Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Tender Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹42.3 LAccepted-AOC 101 VRAJ APARTMENT OPP POLICE HEAD QUARTER SARU SECTION ROAD JAMNAGAR 361008 | JAMNAGAR | JAMNAGAR | GUJARAT | 361008 | L1 | Accepted-AOC L1 | |
| 2 | L2₹45.6 L+₹3.3 L (7.82%)Rejected-Finance | L2 | Rejected-Finance L2 | |
| 3 | Rejected-Technical NO 2 GF AKSHAYRAJ APARTMENT JUBILEE CIRCLE BHUJ 370 001 | BHUJ | KACHCHH | GUJARAT | 370001 | - | Rejected-Technical due to not satisfied eligible category b(ii) | |
| 4 | Rejected-Technical BLOCK NO 11 VIMLNATH APARTMENT PRATAP VILAS ROAD NEAR SATYA SAI SCHOOL JAMNAGAR GUJARAT 361008 | JAMNAGAR | JAMNAGAR | GUJARAT | 361008 | - | Rejected-Technical Due to not fulfilling eligible category b(ii) |
Tender Value
₹41.5 L
EMD Value
₹83,000
Closing Date
23 May 2023, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE AF Jamnaga No 1
Military Engineer Services GE AF Jamnagar No 1 AF Station Jamnagar 361003
CERTAIN E/M WORK SERVICES FOR DARING III INFRASTRUCTURE AT AF STN JAMNAGAR
2023_MES_585297_2
8218/E8
Open Tender
Miscellaneous Works
Item Rate
180 days
Jamnagar
Refer tender documents
6 documents required · 6 mandatory
₹500
GE AF Jamnagar No 1
₹83,000
Yes
22 Jun 2023
2 May 2023
24 May 2023
2 May 2023
23 May 2023
9 May 2023
Amount
Supply & laying PVC underground cable XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured,electric power cables (heavyduty) with aluminium conductor, 11000 volts Earthed,grade cross sectional area 95 sq. mm 3 core laid in trenches / duct passing through pipe / duct or fixed on pole and connecting and testing etc complete all as specified & directed
Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out in soft / loose soil all as specified.
Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out in soft / disintegrated rock all as specified.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm.
Removing excavated material, soil, exc. 50m but n.exc 100 m and depositing where directed at a level n exc. 1.5 m above the starting point.
Supply & laying ISI marked & conforming to IS - 5820 - 1970 unreinforced precast concrete cable cover Class HV , Type I , flat size 300 mm X 180 mm X 40 mm in trenches as protection to HT UG cable all as specified and directed.
Supply & laying ISI marked & conforming to IS - 5820 - 1970 unreinforced precast concrete cable cover Class LV , Type I , flat size 250 mm X 150 mm X 40 mm in trenches as protection to LT UG cable all as specified and directed.
M&L for providing dry river sand as in sand cushioning to under ground PVC cable including punning down of sand in layer all as specified and directed. (Note: Work shall be executed as per clause 19.75 of standard schedule of rates part-1 (2009) for measurement purpose thickness of sand after punning down will be considered.)
S&F Tubes 80 mm bore, 'light grade' galvanised, with all fitting and fixed complete to walls and ceilings or laid in floors / trenches.
M&L Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm
Supply, installation, testing & commissioning of transformer of capacity 630 KVA step down outdoor type copper wounded 11/0.433 KV (at no load) AC 3 phase 50HZ on secondary side double wound oil immersed naturally all air cooled (ONAN COOLED) with external cooling tubes /radiator ,delta connected as on primary and star connected with natural brought on secondary) side and having tapping at (±) 2.5%,(±) 5% (±) 7.5% to be changed by hand operated OFF LOAD tap changing gear .The maximum temperature rise should not exceed 45 degree centigrade in oil and 50 degree centigrade in HV/ LV winding when measured by the resistance method after continuous full load run in ambient temperature the transformer shall confirming to IS 1180 Part-I:2014; Level II and above and comprising of following accessories complete all as specified and as directed.
(a) HV side Cable box with 03 Nos porcelains HV bushing with arching horns on HV side suitable for 11 KV complete with bushing rods and nuts washers and cable glands suitable for reception of out 3 core 95 Sqmm cable 3 runs, HT Cable 11000 Volts grade XLPE insulated heavy duty including gland complete. (b) 01 No cable end box on LV secondary side consisting of 05 Nos porcelain bushing (One No neutral earth, One No Neutral and Three No for phase connected bushing) with bushing rods and nuts washers and cable glands suitable for reception of out 3.5 core 400 Sqmm cable 3 runs, LT 1100 Volts grade XLPE insulated heavy duty including gland joint complete. (c) Oil conservator with filter type drain valve and oil level gauge.
(d) Dehydrating breather with first filling of dehydrating agent (e) Explosive vent. (f) Thermometer pocket including temperature gauge (g) Two earthing terminals on tank body to facilitate fixing of 32x6mm GI strips. (h) One No thermometer dial type vapour pressure type having range 0-120 degree centigrade with maximum temperature indicator and re-setting device to maximum temperature including needle of temperature gauge: Max reading painted terminal. (i) Oil level gauge. (j) Oil drain filter valve. (k) Oil filling hole on top cover with plug. (l) Air release valve/plug. (m) 4 Nos plain solid cast steel detachable rollers.
(n) First fill of transformer oil conforming to relevant ISI and tested upto 65 KV dielectric strength at 2.5mm air gap. (o)Two No lifting hook at side of transformer (p) 1Nos Breather duly filled with silicajel crystals capacity 1000g (q) Rating plate with terminal plate.
Note : Providing platform for transformer of size 3.0x3.0x1.5m high from GL including excavation in trenches not less than 1 mtr, PCC 1:5:10 type E2 for foundation, brick work in cm 1:6, PCC 1:2:4 type B1 in copping, plaster 10mm thick in cm 1:6 om brick /complete surface PCC 1:4:8 type B1 sub base 75mm thick, as in flour PCC 1:2:4 type B1 100mm thick floor using extra cement returning filling and removal on surplus soil, including 2 Nos ISMB 100mm channel painting with 2 coat aluminium paint over a coat of red oxide primer and 3 coats of white washing on cement work for fixing transformer including ramp of suitable size mounting of transformer complete all as specified and as directed.
(i) The erection, installation of transformer shall be done under the supervision of manufacturers auth rep & certificated to this office shall be submitted by contractor duly signed by auty rep of manufacturer & Engineer-in-Charge.
M&L Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm
Taking out existing HT cable,cutting and rejoining cable RMU to be installed for taping of electric supplynOTE: Earth work, labour charge is deemed to be included in quoted rate
Supply, installation, testing and commissioning of extensible 11 KV , 630 Amps, outdoor type safe plus Extensible Compact switch gear "Ring Main unit" two incoming and one out going having 02 No motorised Vacuum circuit break switch, 01 No load break switch and 01 No Metering module as Bus PT along with bottom cable entry and front cable termination with following specification PCC and block masonary for installation of Ring Main Unit complete as per manufacturer instruction and design all as dirtected:-
STANDARDS AND MECHANICAL DATA Metal Enclosed switchgear: IEC 62271-200 General Purpose switches: IEC 60265-1 Disconnectors and Earthing switches: IEC 62271-102 Circuit Breakers: IEC 62271-100 Common clauses: IEC 60694 Pressure of SF6 gas: 1.4 bar at 20 °C Cable bushings: DIN 47636 Temperature class: -25 °C - +40 °C Outdoor Degree of protection: SF6 tank: IP 67 Front cover: IP 2X Cable cover: IP 3X Enclosure: IP 54 Busbars: 240 mm2 Cu
Earth bar (external): 120 mm2 Cu - Bolt dimension: M10 Thickness of Stainless Steel Tank: 2.5 mm Colours: Front cover: RAL 7035 Side and cable cover: RAL 7035 Enclosure: IS 632 ELECTRICAL DATA – 12 kV - 28kV-1min Rated current busbars: 630 A Rated current cable switch disconnector : 630 A Short time withstand current: Cable switch disconnector with interface C (400-bolt) bushing: 20kA/3 sec. Vacuum circuit breaker with interface C (400-bolt) bushing: 20 kA/3 sec Rated current for transformer T-off : 630 A
Impulse withstand voltage : To earth and between phases: 75 kV Insulation level: Power frequency 1 min: 28 kV A01 to A02 Incoming Vacuum Circuit Breaker Module Type V (i) SafePlus V is a Vacuum circuit breaker module with vacuum circuit breaker, three position isolator/earthing switch, busbars, interlocking, earthbar and stored spring energy mechanism (A-mech.). (ii) SafePlus type V: Vacuum circuit breaker 12kV, 630A - 02 Nos Stored energy mech. for manual operation - 01 Nos
(iii) Self Powered OC+EF Protection Relay - 01 Nos (iv) Set of 03nos. Ring Core Protection CTs of suitable ratio as per feeder load, 2.5VA, 10P10 - 01 Nos (v) Set of 03nos. Ring Core Metering CTs of suitable ratio as per feeder load, 2.5VA, Class 1.0 - 01 Nos (vi) Capacitive voltage indication fixed type VPIS 6-12 kV - 01 Nos (vii) Aux. Relay for generating Potential Free Contact from Capacitive Voltage Indicator - 01 Nos
A03 Load break switch Module Type C (i) SafePlus C is a Load Break switch module with , three position isolator/earthing switch, busbars, interlocking, earthbar and stored spring energy mechanism (A-mech). (ii) SafePlus type C: Load break switch 12kV, 630A - 01 No (iii) Stored energy mech. for manual operation - 01 Nos (iv) Capacitive voltage indication fixed type VPIS 6-12 kV - 01 Nos (v) Aux. Relay for generating Potential Free Contact from Capacitive Voltage Indicator - 01 Nos
A04 Metering Module Type M (i) SafePlus M is an air insulated metering module. (ii) SafePlus type M: Air insulated metering module 12kV, 630A (IAC AF 16kA 1 s)- 01 Nos (iii) Set of 03nos. single-phase potential transformers having ratio 11kV/rt3:110V/rt3, 25VA, Class 1.0 with HRC fuses for protection on primary side and MCBs for protection on secondary side.- 01 Nos (iv) Space Heater (230VAC)- 01 Nos Low Voltage Box inside the metering enclosure for mounting:- 01 Nos · Multifunction Meter for each feeder · CSPC make Under/Over Voltage Relay · 2x12VDC Battery+Charger scheme · R-Y-B Phase Indication
Additional equipment delivered separately or mounted in respective panel. Set of Coupling busbars along with suitable coupling kit.- 01 Nos Manometer- 01 Nos Operating handle- 01 Nos Note :- (i) The Quoted rate shall include construction of foundation/plinth in PCC 1:2:4 type B-2 all as per manufacturer's instruction and standard drawingof manufacturer or as directed by Engg in Charge.
(ii) The contractor shall get the approval of GE for the make of the Switch gears they plan to procure. (iii) Prior to manufacturing the general arrangement drawing design details of the panel shall be got approved by GE.
Supply and laying PCC HT line route indicator of size 450 mm x 230mm x 50 mm above the ground and 250 mm in depth complete with red colour duly engraved HT/LT cable-MES all directed by Engg- in-charge
Supply & laying PVC underground cable XLPE insulated, GI strip or wire armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 500 sq. mm 3.5 core laid in trenches / duct passing through pipe / duct or fixed on pole and connecting and testing etc complete all as specified & directed
Supplying and laying synthetic rubber insulated mats 2.5mm thick for voltage upto 11 kv for electrical purpose as per IS 15652-2006,(superseding IS 5424) suitable for electrical shock safety of sizes 2mx1m complete all as specified and as directed
M&L Plain cement concrete 1:4:8 type D2 (using 40 mm aggregrate) in base & foundations of electric poles, stays structs etc including necessary form work and fair finish to exposed surface without using extra cement etc complete all as specified and directed by Engg-in-Charge.
Material and Labour for renewal of Earthing complete with galvanised steel earth plate electrode 60×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to using galvanised iron strip 25×4mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion.
Note : The Quoted rate for above item includes the cost of following : - (a) Earth electrode. (b) Main earthing lead from earth electrode to test point of 7.5 metre. (c) Material and labour for connecting earth electrode and earthing lead as specified. (d) Adequate quantity of charcoal dust, common salt and adequate quantity of chemical (e) All labour involved including testing of earth net work. (f) Excavation and earth work or drilling hole for electrode.
S&F Tubes 80 mm bore, 'Medium grade' galvanised, with all fitting and fixed complete to walls and ceilings or laid in floors / trenches.
S&F Tubes 25 mm bore, 'Medium grade' galvanised, with all fitting and fixed complete to walls and ceilings or laid in floors / trenches.
Supply and fix Stop valves,bore dia 25mm,cast copper alloy, screwed down, high pressure, with crutch or butterfly handle, screwed both ends for iron pipe or for unions and fixed complete all as specified and directed.
Supply and fix Non Return Sluice Valve of dia 80mm .
M & L for construction of valve chamber of size 750x750x1000 mm deep dimensions (overall internal dimension)for sluice valve etc.with PCC foundation, PCC block masonary wall, Plastering, PCC Coping, White washing, mild steel chamber cover, painting of chamber cover including Excavation and earth work in any type of soil complete all as specified below:-Valve chamber shall be provided with the following specification:- (i) Cement concrete for foundation (1:4:8) type D2 using 40 mm graded stone aggregate 150mm thick extended upto 150 mm beyond the outer face of block masonry. (ii) Walls of valve chamber 200 mm thick with precast cement concrete (1:5:8) (using 20 mm graded stone aggregate) solid building blocks, setting in CM 1:6 complete
(iii) internal and exposed surface of valve chamber both concrete and block masonry surface shall be plastered with CM (1:4), 15 mm thick finished even and smooth. (iv) 50 mm thick coping in PCC 1:3:65 type C1 over block masonry wall. (v) Entire plastered surfaces shall be treated with 3 coat of white wash. (vi) Chamber cover shall be of 6 mm thick MS Sheet with 30x30x5 mm size angle iron frame with hold fast and locking arrangement. (vii) Steel surface shall be painted with two caot s of synthetic paint of first quality over one coat of red oxide primer.
Material and labour for cutting the GI pipes of size 80 mm dia and making 25 mm dia branch connection including necessary fittings etc. all as specified and directed.
Cutting cast iron pipes and reducing to required length before laying in position for insertion of new tees branches, etc
Supply and fixing of cast iron Bends up to bore dia of 150mm , pieces single branch. "Y" junction, , cross (all sockets or socket and spigot) collars, caps and plugs complete all as specified and directed.
Indice Technologies
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .