Loading…
Loading…
Tender Value
₹39.9 Cr
EMD Value
₹11 L
Closing Date
10 Aug 2026, 4:00 pmDue tomorrow
Additional Chief Engineer (P&C)
Supply, Erection, Testing, and Commissioning of 220kV & 66kV Equipment and Materials on Turnkey Basis, including Civil Works, for 220kV Dharampur AIS Substation (Phase – 2) – Upgradation of existing 66kV Dharampur S/s to 220kV level
321108
ACE(P&C)/Contract/220KV Dharampur AIS S/S /E-481
Open
Electrical Works
Works
Vadodara
46 documents required · 38 mandatory · 8 optional
₹11,800
Gujarat Energy Transmission Corporation Limited
₹11 L
18 Jul 2026
18 Jul 2026
18 Jul 2026
10 Aug 2026
18 Jul 2026
Particulars of Item Unit
Supply and Erection of 220kV Equipments considering 25mm/kV
creepage distance (as per respective technical specifications and
relevant special conditions) suitable for One Main Bus and One
Main cum Transfer Bus scheme with Twin AL59(61/3.50) conductor
Surge Arrester 198kV, 10kA, Designation-SM with structure and clamp
connectors(suitable to Single AL-59) as per Technical spec (Drop type)
High Level Surge Arrester 198kV, 10kA, Designation-SM with structure
and clamp connectors(suitable to Twin AL-59) as per Technical spec
PT 220kV/√3-/110V/√3-3C with structure and clamp connectors(suitable
to Single AL-59) as per Technical spec ✓
BPI 8kN with structure and clamp connectors (suitable to Twin AL-59)
as per Technical spec ✓
HBPI-a (6.8Mtr.) 8kN with structure and clamp connectors (suitable to
Twin AL-59) as per Technical spec ✓
HBPI-b (8 Mtr.) 8kN with structure and clamp connectors (suitable to
Twin AL-59) as per Technical spec ✓
HDB Isolator with one ES 1600A 40kA 3s with structure and clamp
connectors (suitable to Twin AL-59) as per Technical spec ✓
HDB Isolator with one ES 1600A 40kA 3s with structure and clamp
6 connectors (suitable to Twin AL-59 at one side and Single AL-59 at other Set. 2
side) as per Technical spec ✓
HDB Isolator without ES 1600A 40kA 3s with structure and clamp
connectors (suitable to Twin AL-59) as per Technical spec ✓
Tandem DB Isolator 1600A 40kA 3s with structure and clamp
connectors (suitable to Twin AL-59) as per Technical spec ✓
CT conventional 1500-1200-600/1, 5C with structure and clamp
connectors (suitable to Twin AL-59) as per Technical spec ✓
High Level CT conventional 1500-1200-600/1, 5C with structure and
clamp connectors (suitable to Twin AL-59) as per Technical spec ✓
CB 2000A 40kA 3s with structure and clamp connectors (suitable to Twin
AL-59) as per Technical spec ✓
220kV Dharampur s/s. - BOQ, R0, Dt-17.10.2025 Page 1 of
Switchyard BOQ of 220/66kV Dharampur SS
Sr. Erection Supply
Particulars of Item Unit
Supply and Erection of 220kV Materials considering 25mm/kV
creepage distance (as per respective technical specifications and
relevant special conditions) suitable for One Main Bus and One
Main cum Transfer Bus scheme with Twin AL59(61/3.50) conductor
220kV Dharampur s/s. - BOQ, R0, Dt-17.10.2025 Page 2 of
Switchyard BOQ of 220/66kV Dharampur SS
Sr. Erection Supply
Particulars of Item Unit
1a Gantry structures GI as per BOM, Steel (W/o A/B part) MT 181.1 ✓
1b Gantry structures GI as per BOM, Bolt nut part MT 11.7 ✓
VHF Tower Mast Structure GI with stub, template complete as per BOM,
Steel and A/B part 1.65 ✓
VHF Tower Mast structures GI with stub, template complete as per
BOM, Bolt nut part 0.1 ✓
Stringing of bus with Twin AL59(61/3.50) conductor for all the three
phases with required Silicon Rubber Insulators, hardwares and
accessories, spacers provided at every 3.0 mtr. interval etc. complete as
per relevant standards and approved drawings with Jumpers for
continuous Bus Arrangement (It includes cost of Conductor, Silicon
Rubber Insulators, hardwares and accessories, spacers etc.all items
required for satisfactory functioning. Any variation in quantities shall be
absorbed by contractor.)
a Main Bus with 32Mtr span including bus jumpers No. of Span 8 8 ✓
b Line flyover bus with 49.5 Mtr span No. of Bay 4 4 ✓
c Transformer flyover bus with 49.5 Mtr span No. of Bay 3 3 ✓
d Bus Coupler Flyover Bus with 49.5 Mtr. Span No. of Bay 1 1 ✓
Droppers (including required suspension string with hardware and
accessories if any) and Jumpers (including Equipment to Equipment)
with Twin AL59(61/3.50) conductor as per standards and approved
drawings with provision of required spacers (Suitable for 350mm
spacing) at every 3.0 mtr. interval. (It includes cost of Conductor,Silicon
Rubber Insulators, hardwares and accessories, Fire Wedge connectors,
spacers etc.all items required for satisfactory functioning. Any variation in
quantities shall be absorbed by contractor)
a 220KV Line Bay No. of bay 4 4 ✓
b 220/66KV Transformer Bay No. of bay 2 2 ✓
c 220KV Bus Coupler Bay No. of bay 1 1 ✓
220kV Dharampur s/s. - BOQ, R0, Dt-17.10.2025 Page 3 of
Switchyard BOQ of 220/66kV Dharampur SS
Sr. Erection Supply
Particulars of Item Unit
Droppers (including required suspension string with hardware and
accessories if any) and Jumpers with Single AL59(61/3.50) conductor
as per standards and approved drawings (It includes cost of
Conductor,Silicon Rubber Insulators, hardwares and accessories, Fire
Wedge Connectors, etc.all items required for satisfactory functioning.
Any variation in quantities shall be absorbed by contractor)
a 220KV Line Bay - LA and CVT No. of bay 4 4 ✓
b 220KV PT Bay No. of bay 2 2 ✓
Stringing of Earth Wire with 7/3.15 GS wire with required hardwares
and accessories etc. complete as per standards and approved drawings
6 for the shown span.(It includes cost of Earthwire,hardwares and
accessories, etc. all items required for satisfactory functioning. Any
variation in quantities shall be absorbed by contractor
a 49.5 Mtr. Of Span No. of span 5 5 ✓
Supply and Erection of 66kV Equipments considering 25mm/kV
creepage distance (as per respective technical specifications and
relevant special conditions) suitable for Two Main Bus scheme with
Twin AL59(61/3.50) conductor.
Surge Arrester 60kV, 10kA, Designation-SM with structure and clamp
1a connectors suitable for Single AL59(61/3.50) and 66KV XLPE cable No. 36
support structure (for 2nos./Phase) as per technical specifications
Surge Arrester 60kV, 10kA, Designation-SM with structure and clamp
1b connectors suitable for Twin AL59(61/3.50) and 66KV XLPE cable No. 6
support structure (for 3nos./Phase ) as per technical specifications
Surge Arrester 60kV, 10kA, Designation-SM with structure and clamp
1c connectors (suitable for Single AL59(61/3.50)) as per technical No. 9
specifications ✓
PT 66kV/v3-/110V/v3-2C with structure and clamp connectors (suitable
for Single AL-59) as per technical specifications ✓
BPI 4kN with structure and clamp connectors(suitable for Twin AL-59)
as per technical specifications ✓
220kV Dharampur s/s. - BOQ, R0, Dt-17.10.2025 Page 4 of
Switchyard BOQ of 220/66kV Dharampur SS
Sr. Erection Supply
Particulars of Item Unit
BPI 4kN with structure and with structure and clamp connectors suitable
3b for Twin AL59(61/3.50) and 66KV XLPE cable support structure (for No. 6
3nos./Phase ) as per technical specifications ✓
BPI 4kN with structure and clamp connectors (suitable for Single AL-59)
as per technical specifications ✓
HBPI 4kN with structure and clamp connectors (suitable for Twin AL59)
as per technical specifications ✓
HDB Isolator without ES 2000A 25kA 3s with structure and clamp
connectors (suitable for Twin AL-59) as per technical specifications ✓
HDB Isolator with one ES 1250A 25kA 3s with structure and clamp
connectors(suitable for Single AL-59) as per technical specifications
HDB Isolator without ES 1250A 25kA 3s with structure and clamp
connectors (suitable for Single AL-59) as per technical specifications
HDB Isolator without ES 1250A 25kA 3s with structure and clamp
9 connectors (suitable for Twin AL59 at one side and Single AL59 at other Set. 2
side) as per technical specifications ✓
CT 1600-1200-600/1 3C 31.5KA 3S with structure and clamp connectors
(suitable for Twin AL-59) as per technical specifications
CT 1600-1200-600/1 3C, 31.5KA 3S with structure and clamp
connectors (suitable for Single AL-59) as per technical specifications
CT 100-50/1 3C 31.5KA 3S with structure and clamp connectors
(suitable for Single AL-59) as per technical specifications ✓
CB 1600A 25kA 3S with structure and clamp connectors (suitable for
Twin AL-59) as per technical specifications ✓
CB 1600A 25kA 3S with structure and clamp connectors(suitable for
Single AL-59) as per technical specifications ✓
Supply and Erection of 66kV Switchyard Materials considering
25mm/kV creepage distance (as per respective technical
specifications and relevant special conditions) suitable for Two
Main Bus scheme with Twin AL59(61/3.50) conductor.
1 Gantry structures GI as per BOM , Steel (W/o A/B part) MT 92.813 ✓
220kV Dharampur s/s. - BOQ, R0, Dt-17.10.2025 Page 5 of
Switchyard BOQ of 220/66kV Dharampur SS
Sr. Erection Supply
Particulars of Item Unit
2 Gantry structures GI as per BOM , Bolt nut part MT 7.133 ✓
Stringing of bus for all the three phases with Twin AL59 (61/3.50)
conductor, Silicon Rubber Insulators hardwares, spacers(suitable for
350mm spacing) at interval of 4.0 mtr complete as per relevant
3 standards and approved drawings.(The scope includes the cost of
Conductor,Silicon Rubber Insulators, hardwares, accessories, spacers
etc.all items required for satisfactory operation. Any variation in quantities
shall be absorbed by erection contractor.
a Main Bus with 27.800 Mtr. Span including bus jumpers No. of Span 2 2 ✓
b Main Bus with 32.950 Mtr. Span including bus jumpers No. of Span 2 2 ✓
c Main Bus with 16.300 Mtr. Span including bus jumpers No. of Span 2 2 ✓
d Main Bus with 33.700 Mtr. Span including bus jumpers No. of Span 2 2 ✓
e Main Bus with 23.600 Mtr. Span including bus jumpers No. of Span 2 2 ✓
f Transformer flyover bus with 22.00 Mtr. Span No. of Span 3 3 ✓
Stringing of bus for all the three phases with Single AL59 (61/3.50)
conductor, Silicon Rubber Insulators hardwares as per relevant
standards and approved drawings.(The scope includes the cost of
Conductor,Silicon Rubber Insulators, hardwares, accessories, spacers
etc.all items required for satisfactory operation. Any variation in quantities
shall be absorbed by erection contractor.
a Line flyover bus with 22.00 Mtr. Span No. of bay 12 12 ✓
Droppers (including required suspension string with hardware and
accessories if any) and Jumpering (equipment to equipment) with Twin
AL59 (61/3.50) conductor as per standards and approved drawings with
provision of spacers suitable for 350mm spacing at 4.0 mtr interval. The
scope includes the cost of accessories ,spacers, fire wedge connectors
etc.all items required for satisfactory operation. Any variation in quantities
shall be absorbed by erection contractor -Qty. per bay of 3phase
a 220/66KV Transformer Bay (66KV side) No. of bay 2 2 ✓
b 66KV Bus Coupler Bay No. of bay 1 1 ✓
220kV Dharampur s/s. - BOQ, R0, Dt-17.10.2025 Page 6 of
Switchyard BOQ of 220/66kV Dharampur SS
Sr. Erection Supply
Particulars of Item Unit
Droppers (including required suspension string with hardware and
accessories if any) and Jumpers with Single AL59(61/3.50) conductor
as per standards and approved drawings. (It includes cost of
Conductor,Silicon Rubber Insulators, Fire wedge connectors,hardwares
and accessories etc. all items required for satisfactory functioning. Any
variation in quantities shall be absorbed by erection contractor)
a 66kV Line Bay No. of bay 12 12 ✓
b 66kV PT Bay No. of bay 2 2 ✓
c 220/66KV Transformer Bay - LA No. of bay 0
d 66/11KV Transformer Bay No. of bay 3 3 ✓
Stringing of Earth Wire with 7/3.15 GS wire with required hardwares and
accessories etc. complete as per standards and approved drawings for
7 the shown span. (It includes cost of Earthwire,hardwares and
accessories etc. all items for satisfactory functioning. Any variation in
quantities should be absorbed by erection contractor.
a Transformer flyover bus with 22.00 Mtr. Span No. of span 3 3 ✓
b Line flyover bus with 22.00 Mtr. Span No. of span 6 6 ✓
E Supply and Erection of 66kV XLPE Cable and Accessories
1 66 kV(E) 1 core 630 sq. mm. Aluminium conductor XLPE insulated Copper wire Mtr
screened, Poly AL-Poly, Aluminium wire armoured, HDPE outer sheathed power 0
cable, as per Technical specification. ✓
2 Earthing/Sheath bonding Cable 6.6 kV 1Cx150 sq. mm. Copper conductor,XLPE Mtr
insulated cable as per technical specification ✓
3 End Termination for power cable complete in all respect with required fabrication No.
for erection on composite solid core station post insulator with high level
structure/Surge Arrester structure. Scope also includes suitable clamp and
connectors etc. complete in all respect with 50 X 6 mm GI earthing strip
connection to main earth mat. Common termination arrangment at Y-phase 40
structure shall be made for all earthing cable. From there, GI earthing strip shall
be invariably connected to main earth mesh.
220kV Dharampur s/s. - BOQ, R0, Dt-17.10.2025 Page 7 of
Switchyard BOQ of 220/66kV Dharampur SS
Sr. Erection Supply
Particulars of Item Unit
4 Three phase earth Link Box with SVL at each Transformer end with No.
maintainance free earthing pit & GI earthing strip 50 X 6 mm to be connected
with main earth mesh including required fabrication of structure, civil work if any.
4-a Transformer end: Single phase earth Link Box with SVL for Transformers spare No.
cable with maintainance free earthing pit & GI earthing strip 50 X 6 mm to be
connecetd with main earth mesh including required fabrication of structure, civil
5 Three phase earth Link Box without SVL at each Transformer end with GI No.
earthing strip 50 X 6 mm to be connecetd with main earth mesh including 6
required fabrication of structure, civil work if any. ✓
5-a Single phase earth Link Box without SVL for Transformer cable with No.
maintainance free earthing pit & GI earthing strip 50 X 6 mm to be connecetd
with main earth mesh including required fabrication of structure, civil work if any.
6 Laying of cable in RCC Cable trench (i.e. Type-1) for 220/66 KV Transfomer 1 &
2 with all requisite materials (like non magnetic material trefoil clamps
(mounted at min. 3Mtr. spacing), phase identification tag, etc.), supervision,
testing of installation, pre-commissioning tests etc. as per approved drawing.
Providing with earthing strip for earthing of cable trench as per earthing
6.1 220/66kV Transformer no. 1 (9 +1 cable) Mtr 150 0 ✓
6.2 220/66kV Transformer no. 2 (9 +1 cable) Mtr 98 0 ✓
6.3 220/66kV Transformer no. 3 (9 +1 cable) Mtr 0
Supply and Erection of General purpose equipments and materials
F as per respective technical specifications and relevant special
11kV/415V,500 kVA Distribution Transformer as per Technical
specification. ✓
220kV Dharampur s/s. - BOQ, R0, Dt-17.10.2025 Page 8 of
Switchyard BOQ of 220/66kV Dharampur SS
Sr. Erection Supply
Particulars of Item Unit
Suitable arrangement of 11KV connection
(A) from separate 11 kVs feeder (feeder termination shall be arranged by
GETCO) to another 11kV/415V, 500 kVA distribution transformer which
comprises of equipments with support structures and clamp connectors as per
technical specifications::
1) 9 kV LA - 3 Nos.
2) Conductor : Single DOG Conductor
3) DP structure with DO fuse, 22kV BPIs arrangement including Dist box
suitable to dist transformer.
(11kV Power Cable shall be supplied by GETCO, however Laying of cable is in
the scope of bidder)
2 (B) from separate 11 kV express feeder (feeder termination shall be arranged Package LS LS
by GETCO) to another 11kV/415V, 500 kVA distribution transformer which
comprises of equipments with support structures and clamp connectors as per
technical specifications::
1) 22 kV outdoor Isolator, 630A, STC: 25 kA – 3 sec. - 1 set
2) 9 kV LA - 3 Nos.
3) Conductor : Single DOG Conductor
4) 11 KV cable support arrangement
5) DP structure with DO fuse, 22kV BPIs arrangement including Dist box
suitable to dist transformer.
(11kV Power Cable shall be supplied by GETCO, however Laying of cable is in
the scope of bidder)
415V AC LT Distribution Box - 800A incomer with Change over switch
3 arrangement and 02 Nos. of 800A Outgoing Feeders as per Ref .Drg No. No 2
GETCO/E/02S- STD/P-031/LTD R0 Dtd. 11.03.15. ✓
3 3 Ton Capacity Split AC (reputed make) No. 6 6 ✓
4 AC unit 1.5 Ton Split (reputed make) No. 6 6 ✓
5 Providing major spares as per Ann A attached herewith Set 0 1 ✓
6 Providing instruments as per Ann B attached herewith Set 0 1 ✓
7 Providing tools and tackles etc. as per Ann C attached herewith Set 0 1 ✓
Supply of Furniture, RO Water Filter System, Water Cooler Etc. as per
Supply and Erection of Fire stand with 4 buckets including concreting as
per our drawing and Instruction of E. I. C. ✓
220kV Dharampur s/s. - BOQ, R0, Dt-17.10.2025 Page 9 of
Switchyard BOQ of 220/66kV Dharampur SS
Sr. Erection Supply
Particulars of Item Unit
10 Providing of Insulating Mat as per IS 15652:2006(Size2000x1000x2mm) No. 0
Supply and installation of ISI marked fire extinguishers of various types
required for 220 KV sub station.
1) Dry chemical powder type of 9 Kg. capacity. No. 0 2 ✓
2) Dry chemical powder type of 25 Kg. capacity. No. 0 2 ✓
3) Dry chemical powder type of 50 Kg. capacity. No. 0 2 ✓
4) Carbon dioxide (CO2) gas type of capacity 6.5 Kg. capacity No. 0 2 ✓
5) Carbon dioxide (CO2) gas type of capacity 22.5 Kg. capacity No. 0 2 ✓
6) Mechanical Foam type of capacity 9 LT. No. 0 2 ✓
7) Mechanical Foam type of capacity 60 LT. No. 0 2 ✓
Supply and installation of materials for Illumination system in all respect
as per respective specifications and special conditions (Important Note:
Concealed wiring shall be considered for Indoor Illumination)
Providing and Fixing of Energy Efficient LED type (Techhnical spec Cl
No. 2.10.4.8-I LED 3 type) Indoor decorative luminaries as per design
calculation, with respect to required lux level and relevant tender drgs.as
per technical spec. Scope also includes providing and fixing of 15/5 A
plug, Portable Emergency Light, Bell, Fan, Ex- Fan, DC Point,Occupancy
and Light Level Sensor with requisite MCBs and DC 100W lamp , DC
Plug etc all items as per Ann-4 in following rooms (with safety device
i Control Room Package LS LS ✓
ii PLCC Room Package LS LS ✓
iii Office Package LS LS ✓
Providing and Fixing of Energy Efficient LED Type (Techhnical spec Cl
No. 2.10.4.8-I LED 1 or I LED 2 type) Indoor decorative luminaries as per
design calculation, with respect to required lux level and relevant tender
drgs.as per technical spec. Scope also includes providing and fixing of
15/5 A plug, Portable Emergency Light, Bell, Fan, Ex- Fan, DC Point,
Occupancy and Light Level Sensor with requisite MCBs and DC 100W
lamp , DC Plug etc all items as per Ann-4 in following rooms (with safety
i Battery Room Package LS LS ✓
ii LV Room Package LS LS ✓
220kV Dharampur s/s. - BOQ, R0, Dt-17.10.2025 Page 10 of
Switchyard BOQ of 220/66kV Dharampur SS
Sr. Erection Supply
Particulars of Item Unit
iii Store Room Package LS LS ✓
iv Ramp Slope Package LS LS ✓
v Veranda Package LS LS ✓
vi Toilet Gents Package LS LS ✓
vii WC Package LS LS ✓
viii Toilet Ladies Package LS LS ✓
ix Passage (Corridor) Package LS LS ✓
x Water Room Package LS LS ✓
xi Security Cabin Package LS LS ✓
Providing & Fixing of Energy Efficient LED Type (Techhnical spec Cl No.
2.10.4.8-I LED 1 or I LED 2 type) Indoor decorative luminaries as per design
calculation, with respect to required lux level & relevant tender drgs.as per
3 technical spec. Scope also includes providing and fixing of 15/5 A plug, Portable
Emergency Light, Bell, Fan, Ex- Fan, DC Point, Occupancy & Light Level
Sensor with requisite MCBs and DC 100W lamp , DC Plug etc all items as per
Ann-4 in following room.
i Store building Package LS LS ✓
Outdoor Lighting
Providing and fixing of flood light luminaries as per design for (220kV)
switch yard area with Philips/CGL/Bajaj/GE/Oshram make with control
gear box and ancillaries or Equivalent make LED 150/250/400 W
suitable for mounting on structure at appropriate height ( as per design)
as per specifications TS illuminations cl. no 2.10.4.8 with necessary GI
3 Package LS LS
fabrication and GI bolt nuts to fix control gear box at the structure with
complete internal and external wiring to J. box ,Dist panel/section feeder
pillar etc with supply of required 3 c x 2.5 mm2 copper armoured cable
(as per spec ) .The scope includes supply and erection of all the
materials required for satisfactory functioning of above work.
220kV Dharampur s/s. - BOQ, R0, Dt-17.10.2025 Page 11 of
Switchyard BOQ of 220/66kV Dharampur SS
Sr. Erection Supply
Particulars of Item Unit
Providing and installation of Energy efficient LED type post top lantern for
main gate and road from main gate to switchyard via control room as per
design with Philips/CGL/Bajaj/GE/Oshram or Equivalent make and
ancillaries suitable for mounting on Gate pillars and 4.5 mtr poles with
necessary GI fabrication and GI bolt nuts to fix control gear box with
4 complete internal and external wiring to J.box,Dist panel/section feeder Package LS LS
pillar, fixing terminal etc. with supply of required 3 c x 2.5 mm2 copper
armoured cable as per spec .This also includes the supply and erection
of required 4.5 mtr poles and its foundation work as per spec and
earthing with main mesh. The scope includes supply and erection of all
the materials required for satisfactory functioning of above work.
Providing and fixing of street light luminaries for reamaining area (like
road, near whole compound wall/fencing area etc.) of switch yard
complete as per design with Philips/CGL/Bajaj/GE/Oshram or
Equivalent make LED lamp and ancillaries suitable for mounting on
mtr swaged poles as per spec.TS illuminations cl. no 2.10.4.8 (S-LED)
at appropriate height with necessary GI fabrication and GI bolt nuts to fix
control gear box with complete internal and external wiring to J. box
5 Package LS LS
,dist panel/section feeder pillar, fixing terminal etc with supply of required
3 c x 2.5 mm2 copper armoured cable (as per spec). This also includes
the supply and erection of 7.0 mtr swaged pole and foundation work as
per spec. and panting with two coats of primer and two priming of zinc
chromate as well as earthing with main mesh. The scope includes supply
and erection of all the materials required for satisfactory functioning of
Supply and Erection of main lighting Panel ACP-1 as per Specifications.
Set comprises minimum 3 nos.of such panels qty may be more if
6 required as per design.Scope also includes the providing and erection of Set 1
cable size (as per design requirement) and 25x6 GI strip for earthing with
Supply and Erection of main lighting Panel ACP-2 as per Specifications
Set comprises minimum 2 nos.of such panels qty may be more if
7 required as per design.Scope also includes the providing and erection of Set 1
cable size (as per design requirement) and 25x6 GI strip for earthing with
220kV Dharampur s/s. - BOQ, R0, Dt-17.10.2025 Page 12 of
Switchyard BOQ of 220/66kV Dharampur SS
Sr. Erection Supply
Particulars of Item Unit
Supply and Erection of main lighting Panel ACP-3 as per Specifications
Set comprises minimum 2 nos.of such panels qty may be more if
8 required as per design.Scope also includes the providing and erection of Set 1
cable size (as per design requirement) and 25x6 GI strip for earthing with
Supply and Erection of main lighting Panel ACP-4 as per Specifications
Set comprises minimum 2 nos.of such panels qty may be more if
9 required as per design.Scope also includes the providing and erection of Set 1
cable size (as per design requirement) and 25x6 GI strip for earthing with
Supply and Erection of main Yard light Dist. Board as per designed
capacity ratings.Scope also includes the providing and erection of cable
size (as per design requirement) and 50x6 GI strip for earthing with main
Supply and Erection of Lighting Transformers as per designed
capacity.Scope also includes the providing and erection of cable size (
11 as per design requirement) and 50x6 GI strip for earthing with main Set 1
mesh. Please refer the drawing "General Schematic for Illumination" in
the TS Illumination. ✓
Providing of concreting in 1:2:4 mix including muffing for erection of pole
12 and Dist boxes panels including excavation of HR/SR as per approved Package LS LS
Providing and fixing of ' B ' Class ISI marked GI pipe of 25 mm inner
13 diameter for cable looping, road crossing with necessary elbow / band to Package LS LS
Providing and fixing of GI clamp (25mm wide GI strip with 6 mm GI nut
bolts) on structure at approx. 1/2 Mtr. Interval for clamping of cable .
Clamp should be fix in such a way that cable can be easily mount inside
it and sustain standing on structure. This also includes required other
14 Package LS LS
materials ,accessories required for complete functioning of Illumination
system of whole project (switch yard and all buildings, structures) those
are not covered in this schedule for Illumination. Please refer the
drawing "General Schematic for Illumination" in the TS Illumination.
220kV Dharampur s/s. - BOQ, R0, Dt-17.10.2025 Page 13 of
Switchyard BOQ of 220/66kV Dharampur SS
Sr. Erection Supply
Particulars of Item Unit
Note: The qunatities of the ACP's mentioned in the schedule of
requirement are based on std. requirement, which shall be finalised
during detail engineering. The bidder has to assess the qty. of
ACP's at the time of quoting the bid. The qty of ACP's finalised
during detail engineering is binding to the bidder and no any extra
payment shall be made. In all the case the decision of GETCO will
Visual Monitoring System (VMS) as per technical specification.
H (Along with local PC monitoring set up and remote end PC Lump Sum LS LS
monitoring set up shall be in the scope of supply)
Supply and installation of materials for Earthing system in all
respect as per respective specifications and special conditions
(Successful bidder has to submit the complete design and BOQ for
approval with latest Soil resistivity report)
Supply and Installation of earthing strips/round bars as shown below
including digging of 600 mm depth and 450 mm wide trench fixing on
structure as per std equipment earthing philosophy including fixing
arrangement with two bolt arrangement, jointing, welding etc. complete.
a) 75 x 10 mm GI strip. RMt. 5500 5500 ✓
b) 50 x 6 mm GI strip. RMt. 8900 8900 ✓
c) 40 mm dia steel rod RMt. 5000 5000 ✓
d) 40mm dia 3mtr long steel rod Nos. 102 102 ✓
e) 7/3.15 earth wire for earthing of towers with peak RMtr. 1150 1150 ✓
Providing and installing Check pit as per drawing and instruction of
Engineer In charge with provision of earth chamber. ✓
Supply, Installation, Testing and Commissioning of maintenance free
treated earth electrodes, as per attached drawing no. GETCO/E/STD/P-
021 (1 OF 2) R3 dated 29.05.20 and Technical specifications GETCO/E/TS-
Maintenance free earth pits /R1 dated 04-06-15.
Providing BB masonry inspection chamber (man hole) incl.light type CI
cover as per GETCO drawing. ✓
220kV Dharampur s/s. - BOQ, R0, Dt-17.10.2025 Page 14 of
Switchyard BOQ of 220/66kV Dharampur SS
Sr. Erection Supply
Particulars of Item Unit
Earthing Adequacy study for whole switchyard after commisioning
earthmat in all respect (Scope as per annexure-E) ✓
Thermo scanning of whole switch yard in live condition after one month
of commissioning of substation. All hot points found during above test,
6 must be attended by Erection contractor. Upon attending the same, he Job LS -
shall have to submit soft and hard copies of thermoscanning report to
substation in-charge for record purpose. ✓
Supply,Installation and Commissioning of Solar roof top System on
7 Control Room and other Buildings with generation capacity of 45KW as Package LS LS
per Technical specifications. ✓
Note: Extra earth should be removed away from the site s/s
premises or refilling earthing pits if required. All required materials
for this job such as Copper Bonded Earthing Steel Rods, CI cover
with frame,cement,sand, Ground Enhancement Material, gravel,
bricks etc. to be supplied by the contractor.
Following special conditions are applicable for items included in
1) ‘PROPERTY OF GETCO’ must be embossed on each kit.
2) Guarantee/Warrantee of all kits shall be 3 years after successful
commissioning at GETCO substation.
3) Supply & Erection of 220/66KV Transformers are not in the scope of
awardee, but awardee will erect the itmes other than the scope of
transformer manufacturer and witness during the erection and testing of
the same and provide all the result in as built drawings/documents.
4) If terrace area of control building is not sufficient for installation of
specified capacity of Solar roof top system, then remaining capacity of
Solar roof top system shall be installed on other buildings.
Dismantling of 66kV Equipments with structure, clamps and
J connectors erected with Single Bus scheme including shifting and UOM QTY
stacking of all material at the site store.
220kV Dharampur s/s. - BOQ, R0, Dt-17.10.2025 Page 15 of
Switchyard BOQ of 220/66kV Dharampur SS
Sr. Erection Supply
Particulars of Item Unit
Dismantling of 66/11kV class power transformer including draining of oil
1 into oil barrels, fixing of blanking plates, shifting stacking of all material at No.
the site store.
2 Surge Arrester 60kV, 10kA, with structure and clamp connectors No.
3 PT 66kV/v3-/110V/v3-2C with structure and clamp connectors. No.
4 BPI 4kN with structure and clamp connectors. No.
HDB Isolator without ES 630A 25kA 3s with structure and clamp
HDB Isolator with one ES 630A 25kA 3s with structure and clamp
7 CT 600-300/1 3C 31.5KA 3S with structure and clamp connectors. No.
8 CB 1600A 25kA 3S with structure and clamp connectors. Set.
Dismantalling of S/S & Equipment structure. The dismentalled S/S &
9 Equipment structures are to be stacked in proper manner in the same MT
premises as per the instruction of EIC
Dismantling of Bus complete in all respect with fixing of all fittings,
insulators sag compensating plate/spring and all accessories as per the
instruction of Engineer –In-Charge
c) Single Moose/ AL-59 /Zebra conductor
Dismantling of control panel relay panel or C/R panel or RTC panel
11 including disconnection of all control cables. Job includes shifting of No.
panel from S/S site to site store.
12 Removal of control and LT Power Cables as per instruction of E.I.C. LS LS
220kV Dharampur s/s. - BOQ, R0, Dt-17.10.2025 Page 16 of
Switchyard BOQ of 220/66kV Dharampur SS
Sr. Erection Supply
Particulars of Item Unit
220kV Dharampur s/s. - BOQ, R0, Dt-17.10.2025 Page 17 of
Switchyard BOQ of 220/66kV Dharampur SS
Sr. Erection Supply
Particulars of Item Unit
220kV Dharampur s/s. - BOQ, R0, Dt-17.10.2025 Page 18 of
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
04. EMD BG Format.pdf
04. EMD BG Format.pdf
05. SD cum PBG Format.pdf
09.MAAT LA Networth Form.pdf
10. Form of LD undertaking 1B.pdf
11. Form of LD undertaking 1A.pdf
Amendment- Structure weight.pdf
TS SS STR R12 11.03.2024.pdf
1Cx50 sq mm Amendment 1 LT Control and Power Cable-1CX50 GTP.pdf
11kV XLPE CABLE R2 Feb.23.pdf
66KV 630SQ MM 1C POLY AL POLY UG Cable R4 July 22.pdf
AL59 ZEBRA and MOOSE GETCO- R4 July 22.pdf
EARTH WIRE - R5.pdf
EARTH WIRE ACCESSORIES 7-3.15-R2.PDF
FIRED WEDGE CONNECTOR R2 Mach- 23.pdf
G.I. EARTHING STRIPS.PDF
HW and ACCS AL59 CONDUCTOR - R2 JULY 2022.pdf
LT CONTROL and POWER CABLE - R4 SEPT 2025.pdf
MS PLAIN and TOR BAR.PDF
R1 - STEEL DRUM .pdf
R5 - ACSR cond MOOSE ZEBRA PANTHER DOG.pdf
R5 May 24- Silicon Rubber.pdf
SS HW 220 and 400KV SS R2.PDF
Standard MQP GI Tower material for issuence to SUPPLIER COPY.PDF
TS LAYING CABLE 66KV R2 July 2018.pdf
66 kV CT and PT R8 metering Jun-22.pdf
220 kV CT and PT R10 Jun -22.pdf
Amendment to 220 kV CT (R10) Clause - 2.3.1 -13.pdf
Amendment 1 to SF6 CB TS- Validity of type test reports.pdf
Amendment for TTR validity 26.02.2026.pdf
400 220 132 66 KV BPI R4 June-22.pdf
33 22 11 KV ISO R4 June-22.pdf
66 kV Isolator R6 June- 22.pdf
400 220 132 kV DB Tandem Isolator R6 June 22.pdf
Amendment to 66 KV Isolators (R6) 22.06.2023.pdf
11 22 33 KV LA R2 July-23.pdf
66 KV LA R6 June 22.pdf
220 132 66 KV LA Model (1).pdf
400 220 132 kV LA R6 June 22.pdf
Addendum terminal connector 10.06.2025.pdf
Terminal Connectors R2 June 22.pdf
66 kV 33KV TRF Specification R14 Jun22.pdf
Amendment Dist TRF - 1.pdf
Dist Trans 63KVA to 500KVAR5 Aug22.pdf
(AC) POWER CABLE BLOCK DIAGRAM -Model.pdf
(DC) POWER CABLE BLOCK DIAGRAM -Model.pdf
Control room Pannel Aaarangement-Model.pdf
REVISED 220kV PSLD-Model.pdf
TYP.CABLE BLOCK DIAGRAM (66KV)-Model.pdf
TYP.CABLE BLOCK DIAGRAM (220 KV )-Model.pdf
PROTECTION PHILOSOPHY_Final.pdf
Amendment-1 to TS of 66kV CRP 180423.pdf
Amendment-1 to TS of 400 220 132 kV CRP 180423.pdf
Amendment-1 to TS of Busbar Protection Panels 180423.pdf
Ammendment for TTR validity 26.02.2026.pdf
TS - GPS based Time Synchronization Equipment R2 July 22.pdf
TS - 110-220V DCDB.pdf
TS 220V Battery Chargers - R4 Feb 25.pdf
TS - Bay MK - R2 June 22.pdf
TS - CT-PT-CVT JB - R1 June 22.pdf
TS - Yard LT ACDB - R2 June 22.pdf
TS 66 KV Control and Relay Panels R7 May 2025.pdf
TS 400 220 132 kV Control and Relay Panels R8 160922.pdf
TS for Ni-Cad Battery Set-R3 Feb 25.pdf
TS for Plante Type Lead Acid Battery sets R2 Feb 25.pdf
TS LT Panel board 400A R5 April 2025.pdf
TS_Numerical Busbar Protection Panels_R3_120722 1.pdf
TS_Protection Relays for 11_22kV System R1_060822.pdf
TS_Protection Relays for 66kV sysetem R3_May 2025.pdf
R0 LAYOUT SECTION OF 220KV DHARAMPUR SS(220KVand66KV)Dt.06.06.2026.pdf
R0 SLD OF 220kV DHARAMPUR SS 06.03.2026.pdf
R3-1 LAYOUT PLAN OF 220kV DHARAMPUR SS 06.03.2026.pdf
R3-2 LAYOUT PLAN OF 220kV DHARAMPUR SS 06.03.2026.pdf
1.EARTHING NOTES-Model.pdf
2. EARTHING NOTES-Model.pdf
3A.EARTHING NOTES-Model.pdf
3B.EARTHING NOTES-Model.pdf
4.Typical Arrangement of Riser for Earthing System-Model.pdf
5. Typical Arrangement of Welding Joint(NEW)-Model.pdf
5A Typical Arrangement of Welding Joint(NEW)-Model.pdf
6. R2 Lightning Arrestor DT 22.12.2025-Model.pdf
7. R2 TYPICAL EARTHING ARRANGEMENT FOR CVT-PT DT 22.12.2025-Model.pdf
8. TYPICAL EARTHING ARRANGEMENT FOR CT-Model.pdf
9. TYPICAL EARTHING ARRANGEMENT FOR ISO.-Model.pdf
10. Typical Earthing Arrangement for Circuit Breaker-Model.pdf
11. TYPICAL EARTHING ARRANGEMENT FOR BPI-Model.pdf
12. R2 Typical Earthing Arrangement for Power Transformer.pdf
12A. Typical Earthing Arrangement for LT Transformer-Model.pdf
13. TYPICAL EARTHING ARRANGEMENT FOR TOWER WITH PEAK-Model.pdf
14. TYPICAL EARTHING ARRANGEMENT FOR TOWER WITHOUT PEAK-Model.pdf
15. TYPICAL EARTHING ARRANGEMENT FOR LM-Model.pdf
16. TYPICAL EARTHING ARRANGEMENT FOR EQUIPMENT OF CAPACITOR.pdf
17. TYPICAL EARTHING ARRANGEMENT FOR BMK-Model.pdf
18. DETAILS OF PANEL EARTHING-Model.pdf
19. TYPICAL EARTHING ARRANGEMENT OF CABLE TRENCH-Model.pdf
20. DETAILS OF EARTHING FOR D.P.STRUCTURE-Model.pdf
21. Typical Earthing Arrangement for Switch Yard Gate-Model.pdf
22.SLIDING GATE-Model.pdf
23. Connection Of Four Electrode Method Of Measuring Soil.pdf
24. MEASUREMENT OF EARTH RESISTIVITY-Model.pdf
MAINTENANCE FREE EARTHPITS (ROCKY SOIL) R4 22.12.25-Model.pdf
Standard Guideline for Earthing of EHV SS R4 Dtd.30.12.25.pdf
TYPICAL ARRANGEMENT OF EARTH TEST PIT(CHEAK PIT)-Model.pdf
Ann-E Adaquacy of earthing 140415.pdf
DG-Incomer arrangement .pdf
Technical Specification of Solar System.pdf
TS- AIO -Desktop and printer-30.04.2025.pdf
TS FPE R1 Feb13.pdf
TS General Erection R1.pdf
TS Illumination System R9 Dtd.30.12.25.pdf
TS VMS R1 Dtd.30.12.25.pdf
TS-Insulating Mat 270312.pdf
TS-Maintenance Free Earthpit 040615.pdf
220 KV CVT with HPI- R5 Jun 22.pdf
DAS Communication Cable and RS 485 to RS 232 Converter.pdf
Static Meter-specification-R3 July 2022.pdf
PP-220kV Dharampur AIS.pdf
Amendment 66KV TRF Nov24.pdf
03.Tender Notice E-481_220KV Dharampur-2 AIS.pdf
01.Part-I Tender Specification 220KV Dharampur AIS_E-481.pdf
02. Amendment -I Part-I 220KV Dharampur AIS_E-481.pdf
SWITCHYARD BOQ - 220kV DHARAMPUR SS.pdf
220kV Dharampur Protection BOQ.pdf
PLCC BOQ -220KV Dharampur SS.pdf
BOQ-Civil work at 220kV Dharampur.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].