Loading…
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Tender Value
₹30 L
EMD Value
₹30,000
Closing Date
29 Jan 2026, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Assistant Manager (North West Zone)
Supply and Installation of New fire fighting system in new AMC Buildings in Chandlodia Wards and different wards of North West Zone of AMC
264067
Tender Notice No 7/2025-26 T No 261
Open
Civil Works
Works
Ahmedabad
3 documents required · 3 mandatory
₹1,500
Yes
Municipal Commissioner, Ahmedabad
₹30,000
Yes
12 Jan 2026
12 Jan 2026
12 Jan 2026
29 Jan 2026
12 Jan 2026
Name of work :-Supply and Installation of New fire fighting system in new AMC Buildings inChandlodia wards and different wards of North West Zone
Rate Amount Approved Make
S.No. Description Qty Unit Supply & Supply &
Installation Installation
Part-A - Fire Hydrant System
Supply, Installation, Testing & Commissioning of Fire Hydrant &
Sprinkler System as per the Technical Specifications & tender
Drawings .The work shall be Completed in all respect as per the
Instruction of Engineer Incharge.The system shall be Integrated with
BMS (Refer the Technical Specifications of BMS Specified in
Electrical Tender Document).The Auto Glow Signage applicable for
the respective system shall be scope of Vendor.The Vendor shall
Prepare and submit 06 Sets of detailed shop Drawings as per Tender
Specifications/Tender Drawings, Vendor also shall Submit 06 Sets of
As Built Drawings and 03 Sets of Soft Copy (in the form of CD in
Editable Format alongwith applicable Test Certificates,Data
Sheets,Operation & Maintenance Manual).
Supply, installation, testing, & commissioning of electric driven Main
1 Fire Pump suitable for automatic operation consisting of the 1 Set 3,50,000.00 350000.0 Kirloskar / Wilo / Lubi
following specification.
Back Pull out ,centrifugal end suction type pump complete for
delivery of 137 m3/hr (2280 LPM) with 2900 rpm against a total
1.1 head of 70 metres with bronze impeller complete with Gland Packing
with Complete accessories like Base Frame,Anti vibration
Pads,Coupling etc to make the system functional in all respect.
Squirrel cage induction , 3 phase ,415 Volt, 50 Hz, Energy Efficient
1.2 Motor suitable for above pump. (As per the Specifications of Motors
specified in the Electrical tender Document)
Supply, installation, testing, & commissioning of diesel engine driven
2 Standby Fire Pump suitable for automatic operation consisting of the 1 Set 6,25,000.00 625000.0 Kirloskar / Wilo / Lubi
following ( as per specification ).
Back Pull out ,centrifugal end suction type pump complete for
delivery of 137 m3/hr (2280 LPM) 2150 rpm against a total head of
2.1 70 metres with bronze impeller complete with Gland Packing with
Complete accessories like Base Frame,Anti vibration Pads,Coupling
etc to make the system functional in all respect.
Air cooled (Radiator Type) Diesel Engine developing suitable Power
for the above pump Complete with Exhaust Silencer,Hot Insulation
with Cladding,Supports ,Painting Complete with Battery,Charging
system,Cables, Panel (As per General Specifications in electrical
Tender),Diesel Tank (Min capacity for 4 Hrs Opration) Complete
with Nozzles,Level Indicator, Isolation Valves etc with Mounting
Stand ,duly painted (Frame & Tank) in all respect to make the
System Functional.
Supplying, installing, testing, & commissioning of Electric Motor
3 driven Pump suitable for automatic operation consisting of the 1 Set 75,000.00 75000.0 Kirloskar / Wilo / Lubi
following ( as per specification ).- (Terrace Pump)
Back Pull out ,centrifugal end suction type pump complete for
delivery of 900 LPM against a total head of 30 metres with bronze
impeller complete with Gland Packing with Complete accessories
like Base Frame,Anti vibration Pads,Coupling etc to make the system
functional in all respect.
Squirrel cage induction , 3 phase ,415 Volt, 50 Hz, Energy Efficient
Motor suitable for above pump. (As per the Specifications of Motors
specified in the Electrical tender Document) & Supply, Installation,
testing & commissioning of cubical type floor mounted Electrical
panel.The panel shall be designed as per IS standard & Refer General
Specifications of LT Panels defined in Electrical Tender Document
including the list approved makes.The Panel shall have facility to
Operate in Auto/Manual Mode of Terrace Pump. The Pressure
Switch ,Flow switch and control Cabling in between for the
Individual Terrace Pump shall be part of Vendor's Scope.
All incoming power & control cables of suitable size from panel to
motors, pressure switches, etc. including termination with Copper
Lugs & Double Compression Cable Glands, Cable Tray and Earthing Polycan,
as per IS standard and Defined in General Specification of Finolex,Avocab
Electrification of Electrical Tender Document including Approved
Supply, Installation, testing & commissioning of single headed SS
304, ISI mark oblique pattern hydrant valve with 80mm diameter Newage/ Winco /
5 flanged inlet & 63 mm instantaneous type female out let with pvc cap- 1 Nos 7,500.00 7500.0 Shah
chain spring release type lug and accessories as per IS: 5290- 1983 Bhogilal/Protecto
Supply,Installation, testing & commissioning first aid hose reel, full
swinging with 30 mtr long, 25mm dia rubber lined, with ss 304 shut Newage/ Winco /
6 1 Nos 8,500.00 8500.0 Shah Bhogilal /
off nozzle of 6 mm dia. confirming to IS: 884, 1969 including 25mm Protecto
dia pipe connection from riser to hose reel with complete accessories.
Supply ,Installation, testing & commissioning air vessel of Min
mm dia. (8 mm thick) 1.5 meter long made from M.S with 25mm-dia
spring-loaded air release valve, safety valve and gunmetal full way
valve. The Vessel shall be Painted with one Coat of Red Oxide and Giacomini / Rapidrop
Two Coats of Synthetic Enamel Paint . The Vessel shall be Fixed and / Sant
Mounted by Vendor including anchoring etc. Two Numbers Extra
Air vents with Isolation Ball valves to be Provided in the Piping at
the Highest Point.
Supply ,Installation, testing & commissioning of M.S. pipe heavy
Pipe - Jindal Hissar /
Class ‘C’ ISI marked as per IS: 1239/IS 3589 Part-I including cutting,
screwing, welding etc. with all fittings as tees, elbows, reducers,
Pipe Fittings - VS
flanges clamps hangers painting with one coat of primer and two
coats of synthetic enamel paint of approve shade.
U Bolt / Pipe Clamp -
Nut bolts - TVS /
Gasket - Uniklinger /
Paint - Berger / Asian
a 250 NB (6 mm Thickness) 1 Mtrs 4,500.00
b 200 NB (6 mm Thickness) 1 Mtrs 3,500.00
e 80 NB 1 Mtrs 1,350.00
f 65 NB 1 Mtrs 1,150.00
g 50 NB 1 Mtrs 950.00
g 40 NB 1 Mtrs 750.00
g 32 NB 1 Mtrs 550.00
h 25 NB 1 Mtrs 450.00
S.I.T.C of Pressure gauges - Glycerine Filled SS 304 with all
9 accessories like needle- valve, Syphon etc. Range 0-16 Kg/cm2 , Dial 1 Nos 3,500.00 3500.0 H Guru, Micro, Excel
- 150 mm, Size - 1/2 " BSP
Supply,Installation, testing & commissioning of Diaphragm Type
Pressure switch, housing shall be die cast aluminum with SS
10 1 Nos 3,500.00 3500.0 Danfoss / Indfoss
moving parts like pressure element and socket. the range 0 to
Local / ISI Approved
Supply ,Fabrication,Erection and Painting of Steel Structure with &
one coat of Red Oxide and Two Coat of Synthetic Enamel Paint for Anchor Fastner - Hilti
Support complete in all respect with the anchoring etc. / Fischer
Excavation,back Filling and min 100 mm sand bedding of
Underground Pipes as defined in Technical Specification
Excavation 1 m3 650.00
Supply and fixing of Valve chamber including C.I.cover of size
750x750 mm including excavation, C.C. bedding 1:4:8 100 mm thk.,
230 mm thk brick masonary with 100 mm thk. C.C. coping over
masonary 15 mm thk. Smooth cement plaster inside and rough
cement plaster outside including curing as defifined in Civil Tender
Supply, Instalation,Testing & Commissioning of NP-03 Grade Hume
14 Pipe 350 mm dia. (Refer Drawing - HAL-UM-302) & the 1 Mtrs 1,700.00
specifications/Laying Refer Civil Tender Specification.
Supply, Installation, testing & commissioning cast iron double
flanged ,including mating Flanges,type IS marked sluice valve of the Audco,Advance,
following size complete with bolts, nuts, washers and inserted rubber Zoloto
gaskets as required: As defined in Technical Specification
Supply, Installation, testing & commissioning ISI marked C.I (SS304
Disc) Butterfly valve of P.N 1.6 Rating as per Technical Audco,Advance,
Specification ,the mating flange and additional Pair of Flanges shall Zoloto
be considered to Fix the distance piece with Butterfly Valve.
250 NB (Gear Operated) 1 Nos. 32,000.00
200 NB (Gear Operated) 1 Nos 24,000.00
Supply,installation ,testing & commissioning of Ball Valves 3 Piece
17 Design ,Body - Forged or Cast Carbon Steel ,Trim and Ball SS410
Seat SS410 Threaded End as per Technical Specification
Supply,Installation, testing & commissioning ISI marked C.I double
flanged dual plate type Non- Return valves (SS 304 disc) Complete Audco,Advance,
with Mating Flanges,Nuts,Bolts and Gaskets, As per Technical Zoloto
Supply, installation, testing and commissioning of "Y" type Flanged
Strainer with SS 410 mesh of at least 10 times pipe area with flanged Audco,Advance,
inlet and outlet complete Complete with Mating Flanges,Nuts,Bolts Zoloto
and Gaskets, As per Technical Specification.
S.I.T.C of ISI marked Ball Type Foot Valve, CI Body & Nitrile
20 Reinforced Ball PN 1.0 rating with matching Flanges , Nut, bolts,
washer & Gaskets.
S.I.T.C of SS 304 63mm dia branch pipe as per ISI Standard , Newage/ Winco /
21 Complete in all respect with Nuts,Bolts ,Gasket etc .As per Technical 1 Nos 2,000.00 2000.0 Shah
Specification Bhogilal/Protecto
Supply & Installation of outdoor type hose cabinet fabricated from
16g M.S sheet with full front glass door and locking arrangement
suitable to accommodate , 2 no of 15 meter long hose pipe and one Newage/ Winco /
22 branch pipe. It should be painted with one coat of primer and two 1 Nos 4,500.00 4500.0 Shah
coat of synthetic enamel paint. Complete in all respect with Fixing Bhogilal/Protecto
Supports of Steel Members Duly Painted in same color and Clamping
Supply & Installation of outdoor type hose cabinet fabricated from
weather proof FRP sheet with full front glass door and locking
arrangement suitable to accommodate , 2 no of 15 meter long hose
Newage/ Winco /
pipe and one branch pipe. It should be painted with one coat of
primer and two coat of synthetic enamel paint. Complete in all
Bhogilal/Protecto
respect with Fixing Supports of Steel Members Duly Painted in same
color and Clamping arrangement.
Supply,Installation, testing & commissioning 63mm dia 15mtr long
Newage/ Winco /
reinforced rubber lined hose pipe confirming to IS: 636-1962 PART-
A with ISI SS 304 male and female coupling, complete in all respect.
Bhogilal/Protecto
Supply,Installatation,Testing & Commissioning of gun metal 4 way
Newage/ Winco /
fire brigade in let connection with 63mm instantaneous coupling with
plug, cap, chain, complete in all respect including,
Bhogilal/Protecto
Nuts,Bolts,Gaskets etc.
Supply,Installation, testing & commissioning of 100 mm dia size gun
metal 2 way Drawl off connection with 63mm instantaneous Newage/ Winco /
Coupling with Plug, Cap,chain,C.I. Foot Valve,complete in all Bhogilal/Protecto
respect, complete with Nuts,Bolts,Gaskets etc.
Wrapping and Coating of Under Ground Piping with 4 MM Pypkot
27 1 M2 550.00 550.0 IWL/Equivalent
anti Corosive tape , As per Technical Specification
Flow Meter (turbine type/Mechanical Type) On line for Fire Hydrant
Pump Flow Testing - working Flow 137 m3/hr (Actres/Kranti
Make), Body C.I. turbine of SS, Hermetically Sealed, Environmentaly
protected, Complete with fixing arrangement and mating flanges to
make the flow meter functional in all respect.
Centrifugal,Electrical Operated,Vertical, Mono Block, Motor above
& Pump Below,Dewatering Pump for Pump Room , Complete with
Electrical Panel,Level control & Cable etc. For auto operation,
Capacity -270 LPM, Head -15 Meters, The Pump shall be suitable to Kirloskar / Wilo /
Pump Dust,Dirt and Suspended solids of same nature, Complete with Lubi
Aluminium Body,SS 304 Impeller,SS Fasteners,SS 410 Shaft. The
Power supply shall be 3 Phase,415 Volt and the Cable in between
from Panel to Pump shall be vendor's scope. Refer the Secifications
& Approved makes of General Specification of Electrical Tender.
Obtaining approval on entire Fire Protection and detection system
from Local Fire Brigade authority / Insurance co. or from any other
statutory body with all respect the Statutory Approval Charges paid
30 to the Statutory authorities will be re imburshed by HAL on reciept of 1 Lot 1,00,000.00
written approval from Statutory authority and against submission of
Payment reciepts from Statutory Authorities.(Legal Fess shall be paid
Supply & Installation of 6 Kg ABC Extinguisher of stored pressure
type with mono ammonium phosphate discharge tube and pressure
31 gauge complete. Tenderer shall give 3 years guarantee on cylinder 1 Nos 3,000.00
with gas and powder. Quantity & Quality shall be as Latest Code -
15683/BIS Standard.
Supply & Installation of CO2 Fire Extinguisher of 4.5 Kg capacity
fitted with screw down type high pressure control valve with 1.0 M
long rubber braided discharge hose with horn. The Body shall be
CCE approved with IS:2878 marking and supplied with initial charge
of CO2 gas. The valve shall conform to IS:3224.Quantity & Quality
shall be as Latest Code -15683/BIS Standard.
Supply & Installation of 2 Kg ABC Extinguisher of stored pressure
type with mono ammonium phosphate discharge tube and pressure
33 gauge complete. Tenderer shall give 5 years guarantee on cylinder 1 Nos 2,100.00
with gas and powder.Quantity & Quality shall be as Latest Code -
15683/BIS Standard.
Supply & Installation of Fire Bucket 9 Liters Complete with Bucket
hanging arrangement,Canopy and Stand duly Painted with one coat
of Red Oxide and Two Coats of Synthetic Enamel Paint.Quantity &
Quality shall be as Latest Code -15683/BIS Standard.
S.I.T.C of Fire extinguisher cap. 6 Ltr. filled with Wet Chemical / K
35 Type for Kitchen, Portable Type, Applicable fire classes A & K, 1 Nos 18,000.00
Confirms to ISI Approved IS 15683:2006.
S.I.T.C of Fire extinguisher cap. 4 kg.Clean Agent type HHFC 36 FA
Confirms to AS per ISI.
S.I.T.C of Fire extinguisher cap. 5 kg.Modular type Poweder Base as
Supply, Installation, testing and Commissioning of Sprinkler Alarm
Valve with Trim and Water Motor Gong Bell, Working press
38 PSI, Hydraulic Testing Pressure 350 PSI, Body High Tensile C.I.
Seat Ring & Clapper - Bronze, Cover Bolts Steel,Clapper Disc -
EPDM & other accessories as UL Listed/FM approved Specification.
The Mechanical Gong Diameter 205 MM, UL Listed/FM Approved.
Supply Installation testing & Commissioning of Flow switch for the
maximum working temperature of 250°C with flameproof protection.
Sensing Element of SS 316. The Flow switch shall hooked up with
the Fire Alarm system the Provision is the part of Vendor's Scope.
The Flow Switch shall be UL Listed/FM Approved.
b 100NB 1 Mtrs 8,500.00
c 80NB 1 Mtrs 7,500.00
d 65NB 1 Mtrs 6,500.00
e 50NB 1 Mtrs 5,500.00
Sprinkler K-5.6, 57 Deg.C, Standard Response, Standard Coverage.
Maximum Working Pressure: 175 psi (12 bar),Thread size: 1/2” (15
mm) NPT,Sprinkler Body: Brass Casting,Body Cap: Stainless
Steel,Deflector: Copper,Deflector Pins: Stainless Steel,Compression
Screw: Brass,Fusible Link Assembly: Beryllium Nickel and Eutectic
Solder,Fusible Link Levers: Stainless Steel,Lever Bar: Copper
Alloy,Belleville Spring Sealing Assembly: Nickel Alloy, coated on
both sides with Teflon Tape and Escutcheon Plate: Brass &
Sprinkler Finish- Chrome Finished.Sprinkler Heads Shall be UL
Listed Approved
Upright Type Sprinkler Heads 1 Nos 450.00
Pendent Type Sprinkler Heads 1 Nos 450.00
Side Wall Sprinkler 1 Nos 550.00
Side Wall Extended Throw Sprinkler 1 Nos 650.00
S.I.T.C of Air release valve with Body Brass, Internal Parts & Float
HDPE complete with all accessories.
S.I.T.C of Inspector's Test Connection with Orifice and Isolation Gun
Metal Ball valves with screwed ends lever operated ASTM A
42 105,TRIM 13% Cr. 800# Including 25NB dia. pipes, fittings, Open 1 7,500.00
Sprinkler, Coupling, pressure gauge, Sight glass & Wall mounted MS
Box for better operations. Nos
S.I.T.C of Flexible Dropper Unit - Complete with Braided SS Hose,
Support Bracket, Inlet/Outlet Connectors and Square Bar - Mild
Steel, zinc plated, Nipples, Reducer and other accessories. Size - 1 X
1/2" or 3/4" with 750 / 1000mm / 1500mm length
750mm length 1 Nos 1,000.00
1000mm length 1 Nos 1,400.00
1500mm length 1 Nos 1,800.00
Providing and fixing Orifice plates, S.S. 304, 12 mm thick, bore and
construction as per TAC's Sprinklers manual / IS:15105, for all
44 horizontal tapping for hydrant system for reduction of pressure in the 1 Nos 1,850.00
range of 3.5-7.00 Kg/cm2 including one pair of Slip-on-Flange, nuts,
bolts, gasket and complete as required.
S.I.T.C of SS Metalic Expansion Bellows for Pumps with ASA #
S.I.T.C of Microprocessor based 4 loop capacity analogue
Addressable Fire Alarm Control Panel with minimum 80 characters
LCD display, 800 event plus 200 alarm log history events, QWERTY
keypad for programming. The panel should be equipped with
sufficient numbers of loops considering 20% spare capacity in each
46 1 Nos 3,00,000.00 300000.0 HoneyWell/GST
loop. Each l0oop shall have a capacity of minimum 300 analog
addressable devices. The panel shall work in degrade mode in case of
CPU failure. Four access levels, flash EPROM, 240 volts AC power
supply, automatic battery charger, 24 volts sealed lead acid batteries
sufficient for 24 hours normal working and 30 mins in alarm
condition. Designed to meet UL 864, 10th Edition.
S.I.T.C of Active Repeater Panel with 80 Characters Liquid Crystal
47 2 Nos 1,20,000.00 240000.0 HoneyWell/GST
Display with backlit control.
S.I.T.C of approved make Addressable Photoelectric Smoke Detector
with sensitivity range of 0.5 to 4.0% obs/ft. The detector shall have
group decision technology for faster response & avoid false alarms.
48 2 Nos 3,750.00 7500.0 HoneyWell/GST
The detector shall have twin bi-colour LED for 360 deg viewing.
Addressing shall be with user friendly rotary decimal switches.The
detector shall work on coperative mode to avoid false alarm.The
detector shall comply UL268, 7th Edition guidelines.
S.I.T.C of Response indicator for all detectors located above false
49 2 Nos 170.00 340.0 HoneyWell/GST
S.I.T.C of approved make Addressable Rate of Rise Heat Detector
50 rated at 8.3 deg C/min. The detector shall have twin bi-colour LED 2 Nos 3,850.00 7700.0 HoneyWell/GST
for 360 deg viewing. Addressing shall be with user friendly rotary
decimal switches. Detector shall comply UL521 guideline.
S.I.T.C of approved make Addressable Duct Smoke Detector.The
High Sensitivity Duct Smoke Detectors capable of 0.02% obs/ft
51 sensisitivity with Smoke Prove/Tubes and Addressable detectors 2 Nos 4,500.00 9000.0 HoneyWell/GST
including the cost of mounting accessories complete as per
specifications and as required. Product Shall be listed under UL
Listed to standard 268A-7th edition & FM approved
S.I.T.C of approved make Addressable Loop Powered Autoaligned
Beam Detector. The beam detector shall be used for High Ceiling
application with a detection range from 5 upto 100 mtrs and highly
resistant to building movement; tolerates +/- 1° movement, Resistant
52 1 Nos 48,500.00 48500.0 HoneyWell/GST
to solid object intrusion, , Built-in imager heater, Resistant to strong
light sources; does not alarm when saturated by sunlight, Automatic
sensitivity threshold level settings and drift compensation. The
detector shall be IP-55 compliant.
S.I.T.C of Sounder cum Strobe with Control Module rated at 80 dBA
53 @ 3m for Audible annunciation and 115cd flashintg at 1 Hz for 2 Nos 4,350.00 8700.0 HoneyWell/GST
visual indication. UL Listed
S.I.T.C of Addressable Manual Call Point (Break Glass Type). The
device shall have an LED which shall blink in normal state & get
54 2 Nos 5,500.00 11000.0 HoneyWell/GST
steady on activation to monitor the heath status of the device. The
device shall comply UL approval.
SS.I.T.C of approved make Addressable Control Module for
Sounders / Strobes / Sounder cum Strobes. The control module shall
provide supervised NAC output rated at 24v DC, 2A. The device
shall have an LED which shall blink in normal state & get steady on
55 2 Nos 4,850.00 9700.0 HoneyWell/GST
activation to monitor the heath status of the device. Addressing shall
be with user friendly rotary decimal switches. Module shall be
supplied with mounting plate from OEM for ease of installation &
S.I.T.C of approved make Addressable Monitor Module for
Sprinklers, Panic Bars & other Third Party Inputs. The monitor
module shall monitor potential free contacts. The device shall have
56 2 Nos 4,550.00 9100.0 HoneyWell/GST
an LED which shall blink in normal state & get steady on activation
to monitor the heath status of the device. Addressing shall be with
user friendly rotary decimal switches. Module shall be supplied with
mounting plate from OEM for ease of installation & maintenance.
S.I.T.C of approved make Isolator Module for Isolating short /
dewired / loose circuits with automatic resetting arrangement.
Isolator Base can also be proposed, however in that case needs to be
57 2 Nos 3,850.00 7700.0 HoneyWell/GST
considered with each detector & module. The device shall have an
LED which shall blink in normal state & get steady on activation to
monitor the heath status of the device. Module shall be supplied with
mounting plate from OEM for ease of installation & maintenance.
S.I.T.C of of 2 Core X 1.5 Sq.mm FRLS Multistrand PVC insulated Polycab/Finolex/Avo
Copper armoured cable with all required accessories. cab
Providing floor mounting stand for keeping 4 Nos. of Fire Buckets
1500 mm in length, 900 mm in height frame made out of 30x30x4
mm. angle iron with cross supports for legs, welded with 4 hooks and
59 duly painted with one coat of red lead and two coats of silver paint. 2 Nos 2,850.00
With providing round bottom Fire bucket of 9 Litres capacity (4 nos)
as per IS: 2546 made out of 24 gauge G.I. sheet with extra handle at
bottom duly painted white inside and red outside with Fire mark, on
provided stand .
S.I.T.C of Emergency evacuation Exit sinages self illuminating with
60 battery back up of 2 hrs, along with all required accessories such as 2 Nos 3,850.00
driver, Junction box etc required to complete the job.
61 Agni 4 Nos 650.00 2600.0 Agni
S.I.T.C of 2 Zone Microprocessor Based Main Alarm Panel With
62 Power Supply & Built In LCD Display, Real Time Clock & Event 2 Nos 7,500.00 15000.0 Agni
63 S.I.T.C of Conventional Electronic Hooter with strobe 2 Nos 950.00 1900.0 Agni
64 S.I.T.C of Conventional Manual Call Point 2 Nos 650.00 1300.0 Agni
S.I.T.C of 2 core x 1 sq. mm flexible wire with pvc conduit & Polycab/Finolex/Avo
accessories for alarm system cab
S.I.T.C of 3 core x 1 sq. mm flexible wire with pvc conduit & Polycab/Finolex/Avo
accessories for on off switch from pump house to each floor cab
S.I.T.C of Conventional Smoke detectors Sensor
S.I.T.C of of Conventional Heat detectors Sensor
69 S.I.T.C of of Fire retadent Paint 2 Hour Rating 2 Lit. 950.00
S.I.T.C of Fire Rated door 2 Hours Rating size as per Requirement.
71 S.I.T.C of Fire Men Axe. As per the Requirement. 2 Nos. 1,650.00
Supply & Fixing of Auto glow Signage's (ACP SHEET / HEAVY
Fire Equipment 4" X 12" 2 Nos. 350.00
Fire Extinguisher 8" X 4" 2 Nos. 350.00
Incase of fire do not use lift, use, Use staircase 8’’ X 8’’ 2 Nos. 500.00
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
Notice Inviting Online tender.pdf
Vol_1 Part_A Tender Document.pdf
Technical Specifications for Fire Alarm _12.01.26.pdf
Technical Specification for Fire Protection System_12.01.26.pdf
BOQ__Fire_Protection_Work_261.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .