Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.1 CrAccepted-AOC | ₹1.1 Cr | L1 | Accepted-AOC LOWEST QUOTED BIDDER |
| 2 | L2₹1.3 Cr+₹15.4 L (13.4%)Rejected-Finance 24 824 GOVERDHAN COLONY MAIN BHIND ROAD GOLE KA MANDIR | ₹1.3 Cr+₹15.4 L (13.4%) | L2 | Rejected-Finance NOT THE LOWEST QUOTED BIDDER |
| 3 | L3₹1.3 Cr+₹20.1 L (17.6%)Rejected-Finance 0001D ATM HOUSE AIR FORCE NEENA THAPA GORAKHPUR UTTAR PRADESH 273008 UDYAM UP 32 0054752 | GORAKHPUR | UTTAR PRADESH | 273008 | ₹1.3 Cr+₹20.1 L (17.6%) | L3 | Rejected-Finance NOT THE LOWEST QUOTED BIDDER |
| 4 | L4₹1.4 Cr+₹23.5 L (20.5%)Rejected-Finance DOOR NO 43 2 BESIDES VIZAG DEFENCE ACADEMY 104 AREA KAPPARADA VISAKHAPATNAM 530013 | VISAKHAPATNAM | VISAKHAPATNAM | ANDHRA PRADESH | 530013 | ₹1.4 Cr+₹23.5 L (20.5%) | L4 | Rejected-Finance NOT THE LOWEST QUOTED BIDDER |
| 5 | L5₹1.4 Cr+₹24.7 L (21.6%)Rejected-Finance 29 MODEL TOWN BEHIND GURUDWARA PATHANKOT | PATHANKOT | PATHANKOT | PUNJAB | 145001 | ₹1.4 Cr+₹24.7 L (21.6%) | L5 | Rejected-Finance NOT THE LOWEST QUOTED BIDDER |
| Sl No | Description | Qty | Unit | om sai enterprises L3 | MS ENTERPRISES L6 | Mavee Syndicate L4 | OM SAI POWER SYSTEMS L1 | kailu construction co L5 | anand enterprises L2 |
|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Supply & install, commissioning, testing of out door type Main Panel board - 1 including with followng LT switch gears, LT type (CPRI approved) with suitble rated Aluminium bus bar with color code of panel size not less than 60 cm depth with suitable length and width for sufficient working space/gap between switch gears duly fabricated MS sheet of 3.15mm thick CRCA sheet powder coated angle size not less than 50 x 50 x 5 mm thick frame factory made totally enclosed dust and vermin proof, side hinged opening arrangement on front and back, carring hooks, danger board,dist line diagram, earth terminals with weather proof canopy of top with locking arrangement, and incl cable entry and exist from bottom to both side with necessary arrangement of cable gland plates and providing cable glands including taking down old US one complete all as specified and as directed. | 2 | Each Job | 6,00,000 ₹12,00,000 | 4,90,993 ₹9,81,986 | 5,75,000 ₹11,50,000 | 2,10,000 ₹4,20,000 Lowest | 4,00,000 ₹8,00,000 | 3,25,000 ₹6,50,000 |
| 1.01INCOMING | |||||||||
| 1.02Supply & fix ACB LT switch gear 440 Volts 3 phase, 4 wire 50 cycles, cubicle or truck type complete with air circuit breaker, overload protection, no-volt release with necessary CTs,meter and cable boxes of rating upto 800 Amps-01 No | |||||||||
| 1.03OUT GOING | |||||||||
| 1.04MCCB 4 pole,415 volt ,50 Hz , repturing cap 63A, 25 KA - 02 Nos | |||||||||
| 1.05MCCB 4 pole,415 volt ,50 Hz , repturing cap 100 , 25 KA - 01 No | |||||||||
| 1.06MCCB 4 pole,415 volt ,50 Hz , repturing cap 40A, 25 KA - 01 No | |||||||||
| 1.07MCCB 4 pole,415 volt ,50 Hz , repturing cap, 400A 50 KA - 03 Nos | |||||||||
| 1.08Astronomical time switch complete with all accessories in built panel - 01 Set | |||||||||
| 1.09digital Volt, Ammeter & Freq Meter incl selector switch - 01 Set | |||||||||
Tender Value
₹1.4 Cr
EMD Value
₹2.2 L
Closing Date
24 Nov 2025, 6:00 pmClosed
CWE (AF) Secunderabad
CWE (AF) Secunderabad
SPECIAL REPAIR TO ELECTRICAL PANELS, JUNCTION BOXES AND ALLIED WORK AT AFS BIDAR
2025_MES_737138_1
85663/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE (AF) Bidar
As per NIT
9 documents required · 9 mandatory
₹1,000
GE (AF) Bidar
₹2.2 L
Yes
22 Dec 2025
27 Oct 2025
26 Nov 2025
27 Oct 2025
24 Nov 2025
17 Nov 2025
27 Oct 2025 - 13 Nov 2025
Amount
Supply & install, commissioning, testing of out door type Main Panel board - 1 including with followng LT switch gears, LT type (CPRI approved) with suitble rated Aluminium bus bar with color code of panel size not less than 60 cm depth with suitable length and width for sufficient working space/gap between switch gears duly fabricated MS sheet of 3.15mm thick CRCA sheet powder coated angle size not less than 50 x 50 x 5 mm thick frame factory made totally enclosed dust and vermin proof, side hinged opening arrangement on front and back, carring hooks, danger board,dist line diagram, earth terminals with weather proof canopy of top with locking arrangement, and incl cable entry and exist from bottom to both side with necessary arrangement of cable gland plates and providing cable glands including taking down old US one complete all as specified and as directed.
INCOMING
Supply & fix ACB LT switch gear 440 Volts 3 phase, 4 wire 50 cycles, cubicle or truck type complete with air circuit breaker, overload protection, no-volt release with necessary CTs,meter and cable boxes of rating upto 800 Amps-01 No
OUT GOING
MCCB 4 pole,415 volt ,50 Hz , repturing cap 63A, 25 KA - 02 Nos
MCCB 4 pole,415 volt ,50 Hz , repturing cap 100 , 25 KA - 01 No
MCCB 4 pole,415 volt ,50 Hz , repturing cap 40A, 25 KA - 01 No
MCCB 4 pole,415 volt ,50 Hz , repturing cap, 400A 50 KA - 03 Nos
Astronomical time switch complete with all accessories in built panel - 01 Set
Indicator, danger board,line diagram - 01 Set
Supply & Install, commissioning, testing of out door type Main panel board -2 including with followng LT switch gears, LT type (CPRI approved) with suitble rated Aluminium bus bar with color code of panel size not less than 60 cm depth with suitable length and width for sufficient working space/gap between switch gears duly fabricated MS sheet of 3.15mm thick CRCA sheet powder coated angle size not less than 50 x 50 x 5 mm thick frame factory made totally enclosed dust and vermin proof, side hinged opening arrangement on front and back, carring hooks, danger board, dist line diagram, earth terminals with weather proof canopy of top with locking arrangement, and incl cable entry and exist from bottom to both side with necessary arrangement of cable gland plates and providing cable glands including taking down old US one complete all as specified and as directed.
INCOMING
MCCB 4 pole,415 volt ,50 Hz ,cap 400A of repturing cap 50 KA - 01 No
OUT GOING
MCCB 4 pole,415 volt ,50 Hz ,cap 160A of repturing cap 25 KA - 03 Nos
MCCB 4 pole,415 volt ,50 Hz , cap 100A of repturing cap 25 KA - 03 Nos
MCCB 4 pole,415 volt ,50 Hz ,cap 63A of repturing cap 25 KA - 03 Nos
MCB DP (6-40A) 230 Volt single ph,10KA - 05 Nos
Astronomical time switch complete with all accessories in built panel - 01 Set
Indicator,danger board,line diagram - 01 Set
Supply & install, commissioning, testing of out door type Main panel board - 3 including with followng LT switch gears, LT type (CPRI approved) with suitble rated Aluminium bus bar with color code of panel size not less than 60 cm depth with suitable length and width for sufficient working space/gap between switch gears duly fabricated MS sheet of 3.15mm thick CRCA sheet powder coated angle size not less than 50 x 50 x 5 mm thick frame factory made totally enclosed dust and vermin proof, side hinged opening arrangement on front and back, carring hooks, danger board,dist line diagram, earth terminals with weather proof canopy of top with locking arrangement, and incl cable entry and exist from bottom to both side with necessary arrangement of cable gland plates and providing cable glands including taking down old US one complete all as specified and as directed.
INCOMING
MCCB 4 pole,415 volt ,50 Hz , cap 250A of repturing cap 50 KA
OUT GOING
MCCB 4 pole,415 volt ,50 Hz , cap 160A of repturing cap 25 KA - 03 Nos
MCCB 4 pole,415 volt ,50 Hz , cap 125A of repturing cap 25 KA - 02 Nos
MCCB 4 pole,415 volt ,50 Hz ,cap 63A of repturing cap 25 KA - 02 Nos
Indicator, danger board, line diagram
Supply & install, commissioning, testing of out door type Main panel board - 4 including with followng LT switch gears, LT type (CPRI approved) with suitble rated Aluminium bus bar with color code of panel size not less than 60 cm depth with suitable length and width for sufficient working space/gap between switch gearsduly fabricated MS sheet of 3.15mm thick CRCA sheet powder coated angle size not less than 50 x 50 x 5 mm thick frame factory made totally enclosed dust and vermin proof, side hinged opening arrangement on front and back, carring hooks, danger board,dist line diagram, earth terminals with weather proof canopy of top with locking arrangement, and incl cable entry and exist from bottom to both side with necessary arrangement of cable gland plates and providing cable glands including taking down old US one complete all as specified and as directed.
INCOMING
MCCB 4 pole,415 volt ,50 Hz , cap 200A of repturing cap 25 KA
OUT GOING
MCCB 4 pole,415 volt ,50 Hz ,cap 100A repturing cap 16 KA - 02 Nos
MCCB 4 pole,415 volt ,50 Hz , cap 63A of repturing cap 16 KA - 01 Nos
MCB DP (6-40A) 230 Volt single ph,10KA - 02 Nos
Indicator, danger board, line diagram
Supply & install, commissioning, testing of out door type Feeder piller box Sub panel 1 including with followng LT switch gears, LT type (CPRI approved) with suitble rated Aluminium bus bar with color code of panel size not less than 60 cm depth with suitable length and width for sufficient working space/gap between switch gears duly fabricated MS sheet of 3.15mm thick CRCA sheet powder coated angle size not less than 50 x 50 x 5 mm thick frame factory made totally enclosed dust and vermin proof, side hinged opening arrangement on front and back, carring hooks, danger board,dist line diagram, earth terminals with weather proof canopy of top with locking arrangement, and incl cable entry and exist from bottom to both side with necessary arrangement of cable gland plates and providing cable glands including taking down old US one complete all as specified and as directed.
INCOMING
MCCB 4 pole,415 volt ,50 Hz , cap 250A of repturing cap 50 KA
OUT GOING
MCCB 4 pole,415 volt ,50 Hz ,cap 100A repturing cap 16 KA - 02 Nos
MCCB 4 pole,415 volt ,50 Hz , cap 63A of repturing cap 16 KA - 03 Nos
MCB DP (6-40A) 230 Volt single ph,10KA - 02 Nos
Astronomical time switch complete with all accessories in built panel - 01 Set
Indicator, danger board, line diagram
Supply & install, commissioning, testing of out door type Feeder piller box Sub panel 2 including with followng LT switch gears, LT type (CPRI approved) with suitble rated Aluminium bus bar with color code of size not less than 60 cm width with suitable other dimentions for working space duly fabricated MS sheet of 3.15mm thick CRCA sheet angle size not less than 50 x 50 x 5 mm thick frame factory made totally enclosed dust and vermin proof, side hinged opening arrangement on front and back, carring hooks, danger board,dist line diagram, earth terminals with weather proof canopy of top with locking arrangement, and incl cable entry and exist from bottom to both side with necessary arrangement of cable gland plates and providing cable glands including taking down old US one complete all as specified and as directed.
INCOMING
MCCB 4 pole,415 volt ,50 Hz , cap 160A of repturing cap 25 KA -01 No
OUT GOING
MCB DP (6-40A) 230 Volt single ph,10KA-09 Nos
Indicator,danger board,line diagram
All as per item No 7 here in before but New Auto Main failure panel board for DG set capacity of 62.5 KVA to 100 KVA complete all as specified and as directed.
All as per item No 7 here in before but New Auto Main failure panel board for DG set capacity of 320 KVA complete all as specified and as directed.
All as per item No 7 here in before but New Auto Main failure panel board for DG set capacity of 250 KVA complete all as specified and as directed.
All as per item No 7 here in before but New Auto Main failure panel board for DG set capacity of 160 KVA complete all as specified and as directed.
All as per item No 7 here in before but New Auto Main failure panel board for DG set capacity of 200 KVA complete all as specified and as directed.
S&F in repair hot moulded FRP looping /Junction box size 300 mmx250 mmx105 mm for street light poles with locking arrangement and suitable connection for three phase incomming cable 3 phase out going cable and single phase connection for light fitting incl controlled MCB SP-10 Amps -01 Nos enclosed in thermo plastic in closed shock proof safe IP-65, weather,vermin proof,dust and water proof complete with two nos cables entry incl gland of standard size with suitable size mild steel clamps to fixed on pole complete all as specified and as directed. Make :- Neptune / Hensel / Sintex
Taking down US FRP juction box of any type along with US clamps nuts, bolts and washers with connected old wire complete all as specified and as directed.
Taking down US Earthing of any type and size complete along with earth strip/wire and plate complete all as specified and as directed. Note :- Earth work for taking out is deemed to include in quoted rates.
M&L for Earthing for Panels complete with galvanized steel plate electrode of size 600x600x6.3mm thick buried directly in ground with earth pit not less than 2.25 meter deep below ground level with top edge of plate not less than 1.5 meter below normal ground level connected to galvanized iron earth wire 4mm dia earth lead by means of nuts, bolts, check nuts, washers of galvanised iron as steel, protected by galvanized iron pipe 40mm bore (Medium grade) all as directed including cement concrete (1:3:6) type C-1 earth pit with precast RCC (1:1.5:3) type A-1 cover slab of size 42 x 42 x10cm thick reinforced with 8mm dia TMT bars @ 15 cm c/c both ways with 10mm dia mild steel round bar of 30 cm long, bent to shape as lifting handle, funnel, wire mesh, 20 mm bore galvanized iron pipe (medium grade) for watering, charcoal or coke and salt in alternate layers with necessary earth work in soft/loose soil complete all as shown in electrical plate No 3 of SSR Part I including testing on completion and taking down US one complete all as specified and as directed.
All as per item No 16 above but using galvanised iron strip 25×4mm as earthing lead complete all as specified and as directed.
Supply and install steel tubular swaged poles type 410 SP-31 (9.0 metres long) complete with CI based plate and finial including including painting of poles with two coats of synthetic enamel paint over a coat of primer black and white/yellow strips 30CM wide each (05 Nos) up to 1.5 Mtrs height from coping & numbering of poles complete all as specified and as directed. Note :- The existing old PCC Poles should be replaced be replaced with new steel rubler pole and the old pole is credited to Contractor as shedule of credit.
Excavation in trenches not exceeding 1.5 mtr wide and not exceeding 1.5 m in depth for taking out / for laying under ground cables / pipes etc and getting out in soft / loose soil complete all as specified and as directed.
Removing excavated soil to a distance n-exc 50 mtr and depositing where directed at a level n-exc 1.5 mtr above the starting point complete all as specified and as directed.
M&L cable cushioning shall be using riddled earth/soil by sieving excavated soil as per IS-1255-1983 as in cable cushioning punned depth upto 18 cm thick complete all as specified and as directed. Note :- Filling beyond cable cushioning will be measured under return filling in item catered separately.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25cm complete all as specified and as directed.
Supply and laying unreinforced pre cast concrete cable cover class LV, Type I, flat, size 250mm x 150mm x 40mm for cable protection, made out of M-20 grade concrete etc complete all as specified and as directed.
Relaying old serviceable unreinforced pre cast concrete cable cover class LV, Type-I, flat, size 250mm x 150mm x 40mm for cable protection complete all as specified and as directed.
M&L for plain cement concrete in foundations, filling and mass concrete type D2 1:4:8 with 40mm graded stone aggregate for foundation of pole etc complete all as specified and as directed.
M&L for providing PCC 1:3:6 type C-2 using 40mm graded stone aggregate as foundations, filling and mass concrete complete all as specified and as directed.
M&L for providing plain cement concrete type B1, 1:2:4 using 20 mm stone aggrigate in coping or chamfered on edges complete all as specified and as directed.
M&L for preparation old painted surfaces with synthetic enamel paint to LT steel tubular pole 8.5/9/8.0 mtr long including clamps,brackets,chanel,cross arms, bracing support, pipe of support for cable and swan neck etc including zebra painting at bottom up to 1.5 mtr above from the PCC coping and writing pole No with white paint complete etc complete all as specified and as directed. Note :- Pole number shall be marked with white enamel paint over a base of size 20cmx20cm on prepared with two coats of black enamel paint on pole surfaces.
M&L for 40mm dia steel tubes (light grade) galvanised with fittings, laid in trenches / wall for protection of underground earth strip when crossing the road / fixing on wall as in repair complete all as specified and as directed.
M&L for street light bracket made to shape from 40mm dia length 1.5m GI Pipe medium grade incl two number of clamps made from 50 x 6 Flat iron nut bolts complete all as specified and as directed.
Supply and fix LED type street light fitting 70 watt pressure dia cast aluminum housing LED street light luminaries with IP 66 including GI pipe medium grade with suitable size bracket bend in 120 degree and clamps,nuts,bolts etc with all accessories complete all as specified and as directed. Make :- Havells and equivalent Make Philips / CG
S&F 1.5 sqmm 3 core, 1100 volt grade heavy duty cable, PVC insulated copper multistranded conductor, served with inner sheathing of PVC tape and overall PVC sheathed laid in proposed PVC conduit for making connection of street light from FRP junction box to street lights including provision of flexible pipe to conealed the copper wire from weather expose complete all as specified and as directed.
Supply and laying or fixing or passing through pipe, 1100 volts grade heavy duty cable of size 2 core 6 sqmm nominal cross section in service connections of PVC insulated aluminium multi standard conductor served with an inner sheathing of PVC tape and overall PVC sheathed complete all as specified and as directed. Make :- Havells / Plaza / Finolex / Kalinga / Kei / Anchor.
Supply and lay cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 240 sq mm 3½ core including provision of LT cable path indicator CI round shape mentioning LT cable of Blue color paint fixed with 0.75 Mtr lenth angle iron of size 40x40x4 mm laying intervals 20 Mtr and refer laying of cable shall be compile with SSR Part -I Section 19.75.1 complete all as specified and as directed. Note:- Cable path indicators and end termination joints with aluminium lugs / thimbles deemed to include with quoted rates.
All as per item No 34 above but size 185 sq mm 3.5 core complete all as specified and as directed.
All as per item No 34 above but size 150 sq mm 3.5 core complete all as specified and as directed.
All as per item No 34 above but size 120 sq mm 3½ core complete all as specified and as directed.
All as per item No 34 above but size 95 sq mm 3½ core complete all as specified and as directed.
All as per item No 34 above but size 70 sq mm 3½ core complete all as specified and as directed.
All as per item No 34 above but size 50 sq mm 3½ core complete all as specified and as directed.
All as per item No 34 above but size 35 sq mm 3½ core complete all as specified and as directed.
All as per item No 34 above but size 25 sq mm 4 core complete all as specified and as directed.
All as per item No 34 above but size 16 sq mm 4 core complete all as specified and as directed.
All as per item No 34 above but size 25 sq mm 2 core complete all as specified and as directed.
All as per item No 34 above but size 16 sq mm 2 core complete all as specified and as directed.
All as per item No 34 above but size 10 sq mm 2 core complete all as specified and as directed.
M&L for removing serviceable LT cable of any size duly testing the cable by the megger and taking down existing serviceable for relaying as specified such as relaying / rerouting and shifting the cable to laying as reqd at site under relevent items of this schedule complete all as specified and as directed Note :- 1. Taking down removal of the cable rates deemed to include in quoted rates. 2. Excavation,earth work and other necessary items for the relaying/rerouting of the cable measured and paid separately under relevent items.
M&L for removing brick/cover from trench for re use of serviceable bricks and re-laying old serviceable bricks of any type and size bricks, for cable protection in trenches laid dry and flat over the relaid/re-routing cables complete all as specified and as directed.
Material and labor for relaying/re routing Old serviceable LT cable of any size as specified and shifting the cable as reqd at site complete all as specified and as directed. Note :- (i) Taking down & transport for removal/rerouting of the cable rates measured and paid separately in quoted rates. (ii) Excavation,earth work and other necessary items for the relaying of the cable measured and paid separately under relevent items.
M&L for removing brick/cover from trench for re use of serviceable bricks and re-laying old serviceable bricks / covers of any type and size for cable protection in trenches laid dry and flat over the laid cables complete all as specified and as directed.
M&L in repairs for straight through cold shrink type joint 1100 Volt complete with jointing material and accessories suitable for 16 to 70 Sqmm 3.5 Core complete all as specified and as directed.
M&L in repairs for Straight through cold shrink type joint 1100 Volt complete with jointing material and accessories suitable for 95 to 185 Sqmm 3.5 Core complete all as specified and as directed.
M&L for PCC preparation including cutting up to 45 cm width and depth of the road / hard standing and making good disturbed surfaces by using PCC type C-2 (1:3:6) by using 40mm graded stone aggregate for the fixing the pipe / laying cables complete all as specified and as directed.
M&L for 50mm dia steel tubes (light grade) galvanised with fittings, laid in trenches / wall for protection of underground earth strip when crossing the road / fixing on wall as in repair complete all as specified and as directed.
M&L for 75 mm dia HDPE pipes PN 10 with fittings, laid in trenches / wall for protection of underground cable when crossing the road / fixing on wall complete all as specified and as directed.
M&L for fabrication of cross arms bracings supports,clamps and back plates,iron stainer, water gate, ladder for clear water tank etc as required structural steel section including nuts, bolts, washers, welding,bending, cold or hot, drilling holes for bolts in any shape or size and including of one coat of primer and one under coat and one finishing coat of paint complete all as specified and as directed.
Supply and fix in replacement digital voltmeter 0 - 500 Volts complete all as specified and as directed.
Supply and fix in replacement digital ammeter 0 - 500 Volts complete all as specified and as directed.
Supply and fix in replacement neon indicating lamp (Red, Yellow, Blue) complete all as specified and as directed.
Supply and fix self adhesive reflective radium stickers 75 mm wide around the street light poles 1.5m above ground level complete all as specified and as directed.
Dismantling and taking out switch gears from Old LT panel of any type duly disonnecting the incoming and out going cables, switch gears,instruments and other spares / accessories carefully for re use serviceable items and old US spares shall be leave with panel for credit schedule complete all as specified and as directed.
S&F cable end jointing kit for LT, 1100 Volt (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3.5/4 core XLPE armoured aluminium conductor cable of size 16 to 50 sqmm with provision of lugs / thimbles / aluminium jumpers for OH/UG connections complete all as specified and as directed. Make :- Dension/3M
All as per item No 62 above here in before but joint of size 70 sqmm to 95 sqmm
All as per item No 62 above here in before but joint of size 120 sqmm to 150 sqmm
All as per item No 62 above here in before but joint of size 185 sqmm to 240 sqmm
All as per item No 62 above here in before but joint of size 300 to 400 sqmm
Demolishing the broken earth pit chamber and constructing new earth pit chamber and PCC chamber cover duly repair and maint of the existing earth of any type to obtain permissible value complete all as specified and as directed.
M&L for disconnecting faulty / burnt end portion of cable by removing the cable from loop including necessary excavation & earth work, relaying and reconnecting the cable by removing faulty/burnt portion of incoming and out going cables at panel boards and preparing fresh terminals with suitable size of thimbles, lugs of suitable size to connecting cables and clean / levelling soil around panel board complete all as specified and as directed.
anand enterprises (BID ID -3485539)
om sai enterprises (BID ID -3478523)
Mavee Syndicate (BID ID -3480706)
kailu construction co (BID ID -3481621)
MS ENTERPRISES (BID ID -3479218)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.34 MB
85663TENDERPDF.pdf
Tender Documents • 0.81 MB
BOQ_825364.xls
BOQ • 1.87 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .