R G DESAI
Work of erection of 66KV equipment, structures, control wiring, yard Lighting, Control-Room & Staff-Quarter Electrification etc at 66 KV Hathrol Sub Sation with Mesh earthing and furniture & 66 KV Hathrol LILO line from existing 66 kV Rupal-Punsari line.
322102
2026-27 / HTC / 27
Open
Electrical and Maintenance Works
Works
Sabarkantha
16 documents required · 16 mandatory
₹1,180
GETCO,Himatnagar
8 Jul 2026
8 Jul 2026
8 Jul 2026
30 Jul 2026
8 Jul 2026
Erection of 66KV Breaker (Any type / Make)
including supporting structure & fixing all its
accessories, fittings, connections etc.
complete as per owner's/supplier's manual
and instruction of E.I.C. including individual &
1 interpole wiring of operating box and that 4 5535
with M.K.Box. with assisting to the erection
engineer Erection without crane is permitted.
Rates are inclusive of
dragging/loading/unloading of same from site
store to erection site.
Erection of 66KV CT/PT (all type make) on its
erected structure including complete
2 dragging/ loading/ unloading of same from site Phase 18 623
store to erection site and fixing of required
clamps, connectors as per instructions of E.I.C.
Erection of 66KV LA (All type/make) on its
erected structure including complete
dragging/loading/ unloading of the same from
3 site store to erection site and fixing of required Phase 12 415
clamps, connectors, corona rings, surge
counter and other accessories etc. as per inst.
Erection of 66KV Centre Break Isolator (All
make) with earth blade on its erected
structure consisting of 3 base channels with
porcelain/solid core insulator including
interconnected piping with operating Set of
mechanism and accessories with final pole
adjustment for simultaneous operating &
closing. The rates are inclusive of dragging /
loading / unloading of the same from site store
to erection site as per instruction of E.I.C.
- - DO - - as above but without earth blade Set of
complete. pole
Erection of 66KV Poly cone/Solid Core/Bus
Post Insulator on its erected structure
including minor required fabrication &
complete fixing of accessories and shifting of
same including loading/ unloading from its site
store to erection site.
Laying of any size of 11KV XLPE cable including
excavation of trench 300mm wide & 600mm
deep including laying and filling up sand of
100mm layer from bottom & bricks on three
side of cable & refilling the trench with
7 Murram/soil & ramming etc. Required bricks, Mtr 150 138
sand, etc. will have to be supplied by the
contractor. Rates are inclusive of shifting of
cable drum to the site from S/S site store.
Drum should be handled only by jacking to
avoid damage to cables.
Laying of any size of 11KV XLPE cable in ready
made cable trench or in open space. Rates are
8 inclusive of shifting of cable drum to the site Mtr 600 63
from S/S site store. Drum should be handled
only by jacking to avoid damage to cables.
Erection of Structure for Equipment/Lighting
Mast/ VHF Mast including punching of nut
bolts. Rates are inclusive of minor required
fabrication and shifting of same up to erection
site from its s/s Store. including Stub Setting as
per instruction of EIC..
Erection of 66/11KV, class Power
Transformer with complete mounting of all
the accessories i.e. bushings, radiators,
conservator tank etc. including laying of cable
between all accessories/mounted on the
transformer/ marshalling KIOSK, painting of
10 rail and neutral supporting channels, filling
and filtration of oil with filter machine as per
direction of E.I.C. manufacturer Engineer or
as per instruction manual. Filter machine
shall be arranged by the contractor.
(a)15 MVA No 2 24905
(b)20 MVA No 0 31754.00
Stringing of Single ACSR Zebra Bus complete in
all respect with fixing of all fitting, insulators Rmtr Per
and all accessories as per the instruction of phase
Preparing and fixing of required length of
Jumpers of Single ACSR Panther/ Dog type
conductor in the switchyard on respective Bus Rmtr Per
& equipments, tensioning, Compressing & phase
dressing of jumpers complete as per
instruction of E.I.C.
Installation of Earthing Strips / MS Round Bar
as shown below including digging of 600 mm
Deep and 450 mm Wide Trench in any kind of
soil expects Rocky(HR/SR) / Fixing on
Structures as per attached drawing including
fixing arrangement with Two Bolt
13 Arrangement , Jointing with Nut Bolts and Lap
Welding and applying Zinc Rich Paint on
welded joints including supply of GI Nut &
Bolts as per specification and approved Earth
Mat Lay Put.
(a)75X10 mm GI Strip Mtr 0 52
(b)50 X 6 mm GI Strip Mtr 3500 43
Installation of Earthing Strips / MS Round Bar
as shown below including digging of 600 mm
Deep and 450 mm Wide Trench in Rocky soil
(HR/SR) / Fixing on Structures as per attached
drawing including fixing arrangement with
Two Bolt Arrangement , Jointing with Nut
14 Bolts and Lap Welding and applying Zinc Rich
Paint on welded joints including supply of GI
Nut & Bolts as per specification and approved
Earth Mat Lay Put.
(a)75X10 mm GI Strip Mtr 0 174
(b)50 X 6 mm GI Strip Mtr 0 164
Excavation in Hard Rock for excavation of
earthing pits/trenches Yard lighting poles, etc.
Providing & fixing, Testing and
Commissioning of Maintenance Free Treated
Earth Electrodes suitable for Normal soil as per
drawing no GETCO /E/P-021(1 OF 2) R2 DT
04.06.2015 and technical specification
GETCO/E/TS-maintenance free earth pits/R1
dated 04.06.2015 for 66/11 kv substation with
ground enhancement material/back
fill/grounding compound as per IEEE 80-2000
CLAUS 14.5(d) and as per part 7 of IEC
using copper bounded earth electrode(with
250 micron copper coating)having 24 mm
(mim) and 3000 mm length which shall be
capable of handling STC of 25 KA-1 sec work
also include Providing BB masonry inspection
chamber(man hole) incl. light type CI cover
Supply ,Installation Testing and
Commissioning of Maintenances Free Treated
Earth Electrodes suitable for Rocky Soil as per
drawing no GETCO /E/P-021(2 OF 2) R2 DT
04.06.2015 and technical specification
GETCO/E/TS-maintenance free earth pits/R1
dated 04.06.2015 for 66/11 kv substation with
ground enhancement material/back
fill/grounding compound as per IEEE 80-2000
CLAUS 14.5(d) and as per part 7 of IEC
using copper bounded earth electrode(with
micron copper coating)having 24 mm (mim) and
3000 mm length which shall be capable of
handling STC of 25 KA-1 sec work also include
Providing BB masonry inspection chamber(man
hole) incl. light type CI cover
Installation of 20/32/40 mm dia., 3 mtr. Long
18 vertical spike for mesh type earthing in Normal No 0 871
Installation of 20/32/40 mm dia. 3 mtr long
vertical spike for mesh type earthing
Erection of 66KV Control Panel, Relay panel or
C/R Panel or RTCC Panel including grouting of
panel, jointing with adjoining panels with
providing required B/N including required
fabrication for joining panels & entry of control
cables and complete vermin proofing.
Erection of 11 kV CB Panel of any make
including grouting, jointing with adjoining
panel and Horizontal , Vertical levelling
including required fabrication for entry of
Power Cable, Control Cable and complete
vermin proofing, job includes required bolts /
nuts etc and shifting of panel from SS Site store
to work site.
-DO- but Erection of LT panel Board & Battery
Charger (01 each) of any make as per
manufacturers instruction manual including
grouting, vermin proofing etc.
Erection of 250 / 100AH, 110 Volt D.C. Battery
Set on wooden/FRP stand as per instruction
manual of supplier, including first filling of
battery electrolyte, proper connection of cells
and applying, charging/discharging cycles as
per manufacturer's instruction manual and
instruction of EIC. applying charging/ dis
charging cycles as per manufacture/
instruction of engineer in charges ( 100 AH,
110 volt DC)
Erection of station transformer of 22KV or
11KV/430V, 63/100KVA on its plinth/DP
Structure ,grouting of foundation bolts, fixing
of channels.., D.O. fuse by fabricating str.& its
painting, danger board etc. including
connection with power cable/LV cable
terminations including shifting of all types of
materials and equipments as per EIC.
Minor Fabrication for erection of any
Equipment /Structure /Panel or anywhere in
25 L.S. (Max) 2 4992
sub stations as well as at opposite end
substation also Inst. Of E.I.C.
Erection of support structure for 11kv Power
cable termination at 11kv bushing for 15/20
MVA power transformer as per DRG No
GETCO/E/06S-STD/11KVSTR-A2-02. Job also
include minor fabrication if required as per
instruction of E.I.C.
Erection of supporting structure for Station
transformer as per drawing no : GETCO/E/06S-
STD/11KV STR A3-03. Job also include erection
27 of required 11kV LA and D.O fuse and minor No 1 998
fabrication if required as per instruction of
E.I.C.11kV LA and D.O Fuse will be provided by
GETCO free of cost.
Providing & fixing of Set of following Items on
11KV support structure for termination of
power cable to LV Bushings of Power
Transformer as per Drawing and instruction of
EIC. 1) 03 Nos. of
Alluminium Alloy Bus Bar of size 75X20 X
2) 11KV Post Insulator of PCD 127 mm - 12 No
3) 03 Nos. Copper laminated fusion welded
flexible jumper of size 75 X 10 X 600 mm having
2000 Amp capacity. Job also includes fixing of
03 Power cables& 03 Flexible Jumpers to Bus
with fabrication and providing Good Quality
Stainless Stell Nut Bolt of appropriate Size.
Erection of 11KV D.P. Structure (Girder/PSC
Pole) including required fabrication in Top
Channel, Cross Bracing, Level Piece etc with
providing required b/n. Works also includes
painting with one coat of Red Oxide, Two coat
of approved make alluminium paint. job also
includes erection of 11KV LAs. All the items will
be provided by GETCO free of cost.
Erection of 11KV D.P. Structure (Includes fixing
of 11KV A.B switches, 11kv pin insulators , and
jumpering 11kv cable to A.B switch & A.B
switch to 11kv Bus between D.P structure &
Cross Boundry). job also includes erection of
11KV LA and minor fabrication for fixing of
above items. All the items will be provided by
GETCO free of cost.
Providing of M15 Grade Concrete for various
equipment structure, Guy, 11kv DP, M.K. Box,
Neutral channels, cable support channel,
grouting of Pole/ Flood light structure with
cement, sand & metal in proportion of 1:2:4
respectively. The rates are inclusive of supply
of sand, metal, water & cement ,Muffing and
with smooth cement mortar (1:6) finish.
Loading, Transporting & Unloading of all SS
material like SS Structure, indoor & out door
32 SS Equipments, DP Structure, earthing Job 1 51720
materials etc.for SS & opposite end feeder bay
-Store to SS Site
Supply & laying of 1 Core X 25mm2,
Armroured Copper Cable/multi-strand
flexible of approved make ISI marked in ready
made trench or PVC pipe from Battery Charger
to Battery Set including termination at both
side as per inst. of EIC.
Providing and fixing of various type of sign
Board, sticker, Big Sign Board, earthing pit
board, earthing pit Board & Single line diagram
etc as per instruction of IEC. Sticker of red,
white, black Letters are to be utilised for
various sign board.
Earthing Pit Board Size:- 6" x 6" -30 Nos.
Safety Slogan Board, Hard Sheet board size 2'
x 2'and 4mm thick (Gujarati Language)- 2 Nos.
34 Safety Slogan Board, Hard Sheet board size 3' Job 1 24957.00
x 2'and 4mm thick (Gujarati Language) with
red and Yellow colour.-03 Nos.
Single line diagram size 5' x 3' Digital with
Alluminium frame with fitting and as per
approved diagram given by IEC.-01 No.
Big sign board size 5' x 4' and 2mm thickness
indicating sub station name digital with S.S.
rod with hole & as per approved symbol with
fitting charge.- 01 No.
Switch yard sign Board 12" X 6" with 2 mm
Thickness black & white Gujarati language.25
Safety Slogan Board size 2" x 6" in side control
room.-05 Nos.
Various type of control room equipment
sticker size-24 cms x 5cms.--18 Nos.
Safety picture board size :- 3' x 3' (Laminated
for O/D use)-03 Nos.
Name plate board of transformer size :- 2' x 1'-
Cable marker size:- 6" x 6", Radium, fixed on
750mm long M.S.Rod for fixing arrengement.-
P & F radium stiker for outdoor & indoor
equipment identification like LA ,Isolater, Circuit
35 Sq. inch 500 2
breaker ,Transformer, CT, PT, MK Box , CR panel
,11 kv Panel etc..
Providing and Fixing of fire stand from 75mm
Gl pipe B Class ISI mark heavy duty having 5ft
width and 4ft height as per inst of Engr. In
charge work includes cutting,drilling, welding
of pipe as required. Fabrication and supply of
16mm dia meter hook required size for
buckets. 4 Nos.of fire buckets are to be
provided fire stand should grouted with
excavation of pit size 300mm x 300mm-2 Nos.
of 600mm depth with 1:3:6 mix muffing
300mm in height including leveling of stand.
The fire stand is to be painted with post box
red colour of approval quality as per
instruction of EIC. All required approved
material including cement, sand, metal etc are
to be provided by contractor.
Providing, Fabrication and erection of VHF SET
Anteena support pipe on control room by
providing 25mm dia. B Class GI pipe of length
37 20 feet.including providing & fixing of 4 nos. of Job 1 1496
guy from GI wire 10 SWG. This job includes
painting of GI pipe by good quality paint white
and red alternatively
Labour charge for fixing of 11KV XLPE Indoor
38 / outdoor cable kit of any make for size 95 to No 24 748
300mm2. Cable kit provided by GETCO.
Providing & Fixing of
RAYCEM/MSEAL/CABSEAL make heat
shrinkable type 11KV XLPE Outdoor cable
Termination kit suitable for 11KV, 3C x
39 sqmm to 300 sq.mm XLPE power cable by No 6 6139
using Long Barrel Alluminium Lugs of
adequate capacity of Reputed Brand like
Jainson, Hex etc. Job also includes providing
of Bimatallic Square washer of proper size.
Providing & Fixing of Total Revival Type
Water R.O. Plant including Commissioning &
Testing and also with required peripherals for
installation of plant as per site condition
(1) Dimension: 320 X 275 X 410 mm
(2) Weight : 8 KG
(3) Water flow : 8 to 12 LPH (4) Input
power : 230V AC
(5) RO membrence : TFC spiral
RO Plant shall have guarantee for the
Providing and fixing of ISI marked Insulating
Mattysheet Suitable for 11KV Class As per
following specification. Reference IS:15652-
2006 with latest amendment. Suitable for
Voltage Class :B
Max Use Voltage : 11KV
AC proof voltage : 22KV
Dielectric strength : 45KV
Leakage current : < 10 micro ampere
41 Colur RED/BLUE sq.mtr 17 4492
Make : Vardhman or equivalent (
Rubberhouse India) Width :1 mtr.
Thickness :2.5 mm.
Surface :Chequred on one side and other side
plain. NOTE: Contractor has to supply Rubber
Matty strictly as per IS:15652-2006 with latest
amendment specification and shall submit
test certificate for routine test as per relevant
Providing & fixing of reputed make ISI marked
(with latest amendment) 9 KG Capacity Dry
42 Chemical Powder Type Fire Extinguisher. No 2 6301
Note: Contractor shall submit Test certificate
for routine test as per relevant IS.
43 - Do - but CO2 Type : 6.5 Kg No 2 7047
44 - Do - but CO2 Type : 22.5 Kg No 2 17817
- Do - but Mechanical Foam Type : 50 LTRs
TOTAL: SCHEDULE B - 1 Amount
SCHEDULE B - 2 : CONTROL WIRING
Description of work/Supply Unit S/S Qty Rate Amount
Preparing of complete schedule of wiring for
line/ transformer bay for 66KV bays in
46 triplicate. necessary drawing will be provided Bay 4 1996
by the GETCO. Schedule should be approved
by EE. or DE in charge.
Laying of Control Cable Up to 7 Core, 1.1KV
PVC, armored copper/ aluminum control
cable in readymade cable trench and inside
Hume pipe including binding / clamping of
47 cable with GI wire or saddles as per the Mtr 2000 6
requirement including the supply and fixing of
identification tags at both ends in between if
required to following size (Cable will be
supplied by GETCO at free of cost)
48 As above but for, Above 7 Core Control Cable Mtr 2000 10
Laying of Control Cable Up to 7 Core, 1.1 KV
PVC armored copper /aluminum cable in
ground by digging trench of suitable width and
450 mm depth in any type of soil including
supply and fixing of identification tag on both
end and at distance every 100 mtrs for
50 As above but for, Above 7 Core Control Cable Mtr 150 26
Providing and fixing 'B' class G.I. pipes of
following size for cable protection including
fixing with the structures.( Non SOR) including
required 'L' & 'T' band, coupling for CT,PT,
51 Transformer, M.K.Box cabling on structure
including required fabrication.(weight of pipe-
25kg/meter)
{a} 40mm dia Mtr 150 255
{b} 50mm dia Mtr 80 284
Termination of Control Cable at Panel / M.K./
Equipments including supply of required size
52 of brass cable glands, lugs, ferrules, PVC End 150 199
Binding Tape, Buttons etc. Up to 7 Core
Control Cable.
53 As above but Above 7 Core Control Cable., End 100 349
Providing & Installation and Commissioning of
Remote Control switch Board for ON/OFF
control of all 11kv Panel from operator's table
with supply of good quality metal sheet box (
18 SWG )size 450 x 450 x 125 mm with door,
20 nos standard ISI make and rating industrial
push botton,indication lamp(LED)with
54 installing accept/reset arrangement with Job 1 6489
required ISI marked copper flexible wire size
2.5 Sq. mm including complete wiring in PVC
pipe and fixing on wall or on floor as per inst.
of EIC.only 19/27 core x 2.5 sqmm cable supply
by GETCO.Job includes Supply of required nos.
of Disconnecting Type Terminal for wiring at
11 kV Panel Board end
Providing and fixing of all weather proof, cold
rolled sheet steel Junction Box for CVT & PT, CT
terminations with 30 Nos. of disconnecting
55 type, 'Elmex' make CATDM 4 or equivalent No 6 21549
type connectors and required no of fuses, links
etc.as per instruction of Engineer-in-charge
and as per drawing enclosed here with
TOTAL - 2 ( SCHEDULE B - 2 )
SCHEDULE B - 3 : YARD LIGHTING Amount
Description of work/Supply Unit S/S Qty Rate
Providing & fixing of all weather proof, cold
rolled sheet steel AC Panel - 2 for Yard-
Lighting, AC supply having (1) 63 A ,4P
MCB : 01 NO (2) MCX-12A Contactor :
01 NO (3) Digital timer : 01 NO (4) 20 A,TPN
MCB : 06 NOs (5) Indication Lamps,
NOS ( R , Y , B ) (6) Push Buttons : 02 Each
( Red & Green) (7)Terminal Connectorsas per
site requirement and other detail as per drg.
enclosed including grouting & necessary
fabrication of GI Angle or fixing on GI Structure
and earthing with main grid as per instruction
of EIC as per drawing enclosed.(1 to be utilised
for YArd lighting & 1 to be utilised as
LTDB(Main LT Distribution Board for StationX-
mer as per instru. & Modification of EIC))
Providing & fixing of all weather proof, cold
rolled steel sheet floor mounted fixed type
single door grey color Main AC Dist box having
size 900x600x250 MM with door closing
arrangement and necessary rubber gasket.
Contractor has to supply following materials
with box along with necessary mounting and
(1) L&T/Anchor/Havells Make 100A,4P MCCB -
(2) L&T/Anchor/Havells Make 63A,4P MCB -
(3) 100 A Copper Bus-Bar Link - length 6 inch
size & 25 x 3 MM - 4 Nos.
(4) Tinned Earth Bus 25 x 3 MM Length -
Inch - 1No.
(5) 25 & 16 sqmm Cu. flexible cable - 4 &
Meter respectively.
(6) Required Nos. of Cu. Lugs , etc. as per
instruction of EIC.
Supplying & laying of 3.5 Core x 50 mm2
Alluminium Armoured Control/L.T power
cable from distribution X'mer to Main
Distribution Board near dist. X'mer and from
MDB to indoor LT panel board (LTPB) - both
Runs. in readymade cable trench or by
excavating in any type of soil cable trench size
1 ft. wide 2.5 ft. depth and refilling the same
as per the direction of EIC. Item Includes the
cable laying upto termination box with clamps
& proper clamping of cable on gantries by GI
pipe & glands as per direction. Item includes
providing & supply of bircks, sand as per
requirement. The L.T power cable to be
provided by contractor shall be as per ISI
(Part-I).
Supplying & laying of 4 Core x 25 mm2
Aluminum Armored Cable from LT panel
board (LTPB) to Yard Light AC MK (AC Panel-
2)., AC Panel 1 in C.R. and yard AC Box
Control/L.T power cable of FINOLEX or
equivalent ISI make in readymade cable trench
or by excavating in any type of soil cable trench
size 300mm wide and 600mm depth and
58 refilling the same as per the direction of EIC. Mtr 150 175
Item Includes the cable laying up to
termination box with clamps & proper
clamping of cable on gantries by GI pipe &
glands as per direction. Item includes
providing & fixing of bricks, sand as per
requirement to protect cables .The L.T power
cable to be provided by contractor as under
:As per ISI 1554 (Part-I).
Laying of 4C x 4mm2 Copper cable - Armoured,
from yard-light AC panel-2 to all yard-light
fixture junction boxes on LM & street light
pole & Station transformer to Colony & LT
panel to watchman cabin.(Only laying. Cable
will be supplied by GETCO)
Laying of 4C x 2.5mm2 Copper cable -
Armoured, from yard-light AC panel-2 to all
junction boxes on post top lantern (Only
laying. Cable will be supplied by GETCO)
Providing & fixing of 'B' class ISI marked GI.
Pipe of 32/40mm dia for cable looping & road
crossing with necessary elbow/band for each
61 pole & J.Box for yard lighting & for Mtr 60 180
controlroom flud lights wiring work with fixing
on wall with shadles if required as per inst. Of
Providing & erection of 7.0 Mtr. long swaged
type welded GI tubular street light pole on the
foundation in any type of soil as per inst. of
E.I.C. confirming to relevent IS and as per
atached Drawing No. GETCO/E/STD/LTG.POLE
Providing & erection of 4.5 Mtr. long swaged
type welded GI tubular post top lantern pole
on the foundation in any type of soil as per
inst. of E.I.C. confirming to relevent IS and as
per atached Drawing No.
GETCO/E/STD/LTG.POLE -R2, DT-24-12-2019
Supply and fixing of Pole/Wall/Structure
mounted FRP junction box standard make of
required size with clamp, providing 1 SPN MCB
G class of 16 A having short ckt breaking
capacity of 10KA peak of standard ISI make like
L&T/ANCHOR/MDS /HAVELLS & 2 Nos. of stud
type connector of standard make like
Connectwell. The cable glands & lugs are
ncluded for both incoming & out going cables.
MCBs shall be of standard make like
MDS/HAVELLS & 2 Nos. of stud type connector
of standard make like Connectwell. The cable
glands & lugs are also included for both
incoming & out going cables.
Earthing to tubular pole/luminaries,by coil
type earthing of 10 SWG GI wire in earth pit of
1.5 mtr. Depth in any type of solil by using salt/
coke (charcole) 16 kgs each & remaining filling
with BC soil & clamping the earth wire with
pole & Junction box.
Providing and fixing of Single Piece Cast
Alluminium full frame with Acrylic Cover
integrated Energy Efficient flood light
luminaries on swaged pole / GI structure by
providing required fabrications, of
66 Philips/CGL/Bajaj/GE/Osram make, suitable No 13 7487
for 1 x 250 Watt HPSV/T with allied accessories
such as Capacitor Ignitor, Ballast, Control Gear
Box etc, 4 core 2.5 sq mm double insulated
flexible stranded wire should be used from
control gear fitting to junction box.
Providing & Fixing of LED Street Light Fixtures
(1X120W) (CGL Cat No. LSTO120/CDL 120W or
equivalent under Cat-II or above as per R&B
67 SOR), 4-core 2.5mm2 double insulated flexible No 8 9593
strended wire should be used from control
gear fittings to approved SMC type junction
box as per inst. of E.I.C.
Providing & fixing of 1x40W LED Post Top
Lantern fixtures (CGL Cat No. LPTO-40/CDL
40W or equivalent under Cat-II or above as per
R&B SOR) complete fitting in all respect and
68 core x 2.5 mm2 double insulated PVC flexible No 7 7556
copper cable from control gear fitting to SMC
junction box as per instruction of E.I.C. ( 4 No.
are to be provided on Main gate & 3 No. are to
be provided on 4.5Mtr Tubular pole)
TOTAL - 3 ( SCHEDULE B - 3 )
SCHEDULE B - 4 : CONTROL ROOM INDUSTRIAL ELECTRIFICATION
Description of work/Supply Unit S/S Qty Rate Amount
Providing and fixing of DBS as AC Panel - 1 for
CR of ISI marked Powder coated Pearl DBS of
ivory color , wall mounting, Double door
Distribution board of L&T, Heggar or higher
make fitted with 63Amp Phase Bus bar, Earth
/ Neutral Bars and inter connecting wires
with removable bottom gland plates for all
power cable entry from bottom with DIN
Channel ,incoming contact and 1No - 63Amp
TPN MCB 'C' Series ,6Nos-20A SP MCB 'C'
Series and 13No -10A SP MCB 'C' Series All
MCBs are L&T, Anchor or Higher make only.
Complete in all respect and as per instruction
Supplying & laying of following size
Control/L.T power cable of FINOLEX or
equivalent ISI make in readymade cable
trench or by excavating in any type of soil
cable trench size 300mm wide and 600mm
depth and refilling the same as per the
direction of EIC. Item Includes the cable laying
up to termination box with clamps & proper
clamping of cable on gantries by GI pipe &
glands as per direction. Item includes
providing & fixing of bricks, sand as per
requirement to protect cables . The L.T power
cable to be provided by contractor as under
:As per ISI 1554 (Part-I). 4 Core x 25 mm2
Aluminum cable -Armored, from LT panel
board (LTPB) to AC Panel-1 in Control Room.
Supplying & Laying Sub-main lines of 3X2.5
mm2 ( two for P & N and one for
Earthing)copper PVC insulated wier of ISI
brand in suitable standard make steel conduit
71 pipe having minimum 1.5 mm thickness of Rmtr 150 125
approved brand with ISI brand with clmpes
with it's associated accessories for various
circuits amanating from AC panel 1.as per
inst. of E.I.C.
Point wiring for control room tube lights,
fans, exhaust fans, fency lights, water tight
bulck head lights with PVC insulated 660 V
grade standard copper wire in ISI make GI
conduct pipe 20 mm dia and 1.6 mm wall
thickness size fitted with sadles on the
wall/ceiling. Size of wire shall be with 3C x
sq.mm PVC insulated copper wire for phase
and neutral and earth wire [ Green] and
Amp Anchor Roma or any equivalent switch
72 as per specification with 16 guage M.S. box. Point 60 1298
The box shall be covered with 3 mm thick
decorative mat finish hylum sheet. The work
is all inclusive of supply and fixing of required
materials as afore said [ like M.S.conduct
pipe , sadles , swithces , M.S. box , ceiling
Rose , flexible copper wire etc] to complete
point wiring with each fixture to be earthed
by SWG-12 stranded copper conductor having
green color as per direction and instructions
Providing, fixing & termination for emergency
D.C. supply arrangement. This job includes
supply & laying of 2C x 2.5 mm2 Copper
arrmoured cable from battery charges to
SBDC, fixing & providing SBDC & complete
wiring with supply of wire & D.C. lamp (110V
D.C., 100 watt-4 Nos.) in standard steel
conduit pipe as per drawing No:
GETCO/EE/6S-standard/S-015 as per inst. of
Providing and Fixing point wiring in GI.
Conduit pipe size 20 mm dia and 1.6 mm wall
thickness with single PVC insulated 2.5 Sqmm.
copper wire of ISI standard good quality using
1.5mm thick suitable size ISI mark ( 2+3 pin in
socket ) Anchor brand 15 Amp. 250 Volt plug
74 socket as separate plug point with shock Point 8 1213
proof accessories incl. indication lamp ;
erected on separate decorative mat finish
hylum sheet board on wall with providing
adequate green earthing wire as per
specification and instruction ofEngineer
---- Do ---- as above but with singal PVC
insulated 3Cx1.5 sq. mm.copper wire of ISI
75 mark plug socket for 5A domestic use Point 8 814
separate plug points per direction and
instruction of E.I.C.
---- Do ---- as above but looped on same board
i.e. no separate board, plug socket for 5A
76 Point 11 199
domestic use as per direction and instruction
Providing & Fixing of Ceiling Fan (CBLD) of
1400mm sweep Bajaj/Crompton / Orient/
usha / Cinni make (ISI approved). Fan is to be
purchased from authorised dealer. Flexible
wiring using twin core double PVC 48/0.2 mm
77 copper flexible cord of suitable & approved No 8 3000
make and size from ceiling rose upto fan
terminal & supply and fixing of energy saver
regulators, extra GI pipe of required size and
length for lowering of fan if required as per
instruction of EIC.
Providing and fixing of 41.5W LED Lighting
Fixture (CGL Cat No. LPFC-36-CDL 41.5W or
equivalent under Cat-II or above as per R&B
SOR) as per instruction of EIC.
Providing and fixing of 40W (1X4) LED Lighting
fixtures as per drawing (in office area & Porch
79 Area) (CGL Cat No. LCTLSN-40-CDL (1X4) 40W No 10 3417
or equivalent under Cat-II or above as per R&B
SOR) as per instruction of EIC.
Providing & fixing of 30W LED Street Light
Bulkhead (CGL Cat No. LSTO-30-CDL 30W or
equivalent under Cat-II or above as per R&B
SOR) on out side C/R building and inside cable
trench in C/R including wiring from ceiling rose
to fixture with suitable size of PVC insulated ISI
marked copper wire only as per Instruction of
Providing and fixing of approved make 40w
LED lighting fixtures as per drawing (in porch
81 area) (CGL cat no LCTLSN-40-CDL- (1X4) 40W No 2 3417
or equivalent under cat- II or above as per R &
B SOR as per instruction of Engineer in charge
Providing & fixing of industrial 30W LED street
light bulkhead (CGL Cat No LSTO - 30CDL-30W
or Equivalent under Cat - II or above as per R &
82 B SOR) including wiring from ceiling rose to No 12 2678
fixture with suitable size of PVC insulated ISI
marked copper wire only as per Instruction of
Providing and fixing of heavy duty exhaust fan
in battery room size 18" of Make
83 GEC/KHAITAN/ CROMPTON/ BAJAJ incl. M.S. No 1 3494
lourex shutter of Fan & necessary wall finishing
works and applying bird proof net on
Installation of C. I. Plate ( 10 KG) type
earthing for Control Room Installations with
laying of 10SWG Copper wire to be laid inside
2Mtr. Long heavy duty 19mm PVC pipe .This
84 work include preparation of earth pit of size No 3 499
0.5M x 1.5M depth and back filling by using
Solt, Charcoal 16 Kg. Each, and black cotton
soil with as per Inst. of EIC. Required all
material shall be supplied by contractor.
Same as item No.1 but with Fixing of Electric
bell with bell switch near officer's table. All
materials must be ISI mark and approved by
Engineer I/C
Providing and fixing of18W LED Lighting
fixture(CGL Cat No LCTL - CDL 18W or
86 Equivalent under Cat - II or above as per R & B No 3 1281
SOR) of any standard ISI make and as per
instruction of EIC
TOTAL - 4 ( SCHEDULE B - 4 )
SCHEDULE B - 5 : QUARTER RESIDENTIAL Furniture
Description of work/Supply Unit S/S Qty Rate Amount
P & F Steel chair 'S' type, Over hanging arm
99 with cushion with cane seat/back 1" X 16" No 2 8750
gauge round pipe frame.
P & F Steel rack of size 30" X 36" X 15" with
three partition, prepared with 20 gauges
P & F Steel table of size 54"X30"X30", one side
101 three drawars, one side shelf 1 X 18 gauge No 1 4600
square pipe with Nova pan pre lamination top
P & F Computer table made from pre
lamination Board size with Key Board facility
102 and drawer with continues printer out facility No 1 7200
and mouse tray and also with special tray CPU
and UPS having I.D. 4 X 21 inch C 2.5 F.T.
P & F Steel revolving chair, revolving & titing,
low back high type seat with foam rubber 3" in
seat 2" in back with good quality raxine cover,
five legs, Chromium plated frame
P & F Steel cup board of size 78"X36"X19" four
partition, door and shelves 20 gauge, body
gauge, color olive green as per drawing
TOTAL - 5 ( SCHEDULE B - 5 )
Description of work/Supply Unit S/S Qty Rate Amount
1 Check Survey. 0.50 Km 9277.00
Excavation excluding back filling, but including
shoring, shuttering, dewatering, free cutting
2 for tower footings etc.for :-
a) Normal soil either dry or wet / Sandy soil 17.72 Cu.m 307.00
b) Black cotton soil either dry or wet 105.13 Cu.m 614.00
Installation of steel reinforcement in concrete
foundation including supply of M.S. bars,
binding wire & their cutting, bending, binding
and laying in position as per drawing.
Stub-setting upto including back-filling but
excluding excavation and concreting etc. for all
types of towers / extensions except special
towers. (Weight of stub, cleat & template with
4 Bolt & Nuts of stub & template shall be
a) up to 6 Mtr.Extn. 1.76 MT 8206.00
b) up to 9 to 21 mtr 0.00 Mt 9918.00
Concreting of foundation by M20/M15/M25
mixure including shoring, shuttering,
dewatering etc. for normal tower / tower with
extension upto 21 mtr. (Rates are with
5 cement)
a)M15 (1:2:4) Mixture 0.00 Cu.m 10306.00
b)M20( 1:1.5:3) Mixture 15.00 Cu.m 12246.00
Grounding of towers with pipe type earthing
including excavation and back filling and
6 supply of all material like 32mm dia heavy duty 2.00 Set. 8985.00
3 mtr. Long G.I. Pipe & 50 X 6 mm G.I.flat, bolt-
nuts, salt, coal / charcoal etc. as per drawing.
Erection of super structure upto 6 meter
extention including free cutting, fixing of
tower accessories, attachments except ACD /
DP / NP / CIP / PP and excluding tack welding
of bolts. This includes tacking delivery of tower 11.00 MT 10076.00
7 materials and bolt-nuts from Board's stores
etc. for normal, extension & special towers at
destination and keeping them in safe custody
and transporting the same to erection site.
Same as above but erection of 9/12/15/21 mtr
extension portion only
Fixing of ACD (Anti climbing device ) including
supply of bared wire. (except special tower)
a) 66 Kv 2.00 Loc. 2596.00
Providing & fixing of DP / NP / PP / CIP
including supply of plates and supply of
G.I.bolts & nuts and tack welding as per
Tack welding of nuts upto approx. 10 mtrs.
Height OR two bottom-most panel from
10 ground level at three places on nuts 1200.00 15.00
diametrically and applying zinc rich paint
immediately after tack welding.
Stringing of ONE ground wire inculding Laying
Jointing tentioning, Clamping with
11 Accessories, Jimpering & sister wire, Vibrating 0.00 RouteKm. 16843.00
damper earth bond etc & inculding tree
Stringing of ACSR / AAAC 6 (SIX) conductor for
Single circuit including laying, jointing,
tensioning, clamping with armour rods,
hoisting of insulator string, fixing of jumpers,
12 dampers etc.&with required tree cutting on
entire length for edequate clearances / safe
charging line.
b) For Panther 0.50 112928.00
Painting of Name of line, location
number,colour code & telephone number on
Tower for information of concerned
substation including supply of paints etc…
Erection of stay set complete with stay clamp,
14 turn buckle, eye bolt, anchor rod & binding 12.00 Set 802.00
with 7/8 or 7/10 SWG earth wire.
providing concrete for "H" Frame structure
with M15(1:2:4 ) mix. Including stay sets with
supply of materials like cement of 43 grade,
sand, metal etc. with muffing (400mm
Dia.x300mm Ht.) above ground level for all the
structures.
Conversion of 'A' type 'H' frame structure into
'B' type 'H' frame structure in existing line by
replaceing necessary channels etc.and Job
14 termination and restringing of Dog or Panther 2.00 work(Per 34042.00
3 conductors for making LILO arrangement Loc.)
with existing line or change over of line during
availibilty of specified outage period
Dismantling of ‘A’ & ‘B’ type ‘H’ frame
structure by breaking of muffing upto 450 mm
depth from ground level and cutting the
girders from 450 mm depth from ground level
by gas cutting & crediting the material to
GETCO Store or Substation including
transportation as instructed by Engineer
in-charge.
Dismantling of all three conductors and line
materials such as insulators, hardwares etc.
and crediting to the GETCO’s Store or
16 Substation including transporation as per 0.50 RKM 16136.00
instruction of Engineer in-charge with
submission of pole wise inventory for
preparing C.R.note.
TOTAL - 6 ( SCHEDULE B - 6 )
Total of Schedule (1 to 6) Rs
Total Amount
Total Amount
In words, Thirty-Nine Lakh Fourty-four Thousands Five hundred and Eighty-Eight Rs. only
CERTIFICATE
I we am / are willing to carry out the above work at_______________________________________ % above / below (percentage)
should be written in figures and words. ___________________________________________________________Percentage above /
below the tender amount work out Rs. ______________________________________________Rupees in
words____________________________________________________________________________
Signature of Contractor,
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
2026-27 HTC 27 Tech Bid.pdf
2026-27 HTC 27 Price Bid.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .