Loading…
Loading…
Tender Value
Refer Docs
EMD Value
₹3.2 L
Closing Date
27 Jul 2026, 5:00 pm
DDEM MANDI PARISHAD GHAZIABAD
DDEM MANDI PARISHAD GHAZIABAD
SITC of 20 HP Capacity mud pump With All acceceries 62 5 KVA DG set cable laying etc work at NMY Mathura
2026_RKUMP_1166436_1
3160 Mathura Mud Pump
Open Tender
Electrical Works
330 days
Mathura
SITC of 20 HP Capacity mud pump With All acceceries 62 5 KVA DG set cable laying etc work at NMY Mathura
2 documents required · 2 mandatory
₹5,700
DDEM MANDI PARISHAD GHAZIABAD
₹3.2 L
Yes
6 Jul 2026
6 Jul 2026
28 Jul 2026
6 Jul 2026
27 Jul 2026
6 Jul 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Supplying, Installation, Testing & Commissioning of Unit Rate ‘Silent Type Diesel Generating set as per CPCB IV + or better norms along with having Prime Power Rating of KVA as below, 415 volts at 1500 RPM, 0.8 lagging power factor at 415 V suitable for 50 Hz, 3 phase system & for 0.85 Load Factor, including testing at factory and site with fuel, load for test and other necessary arrangements Complete as per CPWD specifications, should have QR code which should contain drawing, test report OEM manual,Geo- Tag of manufacturing location, rating plate as per relevant IS Code etc. and consisting of the followings: (A) Diesel Engine: Tourbocharged Diesel engine 4 stroke water cooled, multi cylinder, dynamically balanced fly wheel, electric start of suitable BHP at 1500 RPM suitable for above output of alternator at 40 0C, 50% RH & at 1000 Meter MSL , capable of taking 10% over loading for one hour after 12 hours of continuous operation. The engine will be with Electronic governor, Dry type Air filter with service indicator, first filling of engine fuel (after commissioning) lubricating Oil, Coolant and other consumables complete with all the required accessories, the Electronic governor shall be as per ISO 8528.The engine shall comply to the latest CPCB norms (CPCB IV + or better) and Conforming to BS 5514, BS 649, IS 10000, IS 10002, IS 13018 and as per CPWD specifications. (B) Engine mounted Instrument Panel fitted with and having digital dis Plate for following: (i) Start-stop switch with key (ii) Water temperature indication (iii) Lubrication oil pressure indication (iv) Lubrication oil temperature indication (v) Battery charging indication and Voltage indication (vi) RPM indication (vii) Over speed indication (viii) Low lubricantion Oil trip indication (ix) Engine Running Hours indication (x) Fuel Level (C) Alternator: Synchronous alternator rated of appropriate KVA, 415 volts at 1500 RPM, 3 phase 50 Hz, AC supply with 0.8 lagging power factor at 40 0C, 50% RH & at 1000 Meter MSL. The alternator shall be having Screen Protected Drip Proof (SPDP) enclosure IP23, brushless, continuous duty, dynamically balanced rotor, capable of taking 10% over loading for one hour after 12 hours of continuous operation, self cooled,self-excited and self-regulated through AVR conforming to IS13364(Part 2)/IS: 4722/BS 2613 suitable for tropical conditions and with class- H insulation. (D) Base Frame & Foundation: Both the engine and alternator shall be mounted on suitable base frame made of MS channel with necessary reinforcement which shall be installed on suitable cement concrete foundation and vibration isolation arrangement as per recommendations of manufacturer. (E) FUEL TANK: Daily service fuel tank of suitable liters capacity as per CPWD Specifications, fabricated out of 3 mm thick M.S. sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine with MS class ‘C’ pipes of suitable dia. Complete with valves, level indications & accessories as required as per specifications. (F) Exhaust System: Dry exhaust manifold with hospital type exhaust silencer and catalytic convertor. (G) Starting System: 12V/24V DC starting system comprising of starter motors: voltage regulator and arrangement for initial excitation complete with suitable numbers of batteries (180 AH capacity lead acid SMF type) as required as per specifications. The battery shall be housed inside the acoustic enclosure of DG Set. (H) Acoustic and weather proof enclosure with arrangement for fresh air intake for cooling of the engine & alternator, extraction, discharging hot air in to the atmosphere and the temperature rise inside the enclosure, noise level outside enclosure. The acoustic enclosure should be suitable for cable connection/connection through bus-trunking. Such arrangements on acoustic enclosure should be water proof & dust-proof conforming to IP-65 protection. The enclosure shall be as per CPCB IV + or better norms etc. and as per CPWD specifications. (I) AMF Panel: Free standing floor mounted IP 42 automatic mains failure control panel including auto by-pass, suitable for KVA as below for silent type DG set complete with relays, timers, set of CTs for metering & protection and energy analyser to indicate currents, phase and line voltages, frequency, power factor, KWH, Kilo Volt Ampere Reative Hour (KVARH), KVA (Phase & Total), KW & provision for overload, short circuit, restricted earth fault, under frequency, power (aluminium) and control (copper ) cabling of suitable size upto 15 meter between AMF panel, LT Panel and DG Set including connection interconnection etc. as required, all complete and inter locking and communication/ Ethernet /RS485/SNMP port open protocol for BMS integration including suitable software, the panel shall be of DG Set OEM make etc. as per approved by Engineering in charge and including the following: | |||||
| 1.01 | 1. Suitable numbers and appropriate capacity 4 pole motorised electrically operated draw out with cradle type 3 position ACB/ MCCB with electronic release for O/C & E/F and shunt trip.
2. Auto/Manual/Test/Off selector switch
3. Protection for under and over voltage phase reversal (2 nos Over voltage relay, 2 Nos. reverse power relay and 2 Nos. under voltage relay).
4. 3 Sets of current transformers 15 P 10 accuracy for protection and 15 VA class-I for metering
5. Energy analyser unit to indicate current, Voltage( L N & L_L), kW, kVA (Phase & Total), Frequency, KWH, PF.
6. LED Indicating lamps for load on mains and load on set
7. Fuse/ MCB for instruments
8. Battery charger, complete with transformer/ rectifier, D.C. voltmeter and ammeter, selector switch for trickle, off and boost and current adjustment.
9.Main supply failure monitor
10.Supply failure timer
11.Restoration timer
12.Control unit with three impulse automatic engine start/stop and failure to start lockout.
13. Impulse counter with locking and reset facility.
14.ON/OFF/Control circuit switch with indicator
15.Audio/Video annunciation for (i)High water temperature (ii)Low lubricating oil pressure (iii)Engine over speed (iv)Engine fails to start (v)Full load/maximum load warning
16.Protection for over/under Frequency, Loss of AC sensing, Over Current, Unbalancing load with suitable number of relays and accessories
17. Maintenance notification based on Engine Run Hour & due date.
18. Load Management through PLC to achieve auto opening and closing of incomer breakers, bus coupler switching of essential panel , interlocking providing signal to AMF Panel for load status and AMF shall give command to DG Set to auto start / auto stop depending upon load status and requirement etc. and necessary hardware and software required to perform the operation shall be provided by the contractor including all control wiring.
62.5KVA
DSR E/M 2025 29.1.5 | 1 | Nos | 4,37,545 | ₹4,37,545 |
| 2 | Design, Supply, Installation, Commissioning & Testing of Non-Clog Single Stage bottom Suction Submersible Sewage Pumping Plant (900 RPM/20HP Capacity 1000 LPM /30 Mtr Head) Along with Auto Coupling Guide pipe complete with all accessories etc. | 3 | Nos | 3,53,559 | ₹10,60,677 |
| 3 | Supply and erection of factory fabricated and wired metal clad dust and vermin proof floor mounting panel TPN switch board complete with the following HRC type heavy duty TPN fuse switches with fuses and instrument chamber etc. complete in all respects. The instrument chamber shall be separate and shall comprise of flush type ammeter, voltmerer, selector switches for ammeter and voltmeter, instrument fuses, current transormer etc. The board shall have suitable capacity electroytic alumininum busbars as per IS8623 istulate with heat shrink sleeving and mountend on non hygroscopic supports such as CMC/DMC support with deteachable side covers and shall be suitable for extension on the sides. The switches shall be complete with suitable cable end boxes, reverse entery boxes in case of pedestaal type, cable sockets, compression glands and indicating lamp on incoming etc.
The job includes the grounting of the board as per direction of Engineer-in-Charge. All coutgoing switches of 100 Amp. and above will be provided with ampere metre current transformers and selector switches and instrument fuses etc. The switches board shall be fabricated with CRCA sheet with a minimum thickness of 1.6 mm/2 mm. Cubicle type switch board shall be of cat A B & B-II and pedestal type for Cat-B and C only.
Incoming 400 Amp. TPN-1 No
Outgoing
200 Amp.TPN-1Nos, 100 Amp.TPN-2Nos. & 63 Amp.TPN-1Nos.
Cat. B. Cubicle Type SOR 2018 | 1 | nos | 1,42,800 | ₹1,42,800 |
| 4 | S&F of 400 Amp. four pole change over switch on 50mm x 50mm x 6mm angle iron frame, including the cost of labour,T&P, painting and other material required for proper completion f the work as per direction and satisfaction of Engineer in charge. SOR 2018 381 | 1 | Job | 23,420 | ₹23,420 |
| 5 | 20 HP Starters Control Panel For Submersible Pump
GEM | 3 | nos | 21,186 | ₹63,558 |
| 6 | SLUICE VALVE’ 200 mm Dia 24.03 UPJB 2021 | 3 | nos | 29,250 | ₹87,750 |
| 7 | SLUICE VALVE’ 250 mm Dia
34.02 UPJB 2021 | 1 | nos | 48,109 | ₹48,109 |
| 8 | S/F of Non Return Valve 250 mm Dia
SOR 2024-25
DJB
4.58.6 | 1 | nos | 50,500 | ₹50,500 |
| 9 | Supply and laying of aluminium conductor PVC insulated armoured served, sheathed cable 1100 volts grade at a depth of 750 mm. below ground level over a cushion of 75 mm. thick stand alround and protected with burnt bricks on sides and on top. on surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Inchange, complete in all respect. The armoring of the cable shall be properly connected with the earthy conductor by clamps etc. 1. 300 SQ mm X 3.5 Core 20a.1.19 | 60 | Mtr. | 2,322 | ₹1,39,320 |