Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Tender Value
₹1.5 Cr
EMD Value
₹3.0 L
Closing Date
25 Nov 2026, 1:00 pmDue tomorrow
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
SE PWD Kokrajhar Bldg circle Kokrajhar
SE PWD Kokrajhar Bldg circle Kokrajhar
Construction of 6_Bedded ICU Burn Unit at Kokrajhar Medical College and Hospital KMCH under the CSR initiative of NTPC, Bongaigaon. TN_62
2026_BoTC_54823_1
TECH36/SEB/IFB/2024-25/153
Open Tender
Civil Works - Building
Works
Kokrajhar
Please refer Tender documents.
4 documents required · 4 mandatory
₹4,500
₹3.0 L
Yes
5 Nov 2026
5 Nov 2026
25 Nov 2026
5 Nov 2026
25 Nov 2026
5 Nov 2026
5 Nov 2026 - 25 Nov 2026
180 days
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Equipments:
FUNCTION MOTORISED ICU BED: Type of ICU Bed: Actuator Electro-Mechanical (Motorized ), Type of mechanism for functioning or controlling angular motion and height of bed Electro-Mechanical (Motorized), Number of section provided in Bed Top: 4, Bed top perforated: Yes, Number of Side panel: 4, Facility of braking and locking mechanism provided in castor roller 2 Wheels, Facility of instant non powered/mechanical CPR (Cardiopulmonary Resuscitation) release at the head end for emergency: Yes, Accessory' Rail Provided at all four side of bed: NO, Integrated Weighing Scale: No, Material for Head & Foot Panel/Board Polymer based material (ABS Plastic/PP), Material for Bed top Section Polymer based material (ABS Plastic/PP) Material of wheels Polymer based material (Polyester), Maximum Trendlenburg Angle in Degree (Tolerance : ±2 degree) 150, Maximum Reverse Trendlenburg Angle in Degree (Tolerance ± 2 Length of bed in mm (2% tolerance)2000 mm to 2100 mm, Width of bed in mm (2% tolerance) 950 mm to 1000 mm, Mattress provided with ICU bed: Yes, Warran includes bed 2 Years and mattress Nil. | 6 | Each | - | - |
| 2 | BED SIDE LOCKER: Bedside Locker - (SS Top): Overall depth range (mm): 400 mm (+/- 2.5%), overall Width range (mm): 400 mm (+/- 2.5%), Overall Height range (mm): 820 mm (+/- 2.5%), Type of slide of drawer: Fitted with Telescopic Channel Material of Enclosure of bedside locker: Stainless steel, Material of cabinet and Drawer: Stainless steel, Locking system for cabinet and drawer: Yes, Number of Shutters: 1, Number of open shelves: 1, Number of Shelves: 2, Finish: Epoxy, Frame Tube Material: STAINLESS STEEL | 6 | Each | - | - |
| 3 | Overbed Table Type: Typr-2 - Overbed table with top mounted on a tubular metal frame work and having legs fitted with 4 castors, Frame Work Material as per IS 4033 (Latest): Electric resistance butt-welded steel tube (ERW), Top Material (As per IS 4033 Latest): Mild Steel Sheet Overlapped by Stainless Steel Sheet, Top Material Shall be Rust- Resisting or Rust-Proof: Yes, Manufacturing as per IS 4494 Latest): Yes, Finish as per IS 4033(Latest) : YES | 6 | Each | - | - |
| 4 | Cardiac Monitor (Patient Monitor): High End Multipara Monitor: Type of Monitor: Modular, Monitoring Parameters: ECG, HR. Respiration Rate, Sp02, Pulse Rate, NIBP, Temperature, IBP, EtC02 Upgradable, S T Analysis: Yes, PPV (derived value during IBP measurement): Yes, Length of time of full disclosure of patient data in hr: > 72, Length of time of trending in hr: 72. ECG PARAMETERS- ECG Provided: Yes, Number of leads of ECG: 3, ECG Waveform number of leads display: 7, Arrhythmia detect: Yes, Heart rate measurement range: Atleast 30-250 bpm, Accuracy: ± 2 bpm or better. Minimum gradation: 1 bpm or better. RESPIRATION PARAMETERS- Respiration Method: Impedance pneumography, Display waveform of respiration: Yes, Respiration rate measurement range: 0 - 150 bpm or more, Minimum gradation of respiratory measurement: 1 bpm or better. PULSE OXIMETERY PARAMETERS- Measurement technique: Low Perfusion Technology with Motion artifact detection, Probe type: Clip, Probe for Adult and Pediatrics: Reusable, Probe for Neonates: Disposable, SP02 measurement range: 40 - 100%, Accuracy of SP02 measurement: ± 2% or better, Minimum Gradation: 1%. NIBP PARAMETERS- Measurement technique for NIBP: Step-deflation Oscillometric / Linear Inflation, Systolic Blood pressure monitoring range: 30 - 300 mmHg or more, Diastolic Blood pressure monitoring range: 10 - 200 mmHg or more, Accuracy of NIBP Measurement: +1 mm/Hg or better. EMPERATURE PARAMETERS- Number of channels for temperature: 2, Type of probe: Skin, Temperature probe type: Reusable, Temperature probe range: Atleast 30 - 40 degree, Minimum gradation of temperature probe: 0.1 degree C or better, Accuracy in %: +1% or better. IBP PARAMETERS: Number of channels for IBP: 2, ETC02 PARAMETERS- Patient type: Intubated and non-intubated, C02 Measuring range in mmHg: 0 to 99 mmHg or better. ALARMS- Availability of Audio and visual alarms with hi medium and low intensity adjustment: Yes. Operator can set audio visual alarm levels for low or high levels of each parameter independently. Yes, Systolic BP - low and high: Yes. Diastolic BP - low and high: Yes, Mean BP - low and high: Yes, Heart rate - low and high: Yes. SP02 - low and high: Yes, Respiratory rate - low and high: Yes. Temperature - low and high: Yes, Alarm Volume Adjustable: Yes, Activating silence of alarm: Yes. Duration Of alarm silence in seconds: 120, Suspension of all alarms: Yes. Latching of alarm: Yes, Cuff leakage alarm: Yes, Cuff disconnects alarm: Yes, Alarm for innation/deflation errors: Yes. Indicator for low-battery: Yes, EtC02 - low and high: Yes, Escalation of Alarm Priority: Yes, Sensor wire/probe disconnection alarm: Yes. NETWORK PARAMETERS- Ethernet port: Yes, Hardwired: Yes, Connectivity with Network printer. Yes. Connectivity provision with Central Nursing Station: Yes DISPLAY PARAMETERS- Type of display: LCD/LED/TFT, Display Size in inches: 10, Traces of display: >6, Userlnterface of display: Touchscreen, Should be able to connect to additional display: Yes. STANDARDACCESSORIES- Number of reusable pediatric probeprovided: 1, Number of ECG 5/6/10 lead cable provided: 1, Number of IBP cables provided: 2 Reusable Cables, Number of disposable IBP Transducers provided: 5, Number of Pediatrics N IBP cuffs of Small and medium provided:l Set, Number of Skin temperature probe provided: 1 for Adult / Pediatric, Number of Neonatal Rectal temperature Probe provided: 1, Number of Esophageal Temperature probe (Adult) provided: 1, Accessories to wall mount the monitor: Yes. POWER REQUIREMENTS- Power supply: 220-240 VAC, SOHz, Single phase, Mains cable: 3 meter or more with Indian plug. Battery Inbuilt. Minimum Inbuilt Battery back up in minutes: 120, Recharging time of battery in hr: s 6, Weight of the Machine in kgs: S 15, Noise level in dB: S SO, Device Earthing: Yes. CERTIFICATIONS- Compliance to Medical Device Rules MDR 2017 as amended till date: | 6 | Each | - | - |
| 5 | DEFIBRILLATOR: Technology of defibrillator: Biphasic technology, Modes in defibrillator: Automated external defibrillation and manual , Maximum energy selection in joules 200, Capability of ECG Monitoring ECG leads, multi-function electrodes, paddles , Number of wvave-forms4, Patient compatibility to defibrillate Adult, pediatric patients, Type of display TFT, Size of display screen in inch 6.5, Provision to display ECG waveform on bright high- resolution display: Yes, Facility to have synchronized cardio version: Yes, Ability to display CPR index on screen real time: Yes, Ability to filter out CPR artefacts to see organized rhythms without interrupting chest compression: Yes, Provision of within built rechargeable battery: Yes. Battery backup to deliver number of shocks at maximum energy: 100, Weight of defibrillator with battery and paddles in Kg7, Provision of in-built recorder: Yes, Provision of printing ECG trace & stored information: Yes, Facility of External non-invasive pacing: Yes. Type of external transcutaneous pacing modes: Both Demand mode and fixed mode, Pulse width of External non-invasive pacing in milli seconds: 40, Ability to measure chest compression rate and depth in real time with visual feedback on screen with rate and depth indicator: Integrated with defibrillator, Facility to monitor EtC02: Yes, Facility to monitor NIBP: Yes, Facility to monitor SP02: Yes, ECG monitoring Using 5/6 lead Provision of user selectable alarm settings: Yes, The machine should work on mains as well as on rechargeable battery: Yes, Ability to select energy from paddles: Yes, Ability to charge and discharge through paddles as well as from main unit: Yes, Facility for internal defibrillation: Y es, Charging time for maximum energy in seconds 7 , Mechanism of self- test of unit: Automatic and manual, Unit should do self-test with facility to give printout of defibrillator testing report and also have code ready indicator on unit: Yes, Provision of stainless-steel trolley with lockable castors: Yes, Suitability Of defibrillator for transport on ground (ambulance): Yes, Defibrillator should display selected enerw: Yes, Defibrillator should display delivered enerw: Yes, Suitability of defibrillator for transportation in air (aircraft): No, Availability of suitable protection for dust and water: Yes, Accessories. Li-ion Battery: 1. ECG cable: 1, N IBP paediatric cuff with hose: 1, NIBP adult cuff with hose: 1, Reusable airway adaptor to be used with ETC02 main stream side stream sensor and cable: 1, Disposable airway adapter with EtC02 mainstream sensor and cable: 1 One each for incubated and non-intubated patient. External defibrillator paddles: (paediatric in built in adult): 1, Multi-Function Defibrillator & Monitoring pads/gel sheets: 5, Recorder paper roll: 10, Reusable CPR feedback sensor/or similar product reused: 1 | 1 | Each | - | - |
| 6 | SYRINGE PUMP: Microprocessor-based and programmable: Yes, Operating Modes: Flow Rate Mode. Volume and Time, Rate and Time, Weight Mode, Sequence Mode, Flow rate Range in ml/hr: 0.1 - 1500 ml/hr, Flowrate Increment in ml/hr: 0.1 ml/hr, KVO (Keep Vein Open) Rate in ml/hr: 0.1 to 5 ml/hr adjustable, step 0.1ml/h, Accuracy in %: +/- 2%, Bolus Administration: Manual and automatic, Bolus flow Rate Range in ml/hr: 1 to 1500 ml/hr, Bolus Volume in ml: 0.1 - 5 ml in 0.1 ml increments (auto bolus), LED/LCD/TFT Display: Yes, Minimum Display Size in inches: 3 or more, Display Parameters: Flow rate, Syringe Size, Infused volume, Power indicator light, Occlusions, Drug Name, Battery Indicator, Drug library: More than 40, Syringe compatibility: The pump should work with different brands of syringes and is able to automatically detect and accept syringes with volumes of: 5 ml,10 ml,20 ml,50 ml, Audio Visual alarm for: Occlusion, Syringe near- empty, Syringe-empty, Low battery, Internal malfunction, Syringe wrongly fitted, Power supply failure, The syringe pumps should be capable of standalone functioning on IV pole as well as being fixed on a frame/platform/stand: Yes, Keypad Locking Facility: Yes, Occlusion pressure trigger levels: 50 to 900 mmHg Event Log available: Yes, ELECTRICAL REQUIREMENTS- Power Supply: 220-240 V AC, 50 Hz, Minimum Battery run time: 4 Hours or more | 6 | Each | - | - |
| 7 | INFUSION PUMP: Programmable and Microprocessor contrroled: Yes, Operating Modes: Flow Rate Mode, volume and Time, Rate and Time, Weight Mode, Sequence Mode, Ramp up,'down mode, Peristaltic Pump System for Volumetric infusion: Yes, Infusion Rate: 0.1 - 1500 or more, Flowrate Increment in ml/hr: 0.1 ml/hr Accuracy of ±5% or better for set parameters: Yes, Comprehensive alarm package required including: Air KVO Rate: 0.1 to 3 ml/hr adjustable. step 0.1ml/h, Purge and Auto Bolus flow rate: 0.1 to 1000 ml/hour or higher Bolus Volume in m): 0.1 - 5 ml in 0.1 ml increments (auto bolus), Self-test facility: Yes, Must have an anti-bolus system: Yes, Predefined Drug Delivery with facility to add or delete drug: Yes. LED/LCD/TFT Display: Yes, Minimum Display Size in inches: 2.4 or more, Pole clamp: Multi-function mounting clamp: Yes, Event Log facility: Yes, Fitting of device on the IV bottle or bag: Yes, Facility to detect the abnormality in IV Bag or bottle Yes, ELECTRICAL REQUIREMENTS- Power supply: 100-240V, 50 HZ Minimum Battery backup: 4 Hours or more | 6 | Each | - | - |
| 8 | Blood and Fluid Warmer: Hæt exchanger type Dry heat , Maximum flow at which warmer heat blood or IV solution in mL/mjn2 80, Priming Volume in mL< 50, Consumables provided Triple lumen tubing. Warranty in ears 2 years | 1 | Each | - | - |
| 9 | PORTABLE SUCTION: Material of cabinet (Base, top and panel): ABS Plastic molded, Rust proof housing cabinet and castor wheels: Yes, The unit is mounted in such a way as to produce minimum vibrations: YesMaterial of twin jars/bottles: Glass, Suction bottles/jars with Synthetic rubber lid and fitted with arrangement to prevent overflow of fluid to outside: Yes, Capacity of each suction bottle/jar graduated (ml): 4000 ml, Interconnected jar/bottle with overflow protection device: Yes, Double overflow protection with safety device provided: Yes, Non-collapsible suction tubing minimum internal Diameter (mm): 10 mm, Material of suction tube (Medical Grade): Silicon, Minimum Length of suction tube (mtr): 2, Flutter free vacuum control knob provided: YesBacterial suction filter/air filters and water traps betweenthe suction bottle and suction pump provided: Yes, Vacuum Gauge Type: Bourdon tube type, Vacuum Gauge with concentric scale marking in black on white background, mounted in panel, easily visible during use of machine7.5 cm dia: 0 to 760 mmHg, Entire unitmounted on four castor wheels with minimum two breaks: Yes, Facility for easy maintenance: Back open, Weight (Kg): 13 to 20, Integrated Foot on/offswitch and vacuum regulator for hands free operation: Yes, Input power supply: 220+/-10% V, 50Hz, Single phase AC, Power indicator: Yes, Integrated on/off switch on the trolley: Yes, Minimum battery backup on full charge (minutes): 30 Optional , Power cable for usage in ambulance/car provided: Yes, Motor capacity (HP): 0.25 HP, The motor•shall conform to 19996/1979: Yes, Type of suction pump: Oil free, Minimum air flow displacement ofsuction pump (Ltrs/Minute): 51 to 60 Ltrs/Minute, Built-up Vacuum (Maximum): -720 +/-10mmHg (-96kPa), sound level (Maximum) (dB): <55, STANDARD ACCESSORIES- Compatible 3 core power cord with Indian plug and length in Mtr: 2, Number of ars Bottles: 2, Suction tubin set : 1 | 2 | Each | - | - |
| 10 | INSTRUMENTTROLLEY: (660 mm x 430 mm x 830 mm) ALL Medical Grade castor, Manufacturing & Workmanship as per IS 4033 & 5631 (Latest): Yes, Frame Work Material as per IS 4033 (Latest): Electric resistance butt-welded steel tube (ERW), Shelves material: Stainless Steel, Finish as IS 4033 (Latest): Yes, And-static rubber tread of castors: Yes, Diameter of the castor wheel: 50 mm, Material of Trolley: Stainless Steel 304, Finishing of Trolley Surface: Chrome Plated, Thickness of Sheet of Trolley (in mm): 1.8 mm, Material of Castor. Polypropylene, Total Trolley Weight (in Kg): 10 kilograms, Pole Thickness: 10 mm, Ground Clearance: 75 mm | 4 | Each | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.61 MB
SBD62.pdf
Tender Documents • 4.48 MB
BOQ_85880.xls
BOQ • 0.31 MB
LOB62.pdf
Additional Documents • 0.51 MB
CORRKMCH.pdf
PDF • 0.62 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .