The Executive Engineer KSHED
O/o The Executive Engineer Kolkata South Health Electrical Division P.W.Dte. 75, Diamond Harbour Road, Kolkata - 700 023
Annual comprehensive maintenance of Fire Detection System installed at different buildings in the campus of IPGMER SSKM Hospital Kolkata and its Annex Hospitals and Institute of Psychiatry, Kolkata under SSKM H Electrical Sub Division, PWDte.
2026_WBPWD_994328_1
WBPWD/EE-I/KSHED/Q105/25-26
Open Tender
Support/Maintenance Service
Item Rate
365 days
SSKM kolkata
As per Notice
6 documents required · 6 mandatory
₹64,000
O/o The Executive Engineer Kolkata South Health El
17 Feb 2026
27 Jan 2026
16 Feb 2026
27 Jan 2026
14 Feb 2026
31 Jan 2026
30 Jan 2026
Day to day preventive & corrective maintenance of the entire Fire Detection system installed at different buildings within the premises of IPGME&R-SSKM Hospital and it's Annex Hospitals by engaging technical personnel having adequate knowledge & skill in fire detection system as per terms & condition.
Semi-skilled labour - 4 Nos staff
Un-Skilled labour - 4 Nos staff
Replacement cost for following supply & installation of spare parts (Consumable spares & Emergency spares) as and when required for annual preventive and corrective maintenance of Fire Detection System. (As per attached Annexure I & II)
SITC of Microprocessor based Intelligent, addressable fire alarm control panel ( VDS / UL / FM / ULC approved ) fully networkable having requisite numbers of loop with 20% spare capacity with each loop capable of taking requisite number of devices as per latest IS/NBC, 1/4 VGA display character alpha-numeric liquid crystal display.The panel shall be soft addressable type.The panel shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches when ever any alarm is triggered.The Panel should be able to store sufficient numbers of log events in its Memory as per recommended standards. IS / NBC. Shiuld have the provision for incorporating with BMS.
The panel shall have in built rectifier, provision for external & internal printer ( if required ), Loop cards (no field loop card is allowed), L C D unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, in built Surge protection facility, integral SMF lead acid batteries with sealed cells of 24 V capable of running for 24 hours normal working and then be capable of operating the system for 30 minutes during Emargency condition, with integral battery charger complete as required.
The FACP shall be capable of being networked ( future expansion ) with other similar FACP located at different part of the premises through single RS 485 bus.The FACP shall have provision for interfacing with the public address system and BMS( RS 485 ). The panel should have modbus output & ready to communicate with remote computer. The system must be preloaded with licenced software. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/Honeywell/ Notifer / Edward /Secutron/ Securiton).
4 Loop (Make - Siemens / Cerberus Pro)
2 Loop (Make - Esser / Honeywell)
SITC of Analog Addressable Intelligent multisensor detector ( VDS / UL / FM / ULC approved ) with inbuilt optical smoke sensors as well as additional heat detector sensor with decentralise intelligence, soft addressable Photothermal type with inbuilt fault isolator as per NFPA style 7 wiring complete with base having IP as per recommended standard.(Note : Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices ( Numbers of addressable devices in a group will be as per latest recommended IS / NBC ) without any additional cost).
Multisensor detector (Make - Siemens / Cerberus Pro)
Multisensor detector (Make - Esser / Honeywell)
Multisensor detector (Make - Bosch / Applo / GST)
SITC of Addressable Heat Detector (Fixed temperature cum rate of rise) ( VDS / UL / FM / ULC approved ) with twist lockable removal base, built - in fault isolator, drift compensation feature etc including connections as per specifications complete as reqd and having IP as per recommended standard(Note : Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices ( Numbers of addressable devices in a group will be as per latest recommended standards ) without any additional cost).
Heat Detector (Make - Siemens / Cerberus Pro)
Heat Detector (Make - Esser / Honeywell)
Heat Detector (Make - Bosch / Applo / GST)
SITC of Addressable Manual Call Point ( VDS / UL / FM / ULC approved )soft addressable type with in built fault isolator as per NFPA style 7 wiring complete as required.
MCP (Make - Siemens / Cerberus Pro)
MCP (Make - Esser / Honeywell)
MCP (Make - Bosch / Applo / GST)
SITC of Addressable Loop Powered Hooter ( sound output of minimum 90 db ) cum strobe (strength of light 10 cd)complete with inbuilt isolator & IP65 base and ( VDS / UL / FM / ULC approved) approved.
Loop Power Hooter (Make - Siemens / Cerberus Pro)
Loop Power Hooter (Make - Esser / Honeywell)
Loop Power Hooter (Make - Bosch / Applo / GST)
SITC of Addressable transponder/ Monitor Modules ( VDS / UL / FM / ULC approved ) for monitoring flow switches/Fire exit doors / AHU / Lift etc complete as required.
Module (Make - Siemens / Cerberus Pro)
Module (Make - Esser / Honeywell)
Module (Make - Bosch / Applo / GST)
SITC of LED type Response Indicator ( VDS / UL / FM / ULC approved) having 2 Nos. red coloured LED lamps including connections etc.
Response Indicator (Make - Siemens / Cerberus Pro)
Response Indicator (Make - Esser / Honeywell)
Response Indicator (Make - Bosch / Applo / GST/Agni)
S&F of MCP Glass in place of damaged oneas per sample installed at different building or as per direction of EIC.
S&F 12V, 7 Ah UPS Battery FR Type (Make: Exide/Amaron ).
Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded copper Cable (For Loop) (Make - Havells/RR Kable/Polycab/Gloster) in existing prelaid PVC pipe as per direction of EIC.
Supply & Laying of with 20 mm NB PVC rigid conduit pipe (Make: Precision /Polycab) on the surface of the wall as per direction of EIC
The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them.
Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill.
Rate Should be quoted inclusive of LWC and all other related taxes & duties.
Defect Liabibility Period 1 (One) year
Make & model of each and every material to be approved by EIC
stage.html
html • 0.02 MB
cancelled_1.pdf
pdf • 0.32 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 1.32 MB
TenderForm.pdf
Tender Documents • 0.69 MB
AnnexureI.pdf
Tender Documents • 0.16 MB
BOQ_2432640.xls
BOQ • 0.41 MB
TandCPdf.pdf
Tender Documents • 0.53 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .