| 1 | M/S GURBACHAN SINGHInferred winner L1₹47.2 LQualified | L1 | Qualified MII | |
| 2 | L2₹47.5 L+₹27,567 (0.58%)Qualified | L2 | Qualified MSE, MII, Category: General | |
| 3 | L3₹47.6 L+₹38,806 (0.82%)Qualified AIR FORCE ROAD AFS ROAD V P O CHOMON JALANDHAR PUNJAB 144103 | JALANDHAR | PUNJAB | 144103 | L3 | Qualified MSE, MII, Category: General | |
| 4 | L4₹47.9 L+₹63,334 (1.34%)Qualified | L4 | Qualified MSE, MII, Category: General |
Tender Value
Refer Docs
EMD Value
Exempted
Closing Date
7 Aug 2026, 2:00 pmClosed
Supply laying and testing cable XLPE insulated screened PVC bedded galvanized steel etc.
Excavation in trenches not exceeding 1.5 m width and not exc 1.5m in depth etc.
Returning filling in including spreading levelling watering and well ramming in layers etc.
Removal of surplus soil to a distance not exceeding 50 m and depositing etc.
Supply and lay of PCC cable cover class HV type 1 flat size 300mmx180mmx40mm etc.
Supply and lay for dry clean dirtless river sand filling for cable protection with a layer of 8cm deep before laying and 15cm etc.
MandL for Double Wall Corrugated DWC High density polyethylene pipes HDPE of 90mm dia etc.
MandL for fixing GI tubing 80mm dia light grade use for the protection of cable etc.
MandL for manual boring under road crossing and laying pipe across the road etc.
SandF PCC cable route marker of size 900x300x70mm embossed with HT UG cable 11kV etc.
MandL Cable jointing kit for 11 KV Earthed grade cable for outdoor termination Heat shrink type joint etc.
M and L Cable jointing kit for 11 KV Earthed grade cable for straight through heat shrink type etc.
Pick Axe as per IS 273 (Q4)
9585178
GEM/2026/B/7768168
Two Packet Bid
Supply laying and testing cable XLPE insulated screened PVC bedded galvanized steel etc.,Excavation
Bardhaman, West Bengal
Total value wise evaluation
BOQ
6 documents required · 6 mandatory
2 yrs
30%
Exempted
Yes
12 Aug 2026
25 Jul 2026
7 Aug 2026
| Item No | Item Title | Description | Qty | Unit | Consignee | Delivery (days) |
|---|---|---|---|---|---|---|
| 1 | Supply laying and testing cable XLPE insulated screened PVC bedded galvanized steel etc. | Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, 11000 volts grade, of size 120 sq mm 3 core all as specified and as directed. | 2,060 | RM | Bardhaman | 90 |
| 2 | Excavation in trenches not exceeding 1.5 m width and not exc 1.5m in depth etc. | Excavation in trenches not exceeding 1.5 m width and not exc 1.5m in depth getting out in soft/loose soil all as specified and as directed. | 792 | CUM | Returning Filling In Including Bardhaman Spreading Levelling Watering | 90 |
| 3 | Returning filling in including spreading levelling watering and well ramming in layers etc. | Returning filling in including spreading levelling watering and well ramming in layers not exceeding 25 cm in thick using excavated soft/loose soil all as specified and as directed. | 613 | CUM | Bardhaman | 90 |
| 4 | Removal of surplus soil to a distance not exceeding 50 m and depositing etc. | Removal of surplus soil to a distance not exceeding 50 m and depositing where directed by Engr in charge. | 179 | CUM | Bardhaman | 90 |
| 5 | Supply and lay of PCC cable cover class HV type 1 flat size 300mmx180mmx40mm etc. | Supply and lay of PCC cable cover class HV type 1 flat size 300mmx180mmx40mm complete all as specified and directed. | 9,785 | Each | Bardhaman | 90 |
| 6 | Supply and lay for dry clean dirtless river sand filling for cable protection with a layer of 8cm deep before laying and 15cm etc. | Supply and lay for dry, clean, dirtless river sand filling for cable protection with a layer of 8cm deep before laying and 15cm covering above the top edge of cable after laying & punned down to required height, complete all as specified and as directed.
Note . Only punned thickness shall be measured & paid. | 158 | CUM | Bardhaman | 90 |
| 7 | MandL for Double Wall Corrugated DWC High density polyethylene pipes HDPE of 90mm dia etc. | M&L for Double Wall Corrugated (DWC) High density polyethylene pipes (HDPE) of 90mm dia laid in trenches for cable protection complete all as spcified and directed. | 20 | RM | Bardhaman | 90 |
| 8 | MandL for fixing GI tubing 80mm dia light grade use for the protection of cable etc. | M&L for fixing GI tubing 80mm dia light grade use for the protection of cable all as specified and directed by Engr in Charge. | 59 | RM | Bardhaman | 90 |
| 9 | MandL for manual boring under road crossing and laying pipe across the road etc. | M&L for manual boring under road crossing and laying pipe across the road for laying cables complete all as specified and as directed. | 59 | RM | Bardhaman | 90 |
| 10 | SandF PCC cable route marker of size 900x300x70mm embossed with HT UG cable 11kV etc. | S&F PCC cable route marker of size 900x300x70mm, embossed with HT UG cable 11kV and excavation of 40cm depth, grouted in and including PCC (1.2.4) type B 2 (using 20mm graded stone aggregate) complete all as specified and directed. | 50 | each job | Bardhaman | 90 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
bid_9585178.pdf
GEM_BID • 0.16 MB
demand_2026-07-09-18-28-20_e116e42bc723d7f266afc61f78f8b16e.pdf
BOQ • 0.17 MB
36_2026-07-09-18-28-20_7195891292d79d3f3311df2714c1490b.csv
BOQ • 0.00 MB
gtc.pdf
GEM_OTHER • 0.71 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .