| 1 | L1₹21.3 LAccepted-AOC | L1 | Accepted-AOC Being L1 bidder | |
| 2 | L2₹23.5 L+₹66,776.50 (2.93%)Rejected-Finance ASHOKA PARK PALLAVA PARK BVT INS VISHWAKARMA INDIAN NAVY OF GE ND VISAKHAPATNAM | VISAKHAPATANAM | ANDHRA PRADESH | 530001 | L2 | Rejected-Finance Being not L1 bidder | |
| 3 | L3₹25.1 L+₹2.3 L (9.99%)Rejected-Finance DOOR NO 15 1 141 BHAVANA ENCLAVE 1 NEAR HOTEL GRAND BAY MAHARANIPETA NOWAROJI ROAD VISAKHAPATNAM 530002 | VISAKHAPATNAM | VISAKHAPATNAM | ANDHRA PRADESH | 530002 | L3 | Rejected-Finance Being not L1 bidder | |
| 4 | L4₹26.8 L+₹4.0 L (17.4%)Rejected-Finance D NO 4 96 40 27 FLAT NO 307 GREEN CASTLE APARTMENT GOPALAKRISHNA NAGAR SUJATHANAGAR VISAKHAPATNAM 530 051 | VISAKHAPATANAM | ANDHRA PRADESH | 530051 | L4 | Rejected-Finance Being not L1 bidder | |
| 5 | L5₹27.8 L+₹4.9 L (21.6%)Rejected-Finance MIG 2B 65 VINAYAKA NAGAR VUDA COLONY VISAKHAPATNAM 530044 | VISAKHAPATANAM | ANDHRA PRADESH | 530044 | L5 | Rejected-Finance Being not L1 bidder |
Tender Value
₹39 L
EMD Value
₹78,000
Closing Date
18 Feb 2023, 6:00 pmClosed
Garrison Engineer Utility-I Visakhapatnam
Garrison Engineer Utility-I Near Samudrika Naval Base Post Visakhapatnam -530 014
REPAIR/MAINT OF LT FEEDER PILLAR BOXES, LT UG CABLES AND CONNECTED WORKS OF LT DIST SYSTEM INCL ATTENDING FUSE OFF CALL AT NCB, 32 WEU/HF/DF AREA, CE OFFICE COMPLEX AREA, NIRMAN PARK, 104 AREA, SVN COLONY AND MGEDDA AREA UNDER AGE E/M-II OF GE(U-I)V
2023_MES_576502_1
8498/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
Garrison Engineer Utility-I Visakhapatnam
As per NIT
6 documents required · 6 mandatory
₹500
Garrison Engineer Utility-I
₹78,000
Yes
2 Mar 2023
21 Jan 2023
20 Feb 2023
21 Jan 2023
18 Feb 2023
6 Feb 2023
Amount
Excavation in trenches, not exc 1.5 m wide and not exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out all excavated material in soft / loose soil complete all as specified and directed.
Removing of excavated surplus soil to a distance n. exc 50 m and depositing where directed at a level n. exc. 1.5 m above the starting point complete all as specified and directed.
Returning, filling in and including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick complete all as specified and as directed.
M&L sand cushioning with clean and dry sand in trenches for protection of UG cable and including punning down complete all as specified and directed. Note:- Punned thickness shall only be measured and paid.
Supply & laying sub class 'B', class designation 75 bricks of old size, laid along alignment of cable as protection to cable in trenches complete all as specified and directed.
S&F 50 mm bore galvanised steel tubing, light grade with necessary fittings, laid under road crossing, for cable protection including taking down complete all as specified and directed. Make - Tata / Jindal Steel / Surya Roshni Ltd. / Bhushan Power & Steel Ltd. / M/s APL Apollo Tubes Ltd
All as per Item No. 6.00 but size of 80 mm bore
M&L for cutting the tarmac / hard standings in road and excavating trenches across the road in size not exceeding 0.45 m wide and 0.6 m depth for laying cable including refilling earth & making good top surface of the disturbed portion with 100mm thick PCC 1:3:6 / bituminous mix as per existing & matching with the surroundings complete all as specified and directed.
Supply & laying LT XLPE insulated, armoured heavy duty electric cable with alumimium conductor, 1100 volts grade, cross sectional area 16 Sqmm x 4 Core, laid in trenches / duct / on pole including taking down complete all as specified and directed. Make :- Havells / KEI / Polycab / Gloster / Asian Cables / Finolex
All as per item No. 9.00 but cross sectional area 25 Sqmm x 4 Core
All as per item No. 9.00 but cross sectional area 35 Sqmm x 3.5 Core
All as per item No. 9.00 but cross sectional area 50 Sqmm x 3.5 Core
All as per item No. 9.00 but cross sectional area 70 Sqmm x 3.5 Core
All as per item No. 9.00 but cross sectional area 95 Sqmm x 3.5 Core
All as per item No. 9.00 but cross sectional area 120 Sqmm x 3.5 Core
All as per item No. 9.00 but cross sectional area 150 Sqmm x 3.5 Core
All as per item No. 9.00 but cross sectional area 185 Sqmm x 3.5 Core
All as per item No. 9.00 but cross sectional area 240 Sqmm x 3.5 Core
All as per item No. 9.00 but cross sectional area 300 Sqmm x 3.5 Core
M&L preparation of old painted surfaces of LT panels etc. by scraping and making the surface smooth and including applying two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed. Make :- Jotun India Pvt Ltd / Apcolite (Asian) / Luxol (Berger) / Jenson & Nicholson Paints Ltd (Borolac) / Shalimar Paints Ltd (Superlac)
S&F MCCB 3 pole 320-400 Amps breaking capacity 35/36 KA, Ics = 100% Icu including taking down complete all as specified and directed. Make :- L&T / Havells (Brand- HIM & HIX) / Panasonic / Hager / ABB / Legrand / Indo Asian (Optipower)
All as per item No. 21.00 but 250 Amps
All as per item No. 21.00 but 200 Amps
All as per item No. 21.00 but 150/160 Amps
All as per item No. 21.00 but 25 - 100 Amps braking capacity 16 KA
S&F MCCB 4 pole 630 Amp, breaking capacity 36 kA, Ics = 100% Icu including taking down complete all as specified and as directed. Make :- L&T / Havells (Brand- HIM & HIX) / Panasonic / Hager / ABB / Legrand / Indo Asian (Optipower)
All as per Sl item No. 26.00 above but 400 Amp
All as per Sl item No. 26.00 above but 250 Amp
All as per Sl item No. 26.00 above but 200 Amp
M&L straight through joint, heat shrinkable type complete with jointing materials and accessories, suitable for 1.1 KV, 3.5/4 core XLPE aluminium conductor cable of size 10/16 Sqmm including taking down complete all as specified and directed. Make:- 3M / Denson / Raychem
All as per Item No. 30.00 but cable of size of 3.5 core 25 to 50 Sqmm
All as per Item No. 30.00 but cable of size of 3.5 core 70 to 150 Sqmm
All as per Item No. 30.00 but cable of size of 3.5 core 185 to 300 Sqmm
M&L for removing electrical connections of 3 / 4 pole Air circuit breaker of capacity 400 to 1200 Amps, 415 V, 50 HZ of make L&T / C&S / GE / ABB, strip opening of the ACB, inspecting the parts for serviceability / overhauling complete and carrying out following repairs / maintenance :- a) Cleaning insulation parts including bushings with CTC solution. b) Checking alignment and condition of movable and stationary contacts and adjust them all as per manufacturer's instructional manual. c) Checking the bolts, nuts, washers, cotter pins and all terminal connections are in place and tight, replacing worn-out parts. d) Checking arc chutes for damage and replacing damaged parts. e) Cleaning and lubricating the operating mechanism with light machine oil (SAE-20 or 30) for pins and bearings and with a non-hardening grease for wearing surfaces, adjusting breaker operating mechanism all as per manufacturer's instructional manual, replacing the same if there is excessive wear and tear. f) Checking / inspecting shunt trip coil for serviceability and replacing the same if required. g) Replacing worn or burned contacts, Checking control device free for operation. h) Checking after servicing the circuit breaker to verify the contacts move to the fully opened and fully closed positions, that there is an absence of friction and that the electrical operation is functional. Note : (i) The rate quoted deemed to be inclusive of T&P and minor spares like lubricants, nuts / bolts / washers / pins etc. (ii) Major spares like contacts, shunt trip coil, relays, CTs etc if replaced, shall be measured & paid separately.
S&F in repairs under voltage release coils of make as per existing suitable for air circuit breakers of capacity 400 to 1200 Amps all as specified and directed.
S&F in repairs closing coil of make as per existing suitable for air circuit breakers of capacity 400 to 1200 Amps all as specified and directed.
S&F in repairs shunt release or Tripping coil (110 /220 V DC or 240 V/415 V AC) of make as per existing suitable for air circuit breakers of capacity 400 to 1200 Amps all as specified and directed.
S&F in repairs arcing contacts (fixed / moving) of make as per existing suitable for air circuit breakers of capacity 400 to 1200 Amps all as specified and directed.
S&F in repairs on-load change over switch 400 Amp capacity four pole 415 volts with advance neutral, front operating handle complete all as specified and directed. Make:- ABB /L & T / Legrand / Siemens / Schnieder / Havells India Ltd. / Indo Asian
All as per Sl Item No. 39.00 but suitable for 250 Amp
M&L for strip opening AMF panel of 100 to 250 KVA capacity DG set, checking, inspecting, calibrating AMF panel, replacing the burnt copper wiring with suitable flexible copper wire, inspecting the contactor coils & replacing the defective coils, cleaning the fixed / moving contacts with CTC complete including setting of AVR of Alternator incl testing & commissioning all as specified and directed.
M&L for Maintenance and attending complaints / breakdowns at Nirman park, 104 Area and SVN Colony area comprising of LT panels, over head lines / underground LT cables up to main distribution boards at buildings including day to day maintenance of LT panels / Perimeter lights for smooth & trouble free LT power supply including rectification of minor defects to electrical controls gear / accessories as directed by Engr-In -charge. Note : Unit rate quoted shall deemed to be inclusive of the following:- (a) Attending minor repairs / breakdowns without involving any new (major) materials. (b) Rate shall include cost to provide tools for attending break down and minor materials like lugs, PVC tapes, including issue / maintaining Job Cards and Complaint registers etc. (c) Major repairs / Break downs involving S&F of materials such as cables, Joints, MCCBs etc are outside the scope of this item and shall be measured and paid separately. (d) Contractor should ensure to carry out the work through qualified Technician / Electrician and assisted by the helper. Necessary tools & plants and transportation charges are deemed to be included in the unit rate quoted. (e) On completion of the task /attending break down, necessary Job card duly signed by the stake holder shall be submitted to Engr-in-Charge.
M&L earthing complete with galvanised steel earth plate electrode of size 600 x 600 x 6 mm thick buried directly in ground in vertical position (earth pit not less than 2.25 m deep below the normal ground level) with top edge of the earth plate not less than 1.5 m below normal ground level, connected to earth lead of galvanised iron strip 32 x 6 mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel, all as shown in electrical plate No. 3 connected to earthing test point including dismantling complete all as specified and directed. Note:- The unit rate shall also include for earth work in any type of soil, PCC 1:3:6 type C1 chamber, RCC 1:1.5:3, type A1 cover slab, 50 mm thick reinforced with 8 mm dia TMT bar @ 140 mm C/C both ways, 10 mm dia plain bar lifting handle embedded in cover slab, Main earthing lead from earth electrode to test point upto 7.5 m length, 20 mm bore medium grade GI watering pipe, 40 mm bore GI light grade earth lead protection pipe, funnel, wire mesh, copper lugs, charcoal and common salt in alternate layer etc.
M&L cement concrete 1:3:6 type C1, (using 20 mm graded crushed stone aggregate) as in copings, benching and the like etc. including necessary formwork & demolition complete all as specified and directed.
M&L for replacement of LT panel board canopy, door, body etc. made out of 2 / 3.15 mm thick CRCA sheet, duly power coated with one coat of synthetic enamel paint over a coat of primer with removable door hinges, neoprone gasket and locking arrangement, including welding work for fixing the door complete all as directed. Note:-Unit rate quoted shall be considered to include hinges, locking arrangement, neoprone gasket etc reqd for one LT panel. Contactor shall quote their rates accordingly.
M & L for excavating existing cable of size 10/16/25 Sq mm to 120 Sqmm, 3.5/4 core & taking out from its loop of length 3 to 5m, cleaning, cutting of old termination at end and reconnecting the same along with termination at ends with new aluminium lugs of suitable size and refilling of cable trench with existing sand and bricks complete all as directed. Note: The rate quoted shall include for necessary earth work
All as per item No. 46.00 but for cable of size 150 to 300 Sqmm, 3 core
S&F in repair phase indicator lamps (Red, Yellow and blue) suitable for fitting in existing panel complete all as specified and directed. Make:- L&T / Siemens / GE / RR Micro / BCH / Schneider
S&F in repair DMC insulator for bus bar support in panel board complete all as specified and directed.
SRI SRK ENGINEERS
SRIESWARI ENTERPRISES
MSN ENGINEERING WORKS
jyothi constructions
M/s SS Engineering Enterprises
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .