Ics=Icu =1 433 V ) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
i) 12 Nos. - 63 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB.
Panel as above
BASEMENT VENT. PANEL-2 (ZONE-4,5)
Incomers:
i) 2 No. 250Amps. 4P MCCB '25ka, Icu=Ics with M.P based release having O/L ,S/C earth fault protection & necessary interlocking arrangement between two nos. incomers & one no. bus coupler and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF/TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 250Amps. 4P MCCB '25ka, Icu=Ics with Thermal Magnetic based release having O/L ,S/C protection.
Bus Bar :
2 sections of TPN aluminium extensible type main bus bars of minimum of 300 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with motor duty MCCB with front operating handle for O/C, S/C protection of following capacity and rating minimum 25kA (Ics=Icu =1 433 V ) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
i) 10 Nos. - 63 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB.
ii) 4 Nos. - 32 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB.
Panel as above
BASEMENT VENT. PANEL-3 (ZONE-3,6)
Incomers:
i) 2 No. 250Amps. 4P MCCB '25ka, Icu=Ics with M.P based release having O/L ,S/C earth fault protection & necessary interlocking arrangement between two nos. incomers & one no. bus coupler and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF/TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 250Amps. 4P MCCB '25ka, Icu=Ics with Thermal Magnetic based release having O/L ,S/C protection.
Bus Bar :
2 sections of TPN aluminium extensible type main bus bars of minimum of 300 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with motor duty MCCB with front operating handle for O/C, S/C protection of following capacity and rating minimum 25kA (Ics=Icu =1 433 V ) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
i) 10 Nos. - 63 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB with MFM meter & required CT's.
ii) 6 Nos. - 32 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB with MFM meter & required CT's.
Panel as above
VAC PANEL - (ESS Room)
Incomers:
i) 2 No. 125Amps. 4P MCCB '25ka, Icu=Ics with thermal magnetic based release having O/L ,S/C earth fault protection & necessary interlocking arrangement between two nos. incomers & one no. bus coupler and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF/TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 125Amps. 4P MCCB '25ka, Icu=Ics with thermal magnetic based release having O/L ,S/C protection.
Bus Bar :
2 sections of TPN aluminium extensible type main bus bars of minimum of 150 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with motor duty MCCB with front operating handle for O/C, S/C protection of following capacity and rating minimum 25kA (Ics=Icu =1 433 V ) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
i) 2 Nos. - 40 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB with MFM meter & required CT's.
ii) 6 Nos. - 32 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB with MFM meter & required CT's.
Panel as above
SMOKE EXT. PANEL-1 ( Elect. Room-MZ1)
Incomers:
i) 1 No. 250Amps. 4P MCCB '25ka, Icu=Ics with M.P based release having O/L ,S/C earth fault protection and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF/TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus Bar :
TPN aluminium extensible type main bus bars of minimum of 315 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with motor duty MCCB with front operating handle for O/C, S/C protection of following capacity and rating minimum 25kA (Ics=Icu =1 433 V ) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
i) 7 Nos. - 63 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB.
ii) 2 Nos. - 40 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB .
iii) 6 Nos. - 32 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB .
Panel as above
SMOKE EXT. PANEL-2 ( Elect. Room-MZ4)
Incomers:
i) 1 No. 250Amps. 4P MCCB '25ka, Icu=Ics with M.P based release having O/L ,S/C earth fault protection and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF/TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus Bar :
TPN aluminium extensible type main bus bars of minimum of 300 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with motor duty MCCB with front operating handle for O/C, S/C protection of following capacity and rating minimum 25kA (Ics=Icu =1 433 V ) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
i) 7 Nos. - 63 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB
ii) 4 Nos. - 32 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB .
Panel as above
SMOKE EXT. PANEL-3 ( Elect. Room-MZ7)
Incomers:
i) 1 No. 250Amps. 4P MCCB '25ka, Icu=Ics with M.P based release having O/L ,S/C earth fault protection and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF/TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus Bar :
TPN aluminium extensible type main bus bars of minimum of 300 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with motor duty MCCB with front operating handle for O/C, S/C protection of following capacity and rating minimum 25kA (Ics=Icu =1 433 V ) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
i) 8 Nos. - 63 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB.
Panel as above
SMOKE EXT. PANEL-4 ( Elect. Room-MZ8)
Incomers:
i) 1 No. 250Amps. 4P MCCB '25ka, Icu=Ics with T.M based release having O/L ,S/C earth fault protection and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF/TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus Bar :
TPN aluminium extensible type main bus bars of minimum of 300 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with motor duty MCCB with front operating handle for O/C, S/C protection of following capacity and rating minimum 25kA (Ics=Icu =1 433 V ) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
i) 7 Nos. - 63 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB.
ii) 1 Nos. - 40 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB.
iii) 2 Nos. - 32 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB.
Panel as above
DEP. SMOKE EXT. PANEL-1 ( Elect. Room-UDP1)
Incomers:
i) 1 No. 250Amps. 4P MCCB '25ka, Icu=Ics with M.P based release having O/L ,S/C earth fault protection and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF/TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus Bar :
TPN aluminium extensible type main bus bars of minimum of 300 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with motor duty MCCB with front operating handle for O/C, S/C protection of following capacity and rating minimum 25kA (Ics=Icu =1 433 V ) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
i) 9 Nos. - 63 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB.
iii) 3 Nos. - 32 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB.
Panel as above
DEP. SMOKE EXT. PANEL-2 ( Elect. Room-UDP2)
Incomers:
i) 1 No. 250Amps. 4P MCCB '25ka, Icu=Ics with M.P based release having O/L ,S/C earth fault protection and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF/TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus Bar :
TPN aluminium extensible type main bus bars of minimum of 300 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with motor duty MCCB with front operating handle for O/C, S/C protection of following capacity and rating minimum 25kA (Ics=Icu =1 433 V ) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
i) 9 Nos. - 63 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB.
ii) 4 Nos. - 32 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB.
Panel as above
PRESS. PANEL-1 ( Elect. Room-UDP1)
Incomers:
i) 1 No. 100Amps. 4P MCCB '25ka, Icu=Ics with M.P based release having O/L ,S/C earth fault protection and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF/TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus Bar :
TPN aluminium extensible type main bus bars of minimum of 100 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with motor duty MCCB with front operating handle for O/C, S/C protection of following capacity and rating minimum 25kA (Ics=Icu =1 433 V ) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
i) 1 Nos. - 63 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB.
ii) 5 Nos. - 40 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB.
iii) 5 Nos. - 32 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB.
Panel as above
PRESS. PANEL-2 ( Elect. Room-UDP2)
Incomers:
i) 1 No. 250Amps. 4P MCCB '25ka, Icu=Ics with M.P based release having O/L ,S/C earth fault protection and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF/TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus Bar :
TPN aluminium extensible type main bus bars of minimum of 300 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with motor duty MCCB with front operating handle for O/C, S/C protection of following capacity and rating minimum 25kA (Ics=Icu =1 433 V ) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
i) 1 No. - 63 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB.
ii) 6 Nos. - 40 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB.
iii) 8 Nos. - 32 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB.
Panel as above
TRUSS SMOKE EXT. PANEL-1 (ELECT. ROOM UDP-1)
Incomers:
i) 1 No. 630Amps. 4P MCCB '25ka, Icu=Ics with M.P based release having O/L ,S/C earth fault protection and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF/TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus Bar :
TPN aluminium extensible type main bus bars of minimum of 800 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with motor duty MCCB with front operating handle for O/C, S/C protection of following capacity and rating minimum 25kA (Ics=Icu =1 433 V ) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
i) 16 Nos. - 63 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB.
ii) 2 Nos. - 32 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB.
Panel as above
TRUSS SMOKE EXT. PANEL-2 (ELECT. ROOM UDP-2)
Incomers:
i) 1 No. 630Amps. 4P MCCB '25ka, Icu=Ics with M.P based release having O/L ,S/C earth fault protection and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF/TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus Bar :
TPN aluminium extensible type main bus bars of minimum of 800 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with motor duty MCCB with front operating handle for O/C, S/C protection of following capacity and rating minimum 25kA (Ics=Icu =1 433 V ) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
i) 17 Nos. - 63 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB.
Panel as above
TRUSS SMOKE EXT. PANEL-2 (ELECT. ROOM UDP-3)
Incomers:
i) 1 No. 630Amps. 4P MCCB '25ka, Icu=Ics with M.P based release having O/L ,S/C earth fault protection and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF/TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus Bar :
TPN aluminium extensible type main bus bars of minimum of 800 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with motor duty MCCB with front operating handle for O/C, S/C protection of following capacity and rating minimum 25kA (Ics=Icu =1 433 V ) with front operating handle, Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
i) 19 Nos. - 63 Amp. TPN Motor duty MCCB with 'ON' LED indication lamps backed up with 2Amp back up control MCB.
Panel as above
Meter Board Retail -Arrival-1 (Ele. Rm. AR-2)
Incomers:
i) 1 No. 200Amps. 4P MCCB '25ka, Icu=Ics with micro processor release having O/L ,S/C, earth fault protection equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON,OFF,TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus Bar :
TPN aluminium extensible type main bus bars of minimum of 250 Amp 25kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoings shall have space provision for suitable rating dual source KWH meter, associated earthing, CT's, for required no. outgoing, each in sealable compartment . All outgoing shall be provided with required control cable, inter-connection etc. with suitable size of wires complete as required.
10 Nos. 63A TPN MCB (10 KA) with three phase dual source prepaid metre in Sealable compartment with each MCB in lockable compartment .
10 Nos. one line display in the field at end point for display of balance units/recharge amount.
Meter Board panel as above
Meter Board Retail -Arrival-2 (Ele. Rm. AR-7)
Incomers:
i) 1 No. 200Amps. 4P MCCB '25ka, Icu=Ics with micro processor release having O/L ,S/C, earth fault protection equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON,OFF,TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus Bar :
TPN aluminium extensible type main bus bars of minimum of 250 Amp 25ka capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoings shall have space provision for suitable rating dual source KWH meter, associated earthing, CT's, for required no. outgoing, each in sealable compartment . All outgoing shall be provided with required control cable, inter-connection etc. with suitable size of wires complete as required. as required.
7 Nos. 63A TPN MCB (10 KA) with three phase dual source prepaid metre in Sealable compartment with each MCB in lockable compartment .
7 Nos. one line display in the field at end point for display of balance units/recharge amount.
Meter Board panel as above
Meter Board Retail -Dep-1 (Ele. Rm. DP-2)
Incomers:
i) 1 No. 200Amps. 4P MCCB '25ka, Icu=Ics with micro processor release having O/L ,S/C, earth fault protection equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON,OFF,TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus Bar :
TPN aluminium extensible type main bus bars of minimum of 250 Amp 25ka capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoings shall have space provision for suitable rating dual source KWH meter, associated earthing, CT's, for required no. outgoing, each in sealable compartment . All outgoing shall be provided with required control cable, inter-connection etc. with suitable size of wires complete as required. as required.
7 Nos. 63A TPN MCB (10 KA) with three phase dual source prepaid metre in Sealable compartment with each MCB in lockable compartment .
7 Nos. one line display in the field at end point for display of balance units/recharge amount.
Meter Board panel as above
Meter Board Retail -Dep-2 (Ele. Rm. DP-4)
Incomers:
i) 1 No. 400Amps. 4P MCCB '25ka, Icu=Ics with micro processor release having O/L ,S/C, earth fault protection equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON,OFF,TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus Bar :
TPN aluminium extensible type main bus bars of minimum of 500 Amp 25ka capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoings shall have space provision for suitable rating dual source KWH meter, associated earthing, CT's, for required no. outgoing, each in sealable compartment . All outgoing shall be provided with required control cable, inter-connection etc. with suitable size of wires complete as required. as required.
12 Nos. 63A TPN MCB (10 KA) with three phase dual source prepaid metre in Sealable compartment with each MCB in lockable compartment .
5 Nos. 100A TPN MCCB (25 KA) with three phase dual source prepaid CT operated metre in Sealable compartment with each MCB in lockable compartment .
17 Nos. one line display in the field at end point for display of balance units/recharge amount.
Meter Board panel as above
Meter Board Retail -Dep-3 (Ele. Rm. DP-6)
Incomers:
i) 1 No. 400Amps. 4P MCCB '25ka, Icu=Ics with micro processor release having O/L ,S/C, earth fault protection equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON,OFF,TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus Bar :
TPN aluminium extensible type main bus bars of minimum of 500 Amp 25ka capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoings shall have space provision for suitable rating dual source KWH meter, associated earthing, CT's, for required no. outgoing, each in sealable compartment . All outgoing shall be provided with required control cable, inter-connection etc. with suitable size of wires complete as required. as required.
9 Nos. 63A TPN MCB (10 KA) with three phase dual source prepaid metre in Sealable compartment with each MCB in lockable compartment .
5 Nos. 100A TPN MCCB (25 KA) with three phase dual source prepaid CT operated metre in Sealable compartment with each MCB in lockable compartment .
14 Nos. one line display in the field at end point for display of balance units/recharge amount.
Meter Board panel as above
Lift & Esc. Panel-1 (Electrical Room-MZ3)
Incomers:
i) 2 No. 400Amps. 4P MCCB '25ka, Icu=Ics with M.P based release having O/L ,S/C earth fault protection & necessary interlocking arrangement between two nos. incomers & one no. bus coupler and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON,OFF,TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 400Amps. 4P MCCB '25ka, Icu=Ics with Thermal Magnetic based release having O/L ,S/C protection.
Bus Bar :
TPN aluminium extensible type main bus bars of minimum of 500 Amp 25ka capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with thermal magnetic based adjustable release MCCB with front operating handle for O/C, S/C & earth fault protection of following capacity and rating, 25 KA (Ics=Icu upto 433 V=1s ) with Set of Digital flush type calibrated MFM meters suitable rating class - 1.0 accuracy , showing V,A, KW with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 5 VA Class 1.0 metering. , Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
13 Nos. - 63 Amp. TPN, MCCB 25kA with 'ON' LED indication lamps backed up with 2Amp back up control MCB.
Lift & Esc. Panel as above
Lift & Esc. Panel-2,3 (Electrical Room-MZ6,7)
Incomers:
i) 2 No. 400Amps. 4P MCCB '25ka, Icu=Ics with M.P based release having O/L ,S/C earth fault protection & necessary interlocking arrangement between two nos. incomers & one no. bus coupler and equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON,OFF,TRIP' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Bus couplers:
i) 1 No. 400Amps. 4P MCCB '25ka, Icu=Ics with Thermal Magnetic based release having O/L ,S/C protection.
Bus Bar :
TPN aluminium extensible type main bus bars of minimum of 500 Amp capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with thermal magnetic based adjustable release MCCB with front operating handle for O/C, S/C & earth fault protection of following capacity and rating, 25 KA (Ics=Icu upto 433 V=1s ) with Set of Digital flush type calibrated MFM meters suitable rating class - 1.0 accuracy , showing V,A, KW with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 5 VA Class 1.0 metering. , Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
13 Nos. - 63 Amp. TPN, MCCB &1 No. 100 Amp. TPN MCCB, 25kA with 'ON' LED indication lamps backed up with 2Amp back up control MCB
Lift & Esc. Panel as above
ELV UPS Input Panel
Incomers:
i) 2 No. 250Amps. 4P MCCB '25ka, Icu=Ics with microprocessor based release having O/L ,S/C, earth fault protection equipped with the following:
a) 3 Nos. Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF' indicating light with 2A MCB
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
Electrical Interlocking should be provided to ensure healthy supply available at a time.
Bus Bar :
TPN aluminium extensible type main bus bars of minimum of 300 Amp capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoings:
All outgoing with thermal magnetic based adjustable release MCCB with front operating handle for O/C, S/C protection of following capacity and rating, 25 KA (Ics=Icu upto 433 V ) with Set of Digital flush type calibrated KWH meters suitable rating class - 1.0 accuracy , showing KW with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 5 VA Class 1.0 metering. , Spreader links and phase barrier, solid neutral link complete with wiring , connections etc.
4 Nos. - 100 Amp. TPN, MCCB 25kA with 'ON' LED indication lamps backed up with 2Amp back up control MCB
ELV UPS Input Panel as above
Utility Tunnel Light & Power Panel
INCOMER
i) 2 No. 100Amps. 4P MCCB '25ka, Icu=Ics with thermal based release with operating handle, necessary interlocking ,spreader links, ON indicating lamp with 2A backup MCB having O/L ,S/C, earth fault protection equipped with the following:
Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port with 3 Nos. cast resin current transformers of dual core CT's of suitable Amp. ratio, 15 VA metering. ,protection MCBs as required accessories to complete the system.
BUSBARS
150 Amp TPN busbars of high conductivity electrolytic quality aluminium alloy.
INSTRUMENTS
OUTGOING
5 Nos. 63 Amp 4P MCB ( 10 kA)
5 Nos. 40 Amp TPN MCB (10 kA).
Tunnel Panel as above
External Lighting Feeder pillars Supply, assembly, erection, connecting, testing & commissioning of LT weather proof dust and vermin proof, outdoor feeder pillar/ panel board (as per site requirement) double door type, fabricated out of board/panel shall be made out of modular Polycarbonate thermoplastic enclosure for environment friendly, recyclable, UV resistant, halogen & silicon free, anti acid & anti corrosive. The gasket material shall be Polyurethane; while the gasket shall be internally embedded. Panel shall be openable with locking arrangement/ front operated if panel board type. Panel shall be IP-65 or higher rated and enclosure shall be type tested as per IEC -61439 etc. The feeder pillars shall be complete with 3 phase and neutral bus bars of capacities as described below and moulded case circuit breakers (MCCBs) with adjustable overload relay, copper FRLS control wiring with 1.5 sq.mm, duly painted complete with earth bus, aluminium bus bar, numbering & sign writing, interconnection etc. & CPRI test reports for short circuit, dielectric strength mechanical protection IK-08 and temperature rise.
Incomer
i) 1 No. 100Amps. 4P MCCB '25ka, Icu=Ics with thermal based release with operating handle, spreader links, ON indicating lamp with 2A backup MCB having O/L ,S/C, earth fault protection equipped with the following:
BUSBARS
150 Amp 4P busbars of high conductivity electrolytic quality aluminium alloy.
OUTGOING
Note- All MCCB's shall be with adjustable O/L protection.
8 sets of 40 Amps,4P , MCB with 40 Amps, 4P Contractor.
1 No. 63 Amp, 4P MCB
3 Nos. 63 Amp DP RCCB's of 300 mA leakage current.
3 Nos. 63 Amps DP contractor.
18 Nos. 6 to 20 Amps SP MCB.
External Lighting Feeder pillars-3,4 described as above.
HSD Panel
Supply, installation, testing and commissioning of dust, damp and water proof cubicle free floor, outdoor type (IP 65) double door, factory built sheet steel HSD Pump Control Panel, suitable for auto/manual operation of two nos. of Fuel Pumps working on 415 ±10% volts, 50 Hz AC, 3 phase 4 wire supply system fabricated out of CRCA sheet steel of 2mm thick for frame work and 1.6mm thick for doors/ covers, 3mm thick for gland plates i/c cleaning & finishing complete with 9 tank process for powder coating in approved shade, having TPN Aluminium bus bars of high conductivity, DMC/SMC bus bar supports, entire panel shall have a common tinned copper earth bar of suitable size, neutral links, including copper FRLS control wiring, cable alleys, cable gland plates in two half, danger notice plates, etc. necessary metering, protections & indications, audio and visual alarm for low / high HSD oil level indication, relays, protections, and mounted with the following switch gears, including all civil works like excavation, PCC, brick work pedestal, plastering, refilling etc. complete as required. (MCC For HSD System)
Incoming:
1 No. 63Amps. 4P MCCB '35ka, with thermal magnetic release having O/L & S/C protection equipped with the following
1 Set of 96 Sqmm Digital flush type (0-100A), class 1.0 accuracy ammeter and 3 Nos. cast resin current transformers of 60/ 5 Amp ratio, 10 VA Class 1.0 metering.
R,Y,B . Phase indication LED lamps with 2Amp back up MCB, breaker 'ON/OFF' indicating light with 2A MCB
Bus Bars:
TPN aluminium extensible type main bus bars of minimum of 100 Amp capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete.
Outgoing
ii. 1 No. 32 A TP MPCB with overload and short-circuit protection having rotary operating mechanism, as spare.
i. Potential free contacts to be provided to remote starting facilities of pumps through BMS
HSD Panel as above
ELECTRICAL SYSTEM - Fire Fighting
NOTE:- This panel will be of same design and specifications as other MCC panels .
Fire Pump Control Panel
Incomer
Two (2) Nos. 400 A, 25 KA, Four pole MCCB with M.P based relay for short circuit, over current protections .Each incomer shall be provided with the following.
One (1) No. Multi Function Meter with one set (3 Nos.) of CTs of ratio 400/5A Class 1.0, 15VA.
One set ( 3 nos.) Phase indication lamps with control MCB.
One set ( 3 nos.) ON/OFF/TRIP indication lamp
Busbar :
500A , 25kA TP + N Al. Busbar insulated with heat shrinkable sleeves and shall be colour coded.
Bus Coupler :
One (1) No. 400A ,25 KA ,Four pole , M.P based MCCB with ON/OFF indication lamp and TNC control switch,
Outgoings :
For Main fire and sprinklers pumps -2 Nos.
250 Amps. TP+N MCCB ( Motor Duty) 25 KA with rotary handle on door.
Set of ON / OFF indication Lamps protected by MCB.
Suitable HP fully automatic Soft starter suitable for 75 KW with over load protection & current sensing type single phase preventor complete with all accessories and internal wiring for automatic operation.
Set of ON & OFF Push Buttons
For Jockey pumps of fire & sprinkler -2 Nos.
40 Amps. TP+N MCCB, 25 KA (motor duty) with rotary handle on door.
Set of LED ON / OFF indication Lamps protected by MCB.
Suitable HP fully automatic DOL starter suitable for 7.5 KW with over load protection & current sensing type single phase preventor complete with all accessories internal wiring for automatic operation.
Set of ON & OFF Push Buttons.
Diesel Engine Control - For -2 No.
LED Indication lamp for High / Low Lube oil pressure , High Water Temp and Engine ON indication.
All standard relays and accessories for automatic operation of diesel engine.
For Jockey pumps of water curtain -1 Nos.
32 Amps. TP+N MCCB, 25 KA (motor duty) with rotary handle on door.
Set of LED ON / OFF indication Lamps protected by MCB.
Suitable HP fully automatic DOL starter suitable for Pump motor 5 KW with over load protection & current sensing type single phase preventor complete with all accessories internal wiring for automatic operation.
Set of ON & OFF Push Buttons.
For Water Curtain pump -1 No.
160 Amps. TP with neutral link MCCB ( Motor Duty) 25 KA with rotary handle on door.
Set of ON / OFF indication Lamps protected by MCB.
Suitable HP fully automatic soft starter suitable for pump motor 37.5 KW with over load protection & current sensing type single phase preventor complete with all accessories and internal wiring for automatic operation.
Set of ON & OFF Push Buttons
ELECTRICAL SYSTEM - Fire Fighting panel as above
PUMPS AND EQUIPMENTS For WTP Pump Room
INCOMER
Each Incomer shall consist of :
200 Amps, Three pole, 25 KA MCCB with rotary handle on door.
Set of (R,Y,B) LED phase and ON & OFF indication Lamps.
BUSBAR
1 Set 415Volt, 200 Amps 25 kA Three Phase and neutral busbars of aluminium complete with Heat shrinkable colour coded sherve.
OUTGOING
Domestic Water Supply hydropneumatic pumps set 3 Nos. (2w+1s) pumps
100Amps.25kA TP with neutral link MCCB ( Motor Duty) with rotary handle on door and for Connection to Built up Hydro Panel.---1No.
Soft Water Supply hydropneumatic pumps set 3 Nos. (2w+1s) pumps
40 Amps. 25 kA TP with neutral link MCCB ( Motor Duty) with rotary handle on door suitable for 7.5 HP and for Connection to Built up Hydro Panel.---1No.
Filter Feed pumps set 3 Nos. (2 w+1s) pumps
Pump feeder shall consist of :
Set of ON / OFF LED indication Lamps protected by MCB.
Softener Feed pumps set 3 Nos. (2w+1s) pumps
Pump feeder shall consist of :
Set of ON / OFF LED indication Lamps protected by MCB.
Salt saturator & Chlorine dosing system
Each pump set feeder shall consist of :
25 Amps. SP, 10 KA "C" curve MCB with DOL Starter suitable for single phase 240 V, 50 Hz AC supply. Inter locking with filter feed pump treated water pump suitable for 0.5 HP ---4Nos.
Set of ON / OFF indication Lamps protected by MCB.
For Drainage Sump Pumps Plant Room area - 2 Nos.(1W +1S)
Pump feeder shall consist of :
32 Amps. TP MPCB 25 KA with rotary handle on door suitable for Connection to Built up Panel.--1No
WTP Pump Room panel as above
Pump motor controller cum water level indicating panel at WTP Plant Room
Supply, installation, testing and commissioning of Centralised PLC control panel front operated, cubicle construction, wall mounted type, fabricated out of 2 mm thick CRCA Sheet, with hinged lockable doors, dust and vermin proof, powder coated of approved shade, inter-connections, having, internal wiring, earth terminals, Top / Bottom control cable entry, numberings etc. comprises of touch-screen display board (Min. Diag. size 8") along with all accessories for complete Programmable logical controls & indications, having necessary interlocks, Inputs/Outputs, required number of repeater amplifiers, all audio-visual alarms as per the requirements listed below i/c emergency stop push button on the panel etc. The panel shall have BMS compatible Modbus protocol complete as required and as per technically specified.
Water level indicators and controllers :The hydrostatic pressure sensor (Water level indicator) is working on hydrostatic pressure measurement principle made of Stainless Steel for installation in storage tanks, and capable of providing 4 to 20 mA analogue signal compatible with PLC signal inputs and all control outputs to MCC panel (Plumbing/Water supply),complete as per working requirements for equipment detailed below.
Fire Static Underground tanks- 2 Nos.
Real-Time water level indication monitoring
Low Level audio-visual alarm at less than 30% total capacity.
Raw Water Underground tanks- 4Nos.
Real-Time water level indication monitoring
Low Level audio-visual alarm at less than 30% total capacity.
High Level audio-visual alarm at more than 100% total capacity.
Auto cut-out of raw water pumps at 15%
Domestic Water Underground tanks- 2 Nos.
Real-Time water level indication monitoring
Low Level audio-visual alarm at less than 30% total capacity.
High Level audio-visual alarm at more than 100% total capacity.
Auto cut-off of Raw water pumps at 100%
Auto cut-out of domestic water hydronuematic pumps at 10%
Soft Water Underground tanks- 1 No.
Real-Time water level indication monitoring
Low Level audio-visual alarm at less than 30% total capacity.
High Level audio-visual alarm at more than 100% total capacity.
Auto cut-out of Softener feed pumps at 100%
Complete Set as mentioned above
MOBILE DISTRIBUTION BOARDS WITH STAND
Supplying, installation, testing & commissioning of Mobile distribution boards suitable for 415 V, 3 Phase, 4 wire 50 Hz AC supply system of suitable size fabricated in CRCA sheet steel of 2mm thick i/c cleaning & finishing complete with 7 tank process for powder coating in approved shade.
Entire panel shall have a common copper earth bar of size 25mm x 6mm at the rear with 2 Nos. earth stud, control wiring with 2.5 Sq.mm. PVC insulated copper conductor S/C cable for voltage & Current respectively, cable alleys, cable gland plates in two half, i/c providing, following :
INCOMING :
1 No. - 100 Amps. 25KA, Four Pole, Thermal Magnetic release, MCCB (Ics = Icu at 415 V) with O/C & S/C protection with following accessories for each MCCB's
1 No..- Earth Leakage Relay with CBCT .
1Set.- Phase indication LED lamps with 2 Amps. back up MCB, test terminal block set.
OUTGOINGS
6 No. - 32 Amps. MCB DP 10KA with IP-44 3Pin Plug & Socket
MOBILE DISTRIBUTION BOARDS WITH STAND, as described above
Mobile combination unit
Supplying, installation, testing & commissioning of Mobile combination unit suitable for 415 V, 3 Phase, 4 wire 50 Hz AC supply system of suitable size fabricated in CRCA sheet steel of 2mm thick i/c cleaning & finishing complete with 7 tank process for powder coating in approved shade including providing & fixing of 6 nos. 16A industrial socket outlets with end caps suitable for 230V, with one no 63A MCB 'C' curve and 63A RCCB, suitable cooper bus bars, interconnections & suitable provision for cables incomer & outgoing connections.
32 Amps. TP MPCB 25 KA with rotary handle on door suitable for Connection to Built up Panel.-1 No.
Isolators Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63A MCB
Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.
100A MCCB
200A MCCB
250A MCCB
Isolator Boxes Supplying and fixing enclosure with IP- 20/30 protection, powder coated provision for housing Four pole (4P) MCCB/MCB, concealed in wall after cutting the wall & mending good the damages to original finish / on flat iron frame incl. painting, connection & provision for earthing attachment
MISCELLANEOUS - SUB STATION ITEMS
Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required for HT/LT 33/11KV, 1.1KV cable route marking including PCC base as required all as specified & approved by Engineer Incharge.
Supplying and laying ISI marked following electric insulating mats of 33/11/3.3 KV working voltage grade of approved make as per IS-15652-2007 amended up-to-date complete as required & approved by Engineer Incharge.
2.0mm thick 3.3kv working voltage level grade.
2.5mm thick 11kv working voltage level grade.
3mm thick 33kv working voltage level grade.
Supplying of fire buckets of 10 liters Capacity of approved quality, painted white from inside and red outside and having inscription "FIRE" in white conforming to I.S. 2546/1974 duly amended upto date complete as required & approved by Engineer Incharge.
Supplying and fixing of MS pedestal stand heavy duty with rain protection cover as required suitable for supporting Six fire buckets as required for fire fighting system & approved by Engineer Incharge.
Supplying and fixing carbon dioxide (CO2) type fire extinguishers conforming to IS 15683 with cylinder duly charged of capacity 4.5kgs. including fixing clamps, brackets, bolts and nuts etc. as required & approved by the Engineer Incharge.
Supplying and fixing 10kg capacity Modular Automatic Fire Extinguishers dry chemical powder nitrogen type pre-set at works ranging from 57 deg. C/ 68 deg. C/ 79 deg. C fire extinguishers conforming to IS 15683 including fixing clamps, brackets, bolts and nuts etc. complete as required & approved by the Engineer Incharge.
Supplying and fixing of Shock treatment/ restoration charts written in Hindi/ local language and English duly framed and covered with 3.0 mm glass as required.
First Aid Box made of 16 SWG MS Sheet duly painted within inside and outside surfaces with one coat of primer and two coats of synthetic paint of required shade comprising the following minimum but not limited.
minimum 1 No. band aid bandage 150mm, 1 No. Savlon Soap 30 ml, 1 No bottle Betadine 30 ml, 1 No Packet dressing material etc. as required.
HT 36 KV rubber gloves as per IS 4770-1991
HT 12 KV rubber gloves as per IS 4770-1991
Supplying of Caution Boards manufactured out of 16 SWG, MS sheet of 450mmx 300mm size duly painted white and having `MAN ON LINE' and 'DO NOT SWITCH ON' written in Red complete with hanging arrangement as required and & approved by the Engineer Incharge.
Providing and fixing HT Danger Notice Plate of 250mmx 200mm made of mild steel at least 1.6mm thick and vitreous enamelled, white on both sides and with inscription in letters, figures and conventional signal red colour on front side as required & approved by the Engineer Incharge.
Providing and fixing LT Danger Notice Plate of 200mmx 200mm made of mild steel at least 1.6mm thick and vitreous enamelled, white on both sides and with inscription in letters, figures and conventional signal red colour on front side as required & approved by the Engineer Incharge.
Supplying & fixing of fire sealants to shafts, ceiling, cut-outs etc. with 2 hour fire rated composition as per specifications, NEC2011, relevant IS & as per approved makes of material & making good the same complete with accessories as required per site
UPS SYSTEM
Supply, Installation, Testing and Commissioning of following rated high performance IGBT based PWM technology (three phase Input & three phase Output) online UPS system suitable for input and output parameters as per input THDI < 3%, input power factor <0.99, output power factor 0.9 to 1.0, efficiency 95%, True Online Double Conversion (VFI SS 111 as per IEC 62040-3) ,3 phase input (415 V ± 10% , 50 Hz ± 5% ), and three phase output (415 V ± 3%, 50 Hz ± 1%) with 30 minutes battery backup. The UPS shall have Galvanic Isolation Transformer Inbuilt/External K13 rated copper Wound (After Static Switch) transformer. The UPS shall be made of MS sheet 2mm thick, provided in powder coated fan cooled enclosure painted in colour as per specifications. The UPS shall be suitable for normal, emergency, recharge, by-pass and maintenance mode including bypass arrangement. The Static Bypass Module should be 100% fully rated and suitable terminal box for cables entry from top. The UPS shall have a microprocessor based display and control panel with protections, inbuilt pase reversal protection, Digital Display to monitor & control the various Parameter, Inbuilt static bypass module at the bypass line. Complete system must be provided as per specifications approved drawing and as per site requirement including inter connecting cables from battery to UPS, UPS to panel with single core copper cabling etc. UPS shall work on parallel/ hot redundancy mode, cost of supporting kit shall be included. supports for complete system as approved by the Engineer in charge complete in all respect.
200 KVA UPS described as above (N+1 mode)
30 KVA UPS described as above (N+1 mode)
Supply & installation of following rated KVA solar inverter cum UPS input three phase (415 V ± 10%) output three phase (415 V ± 1%) with sealed maintenance free batteries suitable for 30 minutes backup including providing suitable size of 14 gauge MS battery rack suitably painted. 5 KVA described as above
Prepaid metering system
Supply, Installation & Testing of Prepayment Meters as per “IS 15884: 2010” by “BUREAU OF INDIAN STANDARDS” for AC Direct Connected Static Prepayment Meters for Active Energy” released on February, 2010. Three Phase Liberty Prepayment Meter 10A-60A with Dual register facility with Home display/ Freedom Unit. Meter should have inbuilt disconnect switches as per BIS requirement with Overload and Low balance alarm facility complete as required.
Supply, Installation & Testing of Prepayment Meters are compliance of specification “IS 15884: 2010” by “BUREAU OF INDIAN STANDARDS” for AC Direct Connected Static Prepayment Meters for Active Energy” released on February, 2010. Single Phase Liberty Prepayment Meter 10A-60A with Dual register facility with Home display/ Freedom Unit. Meter should have inbuilt disconnect switches as per BIS requirement with Overload and Low balance alarm facility with Supply, Installation, testing & Commissioning of DG sensing Switch Mode Power Supply Unit for discrimination receivers for sensing of DG set complete as required.
Supply, Installation, testing & Commissioning PC for Local server with 8 GB RAM, 1 TB Hard Disk, DVD Drive, 2.0/3.0/4.0 USB Ports of Standard make alongwith Keyboard, mouse, mouse pad etc. complete with UPS of 800 VA with 20 min. back up, Laser Colour jet Printer complete as required.
Supply, Installation, testing, Commissioning of Vending software certified by (ISO/IEC 27001) & Training of the vending System for Tariff designing as per BIS guidelines & Customer Data Base definition (Vending Services and training, Annual charges for Vending services (Per consumer Meter) shall not be extra paid) complete as required.
Supply, Installation, testing , Commissioning of Token Printer with Serial Port. Tokens are meter specified and encrypted with triple des technology. Also the vending system is ISO/IEC 27001 compliance with certification complete as required.
AUTOMATIC ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM
FIRE ALARM SYSTEM
Supply, Installation, Testing & Commissioning of Microprocessor based intelligent Networkable analogue addressable type fire alarm control panel 10 loops minimum (min. 4.3 inch LCD display), with minimum 600 character display. The panel should be equipped with sufficient numbers of loop with 20% spare capacity having integrated voice evacuation with amplifier as per the quantity and fire fighting telephone system rail mounted with each loop shall have a capacity of minimum 240 analogue addressable devices in one loop. Four access levels, capable of taking Flash Scan devices, flash EPROM sufficient numbers of programmable relay controls for controlling AHUs, pressurization fans, ventilation fans at fire pump room, monitoring of fire sprinkler and fire hydrant pump, addressable 240 volts AC power supply, automatic battery charger, 24 volts sealed lead acid batteries sufficient for 24 hours normal working and then be capable of operating the system for 2 hours during an emergency conditions as required. The Panel shall have BACKNET CARD for integration. (UL 9th Edition Approved and NFPA/ EN54 or latest amended upto date)
Supply, Installation , Testing & Commissioning of the GUI based main network Fire Detection must be capable of graphically representing each facility being monitored with floor plans and icons depicting the actual locations of the various systems; and / or sensors’ locations. The GUI software shall be located in control room in one of the Floors and shall monitor all the Floor Fire Detection, Digital voice evacuation system and 2 way communication panel connected with each other through fibre optics. The software shall provide the facility to Monitor, Control all the Digital voice evacuation system as well as 2 way communication from main control room using voice signals over Fire Network along with the Fire detection signal. The software shall be capable of broadcasting on Voice over IP. (UL 9th Edition Approved and NFPA compliant) a. Operator work station with PC having Intel Pentium I7 Processor including Serial ports (RS232) and USB ports and following accessories etc. complete with software all as specified. b. 8 Gigabytes of RAM memory c. 2 TB of hard disk space d. DVD ROM e. 21” LED colour monitor f. Mouse with Mouse Pad g. Standard Key Board h. Latest Windows Operating System i. Compatible Fire Alarm System Control Software j. Laser Printer colour A4- 1 No k. Software for Automatic Fire Detection and Alarm System l. Software for Aspiration Based Smoke Detection System m. UPS 800 VA or better
Supply, Installation , Testing & Commissioning of Network Repeater Panel with 600 characters; The LCD shall Display all events / detectors, devices status of complete systems in the networked, The NRP shall be equipped with QWERTY/ alphanumeric Keypad. Mounting options include an annunciator box, and blank modules are required for mounting. (UL 9th Edition Approved and NFPA compliant/ EN54 or latest amended upto date)
Supply, Installation, Testing & Commissioning of Automatic Analogue addressable multicriteria detector (smoke+heat) with auto floating sensitivity, mounting base LED, Address/ Electronic Switch to programme the detectors. (UL 9th Edition Approved and NFPA compliant/ EN54 or latest amended upto date)
Supply, Installation, Testing & Commissioning of Automatic Analogue addressable smoke detector, mounting base LED, Address/ Electronic Switch to programme the detectors complete as required. (UL 9th Edition Approved and NFPA compliant/ EN54 or latest amended upto date)
Supply, Installation, Testing & Commissioning of Automatic Analogue addressable heat detector with rate of rise and fixed, mounting base LED, Address/ Electronic Switch to programme the detectors complete as required. (UL 9th Edition Approved and NFPA compliant/ EN54 or latest amended upto date)
Supply, Installation, Testing & Commissioning of Automatic Analogue addressable duct smoke detector, mounting base LED, Address/ Electronic Switch to programme the detectors complete as required. (UL 9th Edition Approved and NFPA compliant/ EN54 or latest amended upto date)
Supplying, installation, testing & commissioning of Response Indicator which consists of steady glowing LED. This LED shall be mounted within a Polycarbonate box and connected in parallel to the built in indicator of the detector as per specifications. The RI shall come "ON" as soon as the detector activates complete in all respects as per specification.
Supply, Installation, Testing and Commissioning of Addressable type Manual call (Pull down type) Station complete with, all accessories as per specifications. (UL 9th Edition Approved/ EN54 and NFPA compliant or latest amended upto date) complete as required.
Supply, Installation, Testing & Commissioning of supply with sounder with 20 Hz to 20KHz operating frequency with multitone/ multi sound patterns to indicate Exit doors and direct occupants for safe and fast evacuation , complete with MS Powder coated Junction Box for mounting on Surface, Cable lugs at Ends, cable compression glands, cable tags and Ferruling as specified in NFPA 72 - 2007 edition. (UL Listed/ EN54 or latest amended upto date)
Supply, Installation , Testing & Commissioning of Strobe Light as per the system requirement. (UL Listed/ EN54 or latest amended upto date)
Supply, Installation, Testing and Commissioning of 2 way communication Fire Fighter's Telephone Jack fitted on wall including the cost of breaking and making good the wall wherever required, complete in all respects as per specifications. (UL 9th Edition Approved and NFPA compliant/ EN54 or latest amended upto date) complete as required.
Supply, Installation, Testing and Commissioning of 2 way communication Fire Fighter's Handset complete with all accessories as per specifications.
Supply, Installation, Testing and Commissioning of fault isolator for isolating shorted, dewired and loose circuits between two successive fault isolators with automatic resetting arrangement complete in all respects as per specifications. (UL 9th Edition Approved and NFPA / EN 54 compliant) complete as required.
Supply, Installation, Testing and Commissioning of Addressable monitor modules for Sprinkler Flow Switch as required. (UL 9th Edition Approved and NFPA compliant/ EN54 or latest amended upto date) complete as required.
Supplying, Installing, Testing and Commissioning of addressable Control Module with relay etc. for Sounder, AHU, Fire Dampers, Smoke Ventilation complete as required and as per specifications. (UL 9th Edition Approved and NFPA compliant/ EN54 or latest amended upto date) complete as required.
ASPIRATION DETECTION SYSTEM
Supply, installation, testing and commissioning of addressable aspiration detector with LED Based Aspiration Detection Unit for area coverage of 28000 Sq. Feet with sensitivity ranging as per specifications along with 8 relay outputs, 3 stage filtration with TCP/IP network capability. The unit should be UL and FM approved complete as per specifications. The cost will include monitored Power Supply Unit for above detector 230 V AC to 24 V DC 1.5 Amp with 24 hour battery backup in normal condition and 30 minutes in alarm condition etc. complete with as per specifications. (UL 9th Edition Approved/ EN54 and NFPA compliant or latest amended upto date)
Supply, installation, testing and commissioning of capillary Sampling Points with length upto 1.5 mtrs.. including accessories etc. complete in all respect, as per specifications.
Supply, installation, testing and commissioning of 25 mm OD Fire Retardant CPVC PIPE with Sampling holes complete in all respect with Tees, Bends complete as per system requirement.
Supply, installation, testing and commissioning of End Caps for 25 mm OD Fire Retardant CPVC PIPE complete in all respect as per system requirement.
Providing, laying, connecting, testing & commissioning twisted pair shielded pvc insulated cable 2core 1.5sq.mm ISI marked for fire telephone jack system including all accessories complete as required.
Providing and laying, connecting, testing & commissioning of 2 Core 1.5 Sq. mm, Glass Mica taped, with Cross Linked Halogen Free insulation, overall screened, HFLS, sheathed, fire resistant copper conductor twisted pair cable. The cable shall have C/W/Z rating to withstand temperature of 950°C complete with all accessories, terminations, glands etc. as per specification in all respect (FM Approved) as per BS 6387, BS 50200, basic design as per BS 7629.
HVAC WORKS
WATER COOLED CENTRIFUGAL CHILLERS WITH VFD:
Supplying of AHRI certified water cooled centrifugal chilling machines having actual capacity of 1000 TR at site condition, suitable for operation on refrigerant R-134a/R-1233zd(E)/ R-514a comprising of the following complete as per specification & as required.
i) - Single/ Multiple centrifugal type compressor open/semi-hermetic complete with automatic capacity control, safety switches, speed increasing gears, forced feed lubrication system etc. as per specifications.
ii) - The unit shall be designed to unload upto 20% of its rated capacity at Constant Condenser Water Entering Temperature & at AHRI conditions. The compressor shall have mechanism for stable operation at part loads.
iii) - Motors shall be SPDP / TEWAC IP54 rated for open drive or TERC for semi-hermetic suitable for operation on 415 ±10% V, 50HZ, AC Supply.
iv) - Air/liquid/refrigerant cooled VFD Starter factory installed unit mounted minimum IP-54 rated or better / Free standing minimum IP-54 rated or better with interconnection of power and control at site with copper cable. An active harmonic filter that limits electrical power supply distortion for the variable speed drive to comply with the guidelines of standard IEEE519-2014 shall be provided. THiD must be limited to 5% using Active Harmonic solutions at equipment level at all loads and suitable for compressor motor complete with ammeter with CTs, overload protection, under voltage protection, protection against phase reversal and independent single phase preventors etc. complete as required. VFD shall be separate with each compressor. in case of free standing, VFD shall be sourced along with the chilling unit.
v) - Necessary drive arrangement
vi) - 1 Set- Lubrication device consisting of Automatic Electric Oil Pump, oil cooler, head tank, oil strainer, automatic pressure regulating valve, oil heater, thermal switch etc. as per specifications.
vii) - 1 No. matching Water Shell & Tube Cooled Condenser of MS shell, integrally finned copper tubes.
ix) - 1 No. matching shell & tube chiller of M.S. shell, copper tubes.
x) - 1 Lot - Refrigerant piping fittings, valves & accessories to interconnect compressor, condenser, chillers & expansion valve.
xi) - 1 Set - Microprocessor based control panel complete with accessories as per specifications & shall be BMS compatible.
xii) - 1 Lot - Refrigerant line accessories comprising of safety valves, angle valves, liquid line indications, liquid level control etc.
xiii) - 1 Lot - Water flow switches for condenser and chiller, water drain and air purge valves wherever required.
xiv) - 1 Lot- Suction line & chiller insulation duly insulated at manufacturer works as required.
xv) - 1 Lot- Frame work for mounting the above condenser, chiller compressor and motor with base plate complete with antivibration pads/springs including PCC/RCC foundation as per OEM recommendation.
xvi) - 1 Lot- Initial/first charge of refrigerant gas and compressor oil.
xviii) - 1 Lot- Necessary vibration isolation mountings for the chilling unit as per manufacturer's drawing.
Chiller:
Chilled Water In - 56°F (13.3°C)
Chilled Water Out - 44°F (6.7°C)
Chilled Water Flow - 2000 USGPM
Chiller Fouling Factor (as per IS 16590 : 2017) - 0.00025 ft2.h.°F/Btu
Condenser:
Condenser Water In - 87°F (30.5°C)
Condenser Water Out - 97°F (36.1°C)
Condenser Water Flow - 3000 USGPM
Condenser Fouling Factor (as per IS 16590 : 2017) - 0.0005 ft2.h.°F/Btu
Minimum COP at AHRI conditions - 6.5
Maximum Power Consumption at 100% load at site condition - 0.59 kW/TR
Maximum permissible pressure drop in evaporator-8 M of water
Maximum permissible pressure drop in condenser-8 M of water
Maximum IPLV at AHRI conditions: 0.35
Maximum NPLV at above conditions :0.38
WATER COOLED CENTRIFUGAL CHILLERS WITH VFD AS ABOVE
Installing, testing & commissioning of AHRI certified water cooled centrifugal chilling machines having actual capacity of 1000 TR at site condition as mentioned above complete as per specification & as required.
AUTOMATIC TUBE CLEANING SYSTEM
Supply of Automatic Tube Cleaning system for 1:2 (1 ATCS for 2 Condenser) with separate Ball traps and Ball Collectors operated by a single /multiple skid with pump / pump less and a controller suitable for Condenser inlet/outlet size. The ATCS system shall be complete with all valves, fittings, piping, control cabling, etc. The ATCS system shall be online with the chiller operation and should not unload the Chiller during cleaning cycle. The ATCS system shall be smart enough to decide to send the balls only to the running chillers and not in standby chillers. The required sponge balls for a period of one year shall be supplied along with the system. Ball Trap - MOC of CS epoxy painted with SS 304 strainer along with Ball Collectors with clear peri - glass view window with complete valves and fittings, check valves and manual valves ATCS Skid complete with pipings and pump. Control Panel complete with all Touch screen Colour graphics screen, motor protection, alarms, feedback mechanism, time lead and lag, etc. complete with Safety and Control Logics. Actuated Motorized valves for Controlling injection and collection separately.
Installing, testing & commissioning of Automatic Tube Cleaning system as mentioned above complete as per specification & as required.
CHILLER PLANT OPTIMIZER a) - Supply of CHILLER PLANT OPTIMIZER as per specifications to control and monitor chillers and other auxiliary equipment in the plant room and to provide output in BacNet over IP. The cost to be inclusive of supplying & installing all necessary accessories as required to complete the installation. All necessary sensors and cabling shall be included.
i) - Water Cooled Chillers of 1000 TR - 4 Nos. (3W+1S)
ii) - Condenser Water Pumps - 4 Nos. (3W+1S)
iii) - Primary Chilled Water Pumps - 4 Nos.(3W+1S)
iv) - Variable Secondary Chilled Water Pumps - 4 Nos.(3W+1S)
v) - Cooling Towers - 4 Nos.(3W+1S)
vi) Twin Pump Pressurisation Unit with Pressureless Expansion tank with built-in De-aerator & automatic water makeup - 1 Set
vii) - Side Stream Filtration System-1 Set
viii) - Cooling Tower Water Treatment System-3 Set
b) - Supply, installation, testing and commissioning of CHILLER PLANT OPTIMIZER along with chiller optimizer including all sensors and software with open protocol. The plant Optimizer should have minimum I/O point as per specification and details given below
c) - Supplying, Installing, Testing & Commissioning of the Central Control Stations consisting of Operator Workstation Intel I7 +Processor(Latest Technology) with min 1 TB HDD, min 8 GB RAM, 2 GB Enhanced graphic Card, DVD Combo Drive, Ethernet Port with Dual Screen Ports. With Windows XP Pro /Windows 8.1 License suitable to BMS software or any latest version of OS with Anti virus As per Specification. MS office package to be provided Location: HVAC Plant Room - 1 Lot.
d) - 24" colour monitor flat screen LED display with complete wall mounted /table mounted Brackets as per specifications- 1 Lot.
e) - SOFTWARES
i) - Supply, installation, testing & commissioning of the Software for CPO System as per technical Specifications with minimum 5 nos. of web license. Supervisory controller should be directly Integrated with BMS server on BACnet over IP. Software shall have the capacity to accommodate hard points as per IO summary.
ii) - Supply, installation, testing and commissioning of software interface with PUMPS / Cooling Towers' VFD (8 Nos.) for two way flow of data between CPO and panels. The price shall include the necessary integrator required for integration and also the networking of all chiller panels. All VFD's will be integrated on Open Protocol over IP with CPO (VFD quantity are mention in IO Summary)- 1 Lot
iii) - Supply, installation, testing and commissioning of software interface for Energy Meter (20 Nos. ) for Chillers, Primary Pumps, Secondary Pumps, Condenser Pumps and Cooling Towers .The price shall include the necessary integrator / gateway required for integration. All EMs will be integrated on open Protocol over IP with CPO ( Load Optimizer /Energy meter quantity are mention in IO Summary)- 1 Lot
f) - CPO SYSTEM DEVICES
Supply of equipment for CPO Stand alone Microprocessor based 32 Bit, UL Listed DDC Controllers with BACnet testing lab certified (BTL) & Network & Supervisory controller on BACnet/IP units for connecting all field DDC controllers as per the specifications for hard wired IO points. The contractor shall decide upon the number of controllers, depending on his Controller capacity. Expandable modules for Inputs/Outputs. Plug in relays , DDC shall be with all accessories & shall be suitable for future expansion. Contractor shall furnish quantity and unit rate for each type of controller considered by him. The above shall be housed in IP45, lockable ,Standard Power Supply, Secure MS powder coated Cabinets to be supplied along with the DDC Controllers Connecting Cables. The CPO should be seamlessly Integrated with BMS on Bacnet Over IP Protocol. Necessary cabling from field devices to plant Optimizer shall be included- 1 Lot.
g) - SENSORS & FIELD DEVICES
Supply, Installation, testing & Commissioning of following equipment for BAS
i) - Pressure transmitters for measuring pressure in water (0-16 Kg/cm. sq). Price should be with all necessary fittings & Accessories to install the same as per Specification- 2 Nos.
ii) - Water Differential pressure switches across the pumps for indicating the pumps Run status. Price should be with all necessary fittings & Accessories to install the same as per Specification- 17 Nos.
iii) - Water Differential pressure Transmitter (0-8 Kg/cm. sq) across the Evaporator for measuring the flow. Price should be with all necessary fittings & Accessories to install the same as per Specification- 4 Nos.
iv) - Water Differential pressure Transmitter (0-2 Kg/cm. sq) across hydraulically farthest AHUs. Price should be with all necessary fittings & Accessories to install the same as per Specification- 1 Nos.
v) - Level transmitter suitable for mounting in cooling tower basin for high-low level monitoring as per technical Specification- 4 Nos.
vi) - Immersion Temperature Sensor with Thermowell as per technical Specification- 16 Nos.
vii) - Outside Air Temperature &Humidity Sensor as per technical Specification- 1 No.
viii) - 2 C x 1.5 Sqmm ATC Shielded armoured cable - 1000 RMT.
ix) - 2 Pair 18 AWG Shielded ATC armoured communication cable - 500 RMT.
Chiller Plant Optimizer as above
Installing, testing & commissioning of Automatic Tube Cleaning system as mentioned above complete as per specification & as required.
PRIMARY CHILLED WATER PUMPS: Supply, installing, testing & commissioning of Centrifugal Horizontal, End-Suction, Top Discharge vertical split casing high efficiency Primary Chilled Water Pumps, complete with CI body, bronze / gun metal / CF8 impeller with stainless steel shaft, bronze or gun metal shaft sleeve, mechanical shaft seals and flexible coupled with electric motor for re-circulation of water for the central air conditioning system. The pump shall be flexible coupled protected by OSHA compliant coupling guard. All pumps shall be aligned properly as required. The pump motor shall be TEFC squirrel cage induction motor having efficiency class IE3 (as per IS 12615) with class 'F' insulation, 1500 RPM synchronous speed, operating on 415 V +/- 10%, 3 phase, 50 Hz AC supply. The motor shall be non- overloading type. Pumps shall be with performance characteristics as given below. The pump and motor shall be mounted on a common base plate. The complete pump set alongwith base plate, coupling and coupling guard shall be factory assembled and tested. Pump set shall be complete with thermal insulation same as chilled water pipes, aluminium cladding at suction and discharge, necessary anti vibration pads, MS base plate, coupling guard, and all other accessories complete as required. Capacity of Primary Chilled Water Pumps: Water Flow Rate - 2000 USGPM Head - 12 M of Water Motor kW - 30 RPM - 1450 Efficiency - 75% or more Pumps: 4 Nos. (3 Working & 1 Standby)
SECONDARY CHILLED WATER PUMPS WITH VFDS :
Supply, installing, testing & commissioning of Centrifugal Horizontal, End-Suction, Top Discharge Secondary Chilled Water Pumps with VFD, complete with CI body, bronze / gun metal / CF8 impeller with stainless steel shaft, bronze or gun metal shaft sleeve, mechanical shaft seals and flexible coupled with electric motor for re-circulation of water for the central air conditioning system. The pump shall be flexible coupled protected by OSHA compliant coupling guard. All pumps shall be aligned properly as required. The pump motor shall be TEFC squirrel cage induction motor having efficiency class IE3 (as per IS 12615) with class 'F' insulation, 1500 RPM synchronous speed, operating on 415 V +/- 10%, 3 phase, 50 Hz AC supply. The motor shall be non- overloading type. Pumps shall be with performance characteristics as given below. The pump and motor shall be mounted on a common base plate. The complete pump set alongwith base plate, coupling and coupling guard shall be factory assembled and tested. Pump set shall be complete with thermal insulation same as chilled water pipes, cladding, rubber flexible connections (PN-16) at suction and discharge, necessary anti vibration pads, MS base plate, coupling guard, and all other accessories complete as required.
i) - Electrical control panel capable of cyclic operation of pumps - Pump working sequence should change after every operation. Control panel with programmable logic controller (PLC) with inbuilt PID controller, digital display (showing electrical parameters like Voltage, Current and Power consumption (both kW and kW.hr.) as well as % speed indication and /or % frequency indication) with fluorescent screen with two lines of min. 20 character each and equipped with function keys and service keys. 3 phase, 415 ± 10% Volts, AC, Air-cooled IP-55 Variable Speed Drive for each pump of suitable capacity rating having standard function of BI loop, energy saving catching a spinning load with speed search, auto hunting jog preset speeds, controlled stop on loss of supply powerloss side through, DDC injection breaking fast stop.
ii) - Microprocessor based control panel shall have suitable hardware & software, compatible with BMS so that it can be integrated directly with standard communication open protocol using backnet / Modbus as well as open IP
iii) - All pumps shall be provided with individual VFD for each pump. Control panel should also consist of cooling fan.
iv) - VFD shall have provision for manual setting of cooling mode.
v) - One panel for each set of secondary pumps shall be provided.
vi) - Differential Pressure Sensors & Transmitters minimum 2 nos.
vii) - Suitable flanged suction and delivery connections.
viii) - The entire system along with pumps & VFD as described above shall be sourced from single manufacturer only.
The system shall be complete in all aspects and suitable for following configuration
Capacity of Secondary Chilled Water Pumps: Water Flow Rate - 2000 USGPM Head - 35 M of Water Motor kW - 75 RPM - 1450 Efficiency - 75% or more Pumps: 4 Nos. (3 Working & 1 Standby) and 1 Nos. Controller
CONDENSER WATER PUMPS: Supply, installing, testing & commissioning of Centrifugal Horizontal, End-Suction, Top Discharge Condenser Water Pumps, complete with CI body, bronze / gun metal / CF8 impeller with stainless steel shaft, bronze or gun metal shaft sleeve, mechanical shaft seals and flexible coupled with electric motor for re-circulation of water for the central air conditioning system. The pump shall be flexible coupled protected by OSHA compliant coupling guard. All pumps shall be aligned properly as required. The pump motor shall be TEFC squirrel cage induction motor efficiency class IE3 (as per IS 12615) with class 'F' insulation, 1500 RPM synchronous speed, operating on 415 V ± 10%, 3 phase, 50 Hz AC supply. The motor shall be non- overloading type. Pumps will be with performance characteristics as given below. The pump and motor shall be mounted on a common base plate. The complete pump set alongwith base plate, coupling and coupling guard shall be factory assembled and tested. Pump set shall be complete with rubber flexible connections (PN-16) at suction and discharge, necessary anti vibration pads, MS base plate, coupling guard, and all other accessories complete as required. Capacity of Condenser Water Pumps: Water Flow Rate - 3000 USGPM Head - 35 M of Water Motor kW - 90 RPM - 1450 Efficiency - 75% or more (3 Working & 1 Standby)
AIR HANDLING UNITS :
Supply, Installation, Testing and commissioning of factory built “EUROVENT CERTIFIED” floor mounted double skin type horizontal/vertical air handling units made of 50 ± 2 mm thick panels fabricated with aluminium extruded profile sections consisting of pre-plasticized G.I. casing of thickness 0.8mm outside layer and 0.8 mm inside layer with polyurethane foam (PUF) insulation of density 40 ± 2 kg/m3 factory injected between them by injection moulding machine, complete with blower section with blower suitable for static pressure as required, cooling coil sections with aluminium finned copper tubes (tubes thickness not less than 0.5 mm) AHRI /EUROVENT certified cooling coil of 6 row deep, complete with pre-filter section (90% down to 10 microns) or space provision for electronic air cleaner as required, fire rated flexible connection, belt drive package with TEFC drive motor of efficiency class IE3 (as per IS 12615) suitable for 415 ± 10% V, 50Hz, 3 Phase AC supply suitably designed for variable frequency drive applications, drain connections, stainless steel (18G) drain pan with PUF insulation, auto purge valve wherever required, necessary vibration isolation arrangement etc. complete as per specification and of following capacities.
i) - Supply air centrifugal fan with efficiency more than 75%.
ii) - Face velocity across filters shall be 500 FPM & across coil shall be 500 FPM.
iii) - Fan belt drive package. The fan and motor shall be mounted on aluminium extruded section.
iv) - Fan outlet velocity not exceeding 9.2 m/s (1800 FPM).
v) - Static pressure of AHU shall be checked by Vendor/Contractor prior to supply of AHU as per site condition. If there is any discrepancy against the BOQ, the vendor/contractor has to take approval from Client / PMC, and nothing extra shall be paid.
vi) - Sound level at 1 m distance to not exceed 70 dB(A). Sound attenuators in supply & return air streams shall be provided if required to meet the specified sound level in both supply & return air ducts.
vii) - Fire rated flexible connection shall be double canvas sleeve.
viii.)-Space to be provided for Electronic air cleaner system in AHUs as mentioned below. Other AHUs shall be provided with Pre-Filter section.
viii.)-For large capacity AHU, wherever two nos. fan motors required, junction box with single incomer & 2 nos. outgoing & internal connection with motor shall be provided with AHU.
a) - Coil shall be designed for following parameters:
Chilled Water IN / OUT - 44 °F/ 56 °F
b) - Mechanical performance of AHU casing shall be tested in Eurovent accredited laboratory as per EN 1886 and should meet the following characteristics: - Mechanical Strength : D1, - Thermal Bridging : TB2, - Thermal Transmittance : T3, - Air Leakage : L1
Air moving capacity shall be as follows:
F/M- DP-8A -3500 CFM /9.0 TR/ 50 mm (SP) with Mixing Box
F/M- DP-6A -4000 CFM /11.0 TR/ 50 mm (SP) with Mixing Box
F/M- AR-9,10 -6000 CFM /16.0 TR/ 50 mm (SP)
F/M- MZ-8 -6500 CFM /17.0 TR/ 50 mm (SP)
F/M- DP-6B -7000 CFM /18.0 TR/ 50 mm (SP)
F/M- MZ-09 -8000 CFM /20.0 TR/ 50 mm (SP)
F/M- MZ-05, DP-8B -9000 CFM /24.0 TR/ 50 mm (SP)
F/M- MZ-7 -9000 CFM /22.0 TR/ 60 mm (SP) (C/W space provision for electronic air cleaner)
F/M- AR-02 -12000 CFM /23.0 TR/ 50 mm (SP)
F/M- AR-15 -13000 CFM /39.0 TR/ 65 mm (SP) (C/W space provision for electronic air cleaner)
F/M- DP-01,02 -13500 CFM /40.0 TR/ 65 mm (SP) (C/W space provision for electronic air cleaner)
F/M- AR-14-15000 CFM /44.0 TR/ 65 mm (SP) (C/W space provision for electronic air cleaner)
F/M- DP-10-15000 CFM /36.0 TR/ 60 mm (SP)
F/M- DP-18-15500 CFM /35.0 TR/ 50 mm (SP)
F/M- DP-15,16-16000 CFM /42.0 TR/ 60 mm (SP)
F/M- DP-09-18500 CFM /45.0 TR/ 60 mm (SP)
F/M- DP-11,12,13-18500 CFM /50.0 TR/ 60 mm (SP)
F/M- MZ-06-20000 CFM /52.0 TR/ 60 mm (SP)
F/M- DP-03,04-21000 CFM /61.0 TR/ 65 mm (SP) (C/W space provision for electronic air cleaner)
F/M- DP-05,07-22000 CFM /58.0 TR/ 60 mm (SP)
F/M- AR-3,4,5,6,7-25000 CFM /47.0 TR/ 60 mm (SP) with Mixing Box
F/M- MZ-01-25500 CFM /64.0 TR/ 65 mm (SP) (C/W space provision for electronic air cleaner)
F/M- AR-12,13-26000 CFM /68.0 TR/ 60 mm (SP)
F/M- AR-01-28000 CFM /72.0 TR/ 65 mm (SP)
F/M- AR-08-29000 CFM /54.0 TR/ 60 mm (SP)
F/M- MZ-3,4-32500 CFM /84.0 TR/ 60 mm (SP)
F/M- DP-14-33000 CFM /86.0 TR/ 60 mm (SP)
F/M- AR-11-35000 CFM /90.0 TR/ 65 mm (SP)
F/M- DP-17-35500 CFM /92.0 TR/ 60 mm (SP)
F/M- MZ-2-40000 CFM /102.0 TR/ 60 mm (SP)
TREATED FRESH AIR UNITS :
Supply, Installation, Testing and commissioning of factory built floor mounted double skin type “EUROVENT CERTIFIED” horizontal treated fresh air units made of 50 ± 2 mm thick panels fabricated with aluminium extruded thermal break profile sections consisting of pre-plasticized G.I. casing of thickness 0.8mm outside layer and 0.8 mm inside layer with polyurethane foam (PUF) insulation of density 40 ± 2 kg/m3 factory injected between them by injection moulding machine, complete with blower section with blower suitable for static pressure as required, cooling coil sections with aluminium finned copper tubes (tubes thickness not less than 0.5 mm) AHRI / EUROVENT certified cooling coil of 8 row deep, complete with space provision for electronic air cleaner, belt drive package with TEFC drive motor of efficiency class IE3 (as per IS 12615) suitable for 415 ± 10% V, 50Hz, 3 Phase AC supply suitably designed for variable frequency drive applications , drain connections, stainless steel (18G) drain pan with PUF insulation, mixing box for fresh air duct connection, auto purge valve wherever required, necessary vibration isolation arrangement etc. complete as per specification and of following capacities.
i) - Supply air centrifugal fan with efficiency more than 75%.
ii) - Face velocity across filters shall be 500 FPM & across coil shall be 500 FPM.
iii) - Fan belt drive package. The fan and motor shall be mounted on aluminium extruded section.
iv) - Fan outlet velocity not exceeding 9.2 m/s (1800 FPM).
v) - Static pressure of AHU shall be checked by Vendor/contractor prior to supply of AHU as per site condition. If there is any discrepancy against the BOQ, the vendor/contractor has to take approval from Client / PMC, and nothing extra shall be paid.
vi) - Sound level at 1 m distance to not exceed 70 dB(A). Sound attenuators in supply & return air streams shall be provided if required to meet the specified sound level in both supply & return air ducts.
vii) - Fire rated flexible connection shall be double canvas sleeve.
a) - Coil shall be designed for following parameters:
Chilled Water IN / OUT - 44 / 56 °F
b) - Mechanical performance of AHU casing shall be tested in Eurovent accredited laboratory as per EN 1886 and should meet the following characteristics: - Mechanical Strength : D1, - Thermal Bridging : TB2, - Thermal Transmittance : T3, - Air Leakage : L1
Air moving capacity shall be as follows:
F/M TFA-01,02- 8500 CFM/ 45.0 TR/ 65 mm (SP) (with Mixing Box)
Supply, installation, testing and commissioning of Factory built “EUROVENT CERTIFIED” Ceiling Suspended double skin type chilled water air handling units made of 50 ± 2 mm thick panels consisting of pre plasticized G.I. casing of thickness 0.6 mm outside layer and 0.6 mm thick inside layer with polyurethane foam (PUF) insulation of density 40 ± 2 kg/m3 factory injected between them by injection moulding machine, complete with blower section with blower suitable for static pressure as required, cooling coil section with aluminium finned copper tubes (tubes thickness not less than 0.5 mm) AHRI/EUROVENT certified suitable row deep of cooling coil, pre-filter section (90% down to 10 microns), belt drive package with TEFC drive motor of efficiency class IE3 (as per IS 12615) suitable for 415 ± 10% V, 50Hz, 3 Phase AC supply, drain connections with drain valve, stainless steel (18 G) drain pan with PUF insulation, fire rated flexible connection, Descaling valve, auto air purge valve, necessary vibration isolation arrangement, fire retardant canvas connection along with suitable size of girder / pipes for support etc., complete as per specifications and of following capacities. (The item shall include suitable rating TPN Isolator/starter arrangement nearby with required cabling, interconnections etc. required to make the system complete working at site)
i) - Supply air centrifugal fan with efficiency more than 75%.
ii) - Face velocity across filters & coil shall be 500 FPM.
iii) - Fan belt drive package. The fan and motor shall be mounted on aluminium extruded section.
iv) - Fan outlet velocity not exceeding 9.2 m/s (1800 FPM).
v) - Static pressure of AHU shall be checked by Vendor/contractor prior to supply of AHU as per site condition. If there is any discrepancy against the BOQ, the vendor/contractor has to take approval from Client / PMC, and nothing extra shall be paid.
vi) - Sound level at 1 m distance to not exceed 70 dB(A). Sound attenuators in supply & return air streams shall be provided if required to meet the specified sound level in both supply & return air ducts.
vii) - Height of Ceiling Suspended AHU upto 5000 CFM should not exceed 600 mm.
viii) - Fire rated flexible connection shall be double canvas sleeve.
a) - Coil shall be designed for following parameters:
Chilled Water IN / OUT - 44 / 56 °F
b) - Mechanical performance of AHU casing shall be tested in Eurovent accredited laboratory as per EN 1886 and should meet the following characteristics: - Mechanical Strength : D1, - Thermal Bridging : TB2, - Thermal Transmittance : T3, - Air Leakage : L1
Air moving capacity shall be as follows:
CSU AR-01,02-2000 CFM/ 7.0 TR/30 mm (SP)
CSU AR-03,DP-10-2500 CFM/ 8.0 TR/30 mm (SP)
CSU BA-01-2500 CFM/ 5.0 TR/30 mm (SP)
CSU AR-04,05,DP-01,02,09 -3000 CFM/ 10.0 TR/30 mm (SP)
CSU DP-05-3500 CFM/ 9.0 TR/30 mm (SP)
CSU DP-17,18-3500 CFM/ 9.0 TR/35 mm (SP)
CSU DP-04,16-4000 CFM/ 11.0 TR/30 mm (SP)
CSU DP-06,07-4000 CFM/ 11.0 TR/35 mm (SP)
CSU DP-03,08,14-4500 CFM/ 16.0 TR/30 mm (SP)
CSU ARG-04,05-4500 CFM/ 8.0 TR/35 mm (SP)
CSU DP-11,12,13,15-5000 CFM/ 15.0 TR/30 mm (SP)
CSU DP-19-5500 CFM/ 18.0 TR/30 mm (SP)
Supply, installation, testing and commissioning of factory built double skin type floor mounted/ Ceiling Suspended air handling unit(fan section only) made of 25 mm thick panels consisting of pre plasticized G.I. casing of thickness 0.6 mm outside layer and 0.6mm thick min. plane GI inside layer with polyurethane foam (PUF) insulation of density 40 ± 2 kg/m3 factory injected between them by injection moulding machine, complete with blower section with blower DIDW forward curved centrifugal fan , vibration isolators and fire retardant canvass connection , squirrel cage induction motor belt driven package with TEFC drive motor (IE-3), mounted within the housing and all other accessories etc. complete as required confirming to specification. Fan section shall be of suitable Static pressure as required & supplied with 50 mm thick washable synthetic type air filters ( with supply air fans only) having efficiency 90% down to 10 micron with extruded aluminium frame. The fan motor shall be suitable for 415 ± 10% Volts, 50Hz, AC power supply.
For Supply
20000 CFM/30 mm SP
18000 CFM/30 mm SP
4500 CFM/30 mm SP
For Exhaust
2500 CFM/20 mm SP
2000 CFM/20 mm SP
Supply, Installation, testing & commissioning of horizontal FAN COIL UNITS (2 PIPE SYSTEMS), blow through type, with centrifugal fan, 3 speed motor, 3 rows cooling coil section, cleanable synthetic media filters, SS condensate drain pan with 9mm thick nitrile rubber insulation, GI casing with insulation, coil connections through copper pipes, condensate drain connections, wiring, control wiring in conduit up to thermostat boxes mounted on wall, Anchors, Hangers, Vibration isolators, fire rated flexible connection at blower discharge, air vent, ball valve set with and without Y-strainer , cooling thermostat with three speed controller for blower motor. Fan coil unit shall be provided with valve package comprising of pressure independent Balancing cum Control Valve with integrated 2 way motorized actuator in a single body for modulating operation suitable for static pressure of 1600 kPa and actuator shall be capable of withstanding 400 kPa shut off pressure, suitable for 24 V AC incoming power supply. Fan coil unit shall be suitable for 230 ± 10% 50 Hz single phase power supply. Thermostat will be mounted on the wall at suitable location. Internal wiring between FCU and thermostat shall be included.
1.0 TR nominal capacity - 400 CFM
1.5 TR nominal capacity - 600 CFM
2.0 TR nominal capacity - 800 CFM
3.0 TR nominal capacity - 1200 CFM
1.5 TR nominal capacity - 600 CFM ( High static Type)
2.5 TR nominal capacity - 1000 CFM ( High static Type)
3.0 TR nominal capacity - 1200 CFM ( High static Type)
Supply, installation, testing and commissioning of the Ceiling mounted 4-way directional air discharge Hydroid Cassette units with centrifugal fan, 3 speed motor, 3 rows cooling coil section, cleanable synthetic media filters, SS condensate drain pan with 9mm thick nitrile rubber insulation, powder coated galvanized steel housing, coil connections through copper pipes, condensate drain connections, wiring, control wiring in conduit up to thermostat boxes mounted on wall, Anchors, Hangers, ball valve set with and without strainer, cooling thermostat with three speed controller for blower motor. The unit shall be provided with valve package comprising of pressure independent Balancing cum Control Valve with integrated 2 way motorized actuator in a single body for modulating operation suitable for static pressure of 1600 kPa and actuator shall be capable of withstanding 400 kPa shut off pressure, suitable for 24 V AC incoming power supply. Fan coil unit shall be suitable for 230 ± 10% 50 Hz single phase power supply. Thermostat will be mounted on the wall at suitable location. Internal wiring between FCU and thermostat is included.
1.0 TR nominal capacity - 400 CFM
VARIABLE REFRIGERANT FLOW SYSTEM
Supply, Installation, Testing and Commissioning of Variable Refrigerant Flow type multi unit air-conditioning system complete with indoor and outdoor units with individual controller for cooling & heating application as per the specifications and drawings.
OUTDOOR UNITS
Supply, Installation, Testing and Commissioning of air cooled variable refrigerant flow modular type outdoor units, each comprising of energy efficient multiple scroll compressors, topping up of R410A refrigerant gas and all accessories as per the specifications. The condensing units shall be suitable to work on cooling as well as heating mode. The condensing units shall be suitable for operation on 415 ±10% volts, 50Hz, 3 phase AC power supply and complete with auto check function for connection error, auto address setting, etc. The outdoor units shall be low noise type. The outdoor units shall be of following capacities :
14 HP nominal capacity high COP outdoor unit comprising of 1 modules of requisite capacity.
INDOOR UNITS
Supply, Installation, testing and commissioning of following type of Indoor Units for variable refrigerant Volume/ flow air-conditioning system suitable for 220 ± 10 % volt, 50 Hz, 1 phase AC supply equipped with pre-filter, fan section with low noise fan, multispeed motor, coil section, internally insulated outer cabinet, insulated drain pan, insulation, pipe connections etc. complete with PVC insulated FRLS copper conductor electric wire upto 1.5 metre length & sockets etc. as per specifications and as required.
Ceiling Mounted Type 4-way Cassette Unit with cordless remote control, drain pump complete with fittings etc.
Wall Mounted Type Hi-wall Units with cordless remote control complete with fittings etc.
Supply, Installation, testing and commissioning of necessary fittings, Y-joints and headers etc.
Supplying, fixing, testing and commissioning of Main centralized controller Push Button Type suitable for groups of indoor units to be installed for control. (BMS Compatible)
Providing, fixing, testing and commissioning of Cassette type split air-conditioning unit for cooling application suitable to operate from 230±10% volt, 50 Hz, 1 phase power supply, with air-cooled evaporator with coil, fan, and fan motor, air-cooled condenser with hermetically sealed Rotary compressor ,condenser coil, propeller fans controls, control panel, Including control wiring, necessary power cable & plug to connect with electrical power, refrigerant piping (Including full circuit of refrigerant pipe and control cabling upto 5 metre length), including gas charging, M.S. frame duly painted to locate Outdoor Unit etc. The Unit should be at least 5 Star rated (on the date of procurements the minimum EER value of the units should be as per BEE Standard ). The Refrigerant pipe size and gas quantity should suit to the copper pipe length at actual.
1.5 TR Cassette Units
Refrigerant Piping Supply & Installation of interconnecting following sizes of one end expanded refrigerant copper pipe work of following outer diameter, insulated with 19/13 mm thick insulation (as per Specifications) between each set of indoor & outdoor units with outer mechanical protection of aluminium cladding for all exposed pipes as per specification. All piping inside the room shall be properly fixed/supported with suitable size of clamp/ M.S. hanger and all external piping shall run in M.S. painted cable tray (separate item) etc. as reqd.
28.6 mm dia with 19mm thick insulation (As per Specifications)
15.9 mm dia with 13mm thick insulation (As per Specifications)
12.7 mm dia with 13mm thick insulation (As per Specifications)
9.5 mm dia with 13mm thick insulation (As per Specifications)
VARIABLE FREQUENCY DRIVE: Supply, Installation, testing & commissioning of HVAC dedicated VFDs with minimum IP 55 enclosures & disconnect, complying with the tender specifications and having: i) - THiD less than 5% ii) - EMC filter category - C1 iii) - PID controller feedback loops - 1 The system shall be complete in all respects and suitable for following motor rating:
Dedicated Outdoor air tempering and Heat recovery Heat Pipe system:
Supply, Installation, testing and commissioning of double skin blow through / draw through type, two tier DEDICATED OUTDOOR AIR UNIT with supply, exhaust air fans, motors and drive sets, Heat recovery Heat Pipe (Total Thermal Efficiency of Heat Pipe unit 75%.) complete with all sections , BMS and VFD compatible squirrel cage induction motor (as per ASHRAE standard 90.1-2016)and high efficiency (IE3) , centrifugal fan , Direct/belt drive package and vibration isolation (spring mounted). MERV-8 filter all accessories for the following capacity . The unit shall be suitable for outdoor condition (with a mixing box, as per specifications).
Supply air Section shall comprise of Fresh air inlet damper and space provision for Electronic Air Cleaner in supply air stream. Filters shall be sized for air velocity of 500 fpm. Supply air backward curved fans shall be with efficiency >70%.
Return air stream shall comprise of Return air inlet damper, Pre filter (MERV 8) in return air stream. Filters shall be sized for air velocity of 500 fpm. Return air backward curved fans shall be with efficiency >70%.
Duty conditions and design parameters are as under, and the DOAS with Heat recovery Heat pipe system shall be designed for giving output of DBT=50 F, & gr/ lbs = 54 for Summer & Monsoon conditions of the geographical and ambient weather conditions of the project.
Geographical Location and design ambient conditions of Tiruchirappalli Outdoor Design Conditions: Summer Dry Bulb Temperature : 40.0 Deg.C (104.0 Deg. F) Wet Bulb Temperature : 25.8 Deg.C (78.4 Deg. F) Monsoon Dry Bulb Temperature : 35.0 Deg. C (95.0 Deg. F) Wet Bulb Temperature : 27.8 Deg. C (82.0 Deg. F)
HRU-1 Supply air quantity : 16800 CFM , 75 mm SP WG Exhaust air quantity : 11000 CFM , 50 mm SP WG Return air temp. ~ 24Deg.C & 60% RH
HRU-2 Supply air quantity : 21500 CFM , 75 mm SP WG Exhaust air quantity : 16000 CFM , 50 mm SP WG Return air temp. ~ 24Deg.C & 60% RH
HRU-3 Supply air quantity : 13400 CFM , 75 mm SP WG Exhaust air quantity : 10500 CFM , 50 mm SP WG Return air temp. ~ 24Deg.C & 60% RH
PRESSURE INDEPENDENT MOTORIZED BALANCING CUM CONTROL VALVE ( FOR COOLING APPLICATION): Supply, installation, testing & commissioning of following sizes insulated electronic, self-balancing, pressure independent type dynamic balancing valve with integrated 2 way modulating control valve in a single body. The actuator shall be capable of accepting upto 10V DC and upto 20 mA electric signal and shall provide similar transduced feedback output to control system. Maximum close off pressure shall not be less than 6 Bar for upto 50 mm valves and 7 Bar for 65 mm & above. Valves should have pressure rating of 16 Bar minimum. The valves & actuators for AHU’s units shall be compatible with Building Automation System.
100 mm dia Valves
80 mm dia Valves
65 mm dia Valves
50 mm dia Valves
40 mm dia Valves
32 mm dia Valves
THERMOSTAT ( FOR COOLING ONLY) : Supply, installation, testing and commissioning of THERMOSTAT for cooling application. The thermostat shall be electronic room temperature controller with digital display , capable of providing individual space temperature control for cooling application. The controller shall produce a single output to cooling coils in response to load change in rooms. The controller shall be designed to modulate the control devices installed in chilled water system.
EVAPORATIVE COOLING SYSTEM (FILL TYPE) : Supplying, installing, testing and commissioning of floor mounted CELLULOSE FILL AIR-WASHER complete with double skin construction fabricated out of extruded aluminium sections with 0.8 mm thick pre-plasticised GI sheet on out side and 0.8 mm thick plane GI sheet inside with 25 mm thick insulation, 40 Kg/m3 density PUF insulation in between. The unit shall comprise of supply fan sections with DIDW backward curve fans (efficiency not less than 75%) suitable for static pressure as required, belt drive package with TEFC drive motor of efficiency class IE3 (as per IS 12615) suitable for 415 ± 10% V, 50Hz, 3 Phase AC supply, giving 95% adiabatic saturation efficiency at 500 FPM air velocity across pads, factory assembled and complete with 16 gauge GI casing for Air washer section, 18G SS-304 water tank, Cellulose fill, water distribution header, PVC piping, butterfly valves, for quick fill, isolation of tank, pumps and brass strainers, Y strainers, fire rated flexible duct connections & aluminium volume control damper at blower discharge and necessary fittings, belt drive package, necessary vibration isolation arrangement etc. complete as per specification and of following capacities. The fan and motor shall be mounted on aluminium extruded section. The quoted price shall also include provision of GSS partitions duly reinforced at intake side of air washer and GSS louvers with bird-screen synthetic washable filters and four bend PVC drift eliminators. The price shall also include horizontal monoblock pumps of suitable rating, factory mounted on mild steel channel base with electric motor for circulation of water. Pumps shall be aligned and suitable for 415±10% volts, 50 cycles 3 phase power supply. One No. 3 phase isolator switch in weather proof enclosure shall be provided near motor.
WTP,STP & HVAC Plant Room : 36,000 CFM, SP= 50 mm wg
BASEMENT VENTILATION SYSTEM
Supply, installation, testing and commissioning of BASEMENT VENTILATION SYSTEM comprising of supply air fans, exhaust air fans, CO sensors, and controls for Normal mode and Emergency mode operation.
The contractor shall provide a turn key ventilation system in accordance with NBC-2016.
The system shall serve both CO-evacuation and smoke extract function. The contractor shall provide a full engineering proposal that includes the information for review by the Consultant as described in Specifications. The rating of main intake & exhaust fans shall be as follows:
Supplying, installation, testing and commissioning of AMCA Certified (For Air and Sound Performance) ceiling hung / floor mounted vane/tube axial flow fans of following capacity with GSS casing/ standard M.S. construction and aluminium alloy impellers with high efficiency aero-foil sections, blades, the impeller directly driven by TEFC induction motor should be of high efficiency class IE3 (for Normal Mode Supply and Exhaust Fans) and IE2 (for Fire Mode Supply and Exhaust Fans) suitable for 3 Phase 50 Hz 415V ± 10 %, of class 'F' insulation(for Supply Air Fans) and class 'H' insulation(for Exhaust Fans), fire rated flexible connection etc. including all accessories complete as required and as per specifications. Motor of exhaust fans shall be of high temperature resistance "Class H Smoke Spill" 250° C for 2 hrs. Motor make shall be same as mentioned on the fire certificate. Fan total efficiency should not be less than 70%. All the fans shall be hot dip galvanized with minimum 220 GSM Zinc Coating and complete with bird screen at inlet. Suitable TP isolator within MS enclosure should be provided. Gravity louvers will be provided at the discharge of the fan so as to avoid reverse flow. Entire fan model & AMCA Seal shall appear in technical submittal of fan.
The fans operating under normal modes shall have low sound level not exceeding more than 75 dB(A)at three meter distance at both ends when measured in hemispherical reverberant room conditions. To achieve specified dB(A) level sound attenuators shall be provided at inlet / outlet and included in the cost. The fans operating under emergency modes shall have sound level not exceeding more than 85 dB(A) at three meter distance at both ends when measured in hemispherical reverberant room conditions. Static pressure of Fans shall be checked by Vendor/Contractor prior to supply of Fans as per site condition. If there is any discrepancy against the BOQ, the Vendor/Contractor has to take approval from Client / PMC, and nothing extra shall be paid.
Air moving capacity shall be as follows:
Exhaust Air Fans (Normal Mode: IE3, Class H)
33000 CFM, SP= 25 mm wg
35500 CFM, SP= 25 mm wg
37500 CFM, SP= 25 mm wg
41500 CFM, SP= 25 mm wg
42500 CFM, SP= 25 mm wg
Exhaust Air Fans (Fire Mode: IE2, Class H)
33000 CFM, SP= 25 mm wg
35500 CFM, SP= 25 mm wg
37500 CFM, SP= 25 mm wg
41500 CFM, SP= 25 mm wg
42500 CFM, SP= 25 mm wg
Supply Air Fans (Normal Mode: IE3, Class F)
33000 CFM, SP= 25 mm wg
35500 CFM, SP= 25 mm wg
37500 CFM, SP= 25 mm wg
41500 CFM, SP= 25 mm wg
42500 CFM, SP= 25 mm wg
Supply Air Fans (Fire Mode: IE2, Class F)
33000 CFM, SP= 25 mm wg
35500 CFM, SP= 25 mm wg
37500 CFM, SP= 25 mm wg
41500 CFM, SP= 25 mm wg
42500 CFM, SP= 25 mm wg
CO Sensor:
Supply, installation, testing and commissioning of Carbon monoxide sensors comprising of a carbon monoxide meter and a 0-10 VDC transmitter an all electronic system that utilizes a microprocessor to measure carbon monoxide (CO), calculate various calibration factors and analog output. The sensor shall average samples over a time period and update the output every 2 ½ minutes. The sensor is intended to be used in enclosed basement, where it shall provide CO data to building automation computers or controllers. A box shall house the sensor and provide an easy-to-mount, sturdy housing for the system. Sensors shall be mounted on walls or columns about 1600 mm above the floor. Sensors shall be evenly spaced and not put in corners, or directly in front of air inlets. Each sensor must have a cable directly to the control panel.
Control Panels:
Supply, installation, testing and commissioning of stand alone intelligent PLC control system for both CO monitoring and smoke control. The basement shall have individual PLC Control Panel. The PLC control system shall control all exhaust & supply air fans located in basement. The broad logic shall be as follows: PLC based Logic panel shall be provided to receive signals from the Carbon Monoxide Detector panel and the Fire Control Panel which will contain DDC (Direct Digital Controller) to give command to Supply and Exhaust fans for their operation on the basis of the logic provided to the PLC panel as detailed in the specification.
EXHAUST AIR AXIAL FLOW FANS(FIRE MODE) : Supplying, installation, testing and commissioning of AMCA Certified (For Air and Sound Performance) ceiling hung / floor mounted exhaust air vane/tube axial flow fans of following capacity with GSS casing/ standard M.S. construction and aluminium alloy impellers with high efficiency aero-foil sections, blades, the impeller directly driven by TEFC induction motor should be of high efficiency class IE2 (as per IS 12615) suitable for 3 Phase 50 Hz 415V ± 10 %, of class 'H' insulation, fire rated flexible connection etc. including all accessories complete as required and as per specifications. Motor shall be of high temperature resistance "Class H Smoke Spill" 250° C for 2 hrs. (UL/CE Listed) Motor make shall be same as mentioned on the fire certificate. Fan total efficiency should not be less than 70%, noise level should not be more than 85 db @ 3 m distance when measured in hemispherical reverberant room conditions. All the fans shall be hot dip galvanized with minimum 220 GSM Zinc Coating and complete with bird screen at inlet. Suitable TP isolator within MS enclosure should be provided. Gravity louvers will be provided at the discharge of the fan so as to avoid reverse flow. Static pressure of Fans shall be checked by Vendor/Contractor prior to supply of Fans as per site condition. If there is any discrepancy against the BOQ, the Vendor/Contractor has to take approval from Client / PMC, and nothing extra shall be paid. Entire fan model & AMCA Seal shall appear in technical submittal of fan. Air moving capacity shall be as follows:
50000 CFM, SP= 20 mm wg
45000 CFM, SP= 20 mm wg
11000 CFM, SP= 20 mm wg
10000 CFM, SP= 20 mm wg
8500 CFM, SP= 20 mm wg
5500 CFM, SP= 20 mm wg
4000 CFM, SP= 20 mm wg
SUPPLY AIR AXIAL FLOW FANS(FIRE MODE) : Supplying, installation, testing and commissioning of AMCA Certified (For Air and Sound Performance) ceiling hung / floor mounted supply air vane/tube axial flow fans of following capacity with GSS casing/ standard M.S. construction and aluminium alloy impellers with high efficiency aero-foil sections, blades, the impeller directly driven by TEFC induction motor should be of high efficiency class IE2 (as per IS 12615) suitable for 3 Phase 50 Hz 415V ± 10 %, of class 'F' insulation, fire rated flexible connection etc. including all accessories complete as required and as per specifications. Fan total efficiency should not be less than 70 %, noise level should not be more than 85 dB(A) @ 3 m distance when measured in hemispherical reverberant room conditions. All the fans shall be hot dip galvanized with minimum 220 GSM Zinc Coating and complete with bird screen at inlet. Suitable TP isolator within MS enclosure should be provided. Gravity louvers will be provided at the discharge of the fan so as to avoid reverse flow. Static pressure of Fans shall be checked by Vendor/Contractor prior to supply of Fans as per site condition. If there is any discrepancy against the BOQ, the Vendor/Contractor has to take approval from Client / PMC, and nothing extra shall be paid. Entire fan model & AMCA Seal shall appear in technical submittal of fan. Air moving capacity shall be as follows:
50000 CFM, SP= 20 mm wg
10000 CFM, SP= 20 mm wg
8500 CFM, SP= 20 mm wg
4000 CFM, SP= 20 mm wg
SUPPLY AIR AXIAL FLOW FANS(FOR PRESSURISATION) : Supplying, installation, testing and commissioning of AMCA Certified (For Air and Sound Performance) ceiling hung / floor mounted supply air vane/tube axial flow fans of following capacity with GSS casing/ standard M.S. construction and aluminium alloy impellers with high efficiency aero-foil sections, blades, the impeller directly driven by TEFC induction motor should be of high efficiency class IE2 (as per IS 12615) suitable for 3 Phase 50 Hz 415V ± 10 %, of class 'F' insulation, fire rated flexible connection etc. including all accessories complete as required and as per specifications. Fan total efficiency should not be less than 70 %, noise level should not be more than 85 dB(A) @ 3 m distance when measured in hemispherical reverberant room conditions. All fans shall be hot dip galvanized with minimum 220 GSM Zinc Coating and complete with bird screen at inlet. Suitable TP isolator within MS enclosure should be provided. Gravity louvers will be provided at the discharge of the fan so as to avoid reverse flow. Static pressure of Fans shall be checked by Vendor/Contractor prior to supply of Fans as per site condition. If there is any discrepancy against the BOQ, the Vendor/Contractor has to take approval from Client / PMC, and nothing extra shall be paid. Entire fan model & AMCA Seal shall appear in technical submittal of fan. Air moving capacity shall be as follows:
20000 CFM, SP= 20 mm wg
11000 CFM, SP= 20 mm wg
10000 CFM, SP= 20 mm wg
SUPPLY AIR AXIAL FLOW FANS(FOR BASEMENT/ SERVICE YARD) : Supplying, installation, testing and commissioning of AMCA Certified (For Air and Sound Performance) ceiling hung / floor mounted supply air vane/tube axial flow fans of following capacity with GSS casing/ standard M.S. construction and aluminium alloy impellers with high efficiency aero-foil sections, blades, the impeller directly driven by TEFC induction motor should be of high efficiency class IE3 (as per IS 12615) suitable for 3 Phase 50 Hz 415V ± 10 %, of class 'F' insulation, fire rated flexible connection etc. including all accessories complete as required and as per specifications. Fan total efficiency should not be less than 70 %, noise level should not be more than 75 dB(A) @ 3 m distance when measured in hemispherical reverberant room conditions. All the fans shall be hot dip galvanized with minimum 220 GSM Zinc Coating and complete with bird screen at inlet. Suitable TP isolator within MS enclosure should be provided. Gravity louvers will be provided at the discharge of the fan so as to avoid reverse flow. Static pressure of Fans shall be checked by Vendor/Contractor prior to supply of Fans as per site condition. If there is any discrepancy against the BOQ, the Vendor/Contractor has to take approval from Client / PMC, and nothing extra shall be paid. Entire fan model & AMCA Seal shall appear in technical submittal of fan. To achieve specified dB(A) level sound attenuators shall be provided at inlet / outlet and included in the cost. Air moving capacity shall be as follows:
11000 CFM, SP= 20 mm wg
3000 CFM, SP= 20 mm wg
2500 CFM, SP= 20 mm wg
EXHAUST AIR AXIAL FLOW FANS(FOR BASEMENT/ SERVICE YARD) : Supplying, installation, testing and commissioning of AMCA Certified (For Air and Sound Performance) ceiling hung / floor mounted exhaust air vane/tube axial flow fans of following capacity with GSS casing/ standard M.S. construction and aluminium alloy impellers with high efficiency aero-foil sections, blades, the impeller directly driven by TEFC induction motor should be of high efficiency class IE3 (as per IS 12615) suitable for 3 Phase 50 Hz 415V ± 10 %, of class 'H' insulation, fire rated flexible connection etc. including all accessories complete as required and as per specifications. Motor shall be of high temperature resistance "Class H Smoke Spill" 250° C for 2 hrs. (UL/CE Listed) Motor make shall be same as mentioned on the fire certificate. Fan total efficiency should not be less than 70%, noise level should not be more than 75 db @ 3 m distance when measured in hemispherical reverberant room conditions. All the fans shall be hot dip galvanized with minimum 220 GSM Zinc Coating and complete with bird screen at inlet. Suitable TP isolator within MS enclosure should be provided. Gravity louvers will be provided at the discharge of the fan so as to avoid reverse flow. Static pressure of Fans shall be checked by Vendor/Contractor prior to supply of Fans as per site condition. If there is any discrepancy against the BOQ, the Vendor/Contractor has to take approval from Client / PMC, and nothing extra shall be paid. Entire fan model & AMCA Seal shall appear in technical submittal of fan. To achieve specified dB(A) level sound attenuators shall be provided at inlet / outlet and included in the cost. Air moving capacity shall be as follows:
20000 CFM, SP= 20 mm wg
18000 CFM, SP= 20 mm wg
11000 CFM, SP= 20 mm wg
10000 CFM, SP= 20 mm wg
4500 CFM, SP= 20 mm wg
3000 CFM, SP= 20 mm wg
2500 CFM, SP= 20 mm wg
INLINE FANS : Supply of INLINE FANS AMCA Certified (For Air and Sound Performance) suitable for installing in any position in vertical or horizontal ducts. The casing shall be double skin, internally acoustically lined and constructed of galvanised steel. The inline fan shall be with backward/forward curve centrifugal impeller fitted with maintenance free external rotor motor, flexible connections at the discharge & inlet. The motor shall be suitable for 220±10% volt single phase 50 cycles AC supply. Quoted price shall be inclusive of electronic speed regulator and wiring between fan & speed regulator for single phase fans. Incase of 3 phase fans quoted price shall be inclusive of DOL starter panel with cabling between starter panel and fan. The incoming power supply to speed regulator / starter panel shall be provided by electrical contractor. The fan shall have low sound level exceeding not more than 55 DBA at three meter distance.
1200 CFM/15 mm SP (Box Type)
1000 CFM/15 mm SP (Box Type)
600 CFM/15 mm SP (Box Type)
400 CFM/10 mm SP
Installing, testing & commissioning of INLINE FANS as mentioned above, as per specifications and complete as required.
1200 CFM/15 mm SP (Box Type)
1000 CFM/15 mm SP (Box Type)
600 CFM/15 mm SP (Box Type)
400 CFM/10 mm SP
PROPELLER FANS : Supplying, installing, testing and commissioning of direct driven PROPELLER FANS for exhaust air as shown in drawings. Each fan shall be complete with permanent split capacitor or shaded pole motor, mounting plate, accessories like wire guard, bird screen and fixed louvers for weather protection as required. The Motor shall be suitable to run on 1 Phase /50 Hz /220 V electrical power.
300 mm dia
ELECTRONIC AIR CLEANER SYSTEM Supply of electronic air cleaner a hybrid air purification system that improves the indoor air quality through reducing harmful pollutants like particulate matter (PMx), PM 2.5, allergens, pollen, smoke, bacteria, pathogens based on Electrostatic precipitation technology. Other forms of air filtration systems such as charged media filters, dielectric media filters, or ionizers (which do not have second stage collector plates) shall not be acceptable. It should be a monobloc structured unit specifically designed for integration in Return Air path of the AHU, to centrally capture the pollutants. It should be equivalent to MERV14 efficiency @ 1708 cfm with low pressure drop of not more than 65Pa @ 492fpm (certification for the same to be provided). It should be UL certified with in built provision to connect to BMS. The product has to be certified as a green product by any of the Green Building councils across the world . The central air cleaner units must have a valid ANSI/ASHRAE 52.2 test report to verify filtration efficiency. The unit must have factory test report to ensure that it meets the following safety and environmental criteria with reference to ES164468, UL 867 and DA 6.2.1. Ozone level of units provided must be within the acceptable limit of 0.05ppm. The units shall have local LEDs at each individual unit to indicate when the units are up for wash/malfunctioning complete as required and as per technical specifications.
Capacity 1708 CFM having minimum dimension 670mm X 610 mm
Capacity 854 CFM having minimum dimension 610mm X 350 mm
Installation, testing and commissioning of electronic air cleaner complete as required and as per technical specifications.
Capacity 1708 CFM having minimum dimension 670mm X 610 mm
Capacity 854 CFM having minimum dimension 610mm X 350 mm
Flush-Mount, 220V/50Hz, 2 cells, remote control, max. 875CFM each unit
Flush-Mount, 220V/50Hz, 1 cell , remote control, max. 460CFM each unit
Installation, testing and commissioning of flush-Mount Commercial Electronic Air Cleaner complete as required and as per technical specifications.
Flush-Mount, 220V/50Hz, 2 cells, remote control, max. 875CFM each unit
Flush-Mount, 220V/50Hz, 1 cell , remote control, max. 460CFM each unit
CHILLED/CONDENSER WATER PIPING: Supplying, laying, fixing, testing and commissioning of following nominal sizes of chilled /condenser water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.)
Note:-The Pipes of sizes 150 mm & below shall be M.S. ‘C’ class as per IS: 1239 and pipes size above 150 mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia. and above. SMACNA Certified wire rope hangers system as per specifications with lock(s) and pre-crimped end fixing(s) to be used for supporting all pipes. For safety, the lock should not have inbuilt unlocking mechanism; separate key to be used to unlock it. To avoid wire slippage, locking mechanism should be wedge type, self locking and double channel type. Ball bearing(s) based or circular gear(s) based locking mechanisms are not acceptable. The wire rope hangers should have a minimum safety factor of 5:1. Additional pipe supports (50 mm dia. and Above) shall be provided as per specifications to handle the load and also to take into account seismic considerations. Support system should be as per specifications.
700 mm dia.
600 mm dia.
500 mm dia.
450 mm dia.
400 mm dia.
350 mm dia.
300 mm dia.
250 mm dia.
200 mm dia.
150 mm dia.
125 mm dia.
100 mm dia.
80 mm dia.
65 mm dia.
50 mm dia.
40mm dia.
32 mm dia.
25 mm dia.
20 mm dia.
INSULATED VALVES: Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water piping duly insulated to the same specifications as the connected piping and adequately supported as per specifications. MANUAL BUTTERFLY VALVES: Supplying, fixing, testing and commissioning of BUTTERFLY VALVE (MANUAL) with CI body SS Disc, Nitrile Rubber Seal & O-Ring, PN-16 pressure rating for chilled water circulation as specified
600 mm dia.
300 mm dia.
250 mm dia.
200 mm dia.
150 mm dia.
125 mm dia.
100 mm dia.
80 mm dia.
65 mm dia.
50 mm dia.
INSULATED VALVES: Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water piping duly insulated to the same specifications as the connected piping and adequately supported as per specifications. MOTORIZED BUTTERFLY VALVES: Supplying, fixing, testing and commissioning of following sizes motorized butterfly valve with CI Body, SS Disc, O-ring and minimum PN-16 pressure rating, conforming to BS 5155, IS 13095, with IP-55 actuator, capable of accepting upto 10V DC, & upto 20 mA electric signal and providing similar transduced feedback output to control system as required. (Third party BMS compatible) 300 mm
INSULATED VALVES: Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water piping duly insulated to the same specifications as the connected piping and adequately supported as per specifications. BALANCING VALVE: Supplying, fixing, testing and commissioning of BALANCING VALVE WITH BUILT IN MEASURING FACILITY with C I body flanged construction with EPDM coated disc with long pitch with protected out pipe insulation & PN 16 pressure rating for chilled water circulation as specified.
300 mm dia.
250 mm dia.
200 mm dia.
150 mm dia.
125 mm dia.
100 mm dia.
80 mm dia.
INSULATED VALVES: Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water piping duly insulated to the same specifications as the connected piping and adequately supported as per specifications. NON RETURN VALVE: Supplying & fixing in position of NON - RETURN VALVE with duel plate of C I body SS plates vulcanized NBR seal flanged end & PN 16 pressure rating for chilled water circulation including insulation as specified.
300 mm dia.
INSULATED VALVES: Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water piping duly insulated to the same specifications as the connected piping and adequately supported as per specifications. Y - STRAINER: Supplying & fixing in position of Y - STRAINER of Ductile CI Body flanged ends with stainless steel strainer for chilled water circulation including insulation as specified.
300 mm dia.
100 mm dia.
80 mm dia.
65 mm dia.
50 mm dia.
INSULATED VALVES: Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water piping duly insulated to the same specifications as the connected piping and adequately supported as per specifications. BALL VALVE WITH & WITHOUT STRAINER: BALL VALVE set with & without strainer having bronze body, flanged end type, PN 16 pressure rating for chilled water circulation as specified. confirming to technical specification including nut, bolts washer, gaskets etc.
40 mm dia.
32 mm dia.
Providing & fixing in position Binder test points at chilled water pipelines i.e. inlet & outlet of air handling units.
AUTO AIR VENTS: Supply, installation, testing and commissioning of Auto air vents valve 25mm dia. conforming to technical specification including nut, bolts washer, gaskets etc.
FLEXIBLE CONNECTIONS : Supplying, fixing, testing and commissioning of Flexible connector for following Dia. pipe having PN 16 working pressure with anti vacuum rings complete with flanges, nuts, bolts, seal etc.to be installed at chillers, primary & secondary pumps suction and discharge.
300 mm dia.
350 mm dia.
VALVES WITHOUT INSULATION: Supplying, fixing, testing & commissioning of following valves, gauges & strainers for condenser water circulation as per specifications. MANUAL BUTTERFLY VALVES: BUTTERFLY VALVE (MANUAL) with CI body SS disc nitrile sheet & O - ring & PN 16 pressure rating as specified.
350 mm dia.
250 mm dia.
200 mm dia.
150 mm dia.
80 mm dia.
50 mm dia.
VALVES WITHOUT INSULATION: Supplying, fixing, testing & commissioning of following valves, gauges & strainers for condenser water circulation as per specifications. MOTORIZED BUTTERFLY VALVES: Supplying, fixing, testing and commissioning of following sizes Motorized Butterfly Valve with CI Body, SS Disc, O - ring and minimum PN-16 pressure rating, conforming to BS 5155, IS 13095, with IP-55 actuator, capable of accepting upto 10V DC, and upto 20 mA electric signal and providing similar transduced feedback output to control system as required. (Third party BMS compatible)
350 mm dia.
VALVES WITHOUT INSULATION: Supplying, fixing, testing & commissioning of following valves, gauges & strainers for condenser water circulation as per specifications. BALANCING VALVE: BALANCING VALVE WITH BUILT IN MEASURING FACILITY with C I body flanged construction with EPDM coated disc with long pitch with protected out pipe insulation & PN 16 pressure rating for chilled water circulation as specified.
350 mm dia.
VALVES WITHOUT INSULATION: Supplying, fixing, testing & commissioning of following valves, gauges & strainers for condenser water circulation as per specifications. NON - RETURN VALVE: NON - RETURN VALVE with dual plate of CI body SS plates vulcanized NBR seal flanged end & PN 16 pressure rating as specified. 350 mm
VALVES WITHOUT INSULATION: Supplying, fixing, testing & commissioning of following valves, gauges & strainers for condenser water circulation as per specifications. Y - STRAINER: Y - STRAINER of Ductile CI Body flanged ends with stainless steel strainer circulation including insulation as specified. 350 mm
VALVES WITHOUT INSULATION: Supplying, fixing, testing & commissioning of following valves, gauges & strainers for condenser water circulation as per specifications. BALL VALVE: BALL VALVE with bronze body , flanged end type, PN 16 pressure rating for chilled water circulation as specified. Confirming to technical specification including nut, bolts washer, gaskets etc.
40 mm dia.
32 mm dia.
25 mm dia.
GI DRAIN PIPES: Supplying, fixing, testing and commissioning of medium class GI condensate drain pipes on wall of following size duly insulated with upto 50 mm dia. 9 mm thick & above 50 mm dia. 19 mm thick closed cell nitrile rubber insulation in the form of pre-formed pipe sections and along with necessary clamps, fittings such as bends, tees etc. adequately supported as per specifications and as required.
50 mm dia.
40 mm dia.
32 mm dia.
25 mm dia.
20 mm dia.
UPVC DRAIN PIPES: Providing and fixing in position the following Rigid UPVC pipes for condensate drain with upto 50 mm dia. 9 mm thick & above 50 mm dia. 19 mm thick insulation (as per specifications) tubing secured with adhesive as per approved specification cut to required length, including the necessary fittings, supports as per specifications.
25 mm dia. with 9 mm thick insulation
20 mm dia. with 9 mm thick insulation
PRE-INSULATED CHILLED WATER PIPE
Supply, laying ,fixing in position in the trench and testing of Pre insulated chilled water pipe. Pre insulated chilled water pipe shall have all straight sections, fittings, elbows, anchors and other accessories factory fabricated, insulated and jacketed. The service pipe upto 6" shall be MS ERW pipes Class 'C' as per IS 1239 standard & above 6" shall be MS ERW pipes as per IS 3589 standard. Elbows, tees, reducers, anchors, field joints and end seals shall be designed and factory fabricated to prevent the ingress of moisture into the system. The service pipe insulation shall be polyurethane foam, for pipe sizes 125 mm and larger, the insulation shall be applied by spraying the foam directly onto the pipe and extruding the HDPE jacket directly on top of the foam having wind-down end seal. Metal diffusion barrier shall be applied between the outer surface of the insulation and the jacketing material so as to eliminate the effect of reduced insulation properties to aging. The insulation shall be bonded to the service pipe & outer HDPE jacket. The Insulation shall have minimum density 48 kg/m3, minimum compressive strength of 300 kPa, max thermal conductivity of 0.023 W/mk at 25 Deg. C, 88% min closed cell content & water absorption less than 10%. The minimum HDPE jacket thickness shall be 3mm for pipe size up to 500mm.The service pipe shall be hydrostatically tested to 150 psig or 1.5 times the design pressure whichever is greater. Excavation of trench, preparation of bedding with 4 inch layer of sand or fine gravel, preparation of PCC pedestal on top of compacted sand or fine gravel and backfilling with a similar material as the bedding in 6 inch compacted layers above the top of the insulated pipe and then with the excavated soil.
80 mm dia. pipes with 25mm insulation
Dirt Separator Supply, installation, Testing and commissioning of Dirt separator In-line for removal of dirt particles within chilled water system. The acceptable design shall incorporate a separating element to force water into tranquillity zones for dirt removal or a tube mesh construction made of copper wire and the flow to be guided through an area with a greater cross-section than the connection dimensions in order to reduce the flow. Dirt particles shall be removed via a valve on the base of the vessel whilst ferrous particles down to 4 µm shall be captured by a magnetic device. It shall be able to remove 5 µm dirt particles. The magnet shall be retractable to enable ferrous particles to be released and discharged through the drain valve. Dirt separator shall be manufactured and designed in accordance with Pressure Equipment Directive PED 97/23/EC or 2014/68/EU. The cylindrical vessel shall be manufactured from welded steel. Inlet and outlet of the unit shall be via horizontally-opposed, coaxial flanged connections in accordance with PN 10. Temperature range -10 C to 110 C The maximum permissible flow velocity shall be 3 m/s. The Dirt Separator shall be sized appropriate to the maximum operating pressure and flow velocity of the system. Given System Flow 8000 USGPM. Inlet and outlet of the unit (Dia-600 mm).
Installation, testing and commissioning of Dirt separator In-line for removal of dirt particles complete as required and as per technical specifications.
Twin Pump Pressurisation Unit with Pressureless Expansion tank with built-in De-aerator & automatic water makeup:
Supply of pressurization system comprising pressureless expansion tank, twin pump pressurization unit, controls, pipings & fittings and controller, skid mounted system For Chilled Water Circuit. System pressure shall be regulated within ± 0.2 bar (2.9 psi) of the set pressure. Expansion pressurization and deaeration of the system to be provided by an integrated pump with pressureless expansion tank(s) for Approximate system volume = 310,000ltr at Max ambient temp. 40 Deg. C and total Static Height 25 meters. The whole system shall be duly tested from factory conforming to international standards PED-97/23/EC. The system shall consist of minimum following components & features: a) Twin pump Pressurization Unit(orientation vertical/horizontal), Solenoid Valve, Flow regulator valve, Safety relief valve, Pressure sensor, Pipe fittings c/w Controller & display. b)Pressureless Expansion Tank c/w high quality butyl rubber bladder, weight sensor, capable of removing dissolved gases and air bubbles. c) Flexible Connection: to connect Pressureless Expansion Tank(s) with Pressurisation unit. d) Backflow Preventer c/w strainer and shut-off valve. e) Controller with IP 54 rating, display unit showing system content, system pressure and status of the main operating components in real-time. top up function, flood limitor/shut down function in event of serious leak. In case of any fault controller shall display the fault code and generate the alarm. f) Unit shall be able to automatically fill in the required makeup water into the tank when the volume goes below the set limit
Note: The contractor shall submit calculations for total system volume and tank sizing calculations.
Installation, testing and commissioning of pressurization system comprising pressureless expansion tank, twin pump pressurization unit, controls, pipings & fittings and controller, skid mounted system, complete as required and as per technical specifications.
Side Stream Filtration System
Supply of SIDE STREAM FILTRATION SYSTEM to remove unwanted solids from a cooling tower sump using a centrifugal-action vortex separator. Control of solids in the recirculated cooling water system shall be accomplished via a side-stream flow of 5-25% of the full-stream system flow through a completely assembled separation / filtration package. The package's pump shall provide sufficient pressure for the re-introduction of side-stream fluid back into system flow. The side stream filtration unit shall have a flow rate of 1100 USGPM and pressure drop of 0.2-0.8 Bar, Maximum working pressure of 10.3 Bar and Maximum operating temperature of 37.8 deg. C. The complete packaged unit shall consist of the pump, Separator, automatic purge valve, unit inlet and outlet connection, purge outlet and piping and electrical control system complete as per specification.
Installation, testing and commissioning of SIDE STREAM FILTRATION SYSTEM complete as required and as per technical specifications.
COOLING TOWER WATER TREATMENT SYSTEM
Supply of Electrochemical Water Treatment System for Cooling Tower for 1000 TR Chillers and Flow rate of 3000 USGPM . The treatment system shall work on the principle of controlled electrolysis, in a reaction chamber, to prevent scaling, corrosion and control formation of bacteria, algae and slime that arise in condenser water systems and also reduces blow down losses. The system shall consist of the following- Carbon steel Reaction tank, Epoxy painted on external side with 3 Nos. TiNiO anodes and a special Polypropylene scraper. Scraper motor to initiate the scraper rotation after fixed time intervals to scrap off the CaCo3 precipitation from the Reaction tank wall. Carbon Steel reaction tank shall have 2" Motorized ON/OFF Electrical drain valve for suitable blow down and Airgas release/intake ball valve on the lid of reaction chamber, which shall facilitate release of Chorine gas, thereby reducing the risk of corrosion. Reaction tank shall have a main Control Panel with PLC, switchgears and Main power supply switch. Control Panel shall have following a. Main pH meter along with pH sensor. b. Main Conductivity meter with pH sensor. Main Electrical Box shall have a digital 25A/36VDC power supply and power requirement for the control panel shall be 380/415 volt, 3 phase, 50 Hz with a neutral. Reaction tank shall have a pump for flow rate of 25-35 m3/hr.
Installation, testing and commissioning of Electrochemical Water Treatment System for Cooling Tower complete as required and as per technical specifications.
DUCTING FOR AIR CONDITIONING / VENTILATION: - FACTORY FABRICATED DUCTING: Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per SMACNA standard and as per approved drawings and specifications of following sheet thickness complete as required. SMACNA Certified wire rope hangers system as per specifications with lock(s) and pre-crimped end fixing(s) to be used for supporting all pipes. For safety, the lock should not have inbuilt unlocking mechanism; separate key to be used to unlock it. To avoid wire slippage, locking mechanism should be wedge type, self locking and double channel type. Ball bearing(s) based or circular gear(s) based locking mechanisms are not acceptable. The wire rope hangers should have a minimum safety factor of 5:1. Additional pipe supports shall be provided as per specifications to handle the load and also to take into account seismic considerations. Support system should be as per specifications
Thickness 0.63 mm sheet (TDF)
Thickness 0.80 mm sheet (TDF)
Thickness 1.00 mm sheet (TDF)
Thickness 1.25 mm sheet (TDF)
DUCTING FOR AIR CONDITIONING / VENTILATION: - SITE FABRICATED DUCTING: Supply, installation, balancing and commissioning of site fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per BIS standard and as per approved drawings and specifications of following sheet thickness complete as required. SMACNA Certified wire rope hangers system as per specifications with lock(s) and pre-crimped end fixing(s) to be used for supporting all pipes. For safety, the lock should not have inbuilt unlocking mechanism; separate key to be used to unlock it. To avoid wire slippage, locking mechanism should be wedge type, self locking and double channel type. Ball bearing(s) based or circular gear(s) based locking mechanisms are not acceptable. The wire rope hangers should have a minimum safety factor of 5:1. Additional pipe supports shall be provided as per specifications to handle the load and also to take into account seismic considerations. Support system should be as per specifications.
Thickness 0.63 mm sheet (TDF)
Thickness 0.80 mm sheet (TDF)
Thickness 1.00 mm sheet (TDF)
Thickness 1.25 mm sheet (TDF)
VOLUME CONTROL DAMPERS: Supply, installation, testing and commissioning of GI volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc. as per specifications.
Supply & fixing of powder coated extruded aluminium black anodized extruded aluminium volume control Collar Dampers with nut, bolts, screws etc. as per approved drawings and specifications.
Supply & fixing of powder coated extruded aluminium continuous type linear grilles complete with nut, bolts, screws etc. as per approved drawings and specifications.
GRILLES & DIFFUSERS: Supplying, fixing, testing and balancing of powder coated extruded aluminium Supply Air Grilles with aluminium volume control dampers as per specifications.
GRILLES & DIFFUSERS: Supplying, fixing, testing and balancing of powder coated extruded aluminium Return/exhaust Air Grills with louvers but without volume control dampers complete as required.
GRILLES & DIFFUSERS: Supplying, fixing, testing and balancing of Supply Air Diffusers of powder coated aluminium with aluminium volume control dampers with anti smudge ring & removable core.
GRILLES & DIFFUSERS: Supplying, fixing, testing and balancing of Return Air Diffusers of powder coated aluminium without volume control dampers with anti smudge ring & removable core.
Supply installation testing and balancing of Supply Air Multi-Slot Diffusers (of approved shade), all diffusers must be multisloted (12.5 mm/20mm/25 mm slot width as per requirements) complete with air pattern controller and shall be equipped with fixed air distribution grid, removable key operated hit and miss volume control damper and anti smudge ring where required as per the shop drawing and specifications.
4 Slot diffusers
Supplying, fixing , testing and balancing of powder coated aluminium construction double skin eye ball type jet nozzles with double flap butterfly damper, mounted on steel face plate suitable for side wall installation of required dia. & as per specification.
400 mm Dia.
Supplying, fixing, testing and balancing of drum louvers with Opposed blade damper of required size & as per specification to be designed for supply of high air volumes for the airport application. The drum louver should made out of extruded aluminium with 50mm thick border. The drum louver should be adjusted in vertical plane & rotate in 30 Deg. upwards or downwards movement with internal guide vanes fitted to drum louver should be adjusted in lateral direction.
FIRE & SMOKE DAMPERS: Supplying, fixing, testing and commissioning of fire dampers in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring, the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications.
Fire damper
Actuator
LOUVERS: Supply & fixing of powder coated extruded aluminium Fresh/ Exhaust air louvers comprising of inclined blade & extended out blade for disposal of rain water, bird screen suitable for outdoor application as required.
Demand Control Ventilation System
Supply ,installation, testing & commissioning of duct mount / non duct type VAQ station made out of heavy gauge extruded aluminium of 1.5 mm nominal thickness consisting of low leakage extruded aluminium volume control damper; Rapid Average Pitot tube; Air Flow Straightener (Honey-Comb patterned).
Supply, installation, testing & commissioning of motorized assembly for dampers with programmable single space DCV controller complete with CO2 sensor as per specification; shall be able to control VFD, supply air damper; shall communicate on EIA-485 through Modbus; differential pressure sensor; & step down transformer of 24V & control cabling as required.
Supply, installation, testing & commissioning of programmable single space DCV controller , shall be able to receive signal from multiple CO2 sensors and control VFD speed. The controller shall communicate on EIA-485 through Modbus & provided with necessary step down transformer of 24V & control cabling as required.
Supply, installation, testing & commissioning of Electronic Differential Pressure sensor & Transmitters ( in ducted application) suitable for installation within duct & 250 pa pressure range with necessary control wiring suitable for transmitting signal to VFD as required.
Supply , installation, testing & commissioning of non-dispersive infrared type Co2 sensor for TFA fans as required suitable for indoor application having range of 0-2000 ppm with accuracy of + 30 ppm. The sensor shall be suitable for 24Vac or dc supply.
DOOR GRILLES: Supply, installation and testing of powder coated (of approved shade) extruded aluminium air transfer door grilles with rear side frame as per approved shop drawings and specification.
MOTORIZED DAMPERS: Supplying, fixing, testing and commissioning of motorized dampers in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring, the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications.
Motorized damper
Actuator
Supply & fixing of powder coated extruded aluminium opposed blade back draft dampers of minimum 18 G frame and 20 G blade provided with suitable links to prevent the back pressure of air as required.
THERMAL INSULATION Supplying, installing and testing of insulation with protective coating on chilled water pipes(outside plant room) and fittings like valves, flanges and unions, etc. as per approved shop drawings and specifications and shall comply NBC 2016.
600 mm dia.
500 mm dia.
450 mm dia.
400 mm dia.
350 mm dia.
300 mm dia.
250 mm dia.
200 mm dia.
150 mm dia.
125 mm dia.
100 mm dia.
80 mm dia.
65 mm dia.
50 mm dia.
40mm dia.
32 mm dia.
25 mm dia.
20 mm dia.
THERMAL INSULATION Supplying, installing and testing of insulation with protective coating on chilled water pipes(inside plant room) and fittings like valves, flanges and unions, etc. as per approved shop drawings and specifications and shall comply NBC 2016.
600 mm dia.
300 mm dia.
DUCT INSULATION: Supply and installation of Thermal insulation material for Ducts. Insulation shall be as per the specifications and shall comply NBC 2016.
insulation for supply air ducts in return air path & return air ducts
insulation for supply air ducts with ducted return
ACOUSTIC LINING: Supply, installation and testing of acoustic lining of required density & thickness and accessories as per specification and complying with NBC-2016.
Acoustic lining for Ducts
Acoustic lining for AHU Rooms
CONTROL PANEL FOR F/M AHU & HRU SUPPLY FAN (OPERATED THROUGH VFD)
Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels including anchoring into the wall, wiring and earthing terminating into MCCB in each panel shall be provided. ( All specification for the panel shall be as per LT Panel)
All internal copper FRLS wiring and earthing of air handling unit motors from the VFD Control Panel shall be included.
The panel shall include the following components and accessories.
a. MCCB as per the ratings given below, suitable for motor duty .
b. Terminal block for power distribution.
c. Phase indicating lights and indicating lights for ON/OFF/TRIP status.
e. Time delay relay for delayed automatic restart of air handling unit motor (0-1 Minute).
f. Control wiring for opening/closing of fire dampers including suitable single phase supply with SP MCB's for four nos. of dampers per VFD control panel.
g. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each AHU panel to facilitate override of the automatic operation.
The number of AHU control panels shall be as follows.
Suitable amps MCCB with 30 HP VFD (VFD identified separately)
Suitable amps MCCB with 20 HP VFD (VFD identified separately)
Suitable amps MCCB with 15 HP VFD (VFD identified separately)
Suitable amps MCCB with 10 HP VFD (VFD identified separately)
Suitable amps MCCB with 4-7.5 HP VFD (VFD identified separately)
CONTROL PANEL FOR FANS (OPERATED THROUGH VFD Control Panel)
Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels including anchoring into the wall, wiring and earthing terminating into MCCB in each panel shall be provided by the electrical contractor.( All specification for the panel shall be as per LT Panel)
All internal copper FRLS wiring and earthing of Fan motors from the VFD Control Panel shall be included.
The panel shall include the following components and accessories.
a. MCCB as per the ratings given below, suitable for motor duty .
b. Terminal block for power distribution.
c. Phase indicating lights and indicating lights for ON/OFF/TRIP status.
e. Time delay relay for delayed automatic restart of Fan motor (0-1 Minute).
f. Control wiring for opening/closing of fire dampers including suitable single phase supply with SP MCB's for one no. of dampers per VFD control panel.
g. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each Fan panel to facilitate override of the automatic operation.
The number of Fan VFD control panels shall be as follows.
Suitable amps MCCB with 20 HP VFD (VFD identified separately)
Suitable amps MCCB with 4-7.5 HP VFD (VFD identified separately)
CONTROL PANEL FOR AHU (OPERATED THROUGH DOL/SD Starter Panel)
Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels including anchoring into the wall, wiring and earthing terminating into MCCB in each panel shall be provided by the electrical contractor.( All specification for the panel shall be as per LT Panel)
All internal copper FRLS wiring and earthing of Air handling units from the Starter Panel shall be included.
The panel shall include the following components and accessories.
a. MCCB as per the ratings given below, suitable for motor duty .
b. Terminal block for power distribution.
c. Phase indicating lights and indicating lights for ON/OFF/TRIP status.
e. Time delay relay for delayed automatic restart of air handling unit motor (0-1 Minute).
f. Control wiring for opening/closing of fire dampers including suitable single phase supply with SP MCB's for four nos. of dampers per control panel.
g. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each AHU panel to facilitate override of the automatic operation.
The number of AHU control panels shall be as follows.
Suitable amps MCCB, 4-7.5 HP
CONTROL PANEL FOR SERVICES AREA,SMOKE VENTILATION & PRESSURIZATION FANS (OPERATED THROUGH DOL/SD Starter Panel)
Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels including anchoring into the wall, wiring and earthing terminating into MCCB in each panel shall be provided by the electrical contractor. ( All specification for the panel shall be as per LT Panel)
All internal copper FRLS wiring and earthing of Fans from the Starter Panel shall be included.
The panel shall include the following components and accessories.
a. MCCB as per the ratings given below, suitable for motor duty.
b. Terminal block for power distribution.
c. Phase indicating lights and indicating lights for ON/OFF/TRIP status.
e. Time delay relay for delayed automatic restart of air handling unit motor, etc.
f. Control wiring for opening/closing of fire dampers including suitable single phase supply with SP MCB's for four nos. of dampers per control panel.
g. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each starter panel to facilitate override of the automatic operation.
The number of Fan starter panels shall be as follows.
Suitable amps MCCB, 20 HP
Suitable amps MCCB, 10 HP
Suitable amps MCCB, 4-7.5 HP
BMS WORKS
Server for BMS software BMS Computer System: Supply, installation, testing and commissioning of I7 Processor or Equivalent Server PC, 4MB Cache with 8 GB RAM, & 1 TB HDD, 10/100 Mbps Ethernet card, USB connection & internal modem, Microsoft(R) Windows(R) 8 or better or latest OS Professional Enterprise, Web server software, DVD-ROM Drive (with RAM), 100/1000 Mbps NIC for Network connection and anti virus software with 22" colour graphics monitor as per Tender Specifications. Accessories included Optical Mouse, Key Pad, LaserJet colour A4 printer with the above BMS System configuration.
BMS Computer System: Supply, installation, testing and commissioning of I7 Processor or Equivalent Server PC, 4MB Cache with 8 GB RAM, & 1 TB HDD, 10/100 Mbps Ethernet card, USB connection & internal modem, Microsoft(R) Windows(R) 8 or better or latest OS Professional Enterprise, Web server software, DVD-ROM Drive (with RAM), 100/1000 Mbps NIC for Network connection and anti virus software with 22" colour graphics monitor as per Tender Specifications. Accessories included Optical Mouse, Key Pad with the above BMS System configuration.
500 VA UPS with half an hour battery backup for Workstation
BUILDING MANAGEMENT SYSTEM WEB-BASED SERVER SOFTWARE BMS System Software : Supply, installation, testing and commissioning of the unlimited multi user with simultaneous minimum 5 user Web Based Graphical Software meeting the requirements in the Given I/O Summary and technical specifications including configuration and facility to create / provide the graphic mapping for all I/O Summary points , animate the Graphics, Navigation between pages, display of logs, changing the time zones, popup alarms, configurable password protection for Building Mgmt. System as per Specifications. Software shall be able to communicate with open protocols like BACNet, Modbus devices simultaneously. Offered software shall have built-in feature for EMS, Alarming, reporting, scheduling & trending. The software shall have unlimited software & Hard ware capacity. During operation & maintenance if any controllers required to replace than software shall have feature to automatically download logics in new controller as of old one automatically, from control station, once the old controllers ip is mapped in new one.
PROGRAMMABLE & APPLICATION SPECIFIC CONTROLLER (DDC) - UL LISTED & BTL certified Supply, installation, testing and commissioning of Bacnet IP/Lonmark IP852 (open Protocols) Direct Digital Controllers, The networkable controllers shall be , UL and BTL Listed with 32 bit microprocessor, real time clock & programmable memory. The Controller shall have built-in two Ethernet ports. Each DDC shall have built in LCD display & dial/button for local control & monitoring. The networkable DDC's shall be capable of peer to peer communication with lockable MS mounting cabinets duly powder coated connector strip, internal wiring and space to house controller & relays, connector etc. as per IO Summary. The Controller shall have built in memory to save graphics & logis for the connected points. The controller shall have minimum 10% spare IO capacity. Any Multiplexer (Mux) / AI to DI / DI to AI converters shall not be allowed. Max one DDC for 2 AHU shall be used. Each DDC shall not have Total IOs (total Points) more than 60 nos., Controller Power supply/SMPS shall be UL Listed
DCC controllers for AHU (Max 2 AHU per Controller)
DCC controllers for TFA, HRU Units System
DCC controllers for Air Washers
DCC controllers for Ventilation System & Smoke Evacuation
DCC controllers for DG system
DCC controllers for Fire Fighting System
DCC controllers for Plumbing / Domestic / Raw System (WTP & STP)
DCC controllers for Electrical System
DCC controllers for Elevators & Airport System
Supply, installation, testing and commissioning of Layer 2 switch with 8/12/24 ports (RJ-45) as required to complete the system complete with supply. The switch shall have port, as required to complete system, to communicate with other switches including Passive components inbuilt 2 SFP ports including SFP modules, rack mountable, SMPS power supply & other termination accessories (Like Pigtails/LIUs/ Convertors/Splicing equipment ,Patch panel, Patch Cord, Etc.) complete as per specifications and as required for BMS DDC Panel Networking. Vendor to decide the quantity and size of network switches based on their network design.
SYSTEM INTEGRATION UNITS FOR 3RD PARTY SYSTEM SOFTWARE INTEGRATION - UL listed Controllers Supply, installation, testing and commissioning of Bacnet IP/Lonmark IP852 (open Protocols) Integration units, to connect individual 3rd party microprocessor system controllers like Chillers, DGs, VFDs, VAV terminal units, UPS, Multifunction Digital Electronic Meters, Fire Detection Systems, STP, Elevators etc. the unit shall be capable of integrating all mentioned devices on BACnet, Modbus & LON etc.as per distribution given below : For Comfort Chillers (50 points/chiller on open Protocol Output BACnet/Modbus) - 1 Set AHU VFD Integration points mentioned in IO summary- 1 Set TFA & Ventilation VFD Integration points mentioned in IO summary- 1 Set For Addressable Fire Detection System Control Panel for 2500 Soft Points- 1 Set For DG System points mentioned in IO summary- 1 Set WTP system points mentioned in IO summary- 1 Set LT Electrical Panel, UPS, Elevators & EM points mentioned in IO summary- 1 Set STP & Hydropneumatic System points mentioned in IO summary- 1 Set Precision AC System- 1 Set Water Consumption Flow Metering- 1 Set Demand Control Ventilation- 1 Set Note: Integration unit shall be of same make as of BMS system
SENSORS AND FIELD DEVICES Supplying, installing, testing and commissioning of the following sensors / transducers / transmitters
Resistance type immersion temperature sensors for measuring Chilled water, condenser water supply and return temperature (Range 32-160 deg. F). The accuracy shall be at least ± 0.36 degrees F. The pressure rating shall be 10 kgf/sq cm .
Outside air temperature , humidity RH & Wet bulb sensors for measuring outside air temperature (Range 35-130 °F). The accuracy of temperature sensor shall be ± 0.36 degrees F and RH sensor is ± 3% . It should be provided with sun shield and rain protection.
Water Bi - Level Switches for indicating level status in Cooling Tower, sumps & Tanks.
Differential pressure switches across the blowers, Filters for indicating status. Pressure differential – 10 mm – 125 mm. The switch shall be with connecting tube and metal bends for connections to the duct. The housing shall be IP 54 rated.
Duct Temperature Sensor shall be with rigid stem and of averaging type. These shall be Platinum sensor suitable for duct installation and accuracy shall be ± 0.06%, for measuring supply -air temperature of AHUs etc.
Duct Temp & RH Sensor shall capable to measure relative humidity of 0 to 100%, suitable for duct installation and accuracy shall be ± 34°F at 70°F & Resistance Change approx. 3ohms/°F, for Measuring return air Temperature & Humidity of AHUs etc.
Differential Pressure Switch across the Pumps for indicating the Pump status of Pumps complete with all accessories
UL Listed Pressure sensor with IP 67 protection for measuring line pressure in Hydrant / Sprinkler lines
Duct pressure transmitter
Duct differential pressure transmitter
Air Velocity Sensors
Flame Proof Sensors
Flame Proof Switch
Current Relay complete as required
WIRING
Supplying, laying, termination, testing and commissioning of signal shielded cables . (2 core 1 mm2), PVC insulated, tinned copper conductor cable Armoured cable.
Supplying, laying, termination, testing and commissioning of signal un-shielded cables . (2 core 1 mm2), PVC insulated, tinned copper conductor cable Armoured cable.
Supplying, laying, termination, testing and commissioning of signal shielded cables. (4 core 1 mm2), PVC insulated, tinned copper conductor cable Armoured cable.
Supplying, laying, termination, testing and commissioning of communication cables. (2 core 1.5 mm2), PVC insulated, shielded, Twisted Pair, tinned copper conductor cable Armoured cable.
Flexible MS Flexible conduit for termination in the DDC Panels
Armoured Cat 6 cables
Supplying, laying, termination, testing and commissioning of power un-shielded cables . (3 core 1.5 mm2), PVC insulated, tinned copper conductor cable Armoured cable.
SITC for Galvanised Cable trays of 100mmx50mmx2 mm size complete as required
FIRE FIGHTING SYSTEM
Providing, Fixing, Single Headed external yard hydrant 63 mm dia. SS-304 landing valve (ISI marked) conforming to IS-5290 (Type -A) with SS-304 blank cap & chain, cast iron wheel, complete as required and as specified.
Providing, Fixing, MS Hose cabinet outdoor type of size 0.750Mx 0.600Mx 0.250M made of 2mm thick MS sheet with 6mm thick glazed glass doors i/c necessary locking arrangement suitable to accommodate 2 nos. 15m long hoses, one no branch pipe, etc. and mounted on wall or with raised brick platform. The cabinet shall be painted with red colour externally & white internally complete in all respects for external hydrant and as specified.
Providing, Fixing, Single Headed internal hydrant comprising of 80 mm NB dia. flanged inlet pipe with reducer, 63mm dia. outlet SS-304 landing valves (ISI marked), conforming to IS-5290 (Type A) with SS-304 blank cap and chain, cast iron wheel complete as required & as specified.
Providing, Fixing, 63 mm dia. SS-304 short Branch pipe with 15 / 20mm (nominal internal diameter) nozzle conforming to IS:903 suitable for instantaneous connection complete to inter-connect hose pipe, coupling etc. as required and as specified.
Providing, Fixing, 63mm dia., 15mtr. long RRL hose pipe (ISI Marked) with 63mm dia. male and female SS-304 couplings duly binded with GI wire, rivets etc. conforming to IS- 636 (Type-A) complete as required & as specified.
Providing, Fixing, First-Aid Hose Reel 20mm dia. x 36.5m long (minimum length) (Thermoplastic Type as per I.S. 12585) complete with swing type drum, bracket, 25mm dia. shut-off valve and 5mm SS -304 nozzle conforming to IS-:884, connection with riser with MS C- class pipe, painting the MS works complete as required & as specified.
Providing, Fixing, of standard fireman's axe as per IS:926 with heavy duty insulated rubber handle.
Providing and fixing in position the industrial type pressure gauges with gun metal / brass valves complete as required
Providing, Fixing, inlet breeching in CI Body having 4 way Gun-metal Fire Brigade inlet connection comprising of 4 nos. 63mm dia. male instantaneous inlet couplings with PVC cap and GI chain as required for 150mm dia. flanged MS pipe connection conforming to IS- 904 complete (to be connected to static tank) as required and as specified.
Providing, Fixing, inlet breeching in CI Body having 2 way Gun-metal Fire Brigade inlet connection comprising of 3 nos. 63mm dia. male instantaneous inlet couplings with PVC cap and GI chain as required for 150mm dia. flanged MS pipe connection conforming to IS- 904 complete (to be connected to static tank) as required and as specified.
Providing, Fixing, fire brigade suction hose coupling (Two way draw out connection) in CI Body, gun metal internal connection with nut for female coupling as per IS-904 complete with 150mm dia. Suction pipe and foot valve (to be connected to static tank) complete as required and as specified.
Providing, Fixing, orifice plate made of 6 mm. thick stainless steel with orifice of required size in between flange & landing valve of external and internal hydrant to reduce pressure to working pressure of 3.5 kg/cm2 complete as required & as specified.
80mm dia.
Providing, Fixing, 'C' Class heavy duty mild steel pipes conforming to IS-1239 including cutting, welding, fittings viz bends, tees, reducers, flanges, nut-bolts, gasket complete and laying in ground including excavation, providing PCC block support at specified interval and giving suitable corrosion treatment by way of min. 4mm thick corrosion protection tape which shall be wrapped comprising of coal tar/ asphalt component supported on fabric of organic/ inorganic fibre as per IS-10221, re-filling the trench etc.as required and as specified.
150mm dia.
100mm dia.
80mm dia.
Providing, Fixing, following sizes of 'C' Class heavy duty Mild Steel pipes conforming to IS-1239 upto 150mm dia. & IS-3589 for sizes greater than 150mm dia., including cutting, welding, nut-bolts, gasket, fitting viz. bends, tees, reducers, crosses, flanges etc. and fixing the pipes on wall / ceiling / beam / floor with suitable MS clamps / structural supports/PCC block and painting two coats of red oxide primer and two coats of synthetic enamel paint of approved shade complete as required and as specified. ( For all applications above ground level)
300 mm dia. (6 mm thick)
250 mm dia. (6 mm thick)
200 mm dia. (6 mm thick)
150 mm dia.
100 mm dia.
80 mm dia.
65 mm dia.
50mm dia.
40 mm dia.
32 mm dia.
25 mm dia.
Providing & fixing Butterfly valve with C.I. body & disc, stainless steel/carbon steel shaft, Hand lever operated, PN 1.6 rating, conforming to IS:13095/BS:5155.
200 mm dia.
150mm dia.
100 mm dia.
80 mm dia.
Providing and fixing C.I. sluice valves (with cap) complete with bolts, nuts, rubber insertions etc. (the tail pieces if required will be paid separately) :
250mm dia.
200mm dia.
150mm dia.
Providing, Fixing, non return valve Rating PN 1.6 Dual Plate type, conforming to API-594 with C.I. body, SS Disc, SS stem, EPDM seal, complete with companion flanges, bolts, nuts, washers & inserted rubber gasket complete as required and as specified.
250 mm nominal bore
200 mm nominal bore
150 mm nominal bore
100 mm nominal bore
80 mm nominal bore
Providing, Fixing, lever operated brass/ bronze ball valve of full flow with SS Balls having minimum working pressure of 16 Kg / Cm2 approved quality (screwed end) :
50mm nominal bore.
25 mm nominal bore
Providing, Fixing, 25mm dia. gunmetal air release valve PN 1.6 with all fittings and forged ball valve on header complete as required and as specified.
Providing, Fixing, Y Type strainer of Ductile CI Body flanged ends with stainless steel strainer having 3 mm perforation , perforation area 1 :4 Pressure rating PN 1.6. Complete as required.
200 mm nominal bore
150 mm nominal bore
100 mm nominal bore
Providing, Fixing, pressure switch, Standard Type, (for operation at 0-15 Kg./sqcm) with required fittings and accessories complete.
Providing, Fixing, reinforced neoprene rubber vibration eliminators/expansion joints (to provide relief from stresses at pipe flanges) suitable for upto 16 kg/cm2 pressure, as per specification of the manufacturers complete as required and as specified.
150mm dia.
100mm dia.
80mm dia.
Air pressure vessel for Fire Pump Providing and fixing double flanged vertical air vessel fabricated from 10mm thick M.S. plate with dished ends fabricated from 10mm M.S. plate, outside painted with one coat of primer and two coats of synthetic enamel paint of approved shade, complete with approved quality of pressure switches, pressure gauges and all other required accessories to operate commonly main fire pump, sprinkler pump, Diesel Fire pumps and Jockey pumps at drop of pressure automatically at required pressure setting complete as required and as specified. Recommended dia. : 450mm Height of shell : 2000mm Working pressure : 9 Kg/Sq.cm Test Pressure : 15 Kg/Sq.cm
Constructing masonry Chamber 90x90x100 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with C.I. surface box 100mm. top diameter, 160 mm bottom diameter and 180 mm deep ( inside) with chained lid and RCC top slab 1:2:4 mix (1 cement :2 coarse sand : 4 graded stone aggregate 20mm nominal size ) , i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick finished with a floating coat of neat cement complete as per standard design
Providing, Fixing, installation control valve (Sprinkler Alarm Valve) of Cast iron body and bronze working parts comprising of water motor alarm, bronze seat clapper and clapper arm, hydraulically driven mechanical gong bell to sound continuous alarm when the Wet riser/Sprinkler system activates, pressure gauges, emergency releases ,strainer, pressure switch, cock valve complete with drain valve and bypass, test control box, ball valves, MS pipe of required size, flanges, orifice plate, fittings, gasket etc. suitable for 150 mm diameter pipe size complete as required as specified.
Providing, Fixing, 25mm dia. inspection and testing assembly with Gun Metal isolation valve, Gun Metal sight glass by-pass valve and connected to line drain with necessary union & fitting complete as per NBC provisions and as specified.
Providing and fixing UL Listed electrically operated water flow switches with threaded connection for indicating water flow in sprinkler branch line suitable for vertical/horizontal mounting as per site requirement complete as required and as specified for pipe sizes of 80 to 150 mm Dia.
Providing, Fixing,15 mm dia. GM sprinkler head with standard response Quartzite Bulb capable to operate at 68 degree C complete with all accessories as required and as specified. (UL Listed)
Pendant type in chrome finish (Standard Coverage)
Upright type in chrome finish (Standard Coverage)
Side Wall type in chrome finish (Standard Coverage)
Providing & Fixing chrome finished Rosette plate with twin - piece recessed escutcheon plate, UL Listed / FM Approved, suitable for 15 mm size sprinklers.
Providing, Fixing, flexible tubes in corrugated SS flex tube, for connecting pendant sprinklers to branch lines complete with all necessary accessories, reducers, O-rings, nipples etc., supporting structural arrangements in the false ceiling/slab as per site requirement for the below lengths and tested for min 15 Kg/Sq.cm pressure with G.I. retainer rings & guide bolts complete as required and as specified. (UL/ EN Listed)
For 700 mm length
For 1000 mm length
For 1500 mm length
Providing, Fixing, Testing and Commissioning of 15 mm dia. NB, Brass Water Curtain Nozzle, suitable for a maximum working pressure of 12.3 kg / cm2 (175 PSI) with K Factor of 23, suitable for mounting in the horizontal position complete as per approved model & instructions of the Engineer-In-Charge.
Providing, Fixing, Testing and Commissioning of Deluge Valve with Electrical operated Trim Set with solenoid valve and switches, Gong valve, Drain valve, Test assembly, 150 mm dia. isolation valve with bypass including actuation & control panel, control cable from deluge valve to solenoid switch 2 Core x 1.5 Sq. mm., UL Listed / FM Approved, complete with drain cock arrangement and with all accessories, welded or screwed as required including cutting holes and chases in brick or RCC walls and making good complete as per approved model.
Providing and Fixing intelligent-type Sprinkler Annunciation Panel for minimum 100 Zones working & 20 spare, compatible for seamless integration with water flow devices, monitor & control modules and BMS systems (programmable outputs), with LCD type display & LED indication for all zones, complete with internal sounder, alarm/fault indications & standby 24V SMF lead acid batteries of suitable capacity with charger complete as required and as specified.
Providing, Fixing, addressable monitor module with existing flow to monitor the water flow in sprinkler system, operating on looped power and install as per site requirement complete as required and as specified.
Providing, Fixing, electrical Fault-isolation Modules to protect the system against wire to wire short circuits on loops, to be installed at the rate of every 5 nos. monitor modules complete as per manufacturer specifications and in an accessible location as per site, excluding wiring to Annunciation Panel, with UL Listed.
Providing, Fixing, ISI marked portable type fire extinguishers of following type complete as per specification and fixed / install as per site condition :
CO2 type 4.5 kg capacity as per IS- 15683
22.5 kg capacity CO2 type cylindrical shape fire extinguisher (Trolley mounted)
6 Kg capacity ABC Dry Powder type
SITC of Mechanical Foam type (AFFF media) 50 Liters Capacity cylindrical shape fire extinguisher with gas cartridge, hose, trolley and all required accessories, complete as per IS-13386 - trolley mounted type for portable use.
Providing and Fixing 3 Nos. G.I. sand buckets painted "Red Colour" complete with G.I. stand duly painted "Red Colour" of suitable size to hang 3 Buckets at a time as per required specifications.
Providing and fixing internal fire hose cabinet fabricated from 14 gauge SS-304,2MM Thickness sheet with single or double glazed front door and locking arrangement, vinyl tape 50% front side, “Fire Hose” with stove enamelled paint, written on front, including necessary supports of approximate size 2100x900x715mm deep to house two lengths of canvas hose with couplings, branch pipe, fire hose reel, nozzle, fireman axe, single outlet landing valve and first-aid hose reel, complete in all respects.
Providing, Fixing, electric driven main fire Hydrant / Sprinkler pumps suitable for automatic operation complete in all respect as required & specified and consisting of the following:
Horizontal type multistage, end suction , top discharge , centrifugal, split casing pump of cast iron body and bronze impeller with stainless steel shaft , mechanical seal, to ensure minimum pressure of 3.5 kg/cm2 at highest and farthest outlet at specified flow of 2280 LPM & 90 m head conforming to IS- 1520 complete with all accessories etc. as required
The pump shall be capable of furnishing not less than 150% of rated capacity at a head not less than 65% or rated head. The shut off head shall not exceed 120% of rated head.
80 HP Squirrel cage Induction motor suitable for operation on 415V, 3 phase, 50Hz, AC supply suitable for the above pump rating , TEFC type confirming to IS-325 with IP:55 protection for enclosure, horizontal foot mounted with class F insulation, flexible coupling & coupling guard with the pump complete as reqd..
Common bed plate fabricated from MS channel / ISMB with spring type vibration isolators. The pump set base shall be held by bolts grouted in the suitable RCC ( 1:2:4) foundation duly plastered including foundation bolts, washers complete as reqd.
Providing, Fixing, of Diesel engine driven standby fire pump suitable for automatic operation complete in all respect as required & specified and consisting of the following:
Horizontal type multistage, end suction , top discharge , centrifugal, split casing pump of cast iron body and bronze impeller with stainless steel shaft , mechanical seal, to ensure minimum pressure of 3.5 kg/cm2 at highest and farthest outlet at specified flow of 2280 LPM & 90 m head conforming to IS- 1520 complete with all accessories etc. as required
The pump shall be capable of furnishing not less than 150% of rated capacity at a head not less than 65% or rated head. The shut off head shall not exceed 120% of rated head.
Heat Exchanger ( Water ) cooled diesel engine developing 80 HP suitable for the pump, flexible coupling & coupling guard with the pump & common bed plate for mounting of engine & pump shall confirming to relevant BS/IS standard with auto starting mechanism.
The common base frame shall be held by bolts grouted in the concrete including foundation bolts, washers as required, vibration damping arrangement by cushy foot & engine panel with battery charger provided by engine manufacturer, connection to engine starting panel, lead acid batteries of 12V/24V, 180AH with casing, lugs, stand & terminations to diesel engine, charger complete in all respect.
Exhaust pipe of required length ( discharge to leave above roof level as per standard) with 50mm thick glass wool pipe section, covered with aluminium cladding, residential silencer muffler, instruments & protection-stop solenoid for auto stop in the event of fault with auto indications, day oil tank of 200 ltrs. with first charge of diesel fabricated out of 4mm MS sheet with inlet/ outlet ON/OFF valves, level indicator, drain pipe, 15mm dia. MS fuel line complete as reqd.
Common bed plate of fabricated MS channel / ISMB with vibration isolator. The base frame shall be held by bolts grouted in the suitable cement concrete foundation duly plastered including foundation bolts, washers as required.
Providing, Fixing, electric driven Pressurization Pump suitable for automatic operation complete as required & as specified and consisting of the following:
Horizontal type end suction, top discharge , centrifugal, Jockey pump of cast iron body and bronze impeller, with SS shaft, to ensure at highest and farthest outlet confirming to IS-1520 complete with all accessories as required.
Suitable HP Squirrel cage induction motor suitable for 415 V, 3 phase,50Hz, AC supply for the above pump T.E.F.C. type confirming to IS - 325 with IP:55 protection for enclosure, horizontal foot mounted, class-F insulation, flexible coupling & coupling guard with the pump complete in all respects.
Common base frame shall be fabricated from MS channel / ISMB with vibration isolator. The base frame shall be held by bolts grouted in the suitable RCC (1:2:4) foundation duly plastered including foundation bolts, washers complete as reqd.
180 LPM 90 M Head & 6 HP
180 LPM 35 M Head & 3 HP
Providing, Fixing, of electric driven main fire Water curtain pumps suitable for automatic operation complete in all respect as required & specified and consisting of the following:
Horizontal type multistage, end suction, top discharge , centrifugal, split casing pump of cast iron body and bronze impeller with stainless steel shaft, to ensure minimum pressure of 3.5 kg/cm2 at highest and farthest outlet at specified flow of 1620 LPM & 35 m head conforming to IS- 1520 complete with mechanical seals, safety relief valve, complete with all accessories etc. as required.
The pump shall be capable of furnishing not less than 150% of rated capacity at a head not less than 65% or rated head. The shut off head shall not exceed 120% of rated head.
30 HP Squirrel cage Induction motor suitable for operation on 415V, 3 phase, 50Hz, AC supply for the above pump TEFC type confirming to IS-325 with IP:55 protection for enclosure, horizontal foot mounted with class F insulation, flexible coupling & coupling guard with the pump complete as reqd.
Common bed plate fabricated from MS channel / ISMB with spring type vibration isolators. The pump set base shall be held by bolts grouted in the suitable RCC (1:2:4) foundation duly plastered including foundation bolts, washers complete as reqd.
GAS FLOODING & FIRE SUPPRESSION SYSTEM
NOVEC 1230 BASED FIRE SUPPRESSION SYSTEM COMPRISING OF PROVIDING ALL MATERIAL, EQUIPMENT, INSTALLATION, LABOUR, TESTING, COMMISSIONING & HANDING OVER OF THE ENTIRE SYSTEM, WITH THE FOLLOWING COMPONENTS: Supply, installation, testing and commissioning Seamless Steel Cylinder Complete with Pneumatical Valve Assembly arrangement, supervisory switch connection for monitoring cylinder pressure, in compliance with Chief Controller of Explosive, off centre with electric & pressure operated control heads as per requirement (Master/Slave Actuation Packages) a safety burst disc, and any other accessories to make the cylinder completely operational including Flexible Actuation Hose (directed to a pressure operated control head on each cylinder valve using actuation hose), container strap, structural supports etc.
BASEMENT BMS & CCTV ROOM Main system (3 X 150 Litres Cylinder) Stand by system (3 X 150 Litres Cylinder) Complete set for Main & stand by system
ARRIVAL FLOOR UPS & BMS ROOM Main system (7 X 150 Litres Cylinder) Stand by system (7 X 150 Litres Cylinder) Complete set for Main & stand by system
ARRIVAL FLOOR SERVER ROOM Main system (6 X 150 Litres Cylinder) Stand by system (6 X 150 Litres Cylinder) Complete set for Main & stand by system
SERVICE YARD BMS ROOM Main system (1 X 120 Litres Cylinder) Stand by system (1 X 120 Litres Cylinder) Complete set for Main & stand by system
Providing NOVEC 1230, factory-filled in the Cylinder, as per the specifications and manufacturer recommendations/ specified design concentration and fill density.
BASEMENT BMS & CCTV ROOM (for main & stand by system)
ARRIVAL FLOOR UPS/BMS ROOM (for main & stand by system)
ARRIVAL SERVER ROOM (for main & stand by system)
SERVICE YARD BMS ROOM (for main & stand by system)
Supply, installation, testing and commissioning Discharge Nozzles designed to provide the proper flow rate and distribution of gas to total flood a hazard area : (180/360 deg. As per requirement)
Supply, installation, testing and commissioning Micro-processor based Alarm Panel (addressable panel of single loop) for required devices capacity, discharge module with minimum 80 character LCD type display & LED indication for all zones, complete with internal sounder, alarm/fault indications & standby 24 v lead acid batteries with charger. This panel needs to be compatible with the central BMS/BAS System through interface convertors.
Supply, installation , testing and commissioning Gas Release Panel with 2-Zone Fire detection and 1-Zone gas discharge module with binary switch timer for release delay and potential free contact to relay "Gas Release" signal panel. This panel needs to be compatible with the Fire Alarm Panel and shall be UL Listed.
Supply, installation , testing and commissioning Electronic Hooter with flashing type multi-Strobe for combined audio + visual alarms, to be wired and located as per instructions of the engineer-in-charge.
Supply, installation , testing and commissioning Abort Switch of approved Pull-Type, as per approved location
Supply, installation , testing and commissioning Release Switch as per approved location.
Supply, installation , testing and commissioning & addressable Photoelectric/ Ionization Smoke detectors complete with mounting base LED, address switch, as per requirements.
Supply, installation , testing and commissioning 1.5mm X 2 core Fire Survival Armoured cable, with Copper conductor (600/1000V) having Cross linkable Ethylene Propylene Rubber (EPR) insulation with Low Smoke Zero Halogen (LSZH) inner & outer sheath, basic design as per BS-7846:2009 / IEC 60502 Part-1:2004. Should retain Circuit Integrity @ 8500C for minimum period of 2 Hrs. as per BS 8519:2010, BS 8491:2008 Cat.3 (120 mins.), BRE Global – UK Certified or approved Equivalent.
Supply, installation , testing and commissioning MS pipes (Seamless piping as per ASTMA 106, Grade 'B' Schedule 40) including all necessary fittings for all low side piping, and MS pipes (Seamless piping as per ASTMA 106, Grade 'C' Schedule 80) for Manifold for 2 nos. Cylinders. (1 Working + 1 Standby) including all necessary fittings as per NFPA 2001 guidelines including all structural supports.
Supply, installation , testing and commissioning Interface modules for communication between Gas Release Panel and specified compatible devices as per the instructions of the engineer-in-charge.
Supply, installation , testing and commissioning Electrical Connections to the Fire Alarm Main Panel including all necessary material and accessories as per requirements and as per instructions of the engineer-in-charge.
Supply, installation , testing and commissioning Photo-luminescent Gas Release caution sign boards for approved locations.
WATER TREATMENT PLANT
Supply, Installation, Testing and Commissioning In-line vertical multistage centrifugal clear water pump set SS-304 casing, SS-304 impeller, SS-316 shaft, CI base with CED coating/Epoxy painted , complete directly coupled with TEFC induction motor of class "F" insulation & efficiency class IE-3, 2900 RPM, suitable for operation on 415 volts ±10%, 3 phase, 50 Hz, A.C. supply ( with mechanical seal ), pressure gauges with gunmetal isolation cocks, vibration elimination pads, etc. mounted on a MS base frame bolted to cement concrete foundation etc. complete in all respects and as per technical specification with the following capacities:
Filter Feed pump No. of Pumps : 3(2W + 1S) Capacity : 35 M3/HR of Each Pump HP : 7.5 hp of each pump Head : 25 M Note:-1 set consists of 3 nos. of pumps (2Working + 1Standby)
Softener feed pump No. of Pumps : 3(2W + 1S) Capacity : 15 M3/HR of Each Pump HP : 3 hp of each pump Head : 25 M Note:-1 set consists of 3 nos. of pumps (2Working + 1Standby)
(Hydropneumatic Pumping System With Variable Frequency Drive)
Supply, Installation, Testing and Commissioning of compact packaged type skid mounted, self contained variable frequency drive hydropneumatic system complete as per following technical specification complete as required:-
(i) In- line vertical multistage centrifugal clear water pump set with SS-304 casing, SS-304 impeller with SS-316 shaft ,CI base with CED coating/Epoxy coated complete directly coupled with TEFC induction motor of class "F" insulation & efficiency class IE-3, 2900rpm, suitable for operation on 415 Volts ±10%, 3 phase, 50 Hz A.C. supply complete.
(ii) The entire system shall be mounted on a common base frame i/c common suction and common delivery of G.I heavy class pipe headers with flanges, interconnecting piping with all required Control Valves, Non-return valves, pressure gauge with isolation cock etc. and all required accessories.
(iii) Pressure vessel of non corrosive FRP composite construction lined with NSF and/or FDA listed material, like high density polyethylene with fully replaceable polyurethane. Air cell burst pressure of minimum of 3 times the vessel operating pressure and prototype cycle tested for 80,000 cycles with charging connections to discharge pipe line with necessary flanges, gaskets, isolating valve, nuts/ bolts etc. with suitable foundation boits & other accessories, complete.
(iv) Panel mounted microprocessor multi pump controller with large graphical display and variable frequency drive (VFD) mounted inside a panel complete with pressure sensor transmitter. The graphical display capable to show number of pumps running & also communicate with other controllers following with open protocol through RS485 port. System should be capable to compensate for frictional losses at lower flows. All alarms should be displayed in the controller. The panel should also have provision for manual / automatic alternate (cyclic) operation of pumps, ON/OFF switch, complete.
(v) Necessary foundationing bolts, vibration elimination pads and other accessories complete as required.
(vi) The entire system alongwith pumps & control panel must be sourced from single manufacturer only for unit responsibility.
Domestic Water Supply Pumps Duty of each pump suitable for:- No. of Pumps : 3nos. (2 W + 1 S) Capacity : 20 m3/hr. of Each Pump HP : 10 hp of each pump Head : 70 Meters Air Vessel : 100 ltr tank Note:-1 set consists of 3 nos. of pumps (2Working + 1Standby)
Soft Water Supply Pumps Duty of each pump suitable for:- No. of Pumps : 3nos. (2 W + 1 S) Capacity : 15 m3/hr. of Each Pump HP : 3 hp of each pump Head : 30 Meters Air Vessel : 100 ltr tank Note:-1 set consists of 3 nos. of pumps (2Working + 1Standby)
Tubewell Submersible pump Providing and Fixing submersible pump of tubewell for suitable rating, chrome steel shaft, suitable for operation on 400 volts + 10% - 15 %, 50 C/s A.C 3 phase supply, speed 2900 RPM, including necessary submersible cable of 2x3x6 Sq. m. size, outdoor type M.S. control panel and all other accessories required to make it completely functional as per the satisfaction of the Engineer-In-Charge, based upon the following specifications: Discharge: Approx. 350 LPM Recommended Head : 80 M min. HP : 10 hp of each pump Control Panel - 1 Nos., DOL starter of required rating (M.S. Fabricated in cubicle pattern).
Providing, Fixing, testing & commissioning of complete stainless steel submersible domestic water pump of SS 304 impeller, SS 304 Pump and Motor casing, SS-304 housing all accessories coupled to motor suitable for operation on 220/240 volt, 1 Phase, 2900 RPM with all accessories such as, Electrical cable from Pump to Panel, NRV, valve, pressure gauge bourden type, common delivery header complete in all respect Fully Automatic control panel for Pump including all accessories for running of pump with consideration of water level in tanks, dry running protection etc. Float switch with weight - 2 Nos. Nos. : 2 Nos. (1 W + 1S) Capacity : app. 350 LPM Head: 50 m HP: 7.5
Pressure Sand Filter Supply, Installation, Testing and Commissioning of vertical Pressure Sand Filter (comprising of minimum 750mm media in four graded layer and minimum Height on Straight 1500mm) fabricated from high performance M.S plate of minimum 10mm thick for shell & 12mm thick for dished ends, Tested to 5.0 Kg/m2 , internally treated with coal-tar epoxy, air scouring, collection system initial charge of media, M.S face piping with necessary flanges, gaskets, isolating valves, accessories, nuts & bolts, external painting with 2 coats of red oxide primer and enamel paint etc. with suitable foundation boits & other accessories, mounting frame, complete as required & as specified as per directions of the engineer-in-charge. with the following: Discharge : 35 m3/Hour Each Filtration Rate : 17500 lit./m2/h Dia. : 1.6 m I.D.
Water Softener Supply, Installation, Testing and Commissioning ‘Cation’ anion exchange process water softener fabricated from minimum 8 mm thick M.S. plate on min. shell and 10 mm thick M.S. plate on dished ends complete with initial charge of filter media and resins, face piping accessories, diaphragm valves of approved specifications, HDPE Brine tank of min. 500 Liters, piping testing and commissioning complete with resins of approved quality and make and regeneration assembly complete with valves, ejector, brine suction valves and piping. All internal parts of the softener shall be rubber lined as per technical specifications.
For Blending Minimum expected rate of flow: 13000 lph Total soft water to be produced between two regenerations: 156 Cu.m Expected raw water hardness : app. 376 ppm Expected treated water hardness: less than 50 ppm Max. working pressure : 2.5 Kg/cm2
HVAC purposes Minimum expected rate of flow: 28000 lph Total soft water to be produced between two regenerations: 336 Cu.m Expected raw water hardness : app. 200 ppm Expected treated water hardness: less than 5 ppm (Zero Commercial Hardness) Max. working pressure : 2.5 Kg/cm2
Chlorinator Supply, Installation, Testing and Commissioning chemical dozing system consisting of 2 nos. electronic dosing pumps (1W+1S) of approved make with all accessories, suitable to doze chemical solution upto 1 ppm doze (of Sodium Hypo-chloride solution) to a filtered water flow of 70000 lph against a pressure of 1.5 kg/cm2 complete with FRP moulded solution holding tank of min. 200 litre with all standard accessories & structural arrangement including suitable foundation bolts & other accessories etc. complete as per technical specifications. Note:1 set consists of 2 nos. of pumps(1W+1S)
Drainage Sump Pump for Plant room & basement
Supply, installation, testing and commissioning compact monoblock dry motor submersible pumps of suitable rating, with non-clog free flow open impeller, solid handling capacity of upto at least 28mm suitable for operation on 415 volts +10% , 3 Phase, 50Hz, A.C supply, speed 2900 RPM including oil chamber, guide wire for lifting & lowering of pump, G.I. galvanized lifting chain, complete.
The above pump sets must be supplied complete with following accessories.
Piping of 80mm dia. for individual pump delivery line and 100mm dia. for common delivery line, to be terminated outside the sump. (The pipe material should be Medium duty G.I) -- 1 Set
80mm dia. Butterfly valve.-- 2 Nos.
80 mm dia. reflux valve.-- 2 Nos.
Necessary cables from pump set to control panel (position of panel marked in enclosed layout in plant room).-- 1 Set
Electrical switch panel with DOL starter having all necessary accessories & safety devices of standard specifications. (Panels with sump pumps for each sump as per site conditions). --1 No.
Automatic built-up water level controller with necessary length of cable upto control panel.
Each set consist of 2 nos. of pumps - 1 working & 1 stand by (Complete set as above with 2 nos. pumps including cost for valves, piping, Control Panel and Cabling, Level Controllers etc. as required and as specified) 2.The entire system alongwith pumps & control panel must be sourced from single manufacturer only for unit responsibility.
Discharge - 250 LPM Each
HP - 3 HP of each pump
Total head - 15 Meters (minimum)
Sewerage Sump Pump for basement toilets
Supply, installation, testing and commissioning compact monoblock dry motor submersible pumps for suitable rating, with non-clog free flow open impeller, suitable for operation on 220/400 volts + 10% -15% minimum solid handling capacity of 46 mm suitable for operation on 240 volts + 5% -15%, 50 C/s A.C single phase supply, speed 960/1440 RPM including oil chamber, guide wire for lifting & lowering of pump, G.I galvanized lifting chain, with following specifications:
The above pump sets must be supplied complete with following accessories.
Piping of 80mm dia. for individual pump delivery line and 100mm dia. for common delivery line, to be terminated outside the sump. (The pipe material should be Medium duty G.I) -- 1 Set
80mm dia. Butterfly valve.-- 2 Nos.
80 mm dia. reflux valve.-- 2 Nos.
Necessary cables from pump set to control panel (position of panel marked in enclosed layout in plant room).-- 1 Set
Electrical switch panel with DOL starter having all necessary accessories & safety devices of standard specifications. (Panels with sump pumps for each sump as per site conditions). --1 No.
Automatic built-up water level controller with necessary length of cable upto control panel.
Each set consist of 2 pumps - 1 working & 1 stand by (Complete set as above with 2 nos. pumps including cost for valves, piping, Control Panel and Cabling, Level Controllers etc. as required and as specified) 2.The entire system alongwith pumps & control panel must be sourced from single manufacturer only for unit responsibility.
No. of Pumps : 2 nos. (1 working + 1 stand by) Discharge - 200 LPM Each Total head - 15 m HP - 2 HP of each pump
Supply installation, testing and commissioning of heavy duty G.I. pipe (For Suction & Delivery of pumps and equipment) confirming to IS. 1239 upto 150 mm and IS 3589 for dia. 200 mm and above with reducers, tees, flanges, elbow, crosses, union etc. and fixing the pipes on wall / ceiling / beam / floor including Clamping/Supporting the same, including painting with 2 coats of bitumastic enamel paint as per the site requirement and shall be duly painted with two coats of approved quality bitumastic enamel paint & shade over a ready-mix primer coat complete as required & as per directions of the engineer-in-charge for the following sizes:
50mm dia.
65mm dia.
80mm dia.
100mm dia.
150mm dia.
200mm dia.
Supply installation, testing and commissioning of reinforced neoprene rubber vibration eliminators/expansion joints (to provide relief from stresses at pipe flanges) suitable for upto 20 kg/cm2 pressure, as per specification of the manufacturers complete as required and as specified complete as per directions of the engineer-in-charge.
65mm dia.
80mm dia.
100mm dia.
150mm dia.
Supply installation, testing and commissioning of Stainless Steel double flange suction " Y" type strainer fabricated out of minimum 1.2 mm thick Stainless Steel sheet with 3 mm dia. perforation holes including nuts, bolts and 3 mm thick rubber insertion complete & tested to 16 Kg/Sq.cm pressure complete as required and as specified complete as per directions of the engineer-in-charge.
65 mm dia.
80 mm dia.
100mm dia.
150mm dia.
Supply installation, testing and commissioning of C.I butterfly valve, class PN 1.6 as per I.S:13095 or BS:5155, including necessary nuts, bolts, gaskets / flanges etc., complete as required and specified by the engineer-in-charge.
65mm dia.
80mm dia.
100mm dia.
150mm dia.
Supply installation, testing and commissioning of forged brass lever operated ball valve, 50mm nominal bore, of full flow with forged brass ball (Machined to mirror smooth finish with hard chrome plated) and spindle with setting and gland of superior quality having minimum working pressure of 16 kg/cm2 etc. complete in all respect.
Supply installation, testing and commissioning of C.I horizontal/vertical type non return valve (dual plate), conforming to IS:5312 with C.I. body, SS Disc, SS stem, EPDM seal, complete with companion flanges, bolts, nuts, washers & inserted rubber gasket complete as required to I.S:5312, Part-I, dual plate type, class PN 1.6.
65mm dia.
80mm dia.
100mm dia.
150mm dia.
Supply installation, testing and commissioning of 750 mm long hot dipped G.I. Puddle flanges for water tanks as per I.S. 1239 (Class C) with 6mm thick M.S. Plate of suitable size and welded all-round the pipe fixed in walls, beams and top slab of R.C.C tanks, complete with all details in all respects and as per drawing.
50 mm dia.
65 mm dia.
80mm dia.
100mm dia.
150mm dia.
200 mm dia.
250mm dia.
Supply installation, testing and commissioning of double flanged Water Flow Meter complete with digital display provision & including Pulse generator and Remote Totalizer complete in all respect as per manufacturers specification, instructions and approval as per engineer incharge.
150 mm dia.
100 mm dia.
80 mm dia.
Providing & fixing butterfly valve (with motorized actuator) of rating PN 1.6, wafer type, in cast iron body with Ductile Iron disc, EPDM seal, SS single piece shaft, conforming to IS-13095 of the following sizes complete with cast iron hand level companion flanges, bolts, nuts, washers & inserted rubber gaskets, as required and as per enclosed specification, with single phase Electrical Actuator, of 15Nm- 400Nm Torque, made of aluminium alloy (resistant to heat, acid , alkali, corrosion), and weather proof heavy duty motor, with stabilized start speed to effectively avoid water hammering, with waterproofing seal (IP 67) for all housing seals, low noise level, built –in thermal protection complete as per specifications
80 mm dia.
100 mm dia.
150 mm dia.
Providing and fixing insect-proof coupling, 80mm dia., to vent pipes of overhead tank with threaded or flanged joints, including G.I. flanges, nuts, bolts, 3mm thick rubber insertions complete.
Supply, installation, testing and commissioning of R.O. Plant capacity of 3500 LPH (Complete system to be compact type, skid-mounted / cabinet enclosed, as per detailed shop drawings to be approved) for the following parameters and consisting of (but not limited to) the following main components:-
(i) Inlet Quantity : 7000 lph
(ii) Output Quantity : 3500 LPH
(iii) Inlet TDS : 600 PPM
(iv) Outlet TDS : 100 PPM
Raw Water pumps of horizontal, centrifugal type suitable for a flow rate of 7000 LPH at 25m head (1.5 HP of each pump). The Pump construction shall be of SS-304 & impeller shall be also SS-304. The motor shall be TEFC suitable for a supply of 415V/3-phase/50Hz supply. The pump shall be supplied complete with base channel coupling foundations, bolts, pressure gauge at inlet and outlet of each pump. -- 2 Nos.
Activated Carbon Filter (automatic type for online installation before the Micron Filters) suitable for a flow rate of 7000 LPH. The material of construction shall be composite FRP. The unit shall be supplied complete with multi-port valves, inlet and outlet branches removal caps of replacement of elements inlet and outlet pressure indicators. -- 1 Set
Special Antiscalant Dosing System consisting of one HDPE tank of 100 litre capacity with a positive displacement diaphragm dosing pump having variable flowrate of 0-6 LPH. The motor shall be suitable for operation at 240V/single phase/50Hz supply. the pump shall be supplied complete with necessary polypropylene piping, valves, strainers & injection fittings. -- 1 Set.
Micron cartridge filter suitable for a flowrate of 7000 LPH to achieve particle filtration of less than 5 microns. The unit shall be supplied complete with inlet and outlet branches removal cap for replacement of element, inlet and outlet pressure indicators. (One for the pressure treatment & other for CIP system) MOC: Polypropylene -- 2 sets
R.O High Pressure feed pumps of vertical, multistage centrifugal type suitable for a flowrate of 7000 LPH at 10 Kg/sq.cm (5 HP of each pump). The pump construction shall be of SS-316-L & impeller shall be also SS-316-L. The motor shall be of TEFC suitable for a supply of 415V/3 phase/50 Hz supply. the pump shall be supplied complete with base channel coupling foundation, bolt, pressure gauge at inlet and outlet of each pump. - 2 Nos.
R.O. modules made out of Spiral Wound Thin Film composite suitable to withstand pressure of 20kg/sq.cm. Suitable BSPT/NPT connections shall be used for connecting feed & reject ends. the modules shall be supplied complete with all necessary instrumentation, valves for sampling, drain, reject & permeate, epoxy-coated structural steel bases and supports, as per following system capacity requirements:
(i) Total net treated water output of system = 3500 LPH
(ii) System recovery = 50 - 60 %
(iii) Filtration area per membrane = 85 sq.ft.
(iv) Number of membranes = The total number of membranes required shall be as per requirements, supported by calculations from the vendor.
Clean in place pump of horizontal end suction suitable for a flow rate of 7000 LPH at 25 m head (1.5 HP of each pump) with 100 ltr HDPE tank. The pump construction shall be of stainless steel SS-304. The motor shall be TEFC suitable for a supply of 415V/3 phase/50Hz supply. The pump shall be supplied complete with base channel, coupling, foundation bolts, pressure gauge at inlet & outlet of the pump. -- 1 Set
Centralised PLC control panel as per details given in technical specifications
Instrumentation mounted in R.O. system/panel as per details given in technical specifications
First fill of all chemicals and lubricants to commission and operate the plants. --1 Lot
All interconnecting piping work with valves:-
i) Low Pressure Side till R.O. feed water pump. Piping shall be of extra strong PVC and all valves shall be of extra strong PVC and all valves shall be PVC ball valves. -- 1 Lot
ii) High Pressure side piping from the R.O. high pressure pumps to the reject stream control valves shall be of SS - 304 using all SS fittings ball valves of suitable pressure rating shall be used till 25 mm size, above 25 mm, flanged globe/ wafer butterfly valves in SS construction shall be used. Rejects pressure control valves shall be globe valve and feed flow control valve shall be of SS-304. -- Lot
(All for above from "A" to "K" complete)
Complete Stainless Steel treated water storage tank (double Wall ) of capacity 7000 Litres including all inlet/outlet connections, accessories, valves, double seal manhole covers, insulation etc. The Stainless steel tank must be ozone resistant and to be used as ozone contact tank. Fabrication to be done as per approved shop drawing.
Providing and fixing PVC water storage tanks, for 7000 lit. capacity, of the approved quality including making solid supported base as per instructions and making all connections to the tank as required to make the tank functioning in all respects of the following capacity .
Hydropneumatic pump for R.O water Supply
Providing fixing and commissioning suitable complete composite hydropneumatic system consisting of horizontal/vertical multistage centrifugal pump having stainless steel impellers, stainless steel shaft, stainless housing and single mechanical seal and pressurised tank of required specifications and of non-toxic rubber diaphragm, complete with all accessories including pressure switch, pressure gauge and electrical panel with all necessary protection and operational devices i.e. alternate pumping operation and shut off during dry running conditions etc., and inclusive of suction and delivery manifold of required size with non-return valve and ball valve and with suitable electrical motor efficiency IE-3 to be operated on 400/440 volt suitable for following duty and with total no. of pumps in each set - 2 nos. (1 working + 1 standby) complete with the approval of Engineer-in-charge. a) Discharge : 3500 LPH b) Maximum head : app.70 M c) HP : 1.5 HP of each pump Vessel (FRP) : As Required
UV DISINFECTION SYSTEM Supply, installation, testing & commissioning of Online UV system with IP-54 rated cabinet housing in sheet steel with electrophoretic dipcoat priming and powder coated finish, and SS-316 treatment chamber material, with electronic ballast type, suitable for operation on 230 volts , 50Hz, for installation on the pressurized discharge line, suitable for tertiary treated wastewater of min. transmissivity of 65% complete with testing & commissioning as required and as specified. Capacity : 7000 LPH
Supply installation, testing and commissioning of recessed bi level Drinking water fountain, with double ss finish bubbler. Drinking water fountain with 8GPH cooling capacity, stainless steel body, approx size 1003mmX Depth 400 mm X height 1035mm, SS bubbler guard operated between 50 to 120 PSI, chilling unit suitable for R134a refrigerant, adjustable thermo state, supply complete with all accessories.R-134a refrigerant. Shall comply with ANSI 117.1 and ADA. Shall be listed by Underwriters Laboratories to US standards. Shall comply with ANSI/NSF 61 and NSF/ANSI 372
Installation, testing and commissioning of recessed bi level Drinking water fountain as above complete with as per specification and as per requirement.
Supply installation, testing and commissioning of Electrically Operated Stainless steel Hand Drier to be operated with 220 volts single phase, with fully hygienic condition, with all accessories including cutting and making good the walls wherever required
LIFT & ESCALATOR
Design, Fabrication, Supply including 02 years DLP (Defect Liability Period) of following Electric Traction Type fully automatic Machine room less (MRL) Passenger Lifts / Staff Lifts / Service Lifts/ Goods Lifts / Fireman Lifts with AC variable voltage & variable frequency drive unit suitable for operation on 415V, 3 Phase, 50 Hz. AC supply, having speed of 1.0 M/sec., power operated centre opening type car & landing doors, electro-magnetic brake system, operating panel with luminous buttons, overload warning indicator, battery operated alarm bell, emergency light, intercom suitable for hook up to AAI's EPABX, infrared ray sensing door protection for full height, reverse phase relay on controller, fire man's switch at Main Landing floor, digital car positions indicator in car & at all floors with up / down direction, light fixtures, ventilation fan, landing sill, main beam in shaft for machine, pit ladder etc. complete with all accessories serving different floors in the lift shaft along with Automatic Rescue Device (ARD) complete with dry maintenance free sealed batteries as required etc., as per detailed specifications enclosed and as under: -
Lift No. L01, L04 20 Passenger Lift, 1360 Kgs @ 1.0 mps, 04 stops, 17.00 mtr rise in Simplex Control; SS Hairline Grade-304 Car with 2-Panel Automatic Power operated SS Hairline Grade-304 Doors of 1100 mm (Width) X 2400 mm (Height) , All Opening on Same Side and Counterweight Safety, as per technical data sheet & specification & work shall be carried out as per direction of AAI
Lift No. L02 2000 Kgs @ 1.0 mps, 04 stops , 17.00 mtr rise in Simplex Control; SS Hairline Grade-304 Car with 2-Panel Automatic Power operated SS Hairline Grade-304 Doors of 1200 mm (Width) X 2400 mm (Height) , All Opening on Same Side and Counterweight Safety, as per technical data sheet & specification & work shall be carried out as per direction of AAI
Lift No. L03 20 Passenger Lift , 1360 Kgs @ 1.0 mps, 04 stops,17.00 mtr rise in Simplex Control; SS Hairline Grade-304 Car with 2-Panel Automatic Power operated SS Hairline Grade-304 Doors of 1100 mm (Width) X 2400 mm (Height) , Reverse Opening and Counterweight Safety, as per technical data sheet & specification & work shall be carried out as per direction of AAI
Lift No. L05, L06, L07, L08, L09, L10 20 Passenger Lift, 1360 Kgs @ 1.0 mps, 03 stops, 10.50 mtr rise in Simplex Control; SS Hairline Grade-304 Car with 2-Panel Automatic Power operated SS Hairline Grade-304 Doors of 1100 mm (Width) X 2400 mm (Height) , All Opening on Same Side and Counterweight Safety, as per technical data sheet & specification & work shall be carried out as per direction of AAI
Lift No. L11~L12, L13~L14 24 Passenger Lift , 1632 Kgs @ 1.0 mps, 02 stops, 05.50 mtr rise in Full Collective: Duplex Control; All Side Glass Lifts with 2-Panel Automatic Power operated Framed Glass Doors of 1200 mm (Width) X 2400 mm (Height) , Reverse Opening and Counterweight Safety, as per technical data sheet & specification & work shall be carried out as per direction of AAI
Lift No. L15~L16, L17~L18 26 Passenger Lift , 1768 Kgs @ 1.0 mps, 02 stops, 10.50 mtr rise in Full Collective: Duplex Control; SS Hairline Grade-304 Car with 2-Panel Automatic Power operated SS Hairline Grade-304 Doors of 1200 mm (Width) X 2400 mm (Height) , All Opening on Same Side and Counterweight Safety, as per technical data sheet & specification & work shall be carried out as per direction of AAI
Lift No. L19, L20 20 Passenger Lift , 1360 Kgs @ 1.0 mps, 02 stops, 05.00 mtr rise in Simplex Control; All Side Glass Lifts with 2-Panel Automatic Power operated Framed Glass Doors of 1100 mm (Width) X 2400 mm (Height) , Reverse Opening and Counterweight Safety, as per technical data sheet & specification & work shall be carried out as per direction of AAI
Lift No. L21 2000 Kgs @ 1.0 mps, 03 stops , 17.00 mtr rise in Simplex Control; SS Hairline Grade-304 Car with 2-Panel Automatic Power operated SS Hairline Grade-304 Doors of 1200 mm (Width) X 2400 mm (Height) , All Opening on Same Side and Counterweight Safety, as per technical data sheet & specification & work shall be carried out as per direction of AAI
Lift No. L22 2000 Kgs @ 1.0 mps, 03 stops (including 01 Emergency stop), 17.00 mtr rise in Simplex Control; SS Hairline Grade-304 Car with 2-Panel Automatic Power operated SS Hairline Grade-304 Doors of 1200 mm (Width) X 2400 mm (Height) , All Opening on Same Side and Counterweight Safety, as per technical data sheet & specification & work shall be carried out as per direction of AAI
Lift No. L23, L24 29 Passenger Lift, 1972 Kgs @ 1.0 mps, 02 stops , 10.50 mtr rise in Simplex Control; SS Hairline Grade-304 Car with 2-Panel Automatic Power operated SS Hairline Grade-304 Doors of 1200 mm (Width) X 2400 mm (Height) , All Opening on Same Side and Counterweight Safety, as per technical data sheet & specification & work shall be carried out as per direction of AAI
Lift No. L25, L26 10 Passenger Lift, 680 Kgs @ 1.0 mps, 02 stops, 04.20 mtr rise in Simplex Control; SS Hairline Grade-304 Car with 2-Panel Automatic Power operated SS Hairline Grade-304 Doors of 800 mm (Width) X 2100 mm (Height) , All Opening on Same Side and Counterweight Safety, as per technical data sheet & specification & work shall be carried out as per direction of AAI
Installation, Testing & Commissioning of above mentioned Passenger Lifts / Staff Lifts / Service Lifts/ Goods Lifts / Fireman Lifts as per detailed specifications and complete as per requirement.
ESCALATORS
Escalator No. ESC01, ESC03 Design, Fabrication, Supply including 02 years DLP (Defect Liability Period) of Escalators having capacity of 9000 passengers per hour at an operating speed of 30 linear meter per minute (0.5 meter per second), having step width not less than 1000mm between interior panel, angle of inclination of 30 degree (30°), suitable for a floor to floor rise of 10500 mm (approx.) with electric motor, control, latest safety devices, control panel i/c stainless steel cladding, with auto start and auto stop. etc. for operation on 415V, 3 phase, 50Hz, AC supply system as specified as per technical data sheet & specification & work shall be carried out as per direction of AAI
Escalator No. ESC02, ESC04, ESC05 Design, Fabrication, Supply including 02 years DLP (Defect Liability Period) of Escalators having capacity of 9000 passengers per hour at an operating speed of 30 linear meter per minute (0.5 meter per second), having step width not less than 1000mm between interior panel, angle of inclination of 30 degree (30°), suitable for a floor to floor rise of 5500 mm (approx.) with electric motor, control, latest safety devices, control panel i/c stainless steel cladding, with auto start and auto stop. etc. for operation on 415V, 3 phase, 50Hz, AC supply system, emergency push Buttons at upper and lower newel post as per technical data sheet & specification & work shall be carried out as per direction of AAI
Installation, Testing & Commissioning of above mentioned Escalators as per detailed specifications and complete as per requirement.
PAVA System
Address and Emergency Sound System Controller
SITC of Digital Public Address and Emergency Sound System Controller certified to International standards of Emergency Sound System EN 54 Certified (IEC 60849) with following features : One working & one Hot Standby/Redundant, in case of failure of any of the controller the another system must automatic switchover without any manual intervention. - Automatic Fault Diagnostic and reporting at central location - From Mic Capsule in call station uptil amplifiers and loudspeaker circuits. The system shall be able to make emergency calls (all calls) even if the network controller has failed.(1main + 1 Hot stand by) -Record calls for automatic playback to previously occupied zones
Digital Power Amplifier 500 W
SITC of EN 54 certified Digital Class-D Amplifier 250W x 2 or 500W x 1, multi channels as per the design/tender requirement. - Built in or external min 1 channel Automatic Volume control circuitry for noise sensing, Front LCD Character Display for status information. - Compliance to Standards for Emergency sound System IEC 60849 - Inbuilt Amplifier Monitoring e.g. for Short Circuit etc. Inbuilt Output monitoring - Loudspeaker line monitoring for every zone/speaker circuit -Separate amplifiers or separate channels of amplifiers for every zone should be considered - Automatic Amplifier Changeover to hot standby amplifier in case of failure of working amplifier with internal relays. - output voltage between 100V, 70V or 50V by changing jumpers - digital signal processing for audio
Call Station and Keypads
Remote Call Station
SITC of EN 54 certified Remote call station with interface unit is to be used for calling purpose and other applications with following features: - Connects to call station interface via CAT-5 cable - Up to 1 km from digital public address optical network - Built-in limiter - 2 supervised control inputs
Call Station with Keypad
Touchscreen call station for GUI feature
6W Metal grille ceiling speaker with fire dome
SITC of 6W ceiling mount EN 54 certified speaker with suitable fire dome having the following specification: - Max Power: 9W,Rated Power: 6Watts, Power Tapping: 6/3W - Effective frequency range(-10 dB) :90 Hz to 20KHz - SPL at rated power (1Khz at 1 m) 98 dB - Opening Angle 1 KHz / 4 KHz (-6 dB): 180/50
Passive Line array
SITC of 60W passive line array speaker, EN 54 certified with suitable to mount having following specification Frequency response Better or equal to 190Hz to 18kHz SPL level at 60W/1W (at 1KHz ,1m) 110 dB/92 dB(SPL) Opening angle at (1kHz/4 kHz 6dB) Horizontal 210 deg./132 deg.; Vertical 50 deg./22 deg. It shall have minimum 12 nos. of 2”drivers
Active Line array
SITC of active line array with suitable to mount having following specification: built in DSP, ADC-DAC, network interface, with software configurable vertical coverage, with ambience noise sensing microphone, thermal overload protection, with RJ-45,ethernet 100 Mbps interface, 24 bit word length,48kHz sampling rate. EN 54 Certified.
Indoor type Active Line array speaker Base only
Indoor type Active Line array speaker Base with Extension
30W cabinet Loudspeaker
SITC of 30W wall mount speaker with excellent speech & music reproduction with suitable to mount having following specification: Max Power: 45W,Rated Power: 30Watts Effective frequency range(-10 dB) : 100 Hz to 18KHz ,SPL at rated power (1Khz at 1 m) 105 dB Opening Angle 1 KHz / 4 KHz (-6 dB): 160° / 81° (hor.) 150° / 90° (ver.) - Safety acc. to EN60065
12W Bidirectional cabinet Loudspeaker
SITC of 12W wall mount bidirectional speaker with suitable to mount having following specification with: excellent speech & music reproduction. The cabinet should have two dual cone loudspeaker drivers, mounted on an angled baffle, providing a wide opening angle. Max Power: 18W,Rated Power: 12Watts, Effective frequency range(-10 dB) : 140 Hz to 20KHz ,SPL at rated power (1Khz at 1 m) 97dB Opening Angle 1 KHz / 4 KHz (-6 dB): 270° / 165° Safety acc. to EN60065
6W Cabinet Speaker
SITC of 6W wall mount speaker with excellent speech & music reproduction with suitable to mount having following specification: - Max Power: 9W,Rated Power: 6Watts, Power Tapping: 6/3 W - Effective frequency range(-10 dB) : 180 Hz to 20KHz - SPL at Sound pressure level at 6 W / 1 W (4 kHz, 1 m)100 dB / 92 dB (SPL) - Opening Angle 1 KHz / 4 KHz (-6 dB): horizontal 165° / 95° , vertical 158° / 73° Dimensions (H x W x D) 243 x 151 x 141/119 mm Safety acc. to EN60065
60W cabinet Loudspeaker
SITC of 60W wall mount speaker with excellent speech & music reproduction with suitable to mount having following specification - Max Power: 90W,Rated Power: 60Watts, Power Tapping: 60/30/15W - Effective frequency range(-10 dB) : 55 Hz to 20KHz - SPL at Sound pressure level at 6 W / 1 W (4 kHz, 1 m)108 dB / 114 dB (SPL) - Opening Angle 1 KHz / 4 KHz (-6 dB): Horizontal 90°, Vertical 90° Safety acc. to EN60065
CD/DVD Player
Noise sensing microphones
SITC of following Volume control units as per technical specification compete as per site requirement in all respect.
Volume control units 12W
Volume control units 36 W
Volume control units 100 W
“SITC of 2c x 1.5 sq.mm fire survival armoured cable (600/1000V) with class-2 Copper conductor having halogen free ceramified silicon insulation as per BS EN 50363 and low smoke zero halogen (LSZH) inner & outer sheath. Should comply to EN 61034-2 & EN 60754-1. LPCB-FPC certificate to be submitted. The cable should meet fire performance circuit integrity test as per BS EN 50200:PH-120 & BS 6387 CWZ. Outer sheath should be in red colour with Anti-rodent & LSZH properties including end terminators, saddles, clamps with screws etc for fixing on wall/ceiling or on cable trays complete as required.”
SITC of 19 "Equipment Rack,42 U Made of MS for housing of all above equipment , front lockable glass door, Fan tray fro colling, Caster wheel base , Main Panel with Spike Buster, Individual FUSE power supply unit, including all internal wiring/ interconnection as required
Supply, Installation, Testing & Commissioning of rack-mountable Workstation (as per specifications) minimum 500GB hard disk, 3GB RAM, i5 processor as per specification & approved make
CCTV System
Supply, Installation, Testing & Commissioning of Enterprise level IP based Closed Circuit Television System (CCTV) based on the following elements and as required to make the system complete and operational in all respects as per specifications, drawings, and standards as required with full compliant with latest BCAS Circular.
SERVERS & WORKSTATION
Database Primary Server: Supply, Installation, Testing & Commissioning of Database Primary Server for entire cameras - Complete as per specifications & preferred make.
Database Failover Server: Supply, Installation, Testing & Commissioning of Database Failover Server for entire cameras - Complete as per specifications & preferred make.
Video Recording Primary Server: Supply, Installation, Testing & Commissioning of Failover Video Recording Servers. All Primary Recording servers kept at Primary Data Center. Each recording server shall support min. of 50 cameras and max. of 100 cameras. Each recording Server shall have min. 25% spare capacity to take additional cameras in future. Recording Server & storage sizing shall be done considering min. write throughput of B12 Mbps/camera - Complete as per specifications & preferred make.
Video Recording Failover Server: Supply, Installation, Testing & Commissioning of Video Recording Servers . All Failover Recording servers kept at Secondary Data Center. Each recording server shall support min. of 50 cameras and max. of 100 cameras. Each recording Server shall have min. 25% spare capacity to take additional cameras in future. Failover Recording Server & storage sizing shall be done considering min. write throughput of 3 Mbps/camera - Complete as per specifications & preferred make.
Video Analytic Primary Server: Supply, Installation, Testing & Commissioning of Video Analytic Server Each Analytic server shall support min. of 50 cameras and max. of 64 cameras. Each Analytic Server shall have min. 25% spare capacity to take additional cameras in future. All Primary Analytic servers kept at Primary Data Center - Complete as per specifications & preferred make.
Video Analytic Failover Server: Supply, Installation, Testing & Commissioning of Video Analytic Server Each Analytic server shall support min. of 50 cameras and max. of 64 cameras. Each Analytic Server shall have min. 25% spare capacity to take additional cameras in future. All Failover Analytic servers kept at Secondary Data Center - Complete as per specifications & preferred make.
SITC of WORKSTATION
Supply, Installation, Testing & Commissioning of CCTV Client Operator Station with 1No. 42/46” LED Display & 1 Nos. 21" LED Display- Complete as per specifications & preferred make.
Supply, Installation, Testing & Commissioning of CCTV Client Operator Station with 1 No. of 46” LED Monitor - Complete as per specifications & preferred make.
Supply, Installation, Testing & Commissioning of A4 size Colour Laser Printer with scan/copy feature - Complete as per specifications & preferred make.
Video Management & VA Software
Supply, Installation, Testing & Commissioning of Digital Video Surveillance Server control software along with server/ NVR/NAS software loaded with necessary camera licenses for 570 cameras with 20 concurrent client user licenses (VMS shall be scalable to incorporate 2000 nos. of cameras) in N+N configuration - Complete as per specifications & preferred make.
Supply, Installation, Testing & Commissioning of Video Analytic Software licenses for 150 cameras & requirement as per specification including Object left VA -50 cameras, License plate recognition - 10 cameras and Image Tracking (attribute search) -50 cameras- Complete as per specifications & preferred make.
Network Storage
Supply, Installation, Testing & Commissioning of Network attached Storage (NAS) - Complete as per specifications & preferred make.
Network attached Storage (NAS) with required storage capacity
(To be estimated for 600 cameras with H.264, Full resolution @ 1920 X 1080, 25 FPS, 30 days of data retention + 25% Spare; The offered storage shall be scalable to add additional 50% usable capacity at site within the same storage; No other upgrades should be required for desired scalability except for disk Arrays enclosures and Disk drives as required. )
Primary Storage (30 days)
Redundant Storage(7 days)
Supply, Installation, Testing & Commissioning of following types of Cameras - complete as per specifications
Indoor Dome Cameras - IP Day/night Colour Mega Pixel camera
Outdoor Dome Cameras - IP Day/night Colour Mega Pixel camera
SITC of Outdoor Fixed Cameras - Box type - IP Day/night Colour Mega Pixel camera
SITC of Indoor IP PTZ Dome Cameras
SITC of Outdoor PTZ Cameras, if required at site
SITC of Multi Sensor camera - 180º panoramic overview if required at site
SITC of Speed Dome Controller Joystick, complete as per specification
Passive work-CABLES
Supply, laying, testing and commissioning of 3 core 1.5 Sq.mm Cu. FRLS Armoured power cable - Complete as per specification
Supply, laying, testing and commissioning of 3 core 1.5 Sq.mm Cu. FRLS Un-armoured power cable - Complete as per specification
Integration
Integration of CCTV system with other system which includes ACS, FAS, VHT for seamless alarm based CCTV camera image pop ups
FLIGHT INFORMATION DISPLAY SYSTEM (FIDS)
FIDS Servers, Software, Licences and Workstations, as detailed below
Supply, Installation, Testing & Commissioning of FIDS Servers (installed in active-active mode in each of two data centres), core software, licenses
Supply, Installation, Testing & Commissioning of Client Software for installation on AAI-provided PCs
FIDS Workstation PCs, with client software
Supply, Installation, Testing & Commissioning of 55" LCD Displays with Mounting Arrangement
Supply, Installation, Testing & Commissioning of 42/43" LCD Displays with Mounting Arrangement
Supply, Installation, Testing & Commissioning of 3x2 LED Board Displays with Mounting Arrangement
Supply, Installation, Testing & Commissioning of Server with accessories for Automatic Flight Announcement System (AFAS)
Supply, Installation, Testing & Commissioning of FIDS package Software as per requirement of the tender
Supply, Installation, Testing & Commissioning of AFAS package Software as per requirement of the tender
Integration with AODB and other systems as required
Charges for the installation, Integration, Testing and Commissioning of the complete System with necessary power distribution boards, power point boxes etc. as per specifications
SITC of PFMS Server software, & licenses
SITC of sensors for Departure pre-security screening area
SITC of sensors for Departure forecourt and building entry vestibules
SITC of sensors for Check-in islands
SITC of sensors for Boarding gate counters
SITC of sensors for Baggage reclaim hall
Integration of PMFS (Passenger Flow Management system)
DISTRIBUTED ANTENNA SYSTEM (DAS)
Optical Item- Master Optical Unit
Supply, Installation, Testing & Commissioning of Active POI SISO (850MHz+ 900MHz+ 1800MHz+ 2100MHz+ 2300MHz) As Per Specifications & Preferred Make.
Supply, Installation, Testing & Commissioning of Active POI MIMO (850MHz+ 1800MHz+ 2300MHz)
Supply, Installation, Testing & Commissioning of Master Unit (4+4 Port) MIMO Supportable (850MHz+ 900MHz+ 1800MHz+ 2100MHz+ 2300MHz+ 2500MHz) As Per Specifications & Preferred Make.
Supply, Installation, Testing & Commissioning of Remote Management System (Hardware + Software) As Per Specifications & Preferred Make.
Optical Item- Remote Optical Unit
Supply, Installation, Testing & Commissioning of Optical Remote Unit, 43dBm, MIMO (GSM, DCS, UMTS, LTE850, LTE1800, LTE2300 and LTE2500), As Per Specifications & Preferred Make.
Optical
Supply, Installation, Testing & Commissioning of 96 Core Armoured LSZH Optical Fibre Cable (Outdoor Type) As Per Specifications & Preferred Make.
Supply, Installation, Testing & Commissioning of 12 Core Armoured LSZH Optical Fibre Cable (Outdoor Type) As Per Specifications & Preferred Make.
Supply, Installation, Testing & Commissioning of Single Mode Simplex Patch Cords SC-APC to SC-APC-5Mtrs. As Per Specifications & Preferred Make.
Supply, Installation, Testing & Commissioning of Fibre Management System 48 Port SC-APC-Rack Mount
Supply, Installation, Testing & Commissioning of Fibre Management System 48 Port SC-APC- Wall mount
Supply, Installation, Testing & Commissioning of Fibre Management System 12 Port SC-APC
Supply, Installation, Testing & Commissioning of LIU 6 Port SC-APC
Supply, Installation, Testing & Commissioning of joint Enclosure
Supply, Installation, Testing & Commissioning of 19" 42U transmission rack for Master Unit Installation
Antenna
Supply, Installation, Testing & Commissioning of Omni Antenna MIMO, 2/4 dBi, 700-2700MHz, PIM: <-130dBc
Supply, Installation, Testing & Commissioning of Omni Antenna SISO, 2/4 dBi, 700-2700MHz, PIM: <-130dBc
Splitter/Coupler
Supply, Installation, Testing & Commissioning of 2way splitter, N(F)
Supply, Installation, Testing & Commissioning of 5dB coupler, N(F)
Supply, Installation, Testing & Commissioning of 7dB coupler, N(F)
Supply, Installation, Testing & Commissioning of 10dB coupler, N(F)
Supply, Installation, Testing & Commissioning of 15dB coupler, N(F)
Supply, Installation, Testing & Commissioning of 20dB coupler, N(F)
Supply, Installation, Testing & Commissioning of Terminator, 50W
Jumper-Connector
Supply, Installation, Testing & Commissioning of Connector, N, Straight / Male, for 1/2 Inch Regular Feeder Cable
Supply, Installation, Testing & Commissioning of Connector, N, Straight / Male, for 7/8 Inch General Feeder Cable
Supply, Installation, Testing & Commissioning of DIN-Male Connector for 1/2" Cable
Supply, Installation, Testing & Commissioning of 1m - 1/4" Jumper Cable - QMA Male - QMA Male (POI To M.U)
Supply, Installation, Testing & Commissioning of 3m - 1/4" Jumper Cable - N-Male - QMA Male
Supply, Installation, Testing & Commissioning of 5m - 1/4" Jumper Cable - N-Male - QMA Male
Supply, Installation, Testing & Commissioning of 1m - 1/2" Jumper Cable - N-Male - N-Male
Supply, Installation, Testing & Commissioning of 3m - 1/2" Jumper Cable - N-Female - 7/16 DIN-Male
Supply, Installation, Testing & Commissioning of 1m - 1/2" Jumper Cable - N-Male - N-Female
Supply, Installation, Testing & Commissioning of Duplexer for 850 MHz (For Tx Rx Separation)
Supply, Installation, Testing & Commissioning of Duplexer for 900 MHz (For Tx Rx Separation)
RF Cable
Supply, Installation, Testing & Commissioning of 1/2-inch Regular Cable, LSZH, Fire retardant
Supply, Installation, Testing & Commissioning of 7/8-inch General Feeder, LSZH, Fire retardant
Accessories
Supply, Installation, Testing & Commissioning of DAS Accessories as per Site Requirement as below :
Z type clamp for Omnidirectional Ceiling Antenna installation
Panel Antenna Clamp (L Type)
Weather proofing Kit
Saddle 32mm
Saddle 25mm
10 mm Trihead MS Screw (1.5 Inch)
PVC Gitti
Cable Tie Size L=300mm * 4.8 mm width
Flexible MS Pipe, 25mm
Insulation Tape Black
Paper Sticker
Fasteners
Electrical Power
1 Core 16 SQMM copper electrical cable Green LSZH
3 Core 10 Sq.mm cable Copper FR-LSZH
Termination lugs RING Type (AC Power cable, 10 sq.mm 3C PVC)
Termination lugs PIN Type (AC Power cable, 10 sq.mm 3C PVC)
Termination lugs RING Type (AC Power cable, 16 sq.mm 1C PVC)
Termination lugs PIN Type (AC Power cable, 16 sq.mm 1C PVC)
ACDB Box for Equipment Room (125 A 1 Nos. 32A 1 Nos., 16A 2 Nos. Single Pole, 6A 12 Nos.)
ACDB Box for Remote Unit (16A 2 Nos. Single Pole)
Nut Bolt 25*8 with washers
Equipment Earthing Busbar, (EGB) Tinned Copper with 27 holes of 8 mm dia. (staggered) with Insulating Studs, G.I. Nut, Bolt and washers
Equipment Earthing Busbar, (EGB) Tinned Copper with 7 holes of 8 mm dia. (staggered) with Insulating Studs, G.I. Nut, Bolt and washers
TRUNK MOBILE RADIO SYSTEM (TMRS)
Equipment at Control Centre- MSO (Centralised Switch) - incl 1 Core Server (Inc. Zone Server, Mgmt. Server, MTIG-IP, Data Server) - incl 1 redundant Zone Server - incl 2 Combined Core/Gateway Router - incl 2 Core LAN Switch - incl 2 Backhaul switch - incl 1 Border Router - incl 1 lot Core System Software - incl 1 Sites License - incl 200-Users Licenses - Incl 1 AIS
Alarming Forwarding
Network Management Terminal - incl 1 at OCC
Console -Local - incl 1 MCC7500 Console with 21" LCD - incl 1 Footswitch - incl 2 Speakers - incl 1 Desk Microphone - incl 1 Headset
MTS4 Base Station (with 2 BR) - incl 2 Base Radios (1 Control and 7 voice channels) - incl Redundant TSC and power supply - incl 1 lot RFDS component - incl 1 lot dual diversity antenna system with 80 meters RF cable
MTP3150 Portable radio (1.8 Watt) - incl 1 whip antenna - incl 1 1700mAH battery - incl 1 belt clip - incl 1 dual unit charger
MTM5200 Mobile radio in vehicle configuration - incl 1 Remote mounted control head - incl 1 Transceiver - incl 1 low profile trunnion - incl 1 13 watt speaker - incl 1 5 meter battery power cable - incl 1 combined TETRA antenna with 5 m RF cable
MTM5200 Mobile radio in Desk mount configuration - incl 1 standard control head - incl 1 Transceiver - incl 1 Desk mic - incl 1 13W speaker - incl 1 230V Power supply unit - incl 1 mag-mount antenna
20 Channel Voice Logger with hardware, software and 1 replay client
Programming software and cables
Critical Spares
STRUCTERED CABLING SYSTEM (SCS)
Supply, Installation, Testing & Commissioning of Category 6A 4 pair UTP Cable 305m,
Supply, Installation, Testing & Commissioning of Category 6A 24 Port Loaded Patch Panel
Supply, Installation, Testing & Commissioning of Category 6A Information Outlet for Field side
Supply, Installation, Testing & Commissioning of Cat-6A Face Plate Singlex with Gl back Box
Supply, Installation, Testing & Commissioning of Cat-6A Face Plate Duplex with Gl back Box
Supply, Installation, Testing & Commissioning of Category 6A UTP Patch Cord 1 Meter
Supply, Installation, Testing & Commissioning of Category 6A UTP Patch cord 2 Meter
Supply, Installation, Testing & Commissioning of Category 6A UTP Patch Cord 3 Meter
Supplying and fixing of PVC Cable Manager finger duct type
Supply, Installation, Testing & Commissioning of Armoured outdoor single mode fiber optic cable, 24 Core
Supply, Installation, Testing & Commissioning of Indoor single mode fiber optic cable, 24 Core
Supply, Installation, Testing & Commissioning of 48 LC Fibre Patch Panel Loaded with Splicing tray. Fibre adaptor plate with adapters
Supply, Installation, Testing & Commissioning of 288 LC Fibre Patch Panel Loaded with Splicing tray, Fibre adaptor plate with adapters
Supply, Installation, Testing & Commissioning of LC type Single mode Fibre Pigtail
Supply, Installation, Testing & Commissioning of LC to LC Fibre Patch Cord Single mode 3Meter
Supply, Installation, Testing & Commissioning of LC to LC Fibre Patch Cord Single mode 5Meter
SITC of 42RU, 800w x lOOOd, 19" Comms equipment rack with front 19" rails and dual 12-outlet PDUs, and mesh-screen front and rear lockable doors, ventilated top cover with cable glands
SITC of 42RU, 600w x lOOOd, 19" Server equipment rack, with front and rear Adjustable 19" rails, and dual 12-outlet PDUs, and mesh-screen front and rear lockable doors, ventilated top cover with cable glands
SITC of 15RU, 800w x lOOOd, 19" Comms equipment rack with front 19" rails and dual 12-outlet PDUs, and mesh-screen front and rear lockable doors, ventilated top cover with cable glands
SITC of 15RU, 800w x lOOOd, 19" Comms equipment outdoor rack with front 19" rails and dual 12-outlet PDUs, and mesh-screen front and rear lockable doors, ventilated top cover with cable glands
Supply, fabricating and fixing of 2.0 mm thick sheet steel hot dip galvanised class B perforated cable tray with horizontal & vertical bends, reducers, Tee's, cross over member and other accessories as required and duly suspended from the ceiling Gl suspenders (8 MM) including Gl bolts & Gl nuts and including painting with powder coating etc. The trays should be tested to handle 150 Kgs of load at a span distance of 1.5 meters.
600 mm width x 50mm depth x 2 mm thickness.
300 mm width x 50mm depth x 1.6 mm thickness.
150 mm width x 50mm depth x 1.6 mm thickness.
Supply, assembly and laying of 150 mm width x 60mm depth x 1.6 mm thickness, complete with jointing sleeve, horizontal bends, vertical bends, level adjustment components and closer, vertical elbow, covers, access outlet, etc. complete with all other accessories under floor installation including cutting and chasing the floor/ or on surface, making good the same, placing in position and cleaning from inside complete etc. as required
300 mm wide x 38 mm deep raceway (3 compartment)
Providing and fixing 350 x 350 x 60-75 mm deep Gl (hot dip galvanized) raceways made out of 1.6 mm thick sheet steel cross over box complete as required as per specification .
Providing and fixing 300 x 200 x 50 mm deep Gl (hot dip galvanized) raceways made out of 1.6 mm thick sheet steel vertical access box complete as required as per specification.
Supplying and fixing of following sizes of G.l. conduit 1.6mm thick along with accessories in surface / recess including painting in case of surface conduit or cutting the wall and making good the same in case of recessed conduit as required.
Supplying and fixing of CCTV Outdoor Pole As per Site Requirement.
MASTER CLOCK
Supply, Installation, Testing & Commissioning of : a) GPS Synchronized Master clock (1+1) redundant mode, As Per technical Specification - 2 Set b) 4” NTP slave clocks As Per technical Specification - 40 Nos.
ACTIVE NETWORK SYSTEM - ICT
Supply, Installation, Testing & Commissioning of Core Switch, As Per technical Specification
Supply, Installation, Testing & Commissioning of Internet Router, As Per technical Specification
Supply, Installation, Testing & Commissioning of Internet Firewall/ Load balancers, As Per technical Specification
Supply, Installation, Testing & Commissioning of 24 Port Rack Switch for Server management, As Per technical Specification
Supply, Installation, Testing & Commissioning of 24 Port MPLS Switch, As Per technical Specification
Supply, Installation, Testing & Commissioning of 24 Port Access Switch Poe, As Per technical Specification
Supply, Installation, Testing & Commissioning of 48 Port Access Switch Poe, As Per technical Specification
Supply, Installation, Testing & Commissioning of A P Indorama's Per technical Specification
Supply, Installation, Testing & Commissioning of Wireless Controller, As Per technical Specification
Supply, Installation, Testing & Commissioning of NMS,As Per technical Specification
Supply, Installation, Testing & Commissioning of AAA Solution ( in HA ),As Per technical Specification
Supply, Installation, Testing & Commissioning of Server Farm Switch, As Per technical Specification
Supply, Installation, Testing & Commissioning of Distribution Switch Type 3,As Per technical Specification
Supply, Installation, Testing & Commissioning of a) Single Mode Transreceiver Module compatible with proposed Switches, Routers, WLC, Firewall and Server : 40G - 8 Nos. b) Single Mode Transreceiver Module compatible with proposed Switches, Routers, WLC, Firewall and Server : 10G - 350 Nos. c) Single Mode Transreceiver Module compatible with proposed Switches, Routers, WLC, Firewall and Server : 1G - 30 Nos. d) Base-T Transreceiver Module compatible with proposed Switches, Routers, WLC, Firewall and Server : 1G - 30 Nos.
Conference Room AV-Equipment
SITC of Conference Room IT AV System -Video conferencing with Camera-3 Nos, Wireless Chairman discussion unit with pluggable super cardiod mic and battery unit-1Nos,Wireless Delegate discussion unit with pluggable super cardiod mic and battery unit-30Nos. Centrak control unit - 2No,Antenna Module - 1No,Wireless digital Lavalier Microphone of 1.9GHz frequency - 1No,Wireless Handheld digital microphone of 1.9GHz frequency - 4No,Digital Signal Processor - 1No,Thin Edge ceiling speaker - 8No,Digital quad core Class - D Power Amplifier - 2No,2ft X 2ft ceiling microphone tile with 29no. Omni directional microphone - 3No,Wireless Microphone Charger - 4No,Dante Interface - 3No,65" 4K professional display - 1No, 4 X 4 presentation matrix - 1No, Control system - 1No,I-pad Mini - 1No,Software license - 1No,Wireelss Presentation device - 1No,Cable cubby - 4No,Complete required as per Technical specification.
VIP Lounge AV-Equipment
Supply, Installation, Testing & Commissioning of Mobile connect device to transmit the audio over Wi-Fi, as per the given next specifications : Low latency audio streaming in stereo, Resolution AD : 24bit Resolution AD : 48KHz, Signal-to-noise ratio (SNR) : 116 dbA @ 44.1 kHz THD+N : < -104 dB, < 0.00063 %, Frequency response : 5 Hz to 21.5 kHz or better, SPDIF/AES : - 9-pin digital breakout cable with two RCA connectors as coaxial SPDIF I/O, Inputs : 1x RCA (XLR), transformer balanced, High-sensitivity input stage (< 0.3 Vpp), Lock range : 27 to 200 kHz, Jitter : < 0.025 UI (4.4 ns @44.1 kHz) ADAT/SPDIF :-, Input : TOSLINK, Standard : 8 channels, 24 bit, up to 48 kHz, Sample split (S/MUX) : 4 channels, 24 bit, 96 kHz, Jitter suppression : > 30 dB (2.4 kHz) or better Users : 100 or more over Wi-Fi.
EPABX - IP PBX Telephone System
Supply of Server based IPPBX (should support hot standby redundancy of Call Control Servers without disconnection of single call during switchover) with support upto 3000 lines with following features :- As Per technical Specification (a) 300 IP Users ( Licenses) (b) 48 Analogue Users (c.) 1 Operator Console IP based along with PC (d) 2 PRI Trunk lines (30 Channel) Circuit with CLIP Facility (e) One Number Scheme on all extensions
Supply of : a) 8 port Voice Mail System for Item No.1 with following features:- As Per technical Specification b) Voice Mail Boxes for all users c) PC/Server for installing Voice Mail System to be provided by bidder d) Unified Messaging Solution for 100 users Instruments (As per annexure A of Technical Specifications)
Supply of PC for Installing Operator Console
Supply of PC for Installing Call Billing Software
Supply of PC for Maintenance Console
Supply of Online UPS with Battery backup of 4 Hours
Main Distribution Frame with Modules for 50 users
Server/Network Rack 42 U for EPABX along with all accessories
Analogue PBT CLIP Telephone Instruments as per specification
Executive IP/SIP Telephone Instruments as per specification
High End IP/SIP Telephone Instruments as per specification
Installation, Testing, commissioning and Training of above items
DATA CENTER
SITC of Server Rack with In-Row Cooling, As Per technical Specification
SITC of Rack Intelligent PDU, As Per technical Specification
SITC of Rack Air-Conditioning Unit, As Per technical Specification
SITC of Auto-Changeover - Timer Switch with for N+1 AC Operation, As Per technical Specification
SITC of Biometric + Proxcard Based Access Controller - IP Connectivity Enabled - Standalone Software for Remote Monitoring - Single Point Authentication for Both the Doors, As Per technical Specification
SITC of IP-Camera - 2 Megapixel 1/3" CMOS Sensor in High Resolution - Vari-Focal Lens 3mm - 10mm F1.6 - Built-in IR Illuminator - Micro SD Card Supported (SDHC up to 64GB) - Real-Time Monitoring Over IP As Per technical Specification
SITC of NTP Server, As Per technical Specification
SITC of Domain Server, As Per technical Specification
SITC of DHCP Server, As Per technical Specification
SITC of Web Server, As Per technical Specification
SITC of NMS Server, As Per technical Specification
SITC of Anti Virus Server, As Per technical Specification
SITC of 200TB Centralized Network Storage for Users, As Per technical Specification
SITC of Printer Server for Users, As Per technical Specification
SITC of Rodent Repellent System for Data Center. As Per technical Specification.
PART - B - OPERATION & MAINTENANCE
ELECTRICAL WORK
OPERATION & MAINTENANCE (2 YEAR UNDER DLP & 5 YEAR AFTER DLP)
Operation of DG sets, Transformers, HT Panels, LT Panels, Lightings, UPS, and associated works, as per standard OEM recommendations & practices and as per conditions of contract.
1st year of operation during DLP.
2nd year of operation during DLP.
1st year of operation after DLP.
2nd year of operation after DLP.
3rd year of operation after DLP.
4th year of operation after DLP.
5th year of operation after DLP.
HVAC WORK
OPERATION & MAINTENANCE(2 YEAR UNDER DLP & 5 YEAR AFTER DLP)
Operation of Chillers, AHUs, Cooling Tower, Fans, Pumps and associated works, as per standard OEM recommendations & practices and as per conditions of contract.
1st year of operation during DLP.
2nd year of operation during DLP.
1st year of operation after DLP.
2nd year of operation after DLP.
3rd year of operation after DLP.
4th year of operation after DLP.
5th year of operation after DLP.
BMS WORK
OPERATION & MAINTENANCE (2 YEAR UNDER DLP & 5 YEAR AFTER DLP)
Operation of Building Management Systems and associated works, as per standard OEM recommendations & practices and as per conditions of contract.
1st year of operation during DLP.
2nd year of operation during DLP.
1st year of operation after DLP.
2nd year of operation after DLP.
3rd year of operation after DLP.
4th year of operation after DLP.
5th year of operation after DLP.
FIRE FIGHTING & FIRE ALARM SYSTEM
OPERATION & MAINTENANCE (2 YEAR UNDER DLP & 5 YEAR AFTER DLP)
Operation of Fire fighting system, Fire Alarm and associated works, as per standard OEM recommendations & practices and as per conditions of contract .
1st year of operation during DLP.
2nd year of operation during DLP.
1st year of operation after DLP.
2nd year of operation after DLP.
3rd year of operation after DLP.
4 th year of operation after DLP.
5 th year of operation after DLP.
WATER TREATMENT PLANT
OPERATION & MAINTENANCE (2 YEAR UNDER DLP & 5 YEAR AFTER DLP)
Operation of Water treatment Plant and its associated works, as per standard OEM recommendations & practices and as per conditions of contract .
1st year of operation during DLP.
2nd year of operation during DLP.
1st year of operation after DLP.
2nd year of operation after DLP.
3rd year of operation after DLP.
4th year of operation after DLP.
5th year of operation after DLP.
PART - C1 - ALL INCLUSIVE COMPREHESIVE MAINTENANCE CONTRACT - ELECTRICAL
ELECTRICAL WORK
ALL INCLUSIVE COMPREHESIVE MAINTENANCE CONTRACT
AICMC of DG sets, UPS and associated works, as per standard OEM recommendations & practices and as per conditions of contract.
First year after DLP
Second year after DLP
Third year after DLP
Fourth year after DLP
Fifth year after DLP
HVAC WORK
ALL INCLUSIVE COMPREHESIVE MAINTENANCE CONTRACT (For 5 Year after DLP)
AICMC of Chillers, AHUs, Cooling Tower, Fans, Pumps and associated works, as per standard OEM recommendations & practices and as per conditions of contract.
First year after DLP
Second year after DLP
Third year after DLP
Fourth year after DLP
Fifth year after DLP
BMS WORK
ALL INCLUSIVE COMPREHESIVE MAINTENANCE CONTRACT (For 5 Year after DLP)
AICMC of Building Management Systems and associated works, as per standard OEM recommendations & practices and as per conditions of contract .
First year after DLP
Second year after DLP
Third year after DLP
Fourth year after DLP
Fifth year after DLP
FIRE FIGHTING & FIRE ALARM SYSTEM
ALL INCLUSIVE COMREHESIVE MAINTENCE CONTRACT
AICMC of Fire fighting system, Fire Alarm and associated works, as per standard OEM recommendations & practices and as per conditions of contract .
1st year after DLP.
2nd year after DLP.
3rd year after DLP.
4th year after DLP.
5th year after DLP.
WATER TREATMENT PLANT
ALL INCLUSIVE COMREHESIVE MAINTENCE CONTRACT (Water treatment Plant))
AICMC of Water treatment Plant and its associated works, as per standard OEM recommendations & practices and as per conditions of contract .
First year after DLP
Second year after DLP
Third year after DLP
Fourth year after DLP
Fifth year after DLP
LIFT AND ESCALATORS
ALL INCLUSIVE COMREHESIVE MAINTENCE CONTRACT
All inclusive Comprehensive Maintenance of all Lifts & Escalators after DLP as provided under the main contract including trouble shooting, preventive maintenance and breakdown maintenance etc. as required as per good engineering practice, recommendation of the manufacturer, instructions of Engineer-in-Charge and as per terms and conditions specified.
1st year after DLP.
2nd year after DLP.
3rd year after DLP.
4 th year after DLP.
5 th year after DLP.
PAVA SYSTEM
ALL INCLUSIVE COMREHESIVE MAINTENCE CONTRACT
All inclusive Comprehensive Maintenance of all PAVA System after DLP as provided under the main contract including trouble shooting, preventive maintenance and breakdown maintenance etc. as required as per good engineering practice, recommendation of the manufacturer, instructions of Engineer-in-Charge and as per terms and conditions specified.
First year after DLP
Second year after DLP
Third year after DLP
Fourth year after DLP
Fifth year after DLP
PART - C2 - ALL INCLUSIVE COMPREHESIVE MAINTENANCE CONTRACT - AIRPORT SYSTEM EQUIPMENTS & AIRPORT IT NETWORK
CCTV SYSTEM
ALL INCLUSIVE COMREHESIVE MAINTENCE CONTRACT
All inclusive Comprehensive Maintenance of all CCTV System after DLP as provided under the main contract including trouble shooting, preventive maintenance and breakdown maintenance etc. as required as per good engineering practice, recommendation of the manufacturer, instructions of Engineer-in-Charge and as per terms and conditions specified.
First year after DLP
Second year after DLP
Third year after DLP
Fourth year after DLP
Fifth year after DLP
FID SYSTEM
ALL INCLUSIVE COMREHESIVE MAINTENCE CONTRACT
All inclusive Comprehensive Maintenance of all FID System after DLP as provided under the main contract including trouble shooting, preventive maintenance and breakdown maintenance etc. as required as per good engineering practice, recommendation of the manufacturer, instructions of Engineer-in-Charge and as per terms and conditions specified.
First year after DLP
Second year after DLP
Third year after DLP
Fourth year after DLP
Fifth year after DLP
ALL INCLUSIVE COMREHESIVE MAINTENCE CONTRACT
All inclusive Comprehensive Maintenance of all PFMS after DLP as provided under the main contract including trouble shooting, preventive maintenance and breakdown maintenance etc. as required as per good engineering practice, recommendation of the manufacturer, instructions of Engineer-in-Charge and as per terms and conditions specified.
First year after DLP
Second year after DLP
Third year after DLP
Fourth year after DLP
Fifth year after DLP
DISTRIBUTED ANTENNA SYSTEM (DAS)
ALL INCLUSIVE COMREHESIVE MAINTENCE CONTRACT
All inclusive Comprehensive Maintenance of all Distributed Antenna System (DAS) after DLP as provided under the main contract including trouble shooting, preventive maintenance and breakdown maintenance etc. as required as per good engineering practice, recommendation of the manufacturer, instructions of Engineer-in-Charge and as per terms and conditions specified.
First year after DLP
Second year after DLP
Third year after DLP
Fourth year after DLP
Fifth year after DLP
TRUNK MOBILE RADIO SYSTEM (TMRS)
ALL INCLUSIVE COMREHESIVE MAINTENCE CONTRACT
All inclusive Comprehensive Maintenance of all Trunk Mobile Radio System (TMRS) after DLP as provided under the main contract including trouble shooting, preventive maintenance and breakdown maintenance etc. as required as per good engineering practice, recommendation of the manufacturer, instructions of Engineer-in-Charge and as per terms and conditions specified.
First year after DLP
Second year after DLP
Third year after DLP
Fourth year after DLP
Fifth year after DLP
MATER CLOCK SYSTEM (MCS)
ALL INCLUSIVE COMREHESIVE MAINTENCE CONTRACT
All inclusive Comprehensive Maintenance of all Mater Clock System (MCS) after DLP as provided under the main contract including trouble shooting, preventive maintenance and breakdown maintenance etc. as required as per good engineering practice, recommendation of the manufacturer, instructions of Engineer-in-Charge and as per terms and conditions specified.
First year after DLP
Second year after DLP
Third year after DLP
Fourth year after DLP
Fifth year after DLP
NETWORK ACTIVE SYSTEM
ALL INCLUSIVE COMREHESIVE MAINTENCE CONTRACT
All inclusive Comprehensive Maintenance of all Network Active System after DLP as provided under the main contract including trouble shooting, preventive maintenance and breakdown maintenance etc. as required as per good engineering practice, recommendation of the manufacturer, instructions of Engineer-in-Charge and as per terms and conditions specified.
First year after DLP
Second year after DLP
Third year after DLP
Fourth year after DLP
Fifth year after DLP
IPPBX SYSTEM
ALL INCLUSIVE COMREHESIVE MAINTENCE CONTRACT
All inclusive Comprehensive Maintenance of all IPPBX System after DLP as provided under the main contract including trouble shooting, preventive maintenance and breakdown maintenance etc. as required as per good engineering practice, recommendation of the manufacturer, instructions of Engineer-in-Charge and as per terms and conditions specified.
First year after DLP
Second year after DLP
Third year after DLP
Fourth year after DLP
Fifth year after DLP
DATA CENTER
ALL INCLUSIVE COMREHESIVE MAINTENCE CONTRACT
All inclusive Comprehensive Maintenance of all Data Center after DLP as provided under the main contract including trouble shooting, preventive maintenance and breakdown maintenance etc. as required as per good engineering practice, recommendation of the manufacturer, instructions of Engineer-in-Charge and as per terms and conditions specified.
First year after DLP
Second year after DLP
Third year after DLP
Fourth year after DLP
Fifth year after DLP
stage.html
html • 0.05 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.07 MB
Download all tender documents and submit your bid