Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹38.1 LAccepted-AOC 13 THAKKAR PLOT DEEPAK KUNJ PORBANDAR 360575 | PORBANDAR | GUJARAT | 360575 | L1 | Accepted-AOC ACCEPTED | |
| 2 | L2₹40.0 L+₹1.2 L (3.15%)Rejected-AOC 121 MADHAV SQUAR OPP AVANTIKA COMPLEX LIMDA LANE JAMNAGAR 361001 | JAMNAGAR | GUJARAT | 361001 | L2 | Rejected-AOC REJECTED | |
| 3 | Rejected-Technical | - | Rejected-Technical REF TECHNICAL EVALUATION DOCUMENT | |
| 4 | Rejected-Technical HQ CWE AHMEDABAD | GANDHINAGAR | GUJARAT | 382006 | - | Rejected-Technical REF TECHNICAL EVALUATION DOCUMENT | |
| 5 | Rejected-Technical 103 HARIAKSH PLAZA HOSPITAL ROAD BHUJ KUTCH GUIARAT 370001 | BHUJ | KUTCH | GUJARAT | 370001 | - | Rejected-Technical REF TECHNICAL EVALUATION DOCUMENT |
Tender Value
Refer Docs
EMD Value
₹78,000
Closing Date
27 Sept 2021, 6:00 pmClosed
GE I CG PORBANDAR
MILTARY ENGINEERING SERVICES, DHQ-01 GE I CG PORBANDAR OPP BIRLA FACTORY PORBANDAR
REPAIR/ MAINTENANCE OF EXTERNAL ELECTRIC AND WATER SUPPLY AT CGAE PBR, CG JETTY PBR, AND CG DHQ NO1 PBR ,REPAIR/MAINTAINCE AND ANNUAL MAINTENANCE CONTRACT OF STAND BY DG SET AT CGAE AND CGDHQ NO 1 PBR UNDER GE I CG PORBANDAR
2021_MES_471472_1
8640
Open Tender
Civil Works
Item Rate
270 days
PORBANDAR
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
Yes
GE I CG PORBANDAR
₹78,000
Yes
1 Dec 2021
30 Aug 2021
29 Sept 2021
30 Aug 2021
27 Sept 2021
16 Sept 2021
Amount
SCHEDULE 'A'
External Electric Supply for HT M&L for dehydration/centrifuging of transformer oil minimum 3 cycles to achieve dielectric strength 50 kV in 2.5 mm gap electrode with centrifuging machine at site and testing of transformer oil before and after de- hydration complete all as specified and as directed at site.Locations ICGAE/CG Jety Pbr/CGDHQ No 1 (a) Oil topping up shall be measured seperately. (b) Contractor has to make his own arrangement for oil filteration plant.
M&L for topping up/replacement of with new transformer oil upto a required level ( 50 KV di-electric strength in 2.5 mm gap electrode to with stand for one minute) in any type and capacity of transformer complete all as specified and directed at site.Locations ICGAE/CG Jety Pbr/CGDHQ No 1 (a) The transformer oil shall be ISI marked and brought at site in sealed container only. (b) The M & L for necessary T & P for collection of transformerr oil samples testing kit and filteration plant.
Supply and fix in replacement breather for transformer oil conservator tank including filled with silica gel for transformer of following ratings complete all as specified and as directed by Engineer-in charge Locations ICGAE/CG Jety Pbr/CGDHQ No 1 (a) 100 to 250 KVA
(b) 315 to 500 KVA
S & F in replacement Silica Gel (Moisture absorbent chemical ) for breather of transformer 11 KV /433 Volt of any make / rating complete all as specified and as directed by engineer-in charge Locations ICGAE/CG Jety Pbr/CGDHQ No 1
S & F in replacement oil temperature indicator gauge suitble for transformer of capacity 11KV/433 Volt complete all as specified and as directed
Supply and fix in replacement HT bushings of transformer 11 KV/ 433 Volts including by disconnecting existng HT connectin, drain out oil up to safe working level and chnging of existing HT bushing with stud, seal etc of 160 KVA TO 630KVA capacity all as specified and as directed by Engineer-In -Charge.
Dismantling of LT bushing of transformer including metal and rubber parts and complete with new metal and rubber parts of any size and shape required for transformer from 160 KVA to 630 KVA complete all as specified and as directed. Locations ICGAE/CG Jety Pbr/CGDHQ No 1
Supply and fix in replacement LT stud of suitable size for transformer of 11/433 Volt for following rating and make all as specified and directed by Engineer-In -Charge.Locations ICGAE/CG Jety Pbr/CGDHQ No 1 (a) 100 to 250 KVA
(b) 315 to 500 KVA
Attending any breakdown immiediately power transformer of following capacity by OEM service engineer to check and repair /replace any spares related break down and make the power transformer serviceable with in 72 Hours complete all as specified and directed at site. Locations ICGAE/CG Jety Pbr/CGDHQ No 1 Note :-(i) Spares will be paid separately under relative items. (ii) Checking of all electrical connection for its proper tightness. (iii) Proper care shall be taken to isolate the supply and it shall be ensured that repairs are carried out on No LIVE switch gears. (iv) Each switch gear/Load break switch/breaker shall be counted as a separate unit for the purpose of measurement. (a) 315 to 400 KVA
(b) 500 KVA to 630KVA
Material and labour for heat shrinkable HT, 11 KV , outdoor type, cable end joint suitable for 11 KV, 3 Phase, AC, 50 Hz, , XLPE Cable including jointing materials complete including taking down old end joints all as specified and as directed for following size. Make: 3M/Denson/Raychem RPG (a) 95 sq mm 3 core
(b) 120-185 Sq.mm 3 core
(c) 240-300 Sq.mm 3 core
Material and labour for heat shrinkable HT, 11 KV , indoor type, cable end joint suitable for 11 KV, 3 Phase, AC, 50 Hz, , XLPE Cable including jointing materials complete including taking down old end joints all as specified and as directed for following size. Make: 3M/Denson/Raychem RPG (a) 95 sq mm 3 core
(b) 120-185 Sq.mm 3 core
(c) 240 sqmm to 300 sqmm
Material and labour for heat shrinkable HT, 11 KV , Straight Through cable joint suitable for 11 KV, 3 Phase, AC, 50 Hz, , XLPE Cable including jointing materials complete including taking down old end joints all as specified and as directed for following size. Make: 3M/Denson/Raychem RPG (a) 95 sq mm 3 core
(b) 120-185 Sq.mm 3 core
(c) 240-300 Sq.mm 3 core
Supply and Fixing in replacement air break switch triple pole, 11KV, mechanically operated mounted on insulators and steel frame, with operating mechanism worked from ground level, for current rating up to 200 amps complete with including insulators horizontal /vertical rod and operating pipe of suitable size and length including taking down the old unserviceble air break switch,jumper connections and reconnecting of suitable size and length and making connection to new AB switch gang operated complete all as specified and as directed by the Engineer - in - Charge. Make: Jaipuria/ Atlas/Pactil
S & F in replacement HT 11 KV drop out fuse assembly with insulator and base including fuse tube, fuse carrier top connectors incomming and out going connectors as as specified and as directed by EIC. (Note:Rate include taking down existing unserviceble/ Faulty DO fuse assembly and fix the new one and make the incomming and out going connections and switch on the supply through the new DO fuse assembly all as directed by EIC) Make: Jaipuria/ Atlas/Pactil
M & L for preventive maintenance of HT ring main unit at main receiving substation comprising of one incoming Two out going as per manufature specification ,work is to be carried out with prior intimation, and taking shut down of Ring main unit , earth the unit completly all as specified and as directed by Engineer In charge. Scope of work consist of following Note: Contractor has to submit the inspection report to depatment after completion of work (a) Check and clean termination and bushing compartment (b) Checking of sealing of gland plate area (c) Checking of mechanical interlock (d) Check close and trip coil condition and gap setting (e) Checking of control circuit , fuses and Electrical interlocks (f) Following test should be carried out at site (i) Test the insulation testing of each Breaker/Isolator (ii) Test Test contacts of breaker and isolators (iii) Check /Reset the relays (g) Checking/Testing of Relays as per following (i) Functional verification of Indivitual feeder by switch On /Off by both incomming so as to confirm with both incomming unit is functional (ii) Check the auxiliary supply and control voltage , (iii) Check the power pack unit and its Voltage. (iv) Check the CT connections , inspection and testing of closing and trip coil by using external test kit .
M & L for Maintenance/Over hauling of HT VCB 11 KV at ICAE Porbandar (1 nos incoming, 1 Nos outgoing) by taking shunt down with prior intimation and cleaning of HT VCB by using air blower , tightning the control circuit , Checking the all fuses , to ensure the smooth functioning of HT VCB by employing the Skilled trades man and helper all as directed by Engineer -In - Charge. Note: Rate Include following (i) Replacement of small piece of wire of sq area up to 1.5 sqmm Control Ckt cable) of Max length 5 Mtrs and replacement of unseviceble indicator lamps asper colour code allas specified and as directedby Engineer - In - Charge. (ii) Rack out /Down the HT VCB kept in Test position , Check the megger value of VCB terminals with body by suitable HT megger of range 5000 Volt and check the servicebility of earthing connection by Earth megger note down the readings.
M & L for Maintenance/Over hauling of HT VCB 11 KV at CG Jetty Porbandar (1 nos incoming, 2 Nos outgoing) by taking shunt down with prior intimation and cleaning of HT VCB by using air blower , tightning the control circuit , Checking the all fuses , to ensure the smooth functioning of HT VCB by employing the Skilled trades man and helper all as directed by Engineer -In - Charge. Note: Rate Include following (i) Replacement of small piece of wire of sq area up to 1.5 sqmm Control Ckt cable) of Max length 5 Mtrs and replacement of unseviceble indicator lamps asper colour code allas specified and as directedby Engineer - In - Charge. (ii) Rack out /Down the HT VCB kept in Test position , Check the megger value of VCB terminals with body by suitable HT megger of range 5000 Volt and check the servicebility of earthing connection by Earth megger note down the readings.
Supply and fix in replacement of charging motor suitable for 11 KV VCB 800 Amps as per existing make and model and directed at site.
Supply and fix in replacement of closing coil 24Volt DC suitable for 11 KV VCB 800 Amps as per existing make and model and directed at site.
Supply and fix in replacement of Tripping coil 24Volt DC suitable for 11 KV VCB 800 Amps as per existing make and model and directed at site.
Supply and fix in replacement of vaccum bottle suitable for 11 KV VCB 800 Amps as per existing make and model and directed at site.
Supply and fix in replacement of Finger contacts for 2 Nos suitable for 11 KV VCB 800 Amps as per existing make and model and directed at site.
Supply and fix in replacement of auxillary metal contacts suitable for 11 KV VCB 800 Amps as per existing make and model and directed at site.
Supply and Fixing in replacement of indiaction LED lights for each phase of 230Volt complete all as specified and as directed
Supply and Fixing in replacement of indication panel suitable for 11 KV VCB 800 Amps as per existing make and model and directed at site.
Supply and Fixing in replacement of master Trip Relay 110volt DC suitable for 11 KV VCB 800 Amps as per existing make and model and directed at site. complete all as specified and as directed
Supply and Fixing in replacement of Auxilary Relay 110 volt DC suitable for 11 KV VCB 800 Amps as per existing make and model and directed at site. complete all as specified and as directed
Supply and Fixing in replaecment of protection Relay (over short Circuit /earth fault) 110 volt DC suitable for 11 KV VCB 800 Amps as per existing make and model and directed at site. complete all as specified and as directed
Supply and Fixing in replacement busbar spout top for RYB suitable for 11 KV VCB 800 Amps as per existing make and model and directed at site. complete all as specified and as directed
Supply and Fixing in replacement busbar spout Bottam for RYB suitable for 11 KV VCB 800 Amps as per existing make and model and directed at site. complete all as specified and as directed
Supply and Fixing in replaecment in replacement of space heater and Thermostate set suitable for 11 KV VCB 800 Amps as per existing make and model and directed at site. complete all as specified and as directed
Supply and fix in replacement Epoxy cast CT rating100/1-1 Amp, 10 VA , Class E, 5P10 of mould type suitable for 11 KV VCB 800 Amps as per existing make and model and directed at site.
M & L for fabrication work such as cutting molding welding and painting for making of MS stand with ms plate for drawout VCB indoor trolly inclduing with four nos wheel with suitable size bearing,inclduing with fixing accessories and painting complete all as specified and as directed
M&L for apply two coat of epoxy paint on site,including preparation of rusted surface of transformer of any capacity and writing SM No./MES No.complete all as specified and as directed.
Excavation in trenches not exc 1.5 m wide and not exc 1.5m in depth and getting out Soft/ Loose soil and including taking out of PCC cable cover and getting out complete all as specified and directed
Returning filling in incl spreading levelling watering and well Ramming in layers not exc 25 cm thick complete all as specified and directed
Removing excavated material not exc 50 m and depositing where directed at a level not exc 1.5 m above the starting point complete all as specified.
Taking out unservicable LT UG cables of any sizes from trenches (location of ICGAE/DHQ No 1/ICG Jetty) complete all as specifed and as directed
Supply & Lay in replacment of XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade of cross-sectional area for following size of cable Make: Polycab/ Asian/ Gloster/Havells/KEI Note : for Item No 40.01 to 40.06 (i) Removing of interlocking/Paverblocks, tiles and refxing with the same location and making good the distrubed surface is deemed to be included in quoted rate. (ii) Fixing accessories for cable layingsuch as clamps and nut bolts are to be included in quoted rate. (a) 16 Sqmm 4 Core
(b) 25 Sqmm 4 Core
(c) 50 Sqmm 3.5 Core
(d) 70 Sqmm 3.5 Core
(e) 240 Sqmm 3.5 Core
(f) 400 Sqmm 3.5 Core
(g) 10 Sqmm 4 Core
Supply and Lay in replacment of OD Double Wall Corrugated (DWC) high density polythene pipes having corrugation on the outer wall and plain surface on the inner wall for protection of underground Cable with all fittings laid in trenches/road/nallah or fixed along wall poles or laid under floor for the following dia (Excavation and earthwork shall be measured and paid separately) complete all as specified and as directed. Make: Rex/Poly/Geminie (i) Fixing accessories for pipe laying such as clamps and nut bolts are to be included in quoted rate. (a) 90 mm Outer dia
(b) 63 mm Outer dia
M & L for Cutting & removing existing joint and supply, jointing and testing straight through Hot shrinkable cable joint including all materials and accessories suitable for 3.5 core XLPE cable of 1100 volts grade complete all as specified and as directed. Make: 3M/Denson/Raychem RPG Note : Excavation and Earthwork shall be measured seperately. a) 25 sq mm to 50 sq mm
b) 70 sq mm to 150 sqmm
c) 185 sqmm to 240 sqmm
Servicing and repair of APFC panel upto 200 KVAR by replacement of worn out spare parts and cleaning of the serviceable contactors and tightning/checking of all internal electical connections and accessories to maintain PF not less than 0.98 by adjusting/ calibrating the APFC relay of any type complete all as specified and as directed Note: Defective parts if any will be measured and paid seprately
Supply only items for APFC Panel, complete all as specified and as directed (a) MCB TP 25/40 Amp, 10 KA, 'C' series. Make: Merlin Garin/L&T/Legrand
(b) Heavy duty gas filled Capacitor,1 to 4 KVAR, 440V, 3phase, 50 Hz. Make: L&T/BCH/EPCOS
(c) Heavy duty gas filled Capacitor,5 to 15 KVAR, 440V, 3phase, 50 Hz. Make: L&T/BCH/EPCOS
(d) Heavy duty gas filled Capacitor,20 to 50 KVAr, 440V, 3phase, 50 Hz. Make: L&T/BCH/EPCOS
(e) Contactor TP 32/40 Amp. Make: L&T/C&S/CG
( f) Relay 6 stage Make Legrand/L&T/ABB/BCH/Neptune
M&L for preparation of old/rusted painted surface of outdoor type/indoor LT panel with sand paper/scrubing of dust etc before painting the panel and painting with one coat of red oxide paint and one coat of syenthtic anamel paint complete all as specified and directed, Location CGAE/ DHQ No1/CG Jetty Pbr Note: Minor repair/ replacement of hinges suitable for screw fastners and fixed in original position
M&L prepairing old rusted surface of Steel tubular pole or any other pole of length 9/11 mtr by means of sand paper/scrubing of duct etc and apply one coat one coat of epoxy based primer before painting complete all as specified and directed,
M&L for apply two coat of epoxy paint on canopy of DG SET of 20 to 25 KVA of any size for location DHQ No1 CGAE ,including preparation of rusted surface of poles by means of sand paper/scrubing of dust etc and apply one coat of epoxy based primer before painting complete all as specified and directed, note: Minor repair/ replacement of hinges suitable for screw fastners and fixed in original position
Supply and Fixing in replacement of LED street light fitting 35 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete.Location CGAE/ DHQ No1/CG Jetty Make Wipro/Philips/GE
Supply and Fixing in replacement of LED street light fitting 70 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete.Location CGAE/ DHQ No1/CG Jetty Make Wipro/Philips/GE
Supply and Fixing in replacement of LED flood light 120 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp.Location CGAE/ DHQ No1/CG Jetty Make Wipro/Philips/GE
M & L Disconnecting the connection of alternator from DG set capacity 20/25 KVA and removes the old main stater rewindings, excitor stator rewindings and excitor rotor rewindings complete Replace the copper winding of coils with new sleeve complete refixing with nuts and bolts and making the connection of coils complete all as specified and as directed
Loading,unloading and Tranporatation charges for reparing /winding of rotor or stator from Dhq No 1 to repairing workshop inclduing all type of tools and plant and return back complete all as specified and as directed
M& L for DIOD assembly Set for 20/25 KVA dg set complete all as specoified and as directed
M & L for servicing cheking the connection of main rotaor of dg set, cleaning the dust paritcal coplete all as specified and as directed
Servicing of DG set ('C' Check) of Cap 20-25 KVA by Rep of authorised service centre as per manufacturer manual and checking of fuel supply system, Lubrication system, cooling system, battery ignition system and rectification of defect if any and including replacement of following, complete all as specified and directed (a) Lub oil filter. (b) Lubrication oil. (c) Fuel filter. (d) Coolent top up. Make of DG set: Mahindra/ Kirloskar Note: Defective parts if any other than listed at (a) to (d) above will be measured and paid separately
Supply only parts/ Items of DG set 20-25 KVA V belt
Hose pipe set
Battery Terminal
Engine Oil 20W / 40 Make : Castrol/Servo/IOC/HP
Coolent
Radiator servicing complete
HWT Switch
VDO Oil Pressure sensor cum Switch 0-7 BA
Water Pump Assembly
controller panel of DG set
Fuel Retrun Pipe
Fuel Supply Pipe
Pipe EGR to EGR valve
AVR of DG for 20/25 KVA capacity including with connection complete all as specified and as directed
Servicing of DG set ('C' Check) of Cap 250 KVA by Rep of authorised service centre as per manufacturer manual and checking of fuel supply system, Lubrication system, cooling system, battery ignition system and rectification of defect if any and including replacement of following, complete all as specified (a) Lub oil filter. (b) Lubrication oil. (c) Fuel filter. (d) Coolent top up. Make of DG set: Kirloskar
Supply only parts/ Items for DG set 250 KVA V belt
Hose pipe set
Battery Terminal
S&F in Replacement Elevated type Omni directional medium intensity taxiway edge light fixture suitable for operation on 5KV, 50Hz, 2.8-6.6 amps current, complete with base plate, breakable coupling, mounting accessories,gasket,blue lens etc.
Supply, laying & testing in replacement of insulated stranded plain anneled copper PVC insulated & PVC sheathed of 5 KV insulated and PVC sheathed of 5 Kv grade single core 6 Sqmm
Supply and laying in replacement of 12" Secondary lead with male female connector complete all as specified and as directed
Supply and Fixing in replacement of Isolating transformer 45 Watt 6.6/6.6 A 50HZ 5 KV grade complete all as specified and as directed
Dismantling cross-arms of MS,channel or angle sections & earth wire etc complete and setting aside for re-use with in 50 m distance.complete all as specified and as directed
M & L for in replacment of Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint complete all as specified and as directed
S&F in replacement Automatic street light swith 230 Volts 3 phase 5 KW 25 with contactor fitted in stainless steel enclosure inclduing incoming and outgoing MCBs, power contactor complete 3 phase circuit board along with nutral switch fixed in repair complete all as specified and as directed. Make:- swaddep 66-3 kW1P of Healer Nature Switch :- Bajaj/Healer/Kakatiya. MCB/Contactor : - L&T/C&S/ABB
Supplying and laying in replacment of synthetic Rubber insulated mats 2.5 mm thick for voltage upto 11 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m
Supply and Fixing in replaecment of LED indiator lamp for RYB phase 230 Volt complete all as specified and as directed
Supply and fix in replacement of aluminium thimble of following size complete all as specified and as directed a) 16-25 Sqmm size
b) 35-50 Sqmm size
c) 70-95 Sqmm size
d) 120-150 Sqmm size
e) 240 Sqmm size
f) 400 Sqmm size
Supply and fix in replacement junction box with PVC junction Box of size 155 x 210 x 92mm with terminals for street light including cable connector for cable connection with IP -66 protection including fixing accessories complete all as spacified and as directed Make Hensel cat No DK 1616G or equivalent Legrand/ABB
Supply and fix in replacment of MCCB 63 Amp 4 Pole 16KA with thermal magnetic setting complete all as specified and as directed Make ABB/L&T/Legrend
Supply and fix in replacment of MCCB 100 Amp 4 Pole 16KA with thermal magnetic operated complete all as specified and as directed Make ABB/L&T/C& S/Legrend
Supply and fix in replacment of MCCB 200 Amp 4 Pole 36KA with thermal magnetic operated complete all as specified and as directed Make ABB/L&T/C& S/Legrand
Supply and fix in replacment of MCCB 250 Amp 4 Pole 36KA with thermal magnetic operated complete all as specified and as directed Make ABB/L&T/C& S/Legrand
Supply and laying in replacement 3- layer PP-R Polypropylene random copolymer) pipes SDR 7.4 (PN16) UV stablised and antimicrobial fusion welded having thermal stability for hot & cold water supply all PP-R plain & brass threaded polypropylene random fittings laid in trenches/Wall complete all as spd and directed. Make SFMC / VECTUS / RELIANCE / AKG / SFC a) 40 mm outer dia
b) 32mm outer dia
M&L for inreplacement of gate valve of PPR pipe for following outer dia complete all as specified and as directed Make SFMC / VECTUS / RELIANCE / AKG / SFC / KPT a) 32 mm
M&L for apply two coat of epoxy paint on sand filteration tank of any size ,including preparation of rusted surface of poles by means of sand paper/scrubing of dust etc and apply one coat of epoxy based primer before painting complete all as specified and directed,
Supply and Fixing in replacement of CPVC pipes Hot and Cold SDR 13.5 pipes & plain CPVC SDR 11 fittings on walls/ceiling or laying in floors of outer diameter 32 mm bore complete all as specified and as directed
Dismantling the centrifugal Pump up to 10 HP including disconnecting suction and delivery line and rewinding the motor with suitable size of copper wire and reassembling after replacement of necessary spares including greasing and painting of 2 coats of synthetic enamel paint using spray machine complete all as specified and as directed.
Taking down submercible pump 3 phase, 415 Volt capacity up to 5 HP, incoming disconnection electric connections, dismantling slots, taking out burnt windings and rewinding the motor with super enameled copper wire as per existing size including insulating material and varnishing,greasing, painting with super enameled paint as per colour coad assembling the motor after rewinding and mounting at its own position, replacing the old nut, bolts and testing all as directed.
Taking out unserviceable foot valve 80 mm dia from the UG sump and S & F new CI/PVC foot valve 80 mm dia ball type incl rubber gasket, strainer bolts, nuts complete all as directed.
M & L for Earthing complete with galvanized steel pipe electrode , 40mm bore, medium grade, 2.5 metre length, buried directly and preferably vertically in ground with top edge not less than 1.25 metres below ground level connected with earthing lead of GI strip 25*4 mm size galvanised iron strip 4 all as shown in electrical plate no. 2 of MES SSR part-1 to the earthing test point all as specified and indicated including testing on completion all as specified and directed. NOTE: cost of earth lead wire GI strip 25*4 mm size and GI pipe for protection of earth strip deemed to be included in unit rate up to 7.5 metre.
Supply,and fixing in replacement of CI sluice valve 100 mm dia flanged end, class PN 1.6 heavy duty with stailess steel spindle and iron wheel at the top including jointing material such as, nuts, bolts rubber packing etc, including old unserviceable sluice valve all as specified and as directed. Make :- Kirloskar / Zoloto / Leader / Upadhyaya
Supply,and fixing in replacement of CI sluice valve 150 mm dia flanged end, class PN 1.6 heavy duty with stailess steel spindle and iron wheel at the top including jointing material such as, nuts, bolts rubber packing etc all as specified and as directed. Make :- Kirloskar / Zoloto / Leader / Upadhyaya
Supply and Fixing in replacement of star delta starter for up to 15 Hp monoblock pump set 415 Volt 3 Phase 50 Hz with contactor and on off push button switch inclduing fixing accessories complete all as specified and as directed.
Taking down carefully burnt out aluminium/copper point wiring (light, fan, socket or power) complete (fittings such as switches, ceiling roses, pendent, regulators, sockets, flourescent tube light fittings etc to be measured and paid for seprately) removing materials to store for schedule of credit and making good to the disturbed surfaces of walls ceilings and floors etc complete all as spd and directed.
Disconnecting of unserviceable sub main wiring of any size and including steel conduit and accessories & removing from site and making good the disturbed surfaces including painting
Modular Point wiring M & L for in replacement point wiring using ISI marked 1.1 kV grade single core FR-LSH flexible cable, conforming to IS: 694- 1990, having multi-drawn thin strands of electrolytic copper conductors, conforming to IS: 8130- 1984 and insulation conforming to IS: 5831- 1984, for phase, neutral and earth continuity conductor connecting to earth dolly, drawn in not less than 25 mm size PVC cassing capping surface/exsisting PVC conduit conforming to IS: 9537 (Part 3)- 1983, colour-coded as specified in IS: 11353- 1985, thick modular cover-plates complete all as specified in IS: 732- 1989 and directed.Make Havells/ Anchor/RR Cables (i) Exsisting Modular sheet metal box should not be removed (ii) Mounting plate and cover plate of exsistng size is to be replace and rate are deemed to be inlcuded in quoted rate. (a) One light/ Bulb Holder /fan/exhaust point / bell point controlled by one, one way switch
(d) One light point controlled by 2, Two way switch
(c) One 5 pin socket outlet 5/6 amps on the same board.
(d) One 5 pin socket oulet 5/6 amps on independent board..
S & F in replacement of modular type 6 A one-way SP switch, conforming to IS: 3854-1997 with finger proof terminalcomplete as specified and directed. Make Anchor/ Havells/Legrend
S & F replacement of modular type 16 A one-way SP switch, conforming to IS: 3854- 1997 with finger proof terminal complete as specified and directed . Make Anchor/ Havells/Legrend
S & F replacement of modular type 2/3 pin combined shuttered type 6 A socket conforming to IS: 1293- 2005 complete as specified and directed. Make Anchor/ Havells/Legrend
S & F replacement of modular type 2/3 pin combined shuttered type 6/16 A socket conforming to IS: 1293- 2005 complete as specified and directed. Make Anchor/ Havells/Legrend
S & F replacement of modular type 6 A bell-push conforming to IS: 8884- 1978 with finger proof terminal complete all as specified and directed. Make Anchor/ Havells/Legrend
S & F replacement of modular type 120 W step fan regulator of 2 module size, conforming to IS: 11037-1984 complete as specified and directed. Make Anchor/ Havells/Legrend
S & F in replacement of 6 A, 250 V high quality robust surface/flush type polycarbonate/PVC ceiling rose, conforming to IS: 371- 1979, having 2/3 terminals and outside diameter not less than 63.5 mm complete all as specified and directed. Make Anchor/ Havells/Legrend
Flush Type Point wiring M & L for in replacment of Point wiring in replacment with 1.5 Sq mm single core PVC insulated but unsheathed multistranded copper conductor FRLSH cable 650/1100 Volts grade drawn through and including non metallic PVC heavy duty cassing capping minimum 25 mm size/ exsisitng conduit but shall be increased as per actual site requirement in accordance with clause 19.125 of SSR Part I) ISI marked with wall thickness not less than 1.8 mm including cassing capping accessories like bends, tees, etc fixed on wall or ceiling etc including 1.5 Sq mm PVC insulated but unsheathed multi stranded copper conductor FRLSH cable as earth continuity wire of suitable size with 3 mm thick bakelite sheet white/coloured top cover for:-Make Havells/ Anchor/RR Cables (i) Exsisting metal sunkem box should not be removed (ii) Backlite sheet of exsistng size is to be replace and rate are deemed to be inlcuded in quoted rate.(iii) PVC box and switch board for mounting of switch sockets are deemed to be included in unit rate. a) One light point/fan point/ bell point controlled by one, one way switch.
One light point controlled by 2, Two way switch
One 5 pin socket outlet 5/6 amps on the same board.
One 5 pin socket oulet 5/6 amps on independent board..
M & L for in replacment of Point wiring complete with 2.5 Sq mm single core PVC insulated but unsheathed multistrand copper conductor FRLSH cabel 650/1100 Volts grade conforming to IS-694 drawn through PVC cassing capping (minimum 25 mm size (external) or exsisting conduit but shall be increased as per actual site requirement in accordance with clause 19.125 of SSR Part I) ISI marked with wall thickness not less than 1.8 mm heavy including 2.5 Sq mm PVC insulated but unsheathed copper conductor FRLSH cable as earth continuity wire for one 3 pin 15 or 16 Amps socket outlet on independent board as specified.Make Havells/ Anchor/RR Cables (i) Exsisting metal sunkem box should not be removed (ii) Backlite sheet of exsistng size is to be replace and rate are deemed to be inlcuded in quoted rate.(iii) PVC box and switch board for mounting of switch sockets are deemed to be included in unit rate.
M & L for in replacment of Point wiring complete with 4.0 Sq mm single core PVC insulated but unsheathed multistrand copper conductor FRLSH cable 650/1100 Volts grade conforming to IS-694 drawn through PVC cassing capping (minimum 25 mm size (external)/ exsisting conduits but shall be increased as per actual site requirement in accordance with clause 19.125 of SSR Part I) ISI marked with wall thickness not less than 1.8 mm heavy duty including 4.0 Sq mm PVC insulated but unsheathed copper conductor FRLSH cable as earth continuity wire for on AC metal socket box complete all as specified.Make Havells/ Anchor/RR Cables
Supply and fix in replacement of switch piano flush button 230 V, 6Amps, Single pole, two way ISI marked complete all as specified and directed.Make Havells /Anchor/Cona
Supply and fix in replacement of Socket outlet flush type 2 in 1, 3 pin, 5A 230 Volt complete all as specified and directed.Make Havells /Anchor//Cona
Supply and fix in replacement of Socket outlet 3 pin, 15 Amp, flush type complete all as specified and directed.Make Havells /Anchor/Cona
Supply and fix in replacement of switch piano flush button 230 V, 16Amps, Single pole,one way ISI marked complete all as specified and directed.Make Havells /Anchor//Cona
Supply and fix in replacement of Rigid non-metallic PVC conduit of 25 mm dia of boxes (junction/ terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc.Make Precision/Prince/Supreme
Supply and fix in replacement of Rigid non-metallic PVC conduit of 20 mm dia of boxes (junction/ terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc..Make Precision/Prince/Supreme
Supply and fixingin replacement of Polycarbonate type 65 mm dia ceiling rose 2/3 terminal suitable for 230 Volt complete all as specified and as directed Make Havells/Legrend/Anchor
Supply and Fixing in replaecment fan regulator steped type 230 Volt complete all asspecified and as directed Make Havells/Legrend/Anchor
M & L in replacment of submain wiring using ISI marked 1.1 kV grade single core HR- FR flexible cable, conforming to IS: 694- 1990, having multi-drawn thin strands of electrolytic copper conductors and insulation conforming to IS: 5831- 1984, type C, HR 85° C + FR for phase, neutral and earth continuity conductor connecting to earth dolly, drawn in not less than 25 mm NB UPVC medium grade surface/recessed exsisting conduits, conforming to IS: 9537 Part- 3, colour-coded as specified in IS: 732- 1989, including making good of disturbed surfaces of wall/ceiling/floor, and painting complete as specified and directed. Make: RR Kabel, Polycab, Havells, Finolex (HR-FR flexible cable) & Precision, Prince, Supreme (PVC conduit) NOTE: 01 run of phase conductor, 01 run of neutral conductor, 01 run of earth continuity conductor and 01 run of concealed conduit shall be measured as one length. a) 2 x 4.0 Sqmm + 1 x 4.0 Sqmm earth wire
b) 2 x 6.0 Sqmm + 1 x 6.0 Sqmm earth wire
Supply and fix in replacement of follwing DB sheet enclosure double door type single pole and neutral 240 Volt with standarad bus bar of follwing size enclosed in complete all as specified and as directed. a) SPN DB double door 240 Volt 8 way with 200 amp rated bus bar complete with fixing accessories complete all as specified and as directed Make Hensal/Legrend/Schnider
b) SPN DB double door 240 Volt 12 way with 200 amp rated bus bar complete with fixing accessories complete all as specified and as directed Hensal/Legrend/Schnider
S&F in replacement of track light, track mount LED COB luminarie with high efficacy housing made of extruded aluminium 240V, 50Hz, 20W, CCT 4000K, complete all as specified and as directed by Engr-in-Charge, Make: ld -57-251-024-40-XX Philips/ GE/Wipro Note- cost of replacing in existing cut out of false ceiling deemed to be included in unit rate
S&F in replacement of Sleek surface downlight LED recessed mounted luminaire,240V, 50Hz, 18W, CCT 5700 K, round in shape, cutout dimension 168 mm complete all as specified and as directed by Engr-in-Charge, fixed in repair. Make: LD06 -221-XXX-57RF* of Wipro /Philips/ GE Note- cost of replacing in existing cut out of false ceiling deemed to be included in unit rate
S&F in replacment of LED recessed mounted luminaire,240V, 50Hz, 2000 Lumen 4000K round/ Squrein shape, complete all as specified and as directed by Engr-in-Charge, Make: SM 251C LED 20S -6500PSU WH Philips /Wipro/ GE Note- cost of replacing in existing cut out of false ceiling deemed to be included in unit rate
Supply and Fixing in replaecment of LED kit COD 48 to 52 Volt DC for search light complete all as specified and as directed
Dismantling the 200WP, 12V solar panel of solar street light and cheking the solar controller, solar battery and solar light complete all as specified and as directed
Supply and fix in replacement solar battery of 100 AH,12V complete all as specifed and as directed
S&F in replacement MPPT Controller suitable for 200Wp, 12 V solar Panel complete all as spd and directed.
Supply and Fixing in replaecment of LED 150 Watt Driver 220 Volt as incoming and 48 to 52 Volt Ac for outgoing for search light
Supply and Fixing in replaecment of copper fuse Link 2 Amp 230Volt ac complete all as specified and as directed
Supply and Fixing in replaecment Housing 20" for sediment & carbon complete all as specified and as directed
Supply and Fixing in replaecment sediment Filter complete all as specified and as directed
Supply and Fixing in replaecment Carbon block complete all as specified and as directed
Comprehensive maintenance of RO water plant of capacity 500 LPH comprising the followings;- (i) RO membrane element-4040. (ii) Sediment filter. (iii) Solenoid valve. (iv) Antisalent chemical. Note : (i) Replacement of minor parts such as spare parts/Union Male/female, elbow,brach etc to be included quoted rate. (ii) Majlor parts to be replaced as mentioned above will be paid separately under relevant item of the schedule.
Supply and Fixing in replacement of membrane element suitable for model No 402 INDROMATIL ION EXCHANGEcomplete all as specified and as directed
M & L for antiscalent chemicals 8211 complete all as specified and as directed
Supply and Fixing in replaecment for solonoid valve 230Volt complete all as specified and as directed
Supply and fixing in replacment of Tank level sensor including fixing complete all as speified and as directed.
Cheking and testing of RO Plant inlet outlet connection of filter PVC tank and other incoming and outgoing connection of electrical panel by Technician complete all as specified and as directed
Supply and fixing in replacment of LLOP sencer suitable for DG set of 20KVA capacity complete all as specified and as directed
Supply and fixing in replacement of NRV of 80 mm dia inclduing fixing accessessoires complete all as specified and as directed
SURESH ELECTRICALS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .