CWE (AF) CHILODA
CWE (AF) CHILODA MES PO CRPF CAMPUS VAYUSHAKTINAGAR GANDHINAGAR 382042
REPAIR AND MAINT OF HT VCB HT DISTRIBUTION SYSTEM AND REPLACEMENT OF HT UG CABLES AT DARJIPURA AF STATION BARODA
2020_MES_399267_2
82066/BRD/E8
Open Tender
Civil Works
Item Rate
180 days
Vadodara
AS PER TENDER DOCUMENTS
6 documents required · 6 mandatory
₹500
GE (AF) BARODA
₹50,000
Yes
1 Feb 2021
4 Jan 2021
27 Jan 2021
4 Jan 2021
25 Jan 2021
12 Jan 2021
5 Jan 2021 - 11 Jan 2021
Amount
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth and getting out in hard/ dense soil for foundation of poles, structures, stay rods, laying of underground cable etc complete all as specified
Excavation in trenches not exc1.5mtr wide , exc.1.5mtr and n.exc 3mtr in depth for foundation of stay/ pole and etc and getting out in hard/dense soil complete all as specified
Returning, filling in soils including spreading, leveling, watering and well ramming in layers each not exceeding 25cm thick complete all as specified
Removing excavated soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified
M&L Sand cushioning with coarse sand in trenches for protection of under ground electric cable, spread in uniform thick 23cm and punned down gently to 18cm after laying cable in trenches complete all as specified and as directed. (NOTE :- Compacted thickness shall be measured and paid)
Supply and laying un-reinforced precast concrete cable cover, class HVP, Type 1 with peak, size 300mm x 180mm x 40mm laid flat dry, in trenches with width of cable cover laid to the axis the of cable for protection of cable complete all as specified and as directed
M&L Plain cement concrete (1:4;8) type D2 using 40 mm graded stone aggregate as in base of foundation complete all as specified
M&L Plain cement concrete (1:3;6) type C2 using 40 mm graded stone aggregate as in foudation including form work complete all as specified
M&L PCC (1:2:4) type B1 (using 20mm graded stone aggregate) as in coping including necessary formwork complete all as specified
M & L Graded stone aggregate of size 40mm grade complete for two pole and four pole structure complete all as specified and directed by Engineer-In-Charge.
M&L Boring of horizontally holes under the road below 1.5 mtr from the road/hard surface by trenchless technology using ultra sound technique and including necessary machine without damaging the existing road and getting out in any type of soil and disposal of soil to a distance not exceeding 50m from the site of work including provision of HDPE pipe of 150 mm dia suitable for 0.4 MPA work pressure
Supply , laying , testing and commissioning of 3 core, 95 Sqmm, 11000 Volts grade(Earthed) XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminum conductor laid in trench/under ground/ wall/ surafce/ tunnel/duct complete as in repairs all as specified
S&F Cable jointing kit suitable for 11 KV grade cable for in door termination heat shrinkable type joint complete with jointing materials and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 Sqmm as in repair
M&L Cable jointing kit for 11 KV (earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 Sqmm complete as in repairs all as specified
M&L Cable jointing kit for 11 KV grade cable for out door termination heat shrinkable type joint complete with jointing materials and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 Sqmm as in repairs all as specified
M&L GI tubing 100 mm dia, light grade for cable protection at road crossing / on poles and tubing sealed at both ends after laying the cables complete as in repairs all as specified
M&L GI tubing 80 mm dia, light grade for cable protection at road crossing / on poles and tubing sealed at both ends after laying the cables complete all as directed
S&F Digital type Ammeter suitable for upto 0-/50/100/200/500 Amps as required at site complete with required accessories for fixing in existing VCB/panel complete as in repairs all as specified
S&F Test position on indication Lamp suitabe for fixing on VCB complete as in repairs all as specified
Disconnecting the electric supply and Servicing of 11 KV AB switches upto 400 Amps by disconnecting, overhauling, greasing and re-assembling same in its original existing position, testing & commissioning including complete all as directed by Engr-in-Charge
Supply only Male contacts suitable for 11 KV Air Break switch including taking down old unserviceable item complete all as directed by Engr-in-Charge.
Supply only Female contacts suitable for 11 KV Air Break switch including taking down old unserviceable item complete all as directed by Engr-in-Charge.
S & F Disc insulator single disc 11 KV grade porcelain vitreous brown or green 145mm high and 255 mm dia complete as in repairs all as specified
S & F Pin type insulator 11 KV grade porcelain vitreous brown or green insulator including one galvanised iron washer and one nut 150mm high and 150 mm dia complete as in repairs all as specified
S&F post top porcelain insulator vitreous brown with GI clamp nuts bolts etc suitable for 11000 Volts grade working pressure complete complete as in repairs all as specified
S&F VCB Breaker Tripping coil 32 VDC suitable to fixing on VCB Panel No3 of MAP Area as in repairs all as specified
Earthing complete with galvanised steel earth plate electrode 600x600 x6mm thick buried directly in ground earth pit not less than 2.25 mtr deep below normal ground level ) with top edge of plate not less than 1.5m below ground level, connecting to the Galvanised iron strip 32X6 mm , by means of nuts, bolts, check nuts and washer etc of galvanised iron and earth lead protected by provision of GI pipe light grade 40mm bore from earth elelctrode to test point including provn of concrete pit in PCC (1:2:4) type B-1 using 20mm graded stone agagregates with 40mm thick cover of RCC (1:2:4) reinforced with XPM (weight not less than 4Kg/Sqm) and frame of angle iron 25 x 25x6mm with lugs 2 Nos and with 6mm dia MS bar handle made to shape, GI pipe light grade 20mm bore pipe for watering perforated at bottom 1.75 mtr long placed on top edge of earth plate, common salt and charcoal filling test point made out of Bronze/Gun metal with fixing arrangement, funnel, wire mesh and earth work in hard/dense soil, returning in and removal of surplus soil to a distance not exceeding 50mtr, all as per electrical plate No 5 of SSR Part-I and connection to earth test point all as specified incl testing on completion. Note :- Item of Earthing includes cost of 7.5m long galvanised iron earth lead 32X6 mm mm size and protection pipe of 40 mm bore GI light grade.
S&F Steel tubalar swaged poles staying in a truely vertical position till the foundations are properly set with the help crane complete with cast iron base plate, finial taper plug, bolts, nuts & screws including drilling of holes to poles for clamps & hooks for running of earth wire/Strip complete all as specified type 410 SP-55,11 mtrs HT poles complete all as directed by Engr-in-Charge. Note:- (i) Crane charges for erection shall be deemed to be including in quoted rate. (ii) Earth work,PCC,coping shall be measured and paid separately. (iii) The rates include staying the poles in atruely vertical position till the foundations are properly set. (iv) The rates include cast iron base plate, nuts, bolts, screws, painting of steel tubular poles, drilling of holes in steel tubular poles for fixing of clamps, hooks for continuous earth wire/strip.
Supply, install , testing,& commissioning of HT 11 KV outdoor type gang operated air break switch triple pole mechanically operated suitable for horizontal or vertical mounting(suitable for existing one) on insulator and steel frame with operating mechanism worked from ground level for current rating up to 400 Amps and connecting up with jumpers,complete as in repairs all as specified
M&L Stay assembly comprising of MS stay plate 6 mm thick and of size 300 x 300 mm and 20 mm dia MS stay rod, 2150 mm long including thimbles GI stay strand 7/3.15 mm dia of required length complete all as shown on electrical plate No.1 on page No.495 of MES SSR Part-I 2009, as specified in SSR complete as in repairs all as specified Note : Loop type insulator, excavation, earth work and concrete shall be measured and paid separately under relevant items of this schedule.
M&L Loop type insulator, vitreous porcelain, white, brown or green, large size with overall dimensions 90 x 140mm size, clearance of hole 25.5 mm complete all as specified and directed by Engr-in-Charge.
M&L Cross arms i.e bracing supporting clamps back plates, nuts, bolts and washers complete including one under coat and one finishing coat with synthetic enamel paint over a coat of red oxide primer complete as in repairs all as specified
Supply , install and testing lightening arrestor expulsion type station class complete with all fittings transmission class, discharge capacity 10 Kilo Amps suitable for 11 KV complete as in repairs all as specified
M&L ACSR jumpers in HT/LT over head line as that of existing size including binding wire, nuts & bolts washers complete all as specified as in repairs.
M&L Danger notice plate of 1.6mm thick mild steel sheet vitreous enameled white, with letters, figures and convention skull and bones in signal red colour and fixed with MS clamps bolts and nuts of approved size for HT 11 KV of size 25 x 20 cm complete as in repairs all as specified
M&L Cradles, hexagonal/rectangular fabricated with galvanised steel 4mm dia complete as in repairs all as specified
Supplying only Tinned Copper fuse wire of 16SWG to 22 SWG or 30 Amps to 200 Amps capacity suitable for 11kV supply
S&F Stringing in position of HT/LT overhead line on pole with continuous aluminum conductor steel reinforced (ACSR) complete as in repairs all as specified
Taking down carefully transformer any capacity(63-315 KVA), any make,any type from pole/plinth by dismantling, disconnecting HT & LT sides, earthing of transformer, supporting angles/cross arms, for repair, opening of top cover, replacing of all joint/types of gaskets HV/LV side(Top,Fins,Conservator tank, HV cable box, LV cable box, radiator etc), HV/LV oil plug, oil filling plug, and reassembling the same after repairs, installing, recommissioning, the transformer at its original place, connecting up HT & LT sides, earthing and supporting angles/cross arms etc and testing & preparing report as per the format attached as appendix and maintaining proper record all as directed by Engr-In-Charge. Note: (i) Spares(other than mentioned above) used will measured and paid saparately the rates quoted shall include labour component. (ii) Once the transformer is taken for repairs, the complete gasket and other jobs mentioned above to be completed irrespective of area/portion of fault. The contractor shall remain responsible for proper functioning of transformer and any kind of leakage after repair for one year and will reattend the repair without any extra cost. Only registered/authoriesd transformer reparing team will be allowed to carryout repairs.
Supply only HV Bushing Make: AP OR Sampat
Supply only HV Complete Metal Part with Stud. Make: Mayur OR GHI
Supply only LV Bushing. Make: AP OR Sampat
Supply only LV Complete Metal Part with Stud. Make: Mayur OR GHI
Supply only Explosion Vent Diaphrarm Change with Gasket.Make:GTPL
Supply only Oil Level Gauge – Flush Type. Make:GTPL
Temperature Gauge with seal. Make: Precimeasure OR Perfect
Supply only Marshalling Box Glass. Make: GTPL
Supply only Silica Gel Breather with assembly. Make: Yogya OR Rinu
Supply only Inspection Chamber and top Led Gasket. Make:Chetak OR Pyramid
Supply only Tap changer Switch assembly with Oil Seal. Make:Nalin
Supply only Conservator oil level glass and gasket.
Supply only HV copper Coil replacement 100 to 160 KVA(per Phase) as per IS
Supply only LV copper Coil replacement 100 to 160 KVA(per Phase) as per IS
Supply only HV copper Coil replacement 250 to 315 KVA(per Phase) as per IS
Supply only LV copper Coil replacement 250 to 315 KVA(per Phase) as per IS Note for item No 39 (i) If the transformer is taken to the workshop it will be responsibility of the contractor to take concerned AGE/JE (E/M) to workshop(strictly at vadodara) and show the parts to be replaced. Proper job card and replaced parts along with proper bill and test report of turns ratio and other parameters of winding to be produced before payment. (ii) Rates of filtering and top up of oil is considered in replacement of coil if carried out at workshop. No extra payment will be done. The transformer should be functional in all repect from workshop iteself.
M&L Shifting of the any make of transformer rating up to 315 KVA mounted on plinth/pole from existing location to new location and existing transformer vice versa, including removing and reconnections of HT/LT side, jumper / cable connection, control cable connection of both transformers including testing and commission complete all as directed by Engr-in-Charge. Note:- (i) The rate quoted is deemed to be inclusive of necessary crane / vehicle charges for shifting and installation of the transformer.
S&F Service position indication lamp suitabe for fixing on VCB complete as in repairs all as specified
Dehydration & filteration of transformer oil by using mobile dehydration & filteration plant, heating and filtering the oil to be carried out till the di-electric strength reaches value 40 KV or above in one minute, for any capcacity of transformer (63-315 KVA)/starter of pumps of any type & any capacity. Note: Samples of before filtration and after filtration to be procured by contaractor in different bottels for each transformer to show the difference between the dielectric strength duly labelled on bottle. Proper standard report to be produced before payment. Offline filtration to be done. Generator for filtration plant to be brought by the contractor.
M & L Topping up/replacement of transformer oil of transformer chamber and conservator with new transformer oil upto a required level of 50 KV di-electric strength to withstand for one minute in any type and capacity of transformer all as directed by Engr-In-Charge Make: SERVO/POWER OIL.
M & L Scrapping/cleaning of outer surfaces of transformer and spray painting with two coats of best qualitiy sythetic enamel paint over one coat of red oxide primer complete including writing of MES No.(stencil cut) in fluroscent yellow colour all as directed by Engr-In-Charge from 63 KVA to 315 KVA capacity transformer of any make and size at plinth mounted or pole mounted on site. Note: The painting work will be redone without any extra cost if the required finishing as per Engr-In-Charge/JE incharge is not achived
S&F Breaker 'ON' indication lamp suitabe for fixing on VCB complete as in repairs all as specified
S&F Breaker 'OFF' indication lamp suitabe for fixing on VCB complete as in repairs all as specified
S&F Auto trip indication lamp suitabe for fixing on VCB complete as in repairs all as specified
S&F Spring charge indication lamp suitabe for fixing on VCB complete as in repairs all as specified
S&F 'Y' Ammeter Switch suitabe for fixing on VCB complete as in repairs all as specified
S&F 'YB' Voltmeter Switch suitabe for fixing on VCB complete as in repairs all as specified .
Dismantling HT/LT pole of any height by taking out from PCC foundation complete and shifting to other location as directed including fixing the pole in true vertical position including excavation and earth work, PCC 1:4:8 type D2 (using 40mm graded stone aggregate) as base concrete and PCC 1:3:6 type C2 (using 20mm graded stone aggregate) in both foundation and coping of poles all as specified in SSR Part I-2009 and applying two coats of aluminium paint to pole surface complete all as directed by Engineer-in-Charge.
M&L Hiring of Fault Locator Machine Vehicle complete from the authorised supplier alongwith their dedicted specialised team, finding out the exact HT fault Location from both end termination of underground cable including necessary excavation work complete all as specified and directed by Engr-in-charge.
M&L Painting to HT poles of OH lines and HT Four poles/two poles and single pole structure complete with cross arms any height and any description thoroughly with necessary cleaning agent including scrapping up of old corroded paint dirt/dust/rust carefully and applying two coats of synthetic aluminum paint including marking of pole No and apply three indigo strip and two white strip on poles :-
(a) Two poles with cross Arms
(b) Four Poles with cross Arms
(c) HT 11 mtrs Single pole
S&F TC Healthy indication lamp suitabe for fixing on VCBcomplete as in repairs all as specified
Cutting anxious green growth / vegetation growth for cleaning out the area around transformer installations and four pole structure yards at ground level by cutting out roots, un wanted plants bushes and removal of the same by surface excavation not exceeding 30 cm deep average 15 cm complete.
Maintenance of earthings of installations like cleaning of earth pits, treatment of earthing by pouring salt water, replacement of perished wire mesh, unserviceable funnel and repair works like patch works to the PCC chambers and RCC cover with cement mortar 1 : 4 all as directed.
Restreching/Restringing, tightening and repair to overhead line ACSR conductor of any size on LT poles including necessary Aluminium binding wire connectors PVC sleeves for jumper, fixing of insulators and prunning of tree complete all as specified and directed. Notes: (i) The distance between pole to pole in RM (contains 2/4/6 runs) i.e one span will only be considered for payment purpose. (ii) Extra aluminium conductor required for jumpers and binding purpose is deemed to be included in the quoted unit rate. (iii) Trimming of tree branches upto 1.50 Mtrs distance around conductor is included in the unit rate quoted.
S&F Power factor meter suitably fixed on VCB complete as in repairs all as specified
Cutting and trimming trees branches any girth and any size touching to overhead lines and cleaning the distance 1.5 mtr length both side of OH line with in a span of 35-50 mtrs each disposing the same, clearing the site all as directed by Engineer-in-Charge.
Taking out HT/LT UG cable laid in underground/trench/cable duct/tunnel/surface and relaying/rerouting the same cable shall laid in underground/trench/cable duct/tunnel/ surface as per direction of Engr-in-Charge. Note:- (i) Earth work shall be measured & paid separately under relevant items. (ii) Taking out & relaying of bricks/PCC covers shall be measured & paid separately under relevant items.
Cutting the existing road straight by manual, depth and width not less than 1 mtr below ground level for passing of underground cable and filling back with excavated soil upto 75% road portion and 25% shall be made with cement concrete 1:2:4 (using 20 mm graded aggregate stone complete all as specified and directed.
S&F Cable route indicator for HT UG Cable of 11000 Volts bolted with 40 x 6 mm flat iron member of height 0.60 mtr, and 80 mm dia CI plate embedded in PCC 1 : 3 : 6 type C2 of size 20 x 20 x 30 cm block complete all as specified and directed.
M&L Galvanised iron strip 32 x 6mm buried in ground for Earthing connection purpose complete all as specified and directed
M&L Replacement of mild steel plates chequered, 5mm thick for duct cover in sub station painted on all sides with two coats of black enemelled paint over a coat of red oxide zinc, primer, complete, all as specified and directed.
Supply and laying rubber cork sheet ISI marked 19mm thick of 1x2 meter size to cover the area in front of indoor control panels and HT/LT equipments, complete all as specified and directed.
Dismantling of HT VCB trolley 11 KV 400 Amps of any make and type from existing site, opening/drawing out the VCB trolley after switching off electric supply, Testing and maintenance of VCB pannels installed in Main Receiving Stn and Power house near Airmen Md Accn which shall include the following work :- Note : (i) Checking of all mechanical/electrical control system for proper functioning,spring charging system, VT & PT Assembly, tripping system, indication system, vaccum interruptur, cleaning & servicing the fixed/moving contacts & blowing out dust and applying the proper lubrication/greasing complete. (ii)Contact Resistance (RYB) and Auxiliary Supply voltage of closing coil, tripping coil, Motor (iii) Timing Test of closing time and opening time. IR value with 5 KV megger Before and after HV (iv) Checking of PT & CT which shall include ratio test and healthiness of the HT and LT fuses and associate circuiting. (v) Breaker testing which inclueds :- (i) Insulation resistance. (ii) Pick up and drop of operating coils. (iii)To check IR Values(CT)(iv) To carryout Polarity test.(CT) (v) To check Knee point voltage / measurement in case of class PS CT
(vi) Servicing of HT, 11 KV, VCB, 400 Amps capacity, 50 Hz, breaking capacity 50 KA by drawing out from and moving contacts for smooth funcitoning including replacement of tripping and closing coils, 30 volts, DC and servicing of solenoid switch all as specified and as directed. (vii) Removing the unserviceable and supply and fixing new HT volt meter 11KV/11V 0 to 15 making it functional in all aspect and HT ampere meter 200/100/5 at main incoming of MAP power house. (viii) Removing the burnt out fixed contact assembly from the HT, VCB, 11 KV, 400 Amps of Areva Make supply and fix contact assembly of copper strip all as specified and directed. (ix) To carryout HV (AC ) Test in open & close condition with suitable HV Kit for both 11 KV VCBs. (x) To check contact resistance (by millivolt drop test or with micro Ohm meter) Note: (i) Servicing of VCB to be done by authorised dealer/ servicing partner of Schnider(Areva/Alstom) and Siemens only and proper bill to be submitted which will be responsibility of the contractor.Strictly No any other unauthorised servicing team/people will be allowed to carry out servicing. (ii) Spare damaged parts will be measured and paid separately under relevant items
S&F following parts as per requirements for HT VCB in repairs :-
(a) Trip coil 30 V DC suitable for HT VCB 11 KV, Amps complete all as specified.
(b) Moving Contact (Male)
(c) Fixed Contact (Female)
(d) Tulip Contact
(e) Terminal Bushing assembly (Hinged End)
(f) Terminal Bushing Assembly (ACP End)
(g) Circuit Spout
(h) ARC Pot Assembly
(j) Back Connection housing
(k) Finger Contact
(l) Trip Assembly
(m) Current Transformer 50/25/5 ( of suitable sizes)
(n) Buffer closing spring removing existing unserviceable spring including testing and commissioning all as specified and as directed. Cat No MRB39S4020500NA(Schneider)
(o) Buffer opening spring removing existing unserviceable spring including testing and commissioning all as specified and as directed. Cat No MRB39S4027200NA(Schneider)
(p) Spout brown colour trape type mounted back side of the VCB Panel 11Kv Epoxy Cast as per sample all as specified and directed by Engr-in-Charge.Make ECS/Baroda Moulds & Dies/Areva
(q) Relay digital type IRI-PRO-V2-3I-EI-5-5 with In 5A and Freq 50 Hz, Uv 24-270 V AC/24-360VDC and Iw- 6W all as specified and directed by Engr-in-Charge including replacing conneted wires of suitable size as per site or sample Make C&S or equivalent. Note for above item No 66 & 67 1.Servicing of VCB to be done by authorised dealer/ servicing partner of Schnider(Areva/Alstom) and Siemens only and proper bill to be submitted which will be responsibility of the contractor 2 Test report also to be produced by contractor strictly. 3. No any other unauthorised servicing team/people will be allowed to carry out servicing.
S&F Oil level gauge – Flush Type as in repairs . Make:GTPL
M&L Replacement air break insulator(DO assembly) for current rating upto 200 Amps, 11000 Volts complete and testing on load. Make : Jaipuria Brothers/BHEL.
M & L Cleaning of grass and bushes around two pole structure and four pole structure, RMU/VCB/Panel area, complete including cutting unwanted ingress upto 6/10mtrX6/10mtr area or area inside chain link fencing complete all as specified and directed by Engineer-In-Charge. Note: The contractor shall bring all the tools and man power for proper cleaning of the area shown by concerned AGE/JE(E/M).
S&F Potential transormer of ratio Pri/Sec 11KV/110V , Type PT-005, Burden VA/Phase : 100,Connection STAR/STAR, Freq : 50 Hz, Lightening Impulse Voltage75KV, Insulation Voltage 28KV, Highest System Voltage : 12KV,Phase 3 and Voltage factor 1.2 Continuous 1.9 Times for 8 Hrs suitable for VCB installed at site as in repairs all as specified and directed by Engr-in-Charge
M&L Air break switch gang operated triple pole mechanically operated, mounted on insulator and steel frame, with operating mechanism worked from fround level for current tating upto 200 Amp 11000 volts and testing on load complete as in repairs all as specified and directed
Shiv Kripa Tradimg
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .