Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.5 LAccepted-AOC | L1 | Accepted-AOC L1 BIDDER | |
| 2 | L2₹11.4 L+₹1.4 L (13.6%)Rejected-AOC | L2 | Rejected-AOC OTHER THAN L1 | |
| 3 | L3₹11.4 L+₹1.4 L (13.9%)Rejected-AOC | L3 | Rejected-AOC OTHER THAN L1 | |
| 4 | L4₹12.5 L+₹2.5 L (24.7%)Rejected-AOC PLOT NO 2 INDUSTRY AREA NEAR LAL WARE HOUSE OPP OLD HOUSING BOARD COLONY SIRSA SIRSA HARYANA 125055 | SIRSA | HARYANA | 125055 | L4 | Rejected-AOC OTHER THAN L1 | |
| 5 | Rejected-Technical | - | Rejected-Technical ENLISTMENT LETTER APPX NOT UPLOADED HAVING CAT REQUIRED |
Tender Value
₹15 L
EMD Value
₹30,000
Closing Date
13 Dec 2021, 6:00 pmClosed
CWE YOL
HQ CWE YOL CANTT
REPAIR/ MAINTENANCE AND IMPROVEMENT OF E/M INSTALLATION, REPAIR TO DG SETS, PUMP MOTOR AND MES INSTALLATION FENCING AND DRAIN AT PALAMPUR
2021_MES_488188_1
CWE/Y-59/2021-22
Open Tender
Civil Works
Item Rate
180 days
PALAMPUR
AS PER NIT
8 documents required · 8 mandatory
₹500
Yes
GE Palampur
₹30,000
Yes
10 Feb 2022
13 Nov 2021
21 Dec 2021
13 Nov 2021
13 Dec 2021
29 Nov 2021
Amount
Excavation in trenches, not exceeding 1.5 mtr wide and not exceeding 1.5 mtr in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. not exceeding 10 Sqm on plan and not exceeding 1.5 mtr in depth and getting out in any type of soil, complete all as specified and directed.
Returning filling in (soil) including spreading, levelling, watering and well ramming in layers n.exc 25cms thick in any type of soil complete all as specified and directed.
Removing excavated materials/ soils, not exceeding 50mtrs and depositing where directed at a level not exceeding 1.50mtrs, complete all as specified and directed.
Sand cushioning to protection of underground cables, laid 8 Cm before laying and 15 Cm after laying of cable, and punned to form an overall layer of 18 Cms thick, complete all as specified and directed Note: Punned thickness shall be measured.
Sub class ‘B brick, old size, brick covering laid dry, flat, transversally along the length of cable on sand cushioning, with width equal to the length of the brick including taking out old bricks, complete all as specified and directed.
Mild steel galvanised iron tubing light grade for cable protection as in road crossing, along poles, walls, floors, drain of 80mm size fixed with MS clamps, nuts and bolts required complete all as specified and directed.
Mild steel galvanised iron tubing light grade for cable protection as in road crossing, along poles, walls, floors, drain of 50mm size fixed with MS clamps, nuts and bolts required complete all as specified and directed.
Mild steel galvanised iron tubing light grade for cable protection as in road crossing, along poles, walls, floors, drain of 40mm size fixed with MS clamps, nuts and bolts required complete all as specified and directed.
XLPE insulated, armoured heavy duty, LT under ground, electric cable with aluminium conductor, 1100 volts grade, cross sectional area 120 Sqmm, 3.5 core laid in trenches, passing through pipe/ ducts/ surface of wall ceiling etc including testing complete all as specified. Note:- Excavation & Earth work, cable cover and sand cushioning shall be measured and paid separately.
XLPE insulated, armoured heavy duty, LT under ground, electric cable with aluminium conductor, 1100 volts grade, cross sectional area 95 Sqmm, 3.5 core laid in trenches, passing through pipe/ ducts/ surface of wall ceiling etc including testing complete all as specified. Note:- Excavation & Earth work, cable cover and sand cushioning shall be measured and paid separately.
XLPE insulated, armoured heavy duty, LT under ground, electric cable with aluminium conductor, 1100 volts grade, cross sectional area 70 Sqmm, 3.5 core laid in trenches, passing through pipe/ ducts/ surface of wall ceiling etc including testing complete all as specified. Note:- Excavation & Earth work, cable cover and sand cushioning shall be measured and paid separately.
XLPE insulated, armoured heavy duty, LT under ground, electric cable with aluminium conductor, 1100 volts grade, cross sectional area 50 Sqmm, 3.5 core laid in trenches, passing through pipe/ ducts/ surface of wall ceiling etc including testing complete all as specified. Note:- Excavation & Earth work, cable cover and sand cushioning shall be measured and paid separately.
XLPE insulated, armoured heavy duty, LT under ground, electric cable with aluminium conductor, 1100 volts grade, cross sectional area 35 Sqmm, 3.5 core laid in trenches, passing through pipe/ ducts/ surface of wall ceiling etc including testing complete all as specified. Note:- Excavation & Earth work, cable cover and sand cushioning shall be measured and paid separately.
XLPE insulated, armoured heavy duty, LT under ground, electric cable with aluminium conductor, 1100 volts grade, cross sectional area 25 Sqmm, 3.5 core laid in trenches, passing through pipe/ ducts/ surface of wall ceiling etc including testing complete all as specified. Note:- Excavation & Earth work, cable cover and sand cushioning shall be measured and paid separately.
XLPE insulated, armoured heavy duty, LT under ground, electric cable with aluminium conductor, 1100 volts grade, cross sectional area 16 Sqmm, 4 core laid in trenches, passing through pipe/ ducts/ surface of wall ceiling etc including testing complete all as specified. Note:- Excavation & Earth work, cable cover and sand cushioning shall be measured and paid separately.
Supply and spreading graded crushed stone aggregate 40mm size around two pole/ four pole structure in 15 cm thickness after cleaning area by removing existing wild grass,vegetation,creepers, small plants / bushes etc complete all as specified and directed.
Cutting and removing grass, vegetation, creepers, small plants / bushes etc clamping up towards the poles and stays etc including cleaning bottom surface area of pole & stay not less than 1m x 1m by surface dressing of earth outside and inside substations, perimeter fencing around pump house area, and in drains surrounding area from site complete all as specified and directed.
Renewal of MCCB any size/ capacity with MCCB, 4 pole, 125 Amps, 25 KA, 415V, adjustable microprocessor release & suitable thimbles/ extended terminal with nuts, bolts and washers etc including minor required additional/ alternation for fixing and connecting up of MCCB in existing panel all as directed by Engr-in-charge.
Renewal of MCCB any size/ capacity with MCCB, 4 pole, 160 Amps, 25 KA, 415V, adjustable microprocessor release & suitable thimbles/ extended terminal with nuts, bolts and washers etc including minor required additional/ alternation for fixing and connecting up of MCCB in existing panel all as directed by Engr-in-charge.
Renewal of MCCB any size/ capacity with MCCB, 4 pole, 200 Amps, 35/36 KA, 415V, adjustable microprocessor release & suitable thimbles/ extended terminal with nuts, bolts and washers etc including minor required additional/ alternation for fixing and connecting up of MCCB in existing panel all as directed by Engr-in-charge.
Repair, maintenance & complete servicing of Mechanical Laundry Machine installed at MH Palampur complete including replacement of unserviceable parts ie. heating coils, dampner springs, drying tumbler, fan belts, thermostat switch, relay capacitor, over load protector, starting knob etc, rewiring if required checking of electrical circuit including oiling, greasing of motor etc for smooth functioning, complete all as specified and directed.
M & L required for inspection, maintenance and servicing of DG sets of following capacities including alternator, electric panel board connection to DG set for routine check (B-Check) of DG set for smooth functioning and carrying out maintenance complete all as directed and specified. Note: (i) B-Check once in six month OR 250 Hrs running of DG set whichever is earlier. (ii) B- Check of all DG sets once shall be paid as one Job (iii) All major spare parts as required and described here-in--after shall be measured and paid separately as supply only and replace only with existing make and minor are included in this item. Contractor quoted rate for this item shall be included this provision and nothing extra shall be admissible. (a) 250 KVA Capacity, make: Kirloskar (Location: Signal Centre)-01 No (b) 140 KVA Capacity, make: Mahindra (Location: MH Sub Station)-01 No (c) 82.5 KVA Capacity, make: Mahindra (Location: VBA)-01 No (d) 75 KVA Capacity, make: Cummins (Location: Local Signal Centre)-01 No (e) 62.5 KVA Capacity, make: Mahindra (Location: 'A' Tank, MES bore well & POI)-03 Nos (f) 40 KVA Capacity, make: Cummins (Location: STP range, Snow view, supply point)-03 Nos
Note: (i) Repeat the activities of A check replacement of lubricating oil. (ii) Replacing lubricant oil filter element with 'O' ring. (iii) Replacing fuel filter element. (iv) Replacing coolant. (v) Replacing Governor oil. (vi) Coolant, Lubricant oil shall be measured and paid separately under relevant items. (vii) Contractor shall employ skilled labour (FGM) for the above repairs and one company engineer/ technician for over all repairs (viii) Replacing water separator (ix) Cleaning of Radiator with chemicals (x) Replacement of by pass filter. (xi) Checking of all radiator rubber hose and replacement if required. (xii) Checking and recording oil pressure, water and oil temperature. (xiii) Checking anti vibration mounting and replacement if required. note : Anti vibration pad shall be measured and paid separately. (xiv) Checking throttle linkage. (xv) Checking battery for cell test, electrolyte level, gravity and topping up to required level. (xvi) Routine check/ repair work of panel, switch, MCCB, main switch, all contactors, engine control unit. (xvii) Checking of AMF panel, all electrical connections etc. (xviii) Checking of earthing resistance. (xix) Cleaning of vegetation around the DG set up to 1.5 mtr area.
Supply only diesel filter (Primary & Secondary) suitable for 250 KVA DG Set.
Supply only diesel filter (Primary & Secondary) suitable for 140 KVA DG Set.
Supply only Diesel filter (Primary & Secondary) suitable for 85.5 KVA DG Set.
Supply only Diesel filter (Primary & Secondary) suitable for 75 KVA DG Set.
Supply only Diesel filter (Primary & Secondary) suitable for 62.5 KVA DG Set.
Supply only Diesel filter (Primary & Secondary) suitable for 40 KVA DG Set.
Supply only Engine oil filter with 'O' ring suitable for 250 KVA DG Set.
Supply only Engine oil filter with 'O' ring suitable for 140 KVA DG Set.
Supply only Engine oil filter with 'O' ring suitable for 82.5 KVA DG Set.
Supply only Engine oil filter with 'O' ring suitable for 75 KVA DG Set.
Supply only Engine oil filter with 'O' ring suitable for 62.5 KVA DG Set.
Supply only Engine oil filter with 'O' ring suitable for 40 KVA DG Set.
Supply only fuel flexible PVC pipe wire braded of existing size
Supply only oil pressure fuel injector pump
Supply only solenoid valve
Supply only oil pressure gauge.
Supply only oil pressure Switch.
Supply only Water temperature gauge
Supply only Ignition switch.
Supply only indicating lamp
Supply only battery terminal heavy duty of brass with nuts and bolts
Supply only Distilled water
Supply only coolant for radiator.
Supply only 20 W 40/ 15 W 40 turbo synthetic superior quality engine oil. Make: Kirloskar/ Catrol/ Volvoline/ servo/ HP/ IOC Note: contractor has to supply engine oil of make as recommended by DG set manufacturer.
Supply only fan belt of approved.
Supply only self starter 12 volts (Make: Lucas/TVS
Supply only self starter 24 volts (Make: Lucas/TVS
Supply only air filter
Supply only asbestos rope of slandered size
2.50m long battery lead heavy duty, multi stranded copper conductor, PVC insulated 35 sqmm single core including soldering of copper lugs.
AVR for DG set 125 KVA complete all as specified and directed.
Dry type maintenance free battery heavy duty 12 volts, 180 AH with initial charging.
Dry type maintenance free battery heavy duty 12 volts, 90 AH with initial charging.
Supply only off load change over switch with enclosure four pole, 415 V 250 Amp.
Four pole contractor suitable for 250 KVA DG set.
Four pole contractor suitable for 140 KVA DG set.
Four pole contractor suitable for 82.50 KVA DG set.
Four pole contractor suitable for 75 KVA DG set.
Controller for 82.50 KVA to 250 KVA DG Set.
HRC fuse for short circuit protection for 75 KVA to 250 KVA DG Set.
Disconnecting existing un-serviceable ammeter, supply and fix digital type Ammeter with CT's.
Supply, fix and connecting 12 volts, 65 AH dry type maintenance free battery for solar light complete with initial charging including taking down old unserviceable battery complete all as specified and directed by Engineer-in-charge.
Draining up the fuel from the existing diesel tank in a separate empty container and disconnecting from the DG set and cleaning internally and out site by removing sludge, mud, water etc and repairs the leakage if any be means of soldering and refixing in the same position, renewal of flexible type fuel pipe of existing size and length and make, refill the fuel for any capacity of DG set complete all as specified and as directed by Engineer-in Charge.
Repair and servicing of alternator of DG set 75 KVA by disconnecting from Engine, opening the front and rear cover, taking out rotor, cleaning the rotor and starter, applying two coats of insulation varnish to the winding, polishing the step rings including replacing carbon bushes, ball bearing etc, resembling the same, testing and refixed in same position complete all as specified and as directed by Engineer-in-charge.
Repair and servicing self starter of DG set (any capacity of DG set) by replacement of burn field coil replacement of armature and carbon bush holder and carbon bush point and solenoid coil and other repairs to make functional complete ass as specified and as directed by Engineer-in-charge.
Dismantling the radiator and fan from the engine for cleaning of copper/ aluminium tubes and cooling find by using descaling solution (MAC solution) and soldering, patch work if required for stop leakage including repair of water pump assembly and replacement of defective parts of water pump and re-assembliying, testing complete 250 KVA DG set complete all as specified and directed by Engineer in Charge.
Dismantling the radiator and fan from the engine for cleaning of copper/ aluminium tubes and cooling fan by using descaling solution (MAC solution) and soldering, patch work if required for stop leakage including repair of water pump assembly and replacement of defective parts of water pump and reassembling, testing complete 140 KVA DG set complete all as specified and directed by Engineer in Charge.
Dismantling the radiator and fan from the engine for cleaning of copper/ aluminium tubes and cooling fan by using descaling solution (MAC solution) and soldering, patch work if required for stop leakage including repair of water pump assembly and replacement of defective parts of water pump and reassembling, testing complete 82.50 KVA DG set complete all as specified and directed by Engineer in Charge.
Dismantling the radiator and fan from the engine for cleaning of copper/ aluminium tubes and cooling fan by using descaling solution (MAC solution) and soldering, patch work if required for stop leakage including repair of water pump assembly and replacement of defective parts of water pump and re-assembliying, testing complete 75 KVA DG set complete all as specified and directed by Engineer in Charge.
Dismantling the radiator and fan from the engine for cleaning of copper/ aluminium tubes and cooling fan by using descaling solution (MAC solution) and soldering, patch work if required for stop leakage including repair of water pump assembly and replacement of defective parts of water pump and re-assembliying, testing complete 62.50 KVA DG set complete all as specified and directed by Engineer in Charge.
Dismantling the radiator and fan from the engine for cleaning of copper/ aluminium tubes and cooling fan by using descaling solution (MAC solution) and soldering, patch work if required for stop leakage including repair of water pump assembly and replacement of defective parts of water pump and re-assembliying, testing complete 40 KVA DG set complete all as specified and directed by Engineer in Charge.
Painting to LT panel (Appx size of panel 1200mm & 900mmx 450mm) only after minor body repairs if required like welding, changing hinges, handles, nut bolts etc and complete removal of existing paint and apply two coats of synthetic enamel paint, including writing MES no complete all as specified & directed.
Repairing of 250 KVA voltage stabilizer servo controlled 3 phase input voltage 300-480 volts and output voltage 230 volts AC supply 50Hz by opening complete for inspection defective parts, preparation list of defects for approval of Engineer-in-Charge, dismantling unserviceable parts for replacement, fixing parts with new one, reassembling, commissioning and testing on full load to entire satisfaction of Engineer-in-Charge. Note: All major spare parts as required and described here-in--after shall be measured and paid separately as supply only and replace only with existing make and minor are included in this item. Contractor quoted rate for this item shall be included this provision and nothing extra shall be admissible
Supply only slow speed high torque synchronizing motor of approved make.
Supply only dimmer stat complete with carbon bruch and holder of approved make.
Supply only PCB (printed circuit board) plate electronic circuit 12 pin of approved make.
Supply only RC network for servo motor of approved make.
Supply only Neon lamps with holder for high and low voltage of approved make.
Supply only Auto/ manual toggle switch of approved make.
Supply only Rotary switch for voltmeter of approved make.
Supply only Rotary switch for Amp meter of approved make.
Painting to 50 KVA voltage stabilizer after minor body repairs if required like welding, changing hinges complete removal of existing paint and apply two coats of synthetic enamel paint, including writing MES No complete all as specified & directed.
Painting to 250 KVA voltage stabilizer after minor body repairs if required like welding, changing hinges complete removal of existing paint and apply two coats of synthetic enamel paint, including writing MES No complete all as specified & directed.
Supply, install, testing & commissioning of CPRI approval LT panel board, outdoor type IP-54, floor mounted, factory made suitable for 415 Volt, 3 Phase, 4 wire, 50 HZ, AC supply system having bus bar chamber made out of size 60 cm x 60 cm x 30 cm with angle iron of size 40 x 40 x 5 mm with copper bus bars duly insulated by insulation of RYB colour 200 Amps rating mounted on porcelain insulators. The panels shall be factory made , double door, made out of 3.15 mm thick MS sheet (CRCA) totally enclosed dust, vermin & rust proof front operated, front & rear opening with locking arrangement fixed with MS angle iron frame of size 40x40x6 mm and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multi stranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable etc all as directed at site and comprising of the following:-
(a) MCCB 160 A, 4P, 415 Volts AC supply , thermal magnetic release type 36 KA-01 No (Incomer) (b) MCCB 125A, 4P, 415 Volt ,25 KA thermal magnetic release type -02 Nos. (Outgoing) (c) Panel mounted multi function meter for measuring Voltage (0-500 Volts), Current (0- 100 Amps) and frequency-01 No (d) RYB neon indicating lamp panel mounting type (Set of three ) - 01 N0. (e ) Internal wiring of the panel board with single core copper cable PVC insulated of suitable size and control fuses (f) Cable entry gland and two nos earthing terminal
Earthing complete with galvanised steel earth plate electrode 60cmx60cmx6mm thick buried directly in ground (earth pit not less than 2.25 meter deep below normal ground level) with top edge of plate not less than 1.5 meter below ground level, connecting to galvanised iron strip 32mm x 6mm (as earth lead strip), by means of bolt, nuts, check nuts and washer of galvanised and earth wire protected by provision of galvanised iron pipe light grade, 15mm bore including provn of concrete pit in PCC M-15, type B-I using 20mm graded crushed stone aggregates with 40mm thick precast cover of size 550 mm X 550 mm X 75 mm of RCC M-15, type B-I, reinforced with XPM (weight not less than 4 kg/ Sqm) and frame of angle iron 25x25x3mm with lugs 2 Nos and with 6mm dia mild steel bar handle made to shape, galvanised iron medium grade 20mm bore pipe for watering perforated at bottom 1.75 meter long placed on top edge of earth plate, common salt and charcoal filling, test point made out of phosphorous bronze with fixing arrangement, funnel, wire mesh and including earth work in any type of soil, returning filling in and removal of surplus soil to a distance not exceeding 50 meter, all as per electrical plate No. 3 of SSR 2009 Part-I and connection to earth test point all as specified and testing on completion.
Deduct Credit Amount as per Schedule of credit as details given on Srl Page No 20 of tender doucments.
M/s Raj Construction
M/s Sheetal Associates
M/S ASHWANI KUMAR AND COMPANY
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .