Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹15.7 LAccepted-AOC 72 546A ERATHARA H LIBERTY LANE KALOOR PO KOCHI 682 017 | KOCHI | ERNAKULAM | KERALA | 682017 | L1 | Accepted-AOC Being lowest | |
| 2 | L2₹16.6 L+₹14,920 (0.91%)Rejected-Finance 137 D THEJAS BURNASHERRY KANNUR KERALA 670013 | KANNUR | KANNUR | KERALA | 670013 | L2 | Rejected-Finance Other than lowest tenderer | |
| 3 | L3₹18.0 L+₹1.5 L (9.31%)Rejected-Finance 606 80 FEET ROAD 7TH BLOCK 2ND PHASE BANASHANKARI 3RD STAGE BANGALORE 560 085 | BANGALORE | BANGALORE | KARNATAKA | 560085 | L3 | Rejected-Finance Other than lowest tenderer | |
| 4 | L4₹18.0 L+₹1.5 L (9.39%)Rejected-Finance JJ BHAVAN TC 10 1378 2 GN 31 CHENCHERY ROAD NALACHIRA PO TRIVANDRUM 695 015 | TRIVANDRUM | THIRUVANANTHAPURAM | KERALA | 695015 | L4 | Rejected-Finance Other than lowest tenderer | |
| 5 | L5₹20.3 L+₹3.8 L (23.1%)Rejected-Finance DOOR NO 3 79 CHENNNADGRAMAPANCHAYAT PERUMBALA KASARAGOD 681317 | PERUMBALA | KASARAGOD | KERALA | 681317 | L5 | Rejected-Finance Other than lowest tenderer |
Tender Value
₹24.8 L
EMD Value
₹49,600
Closing Date
1 May 2023, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE(MAINT)EZHIMALA
GARRISON ENGINEER (MAINT) MILITARY ENGINEER SERVICES INDIAN NAVAL ACADEMY POST KANNUR DIST KERALA 670 310
AS PER BOQ AND TENDER DOCUMENTS
2023_MES_588177_1
GE MAINT EZHIMALA 8551
Open Tender
Civil Works
Item Rate
330 days
EZHIMALA
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
GE MAINT EZHIMALA
₹49,600
Yes
13 Jun 2023
4 Apr 2023
3 May 2023
4 Apr 2023
1 May 2023
18 Apr 2023
5 Apr 2023 - 12 Apr 2023
Amount
Notes for all items of BOQ :- 1. The contractor should visit the site before quoting the tender to know the exact working condition of the station. 2. All requisite safety measures to be adopted by contractor on site. 3. The contractor shall provide and deploy sufficient electrician ( as approved by GE/ Engineer in charge) shall report at 9.00 hrs to JE E/M / Engineer in charge to collect the complaints job card in working days and complete the same complaint within 24 Hrs. 4. The complaints shall be rectified within 24 Hrs, if the complaints is/are not attended / not completed with in 24 Hrs ( except repair/replacement of major items) recovery will be done at Rs. 500 per complaint per day. 5 For major parts like rplacement of MCB,DBs,MCCBs etc should be rectified within 3 working days, if the contractor not rectify within time then the recovery will be done at Rs 1000 per complaint per day. 6. After completion of Job work complaint, the contractor has to produce job card duly signed by user & JE /Engineer in charge. 7 If contractor failed to provide their electrician or attend the complaints then recovery will be done at Rs 1000 per day.
Taking down carefully copper/ aluminium point wiring (light, fan and power socket etc) complete (except concealed conduit) including fittings such as switches ceiling roses, pendent, regulators, sockets, earth plug and socket etc and making good matching to the existing colour to the disturbed surface complete all as specified and directed by Engineer in charge.
M&L colour code point wiring FRLS PVC insulated and unsheathed cable with 1.5 sqmm copper conductor single core multistandred 1100 volt grade conforming to IS 694 drawn through PVC casing caping with suitable size GI flush box fitted with modular cover plate with frame (inner/ outer plate) for mounting 6 Amps switch with socket on independent board including FRLS 1.5 sqmm earth wire copper insulated wire connected to common earth dolly including making good the existing disturbed surface using wall putty and matching colour emulsion paint complete all as specified and directed by Engr-in-charge for the following:- Notes:- (i) Necessary PVC rigid junction boxes for identifying junction as required on site/directed by Engineer in charge for point wiring work with PVC dummy plates shall deemed to be included in the quoted rate. (ii) Same size wire shall be used for phase, neutral and earth conductor. (iii) The wiring shall be done strictly by following proper colour coding using red , blue, yellow for phase, black for neutral and green for earth leads. (iv) Size of copper earth wire must be equal to size of current carrying conductor upto size 16 sqmm.
(a) One Light/ fan point controlled by one switch
(b) One 3 pin socket outlet 5 Amps on the same board with other switches.
(c) 5 Amps socket point on independent board.
All as per item no 3 here in above but 2.5 sqmm for 15 Amps socket on independant board complete all as specified and directed by Engineer in charge.
All as per item No.3 here in above but 4 sqmm for 16/20 Amps socket on independent board complete all as specified and directed by Engineer in charge.
M&L for sub main wiring color coded using 2 runs of 2.5sq mm FRLS PVC insulated copper conductor 1100 Volts grade conforming to IS specification drawn through PVC casing caping along with 1 run of 2.5 sq mm PVC insulated copper conductor FRLS cable as earth lead connected to common earth dolly complete all as specified, including taking down the unserviceable wiring and including making good the existing disturbed surface using wall putty and matching colour emulsion paint complete all as specified and directed by Engineer-in-Charge.
M&L for sub main wiring using 2 runs of 4 sq mm FRLS PVC insulated copper conductor 1100 Volts grade conforming to IS specification drawn through and including PVC casing caping along with 1 run of 4 sq mm PVC insulated copper conductor FRLS cable as earth lead connected to common earth dolly complete all as specified, including taking down the unserviceable wiring and including making good the existing disturbed surface using wall putty and matching colour emulsion paint complete all as specified and directed by Engineer-in-Charge.
M&L for sub main wiring using 2 runs of 6 sq mm FRLS PVC insulated copper conductor 1100 Volts grade conforming to IS specification drawn through and including PVC casing caping along with 1 run of 6 sq mm PVC insulated copper conductor FRLS cable as earth lead connected to common earth dolly complete all as specified, including taking down the unserviceable wiring and including making good the existing disturbed surface using wall putty and matching colour emulsion paint complete all as specified and directed by Engineer-in-Charge. Notes for item No.6 to 8 :- (i) One run of PVC casing and caping alongwith 3 runs of respective size of PVC insulated copper conductor cable with necessary accessories will be measured as one unit. (ii) Strictly follow the proper colour code red/yellow/blue for phase,black for neutral and green for earth. (iii) Necessary PVC rigid junction boxes for identifying junction as required on site/directed by Engr-in-charge for point wiring work with PVC dummy plates shall deemed to be included in the quoted rate.
M&L for sub main wiring using 4 runs of 10sqmm FRLS PVC insulated copper conductor 1100 Volts grade conforming to IS specification drawn through and including PVC casing caping along with 2 runs of 10 sqmm PVC insulated copper conductor FRLS cable as earth lead connected to common earth dolly complete all as specified, including taking down the unserviceable wiring and including making good the existing disturbed surface using wall putty and matching colour emulsion paint complete all as specified and directed by Engineer-in-Charge. Notes :- (i) One run of PVC casing and caping alongwith 6 runs of PVC insulated copper conductor cable with necessary accessories will be measured as one unit. (ii) Strictly follow the proper colour code red/yellow/blue for phase,black for neutral and green for earth. (iii) Necessary PVC rigid junction boxes for identifying junction as required on site/directed by Engr-in-charge for point wiring work with PVC dummy plates shall deemed to be included in the quoted rate.
M&L for sub main wiring color coded using 2 runs of 2.5sq mm FRLS PVC insulated copper conductor 1100 Volts grade conforming to IS specification drawn through existing conduit along with 1 run of 2.5 sq mm PVC insulated copper conductor FRLS cable as earth lead connected to common earth dolly complete all as specified, including taking down the unserviceable wiring and including making good the existing disturbed surface using wall putty and matching colour emulsion paint complete all as specified and directed by Engineer-in-Charge.
M&L for sub main wiring using 2 runs of 4 sq mm FRLS PVC insulated copper conductor 1100 Volts grade conforming to IS specification drawn through and including existing conduit along with 1 run of 4 sq mm PVC insulated copper conductor FRLS cable as earth lead connected to common earth dolly complete all as specified, including taking down the unserviceable wiring and including making good the existing disturbed surface using wall putty and matching colour emulsion paint complete all as specified and directed by Engineer-in-Charge.
M&L for sub main wiring using 2 runs of 6 sq mm FRLS PVC insulated copper conductor 1100 Volts grade conforming to IS specification drawn through and including existing conduit along with 1 run of 6 sq mm PVC insulated copper conductor FRLS cable as earth lead connected to common earth dolly complete all as specified, including taking down the unserviceable wiring and including making good the existing disturbed surface using wall putty and matching colour emulsion paint complete all as specified and directed by Engineer-in-Charge. Notes for item No.10 to 12 :- (i) 3 runs of PVC insulated copper conductor cable with necessary accessories will be measured as one unit. (ii) Strictly follow the proper colour code red/yellow/blue for phase,black for neutral and green for earth. (iii) Necessary PVC rigid junction boxes for identifying junction as required on site/directed by Engr-in-charge for point wiring work with PVC dummy plates shall deemed to be included in the quoted rate.
Supply and fix switch piano, flush mounting type, single pole, one AC 230V grade 5Amps ISI marked complete all as specified and directed by Engineer-in-Charge.
All as per item No.13 here in above but 15 Amp ISI marked complete all as specified and directed by Engineer-in-Charge.
Supply and fix socket outlet 5 amp multi pin type ISI marked complete all as specified and directed by Engineer-in-Charge.
Supply and fix socket outlet 3 pin 15 amp multi pin type ISI marked complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of old unserviceable fan regulator electronic step up type type 100/120 Watt AC 230 watts complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of old unserviceable ceiling rose 3 pole 240V PVC/Poly carbonate insulated body ISI marked complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of old unserviceable switch piano, flush mounting type single pole one 230V grade 5 Amps complete all as specified and directed by Engineer-in-Charge.
All as per item No 19 here in above but 15 Amp complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of old unserviceable socket outlet 3 pin 5 A, complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of old unserviceable socket outlet 3 pin 15 Amp complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of old unserviceable call bell ding dong AC 230 volts complete all as specified and directed by Engineer-in-Charge.
S&F in replacement of old unserviceable modular switch one way 6 Amps 1 module ISI marked complete all as specified and directed by Engineer-in-Charge.
S&F in replacement of old unserviceable modular socket 6 Amps 2 module multi pin ISI marked complete all as specified and directed by Engineer-in-Charge.
S&F in replacement of old unserviceable modular switch one way 16 Amps 1 module ISI marked complete all as specified and directed by Engineer-in-Charge.
S&F in replacement of old unserviceable modular socket 16 Amps 2 module ISI marked complete all as specified and directed by Engineer-in-Charge.
S&F in replacement of old unserviceable white cover plate 2/3/4 module including taking down the defective one complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of old unserviceable switch socket combination 5/16 Amps 5 in one flush type ISI marked complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of old unserviceable MCB single pole AC 240 Volts, 6 to32 Amps C-Series complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of old unserviceable MCB single pole & neutral, AC 240 Volts, 32 Amps C-Series complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of old unserviceable MCB Triple pole & neutral, 40 Amps, 415 Volts AC C-Series complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of old unserviceable RCBO's for earth leakage protection double pole 300mA, 40 Amps complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of old unserviceable modular AC socket with MCB single pole 25/32Amps C-Series, AC 240 Volts complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of old unserviceable lamp holder, PVC type suitable for pendent/batten fittings complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of old unserviceable condenser 4 mfd, AC 440 Volts suitable for exhaust fan complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of old unserviceable condenser 2.5mfd, AC 440 Volts suitable for ceiling fan/exhaust fan complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of old unserviceable fan regulator (Modular) electronic step up type 100/120 Watt AC 230 Volts complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of old unserviceable hylam sheet 3mm thick suitable for switch boards etc complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of old unserviceable LED lamp 10 Watt B 22 suitable for batten/pendent holder complete all as specified and directed by Engineer-in-Charge. Make:- Havells/Crompton/Philips/Bajaj.
Supply and fix in replacement of old unserviceable MCB DB SPN 240V double door outdoor type, 12 way with bush bar of appropriate current carrying capacity, neutral link, earth bar and din rail complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of old unserviceable of MCB DB TPN 415V double door type, 6 way with bush bar of appropriate current carrying capacity, neutral link, earth bar and din rail complete complete all as specified and directed by Engineer-in-Charge.
S&F in replacement old unserviceable wall mounted 10 W 2 ft LED batten, out put lumen ≥ 100 lumen/watts, CCT ≥5500k, efficacy 100 lumen per watt, life 50,000 burning hrs, aluminum body, surge protection 4kV, power factor ≥ 0.95, THD ≤10%, extruded channel in thermally conductive material for efficient heat dissipation with Polycarbonate diffuser and integrated electronic driver making connection to ceiling rose to fitting with 3 core 1 sqmm copper conductor complete all as specified and directed by Engineer-in charge. Make:- Crompton model No. CCS-103-10-65-SL-DP-NWH or equivalent in Philips/Wipro/Havells/Bajaj. Note:- LM79 report accredited by NABL certified lab should be submitted.
S&F in replacement of old unserviceable wall mounted 20 W LED 4ft white batten out put lumen ≥ 110 lumen/watts, efficacy 100 lumen per watt, CRI > 80, CCT ≥5500k , internal surge protection up to 4kV , power factor ≥ 0.95 having extruded aluminium housing provided for efficient heat dissipation with poly carbonate diffuser and integrated electronic driver with all accessories pre-wired and including connecting up 3 core flexible copper conductor cable suitable size from fitting to ceiling rose/connection terminals complete all as specified and directed by Engr-in-charge. Make:- Crompton model No. CCS-103-20-65-SL-DP-NWH or equivalent in Philips/Wipro/Havells/Bajaj. Note:- LM79 report accredited by NABL certified lab should be submitted.
Supply and fixing in replacement old unserviceable LED down lighter fitting 18W, out put lumen >110 lumen/watts, efficiency 120lumen per watt, life 50,000 burning hrs, aluminium body, surge protection 4kV, power factor > 0.98, THD <10% with round shaped surface mounted , PDC aluminium housing and high translucent frosted plastic diffuser makes it a robust luminaire Efficacy 100lm/w with driver making connection to ceiling rose to fitting with 3 core 1 sqmm copper conductor complete all as specified and directed by Engineer-in charge. Make:- Crompton Model PEARL NIOS-R-LCDSPLN-R-18-CDL or equivalent in Philips/Wipro/Havells. Note:- LM79 report accredited by NABL certified lab should be submitted.
Supply and fixing in replacement old unserviceable LED bulk head fitting 10W out put lumen >110 lumen/watts, efficiency 120lumen per watt, life 50,000 burning hrs, surge protection 4kV, power factor > 0.98, THD <10%, IP65 with surface mounted, PMMA diffuser,powder coated white finish housing with driver making connection to ceiling rose to fitting with 3 core 1 sqmm copper conductor complete all as specified and directed by Engineer-in charge. Make:- Crompton Model STUD- LBHP-10-CDL or equivalent in Philips/Wipro/ Havells. Note:- LM79 report accredited by NABL certified lab should be submitted.
Supply and fix in replacement old unserviceable surface mounted 18W luminaire 1x1 tile, out put lumen >110 lumen/watts, efficiency 120lumen per watt, life 50,000 burning hrs, aluminium body, surge protection 4kV, power factor > 0.98, THD <10% lumen/watts, glare free uniform illumination housing with opel diffuser with colour temp 6000K with driver making connection to ceiling rose to fitting with 3 core 1 sqmm copper conductor complete all as specified and directed by Engineer-in charge. Make:- Crompton Model PEARL NIOIII- S-LCTLSNE-18-FO-CDL equivalent in Philips/Wipro/Havells. Note:- LM79 report accredited by NABL certified lab should be submitted.
Supply and fix in replacement old unserviceable recess mounted 36W luminaire 2x2 tile, out put lumen >110 lumen/watts, efficiency 120lumen per watt, life 50,000 burning hrs, aluminium body, surge protection 4kV, power factor > 0.98, THD <10%, glare free uniform illumination housing with opel diffuser with colour temp 6000K with driver making connection to ceiling rose to fitting with 3 core 1 sqmm copper conductor complete all as specified and directed by Engineer-in charge. Make:- Crompton Model Polaris NIO I LCTLRNE-36-FO-CDL or equivalent in Wipro/Philips/Havells. Note:- LM79 report accredited by NABL certified lab should be submitted.
Supply and fix in replacement old unserviceable suspended LED luminaire output lumen >110 lumen/watts, efficiency 120lumen per watt, life 50,000 burning hrs, aluminium body, surge protection 4kV, power factor > 0.98, THD <10% provides soft light and glare free 20W LED, making connection to existing ceiling rose to fitting with 3 core, 1 sqmm copper conductor complete all as specified and directed by Engineer-in charge. Make:- Havells Model CONSTA LED CONSTA544LP20W857 or equivalent in Wipro/Philips/Crompton. Note:- LM79 report accredited by NABL certified lab should be submitted.
S&F in replacement of old unserviceable single phase electronic meters temper proof LCD display with polycarbonate cover 230 V, 10- 60Amp, accuracy class-I 50Hz, conforming to IS 13779, IP-54, with parameters to show data, time, current reading, load, PF, voltage and KWH including taking down of old meter and deposit at MES complete all as specified and directed by Engineer-in charge. Note :- Contractor has to deposit old energy meters to MES for safe custody and it will be MES property and contractor has to submit the old meter Sl no, final reading of old meter, New meter Sl No, initial reading of the new meter for proper accounting of revenue.
Benchmark Engineers and Contractors
LUCKY ENTERPRISES
JEETH CONSTRUCTION
KDR CONSTRUCTION
Gates Infra Construction Co
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .