Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹64.9 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹66.6 L+₹1.7 L (2.59%)Rejected-AOC | L2 | Rejected-AOC L2 |
Tender Value
₹69.1 L
EMD Value
₹50,000
Closing Date
19 Jun 2024, 2:00 pmClosed
Executive Engineer
Executive Engineer Kerala Water Authority (Water Resources Department)(WRD) O/o Office of the Executive Engineer, Public Health Division Pathanamthitta (For and on behalf of Governor of Kerala)
Jal Jeevan Mission Vallicodu Grama Panchayat Supply and erection of Transformerunit, Supply and erection of pump sets
2024_KWA_674920_1
104(Rt)/2023-24/EE/PH/PTA
Open Tender
Electrical Works
Item Rate
180 days
Vallicode
Please refer Tender documents.
9 documents required · 9 mandatory
₹2,760
₹50,000
30 Aug 2024
10 Jun 2024
20 Jun 2024
10 Jun 2024
19 Jun 2024
10 Jun 2024
Amount
working charges
OD254860/2023-2024:Supply of all materials and providing 11KV sub station yard using 4nos. 175x85mm. ISMB joist of 9.5M height, 100x50mm. MS chanel cross arms, 2sets of 200A, 11KV gang operated AB switches with opertating handles of required length,2 sets of 9.6KV,6KA , Lightning Arrestors, 2sets of 11KV, D.O fuses, Pin insulators, Disc insulators and inter connections of the above items using '0' SWG copper wire with proper copper sockets , including all associated civil works and painting of all structurers with two coats of zinchromate primer and aluminium paint etc. complete including earthing, as per standard onstruction practices approved by Kerala Electrical Inspectorate and relevant standards Supply of all materials and providing 11KV sub station yard using 4 Nos.175x85mm ISMB joist of 9.50m height, 100x50mm MS channels cross arms. 2 set of 200A, 11KV gang operated ABswitches with operating handles of required length, 2 sets of 11KV DO fuses. 2 sets of 9.6 kV 6 kA Lightning arrestors, Disc insulators, pin insulators and interconnections of the above items using '0' SWG copper conductor, copper sockets, including all associated civil works and painting of all structures with two coats Zinchromate primer and aluminium paint etc. complete including earthing as per standard construction practices approved by Kerala Electrical Inspectorate and relevant Standards.
OD254861/2023-2024:315 KVA Transformer, .Supply,erection, testing and commissioning of 315 KVA, 11KV/433V. 3phase, 50Hz. ONAN cooled , Outdoor type copper wound distribution transformers,including Construction of plinth ,DP structure, AB units, Fuse units suitable and other fees for KSEB Inspection and documentation for parrallel operation, with HV and LV side cable entry box arrangements, on load tap changer with 17 tap positions having +5% to -15% variations in1.25% steps with RTCC panel with AVR control relay, localand remote indication of tap position including first filling of oil, earthing , Fencing around,etc. complete with all fittings as per IS 2026 and Kerala Electrical Inspectorate standards
OD254862/2023-2024:Supply, Test, install , commission and trial run of CT/PT and TOD Meter of suitable rating and capacity as per KSEB standards
OD254863/2023-2024:MV PANEL BOARD ,Design,engineering, supply erection,testing and commissioning of medium voltage sheet steel clad, totally enclosed, dust tight & vermin proof, indoor floor mounted cubicle type switchboard fabricated out of 14swg mild steel sheet, and bus duct of high conductivity aluminium bus bars, pvc sleeved, air insulated and of adequate size as mentioned below, for operation on 3 phase, 4wire, 415volts, 50Hz. AC supply system. The MCCBs, all meters and relays etc. should be reputed make and conforming IS specifications and are assembled, interconnected, earthed and the switch board should be painted with anti –rust primer coating followed by two coats of paint of approved shade, as per standard construction practices approved by Kerala Electrical Inspectorate and relevant standards . Also includes Providing and fixing CT ,PT ,TOD meter as per KSEB norms- and cables ( if necessary ) for the pump sets in WTP and all allied electrical works for pump sets
OD254864/2023-2024:Power Distribution board (PDB) ("Supply,erection, testing and commissioning of 8 way TPN MCB distribution board comprising to the following. 63A 4 pole MCB 1 No. as incomer with 63A 100mA ELCB and 20A TP MCB-2Nos. & 20A SP MCB- 6 Nos each. as outgoings, <br> With tinned copper busbars/cables, interconnection, housed in a suitable metal enclosure as per KEI standards fixed in open system
OD254865/2023-2024:Cabling Supply,Laying,Testing and Commissioning of following sizes of MV(1100V) cables XLPE Aluminum cables as per IS.standards 3.5x300 Sq. mm (A2XFY/A2XWY type)
OD254866/2023-2024:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required- 3.5x300sq.mm
OD254867/2023-2024:Earthing with G.I. earth plate1200 mm X1200 mm X 12 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. The earthing station should confirm to IS 3043/87. (Booster stn, Raw water) (All civil works shall be done by the contractor)
OD254868/2023-2024:Supply and fixing of M.S. angle cable tray for clamping the various sizes of cables in trenches, through walls, & trusses etc. as per KEI standards.
OD254870/2023-2024:Supplying, installation and testing trial run and commissioning of suitable size three phase 1 HP or suitable vacuum priming pump in the common suction header of the Clear pumping system at Pump House in WTP. The priming pump shall be capable of generating a suction lift of 5 meters in the worst condition. The scope of the work involves providing all necessary accessories, mountains and fittings for the satisfactory functioning of the priming system connecting for a total number of 4 CF pump set at the CW pumping station with required control valves
OD254871/2023-2024::Supply and providing the following safety items approved by Kerala Electrical Inspectorate and relevant standards. 11kv rubber mat 1800 x1900 x12mm- 2 set, 11 KV rubber glouse -4 sets, 11 KV danger board - 4 Nos Shock treatment chart-1, ISI marked, Certified, Approved Pedemilan Dry Chemical Fire Extinguisher- 6 kG with hose and clamps including fixing it to wall as required
OD254872/2023-2024:Provision for making drawing and getting approval ( One for WTP, Booster & RWPH ) Covers the works and documentation Involved in approval from statutory bodies like electrical inspectorate and KSEBL( fees and other statutory remittances will be made by KWA).The work includes soil testing, Earthing design, Preparation of scheme and drawings, submission of the same to the electrical inspectorate and finalize the approval .On completion of the work, approval to be obtained from the inspectorate after incorporating the modification if any due to changes from the approval design and submission of approval. KWA shall only provide supporting letters/ authorisation est for obtaining the approval.
Barnett Associates
Bidder Name
Barnett Associates
TKM Infra Projects
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_1049754.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .