Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.3 LAccepted-AOC | L1 | Accepted-AOC AOC | |
| 2 | L2₹5.5 L+₹86,218.64 (18.5%)Rejected-Finance | L2 | Rejected-Finance Rejected |
Tender Value
₹3.7 L
EMD Value
₹7,500
Closing Date
8 Mar 2021, 11:00 amClosed
Executive Engineer Jal Shakti Division Nahan
Executive Engineer Jal Shakti Division Nahan
Providing Laying Jointing and testing of R/main MSERW pipe and Laying, Jointing and testing of GMS pipes 40mm dia and Supply and errection of submersible pumping machinery with allied accessories
2021_HPIPH_44971_2
NHN-SMR00-722- 16027-16107 dt 26-02-2021
Open Tender
Pumps/Motors
Item Rate
90 days
Nahan
Please refer Tender documents.
12 documents required · 12 mandatory
₹250
Executive Engineer Jal Shakti Division Nahan
₹7,500
Yes
12 Aug 2021
2 Mar 2021
8 Mar 2021
2 Mar 2021
8 Mar 2021
2 Mar 2021
Amount
Rising main
Excavation in drains and channels etc.in earth work for pipes up to all depths in all classification of earthwork such as pick work, jumper work, saturated soil including bailing or pumping out water, blasting soft/hard rock or chiseling soft / hard rock where blasting is prohibited in all lifts including jungle clearance wherever required, trimming & dressing of sides, leveling of beds to correct grade including shoring/struting, planking, timbering & dewatering wherever required stacking the useable/unuseable material/soil seperately & after laying, jointing & testing of pipes, returning the useable soil in trenches in 15 cm layers including consolidating of such deposited layer by ramming & watering & then disposing of all surplus excavated soil/unuseable material as directed with in all leads & lifts including restoration of un-metalled surfaces to its original condition & including cost of diversion for traffic, night signals, fixing caution boards, crossing over trenches for access to houses, fencing etc. complete in all respects with-in all leads & lifts as per directions of the Engineer Incharge.
Providing,laying, testing & commissioning at site in trenches bevelled ended MSERW pipes of Grade A CONFIRMING TO IS/ISO 3183-2007 Or its equivalent grade as per API Specifications, having wall thickness & per Rmt weight as mentioned below & capable of withstanding required test pressure as prescribed in BIS code, in random lengths of 5.5 to 6.50 Mtr. The pipe's ends shall be bevelled suitable for butt welding, including the cost of jointing with butt welding confirming to IS 816-1969 or latest as applicable ends with up to date ammendments ( leak proof) in three layers at site of work with welding rods of standard make & all allied accessories whatever required for welding at site, tees, bends & other specials manufactured from parent pipe as applicable to the particular reach & of approved specification as per site conditions and cutting of pipes wherever required as per site requirement i/c carriage in all leads & lifts and as directed by Engineer in Charge. The pipe shall have's Zinc coating inside & outside confirming to IS-4736-1986 or latest with up to date ammendments & shall be engraved with IS/ISO 3183-2007 , Grade A. The laying shall confirm to BIS 5822-1970 or latest with up to date ammendments to the entire satisfaction of Engineer in Charge. ( Earth work shall be measured & paid for seperately).
Shilli Side
1. 0 90 40 MM 5.10 mm 90 GRADE " A"
Laying, , jointing , testing & commissioning at site in trenches following plain ended GMS pipes of 40 mm dia of Heavy Grade as under confirming to BIS 1239-(Part-1)-1990 or latest with up to date ammendments, capable of withstanding required test pressure as prescribed in BIS code, in randum lengths of 5.5 to 6.5 mtr. The pipe's ends shall be bevelled suitable for butt weld, including the cost of jointing with butt welding confirming to IS 816-1969 or latest as applicable (leak proof) in three layers at site of work with welding rods of standard make & all allied accessories whatever required for welding at site, tail pieces, tees, bends manufactured from parent pipes etc. and cutting of pipes wherever required as per site requirement i/c carriage in all leads & lifts as directed by Engineer-Incharge (Earth work shall be measured & paid for seperately).
Shilli Side RD 90 - 540 450 Rmt
SanariSide RD 0 - 425 425 Rmt
Providing, welding and fixing M.S. plate flanges of various dia. (nominal bore) of following Flange Tables confirming to IS 6392-1971 or latest with up to date ammendments to MSERW/GI pipes after every 90 metres or as per site requirement including cutting of pipes wherever required, welding in three layers (leak proof) confirming to specifications as prescribed in relvent I.S. Code i.e. IS 816-1969 or latest as applicable with up to date ammendments with nuts, bolts & washers & specials etc. confirming to IS-1963 or latest with up to date ammendments including packing sheet i.e. asbestos fibre sheet minimum 3mm thick and painting with anticorosive paints complete in all respect i/c all leads, lifts and carriage of material at site and as directed by the Engineer Incharge.
Sr.No. R.Ds Nominal Dia Length (in Mtrs) Flange table.
From To
Shilli side
Sanari Side
Pumping machinery. (Submersible)
( Shilli Side)
Supply, erection, testing & commissioning of submersible pumping set of reputed make KSB /Kirloskar/Mather & Platt/ Jyoti or any other reputed make,conforming to latest relevent BIS code. The pump should be fitted with free flow impellers of bronze /suitable alloy as per BIS 5659 or latest with up to date ammendments suitable for raw/clear water having characteristics as mentioned in item No. 5 A) ,greased packed bearings & shell with wound stator on motor side & with shaft protection sleeve on pump side ensuring better life for shaft conforming to BIS specifications. The pump shall be directly coupled to a submersible squirrel cage electric induction motor of Kirloskar/NGEF/Jyoti / Crompton make conforming to relevent BIS code with up to date ammendments totally dust & water proof for submersible duty isolated from the pump by intermediate casing with double mechanical seal in oil chamber chamber & grease packed lubricated bearings & provided with stainless steel thrust bearing plate to withstand non vertical loads with minimum wear & tear. It should also be fitted with a device to take up expansion of water with the heating of motor . The pump set should include water level guard, errection clamps, cable clips & depth gauge etc. & suitable for operation on data given below:-
Nos of pump required:- 2 Nos pumps
Static head in mtrs. 176 mtrs
Total Head in mtrs : 203.50 mtrs
Capacity (in LPS) 1.01 LPS
Length of Rising Main 540 mtrs
Dia of R/Main (in mm) 40mm dia
HP:_ 2x5HP= 10 HP
Providing and fixing of Auto control panel with push button star delta starter for submersible pumps of L&T and reputed make fabricated with M.S sheet and Angle stand duly painted and complete with internal wiring ,comprising of main switch of suitable Amp. T.P. Volt meter, ammeter,hour run meter,copper busbar ,phase indicating lamps with GSM based , Remote start/stop operation call/SMS for feedback regarding running of pumps & breakdown message, timer scheduling for fixed hours in a day,Inbuilt protection against overload/undervoltage,Dry run,single phase preventor,Inbuilt GPS tracker,phase reversal configurable volt/current limits with a facility to access the system through minimum 10 Nos. authenticated mobile Nos. complete in all respect, including entire carriage of materials upto all leads and lifts,installation and testing at site with entire satisfaction of Engineer-in-charge.(All meters to be installed shall be DIGITAL.)
Supply and fixing at site of Kirloskar/Kilburn/IVC/Fouress/Gled/BHEL/Leader/KSB/Pelicon make of suitable size cast steel double flanged swing check type reflux valve having bye pass arrangement & size one size larger than the nominal dia of delivery of the pump or equal to dia of column pipe (in case of t/well) and capable of withstanding nominal seat pressure as mentioned in item No.5-(a)+SURGE PRESSURE & conforming to API standards with up to date ammendments for delivery line of pump.Class of valve shall be ASA 300.
P/L suitable size copper PVC insulated armoured power three & half core cable conforming to BIS 1554 (Part I) -1988 or latest with up to date ammendments of Siemen/Gloster/ ICC/EICO /National /IEC make from meter of HPSEB to circuit breaker & from circuit breaker to bus bar switch & starter (one cable carrying all three phases) including all other electrical equipment/accessories such as thimbles,flexible pipe,solder,nuts & bolts,cable glands etc. laid in pipes or trenches under floor. The type,size & make will be subject to approval of HPSEB authorities. In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost .
P/L PVC jointless flat water proof cable as per BIS 694-1990 (latest with up to date ammendments) suitable for the pump sets offered from circuite breaker to motor & motor to starter including all other electrical equipments such as thimbles, flexible pipes, solder,nuts & bolts,cable glands etc. laid in pipes or trenches. The type,size & make will be subject to approval of HPSEB authorities.In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost.
Supply & errection of floor/wall mounted power factor shunt capacitor of suitable KVAR conforming to BIS 2834-1986 or latest with upto date ammendments of BHEL/GEC/Machneil/ Mager/Bajaj/L&T make to raise the prevailing power factor at site to 0.95 for direct connection to induction motor individually,of required KVAR according to HP of motor offered including cable Siemens/Gloster/ICC make from busbar chamber to capacitor & also including L&T//Kilburn/Standard/Siemen/Havells make ICTP switches conforming to BIS 4064-1978 or latest with HRC fuses (Range to be specified by the tenderer).
Supply of 100mm dia circular dial pressure gauge of suitable range & standard make such as Fiebeg/Bourden/ Precision/PREGA with all accessories such as stop cock,copper tubing etc.conforming to BIS 3624-1987 or latest with up to date ammendments.
Sanari side
Supply, erection, testing & commissioning of submersible pumping set of reputed make KSB /Kirloskar/Mather & Platt/ Jyoti or any other reputed make,conforming to latest relevent BIS code. The pump should be fitted with free flow impellers of bronze /suitable alloy as per BIS 5659 or latest with up to date ammendments suitable for raw/clear water having characteristics as mentioned in item No. 11 A) ,greased packed bearings & shell with wound stator on motor side & with shaft protection sleeve on pump side ensuring better life for shaft conforming to BIS specifications. The pump shall be directly coupled to a submersible squirrel cage electric induction motor of Kirloskar/NGEF/Jyoti / Crompton make conforming to relevent BIS code with up to date ammendments totally dust & water proof for submersible duty isolated from the pump by intermediate casing with double mechanical seal in oil chamber chamber & grease packed lubricated bearings & provided with stainless steel thrust bearing plate to withstand non vertical loads with minimum wear & tear. It should also be fitted with a device to take up expansion of water with the heating of motor . The pump set should include water level guard, errection clamps, cable clips & depth gauge etc. & suitable for operation on data given below:-
Nos of pump required:- 2 Nos pumps
Static head in mtrs. 123.50 mtrs
Total Head in mtrs : 143 mtrs
Capacity (in LPS) 0.92 LPS
Length of Rising Main 425 mtrs
Dia of R/Main (in mm) 40mm dia
HP :- 2 x 5HP = 10HP
Providing and fixing of Auto control panel with push button star delta starter for submersible pumps of L&T and reputed make fabricated with M.S sheet and Angle stand duly painted and complete with internal wiring ,comprising of main switch of suitable Amp. T.P. Volt meter, ammeter,hour run meter,copper busbar , phase indicating lamps with GSM based , Remote start/stop operation call/SMS for feedback regarding running of pumps & breakdown message, timer scheduling for fixed hours in a day,Inbuilt protection against overload/undervoltage,Dry run,single phase preventor,Inbuilt GPS tracker,phase reversal configurable volt/current limits with a facility to access the system through minimum 10 Nos. authenticated mobile Nos. complete in all respect, including entire carriage of materials upto all leads and lifts,installation and testing at site with entire satisfaction of Engineer-in-charge.(All meters to be installed shall be DIGITAL.)
Supply and fixing at site of Kirloskar/Kilburn/IVC/Fouress/Gled/BHEL/Leader/KSB/Pelicon make of suitable size cast steel double flanged swing check type reflux valve having bye pass arrangement & size one size larger than the nominal dia of delivery of the pump or equal to dia of column pipe (in case of t/well) and capable of withstanding nominal seat pressure as mentioned in item No.11(a)+SURGE PRESSURE & conforming to API standards with up to date ammendments for delivery line of pump.Class of valve shall be ASA 300.
P/L suitable size copper PVC insulated armoured power three & half core cable conforming to BIS 1554 (Part I) -1988 or latest with up to date ammendments of Siemen/Gloster/ ICC/EICO /National /IEC make from meter of HPSEB to circuit breaker & from circuit breaker to bus bar switch & starter (one cable carrying all three phases) including all other electrical equipment/accessories such as thimbles,flexible pipe,solder,nuts & bolts,cable glands etc. laid in pipes or trenches under floor. The type,size & make will be subject to approval of HPSEB authorities. In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost .
P/L PVC jointless flat water proof cable as per BIS 694-1990 (latest with up to date ammendments) suitable for the pump sets offered from circuite breaker to motor & motor to starter including all other electrical equipments such as thimbles, flexible pipes, solder,nuts & bolts,cable glands etc. laid in pipes or trenches. The type,size & make will be subject to approval of HPSEB authorities.In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost.
P/L double loop earthing with copper plate 600x600x3mm thick electrode complete with material such as charcoal, common salt ,GI pipes,thimbles,nuts & bolts,digging of pits,GI wiring & 25x5mm copper strips of required capacity conforming to BIS 3043-1987 latest with up to date ammendments suitable for above motors & other electrical equipments.
Supply & errection of floor/wall mounted power factor shunt capacitor of suitable KVAR conforming to BIS 2834-1986 or latest with upto date ammendments of BHEL/GEC/Machneil/ Mager/Bajaj/L&T make to raise the prevailing power factor at site to 0.95 for direct connection to induction motor individually,of required KVAR according to HP of motor offered including cable Siemens/Gloster/ICC make from busbar chamber to capacitor & also including L&T//Kilburn/Standard/Siemen/Havells make ICTP switches conforming to BIS 4064-1978 or latest with HRC fuses (Range to be specified by the tenderer).
Supply of 100mm dia circular dial pressure gauge of suitable range & standard make such as Fiebeg/Bourden/ Precision/PREGA with all accessories such as stop cock,copper tubing etc.conforming to BIS 3624-1987 or latest with up to date ammendments.
Errection of all equipments from including cost of tees bends tapers & column pipe of suitable dia and length for submersible pump and any other fittings required as per site conditions and as per direction of the Engineer Incharge ,of all Phases( Shilli and Sanari.)
Bhaw Singh
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .