GE UTILITY AMBALA
GE UTILITY AMBALA CANTT 133001
COMPREHENSIVE MAINT OF PERIMETER SECURITY LIGHTS HIGH MAST LIGHTS AND STREET LIGHTS INCL ALLIED WORKS UNDER ALFA PH AREA UNDER GE UTILITY AMBALA CANTT
2023_MES_592831_1
CA NO GE U AMB T 30 OF 2023-24
Open Tender
Civil Works
Item Rate
240 days
GE UTILITY AMBALA CANTT
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
GE UTILITY AMBALA CANTT
₹88,000
15 Jun 2023
2 May 2023
2 Jun 2023
2 May 2023
31 May 2023
17 May 2023
2 May 2023 - 9 May 2023
Amount
Excavation in trenches not exceeding 1.5 metre wide and not exceeding 1.5 metre in depth for foundation, shafts, man holes,for under ground cable / erection of poles, stays, locating fault of LT cable and stay assembly etc not exceeding 10 square metre on plan and getting out in any type of soil including dressing/trimming of sides and leveling, grading and ramming of bottom of soil complete all as specified and as directed.
All as per Ser item No 1.00 here in before but depth exceeding 1.5 metre and not exceeding 3.0 metre complete all as specified and directed.
Returning, filling in, in soil, including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick each layer complete all as specified and directed.
Removing excavated material / soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed.
Material and labour sand cushioning to cable with a layer of sand 8 cm deep before laying the cable and 15 cms deep after laying the cable (punned down to 18 cms depth after laying and stretching of cable) complete all as specified and as directed.
Supply and lay bricks, common burnt clay, sub class "B', old size, laid in vertical direction to cable as cable protection complete all as specified and as directed.
All as per Ser Item No 6.00 here in before but except bricks, all as specified and directed. Note:- Old bricks retrieved from Ser Item No 11 & 12 here in after shall be re-used.
Material & labour for cement concrete in foundations, filling and mass concrete in foundation to poles, type D2, 1:4:8 using 40 mm graded crushed stone aggregate complete all as specified and directed.
Material & labour for Cement concrete, type C2, 1:3:6 using 40 mm graded aggregate as in foundation etc complete all as specified.
Material & labour for cement concrete as coping to poles, PCC type B1, 1:2:4 using 20 mm graded stone agregate as foundations to poles all as specified.
Disconnecting & taking out defective underground cable from trenches, pole, pipe, floor, wall etc and locate the fault, rectify the defect and relaying the XLPE cable underground PVC insulated and overall sheathed aluminum conductor heavy duty 1100 volts including connecting and testing for any size complete as directed by Engineer-in-Charge (Excavation/earth work & sand cushioning, bricks and joint shall be measured & paid for separately).
Disconnecting & taking out defective underground cable any size and any type from trenches, pole, pipe, floor, wall etc.
Supply and laying, connecting and testing XLPE underground cable insulated, and overall sheathed with aluminium conductor heavy duty 1100 volts grade 10 sqmm 4.0 core including Al thimbles laid in trenches/on pole/road crossing or passing through existing/new pipe under road crossing clamping on wall etc. Note : (i) Earth work, sand, bricks removing, returning filling will be paid seperately. (ii) Cost of laying electrical cable through new/existing pipe under road, buildings, railway tracks, highways are incl in the quoted rates (iii) All equiments, machinery or tool if required for laying electrical cable through new/existing pipes are provided by the contractor without any extra cost.
All as per item ser No 13 here in before but for 4 core 16 Sqmm
All as per item ser No 13 here in before but for 3.5 core 25 Sqmm
All as per item ser No 13 here in before but for 3.5 core 35 Sqmm
All as per item ser No 13 here in before but for 3.5 core 50 Sqmm
All as per item ser No 13 here in before but for 3.5 core 70 Sqmm
Dismantling and taking down security light, street light, hanger light, flood light and high mast lights of any type at any height fittings such as HPSV/HPMV/MH/LED light of 48 Watt/ 60 watt / 70/72 watt/ 90 watt/ 120 watt/ 150 watt/ 200 watt and 300 watt of any make etc. AC 230 volts any wattage from pole/wall roof top/hanger roof including washing/cleaning of perplex cover inspection for location of fault and replacing of defective spare/parts required for smooth functioning, tightening of electric connection complete and assembling and reconnecting all as per site requirment all as specified and directed. Note: Defective spare/ part of relevant light fitting shall be measured and paid separately under relevant item as supply only.
Supply only LED electronic driver/adaptor/SPD for 40-48 watt LED security light fitting of existing make all as specified and directed.
Supply only LED electronic driver/adaptor/SPD for 60 watt LED security light fitting existing make all as specified and directed.
Supply only LED electronic driver/adaptor/SPD for 70/72 watt LED security light fitting existing make all as specified and directed.
Supply only LED electronic driver/adaptor/SPD for 90 watt LED security light fitting existing make all as specified and directed.
Supply only LED electronic driver/adaptor/SPD for 100/ 120 watt LED Flood light fitting existing make all as specified and directed.
Supply only LED electronic driver/adaptor/SPD for 150 watt LED flood light fitting existing make all as specified and directed.
Supply only LED electronic driver/adaptor/SPD for 200-300 watt LED flood light fitting existing make all as specified and directed.
Supplying and fixing in replacement of 1100 volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4mm suspension wire, one twin core cable flat or circular of size 10 sqmm 2 core complete all as specified and directed.
Supply and fixing in replacement or passing through PVC conduit pipe of 1100 volts grade heavy duty, PVC insulated round 3 core 1.0 sqmm copper cable including electrical connection suitable size of lugs,nuts and bolts complete all as specified and directed.
Supply and fixing in replacement or passing through PVC conduit pipe of 1100 volts grade heavy duty, PVC insulated round 5 core 2.5 sqmm copper cable including electrical connection suitable size of lugs,nuts and bolts complete all as specified and directed.
Supply and fixing in replacement or passing through PVC conduit pipe of single core PVC unsheathed multi stranded copper cable (FRLS) 1.5 Sqmm nominal cross sectional area 1100 volts conforming to IS 694 including electrical connection suitable size of lugs, nuts and bolts complete all as specified and directed.
Supply and fixing in replacement or passing through PVC conduit pipe of single core PVC unsheathed multi stranded copper cable (FRLS) 2.5 Sqmm nominal cross sectional area 1100 volts conforming to IS 694 including electrical connection suitable size of lugs, nuts and bolts complete all as specified and directed.
Supply and fixing in replacement of rigid non-metallic PVC conduit of dia 20 mm exclusive of boxes (Junction/terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc. Note: PVC pipe will be clamped at three position on pole and cost of clamp, nut, bolts etc are incl in quoted rates complete all as specified and directed.
Supply & fixing in replacement of Integral LED Flood light Luminaries 100 Watts consisting of suitable number of LEDs and mounted on MCPCB high pressure die cast aluminium housing with sealed toughened glass cover with secondary optics lens, IP 66 protection suitable for mast light mounting, 5700K, LED efficiency >130 lm/Watt and system efficiency 110 lm/W , 240 Volts AC, 50 Hz, CRI>70% operating voltage range 160 V-270 V, Power factor> 0.95, working temperature range -10ºC to 50ºC,built in surge protection of more than 10 kV , Confirm the tests from auth labs : LM79 & LM 80, incl proper fixing and testing of flood lights on 9/11 mtr long steel tubular pole and provide facility of power supply shall be provide as suitable for maint work of light fittings incl make proper connection of new and existing light fittings complete with cutting , welding , drilling holes, nut bolts, washer complete all as directed by Engineer-in-charge.
All as per item Sr No 33 here but for 150 Watts LED Luminaires complete.
All as per item Sr No 33 here but for 200 Watts LED Luminaires complete.
Supply & fixing in replacement of LED street light fitting 45 watts made up of pressure die cast aluminium housing with high efficiency LEDs as lighting source and lens embedded PC cover/ toughened glass having TOP Opening seperate driver compartment with IP 66 protection and impact resistance of IK07 consisting of suitable number of LEDs with sealed toughened glass cover, 5700K, LED efficiency >110 lm/Watt and system efficiency 110 lm/W , 240 Volts AC, 50 Hz, CRI>70% operating voltage range 140 V-270 V, Power factor> 0.95,mains current 0.270A, working temperature range -10ºC to 50ºC,built in surge protection of more than 10 kV, better optics for uniform distrubution with multiple LEDs not less than 2 watt each and having optical grade polycarbonate lens with all accessories , suitable for side entry, pole mounting with bracket arm OD 40 mm, recommended mounting height with suitable inground reinforcement is 8 mtrs, Confirm the safety test as per IS 15885 part-2 from auth labs : LM79 & LM 80, incl proper fixing and testing of street lights on 9/11 mtr long steel tubular pole incl make proper connection of new and existing light fittings complete with cutting , welding , drilling holes, nut bolts, washer complete all as specified and directed by Engineer-in-charge. Note :-PVC heavy duty conduit pipe along with 3/1 run of 1.5/2.5 sqmm PVC insulated unsheathed/sheathed copper multistranded conductor from MCB box to street shall be measured and paid for separately.
All as per item Sr No 36 here but for 70 Watts LED Luminaires complete.
All as per item Sr No 36 here but for 90 Watts LED Luminaires complete.
Supply, fixing and testing of auto day/ night on and off photocell LDR sensor switch 6 Amps for lighting on and off photocell, LDR sensor switch 6amps for lighting on and off water proof 220volt 50HZ,AC supply, model No Quick Sense QS-301 complete with all accessories internally pre-wired including connection with 1.5 Sqmm copper conductor from main supply to sensor, sensor to fittings complete all as specified and directed by Engr-in-Charge.
Supply & fixing in replacement of Automatic Street Light Control Switch with Infrared Sensor based NATURE SWITCH & Voltage Monitoring System (VMS). single phase, 25 Amps per phase, MCB rating 40 Amp, max load 5-8 kw incl circuit copper wire 10 sq.mm. Nature Switch operation should be based on Natural Light Lux level. Required Illuminance Level for Switching ON is ≤ 60 Lux and for switching OFF ≥ 10 Lux. The Sensor should also have part night operation facility of min. 4 to max. 12 hrs. VMS should have Adjustable Over & Under Voltage Trip level and Protection against Phase Loss, Neutral Loss & Phase Reverse. The Sensor & VMS along with suitable Power Contactor(s) and Incoming-Outgoing MCBs should be enclosed in a pole/wall mountable Enclosure made of Rust Proof, Electric Shock Proof, Termite proof and FR grade SMC Junction box conforming to IP54. The circuit should also have provision for Manual Operation (i.e. By-Pass Option for both Sensor (NS-02) and VMS). Madel : Swadeep-02EC-5kW1P-VMS complete all as specified and directed. Note (i) Nut bolts, clamp for fixing on poles/wall are to be included in quoted rates. (ii) The sensor must have the warranty of min of 2 years . (iii) The test certificate and warranty certificate shall be provided by contractor before clai of payment. (iv) Cost of marking description on the box is incl in the quoted rate.
M&L for Detecting of fault in cable HT/LT with fault locator equipment supplying of HT/LT electric supply (11 KV/430 Volts) to make the HT/LT cable serviceable with Straight through joint of size 70-300 Sqmm. Notes (a) The HT fault which is detected through cable fault locator will only be paid under this item including transportation charges demed to be included in the quoted rate. (b) Transportation charges of cable fault locator and DG set deemed to be included in the quoted rate. (c) Earth fault locator will be provided by the contractor for even single HT fault and no delay on this account will be acceptable otherwise penalty will levied Rs 500.00 per hour. (d) Straight through joint , 95 to 300 sqm Labour charges, excavation and making joint deemed to be including in quoted rate.
Supply and fixing LT line separators 1100 V grade PVC spacer to separate LT conductor from each other 4 line as per IS complete as per direction of Engr-in-Charge.
Supply and fixing LT line separators 1100 V grade PVC spacer to separate LT conductor from each other 3 line as per IS complete as per direction of Engr-in-Charge.
Re-streching of loose over head ACSR conductor of any type/GI wire and repair of the broken conductors and adding new length( if required) in place of old and burnt conductor of any size on existing poles with proper sagging including winding with winding wire all as specified. ( Old conductor shall be reused where required for repairing broken length of conductor as directed by Engr-in-charge) . Note:- Each run of conductor will be measured and paid seperately.
Material and labour in replacement of aluminium terminals (thimbles) after cutting the worn out/faulty cable end from LT pillar/panel box including necessary earth work for taking out the cable from loop line, returning, filling in and making cable lead by providing aluminium lugs including crimping with crimping tools in the existing LT cable 25 Sqmm 4 core upto 50 Sqmm including necessary connection all as specified and directed.
All as per item ser No 45 here in before but size of LT cable 70 Sqmm 3.5 core upto 120 Sqmm 3.5 core.
All as per item ser No 45 here in before but size of LT cable 150 Sqmm 3.5 core upto 300 Sqmm 3.5 core.
Trimming of Tree branches OH lines of HT/LT & maintain approaching minimum clearance of 3 Mtr from branches. Proper shutdown will be taken and maintained in the register complete all as specified and as directed.
Supply and fixing in replacement of fabrication of Kiosk box made out of fibre material complete with TPN ,aluminium bus and suitable for one number MCB (SP) including one No MCB (SP) 6 Amps 240 volts with glands for incoming & out going cable including fixing of flat iron clamps of size 20x4mm on PCC/Steel tubular pole complete all as specified and as directed by Engr-in-Charge. Make: Havells/Sintex.
Supply and fix in replacement of MCB SP 6-32 Amps, 240 volt,10 KA 'B' curve including all accessories complete all as specified and directed.
Supply and fix in replacement of MCB DP 16-40 Amps, 240 volt,10 KA 'B' curve including all accessories complete all as specified and directed.
Supply and fix in replacement of MCB TPN 32-63 Amps, 240 volt,10 KA 'B' curve including all accessories complete all as specified and directed.
Dismantling and taking down old unsv PCC LT pole and Supply, fix and erection of PCC pole 9.0 mtr long in true vertical position 102x172 mm at top 102x279 mm at bottom class-10 incl providing black and white strips with synthetic enamel paint 30 cm each alternate upto 1.5 mtr including 2 bands of radium tape of 2' width greeen & red colour above the coping of pole starting with black strip complete all as specified and as directed by Engr-in-Charge. Note (i) Earth work and PCC shall be measured and paid seperately (ii) Description as per direction of Engineer-in-Charge will be printed on each pole without any extra cost.
Dismantling and taking down old unsv Steel tublar LT pole and Supply, fix and erection of steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts,nuts and screws as specified type 410 SP-31, 09 meter long, providing synthetic enamel aluminium paint over one coat of red oxide and black and white strips with synthetic enamel paint 30 cm each alternatively upto 1.5 mtr including 2 bands of radium tape of 2' width greeen & red colour above the coping of pole starting with black strip, incl arrangement of galvanised/Mild steel circular lantern carriage arrangement suitable for 5 luminares symmetrically on steel tubular poles complete all as specified and directed by Engr-in-charge. Note (i) Earth work and PCC shall be measured and paid seperately (ii) Description as per direction of Engineer-in-Charge will be printed on each pole without any extra cost.
Supplying and fixing in replacement of light grade galvanised mild steel pipe 80mm bore with all fittings, laid under roads, drain, paths, fixed to poles/walls with suitable mild steel clamps, bolts, nuts and washers all as specified and directed. Note:- Excavation & earth work shall be measured and paid for separately under appropriate item of this schedule.
All as per Item No 55.00 here-in-before but of size 40 mm bore.
S&F in replacement of bracket made out of GI tubing single piece not welded, bended at proper angle of size 40mm dia, light grade 1.5 mtr long including painting with aluminium paint over one coat of red oxide primer to the bracket including 1.0 sqmm 3.0 core flexible copper cable in PVC conduit with clamp from juction box to connecter of street light fitting all as specified and as directed.
S&F in replacement of MS clamp suitable for holding street light bracket on steel/PCC pole made out of 40 mm x6 mm thick flat iron with M.S nuts bolts 50 mm long 10 mm dia -3 Nos with flat washer 3mm thick -02 No for each including painting with aluminium paint over one coat of red oxide primer to the M.S clamps all as specified and as directed
Dismantling and taking down old u/s earthing and Material and labour for earthing complete with galvanized steel plate earth electrode 60cmx60cmx6mm thick surrounded by char coal and salt buried directly in ground vertically in pit of depth not less then 2.25 mtr below ground level with top edge of the earth plate at depth of not less than 1.5 mtr below ground level surrounded from all sides by char coal dust and common salt in alternate layers of 15 cm depth and earth plate electrode connected to galvanised earth lead wire of 4.0 mm dia by means of GI nuts bolts, check nuts and washers and connected to earthing test point drawn through 15 mm bore GI pipe medium grade for protection of GI earth lead wire including 20mm bore GI pipe medium grade for watering GI funnel PCC earth pit (1:3:6) type C-2 with CI frame and RCC cover all as shown in electrical Plate No 3 on SSR Part - I including testing complete all as specified and as directed. Note : (i) The quoted rate shall include the cost of earth work, GI pipe for watering, GI protection pipe, funnel, wire mesh, RCC cover, etc. complete. RCC cover shall be 50mm thick in 1:2:4 type B-1 using 8mm bars @10cm c/c both way. (ii) The quoted rate shall include the cost of the earth pit covers to be conspicuously marked of plate with stand grouted in PCC. (iii) On testing after completion if the desired earth resistance ismore than 2Ώ the earthing will be redone at no extra cost
Dismantling and taking down old u/s earthing complete with galvanised earth plate electrode 600mm x 600mmx 6.00mm thick surrounded by charcoal and salt, buried directly in ground vertically in a pit of depth not less than 2.25m below ground level with top edge of the earth plate not less than 1.5m below normal ground level, connected to 25x4 mm GI strip earth lead by means of bolts, nuts, checks nut and washers made out of galvanized iron or steel, earth wire protected by galvanized steel pipe 40mm bore medium grade and connected to main switch or main control board all as shown in electrical plate No.3 of SSR Part-I & including necessary excavation and earth work. The rate also include charcoal & salt in alternate layers, 20mm bore GI pipe medium grade for watering and 40mm bore GI protection pipe (light grade), funnel, wire mesh, cast iron cover and frame etc, complete, all as specified or indicated and as directed including testing on completion complete all as specified and directed. Note : (i) The quoted rate shall include the cost of earth work, GI pipe for watering, GI protection pipe, funnel, wire mesh, RCC cover, etc. complete. RCC cover shall be 50mm thick in 1:2:4 type B-1 using 8mm bars @10cm c/c both way. (ii) The quoted rate shall include the cost of the earth pit covers to be conspicuously marked of plate with stand grouted in PCC. (iii) On testing after completion if the desired earth resistance is more than 2Ώ the earthing will be redone at no extra cost
Supply and fixing in replacement MCCB TPN 250 Amps, 415 Volts, 36 KA, 4 pole, Ics=100% Icu, overload adjustable short circuit adjustable type incl spreader link and complete connection all as per direction of Engr-in-Charge.
Supply and fixing in replacement MCCB TPN 200 Amps, 415 Volts, 25 KA, 4 pole, Ics=100% Icu, overload adjustable short circuit adjustable type incl spreader link and complete connection all as per direction of Engr-in-Charge.
Supply and fixing in replacement MCCB TPN 160 Amps, 415 Volts, 25 KA, 4 pole, Ics=100% Icu, overload adjustable short circuit adjustable type incl spreader link and complete connection all as per direction of Engr-in-Charge.
Supply and fixing in replacement MCCB TPN 100 Amps, 415 Volts, 16/18 KA, 4 pole, Ics=100% Icu, overload adjustable short circuit adjustable type incl spreader link and complete connection all as per direction of Engr-in-Charge.
Material and labour for shifting heavy items / excavation / cleaning areas / cleaning site by providing crane/hydra/excavators/tractors/trolley etc as required at site complete, all as specified and as directed.
M&L for drilling hole of any size manually as per site requirement, drilling for laying pipes under the road for crossing electrical cable complete all as per direction of Engr-in-Charge
Material and labour for spraying herbicide (Round up) on area to remove unwanted vegitation/grass at various locations as directed by Engr-in-Charge
Supply and fixing in replacement of on load change over switch with sheet steel Enclosure 415 V, 4 pole, 630 Amps capacity fixed on walls/MS frame/pole/LT panel for electric supply distribution between main and DG set incl necessary connection of cable from LT panels to change over switches complete all as specified and directed by Engr-in-Charge.
M&L Chemical spray (DC 2.26 contact cleaner) in container of 415 ml/300g for precision blended multipurpose product for prevents corrosion penetrates, lubricants, displaces and seals out moisture release rusted mechanisum cleanese etc complete all as specified and directed by Engr-in-Charge.
Supply and installation in replacement of all in one integrated Solar street light 25 Watt compact, aesthetic eco friendly and modern integrated Solar Street in extruded aluminium housing with high efficiency mono crystaline silicon photo voltaic panel, high efficency SMD LED 6500K having secondary lens optic for street light distribution,high performance lithium battery, MPPT charge controller and intelligent control, module/sensor with higher reliability long service life including 50 mm bore GI pipe medium grade pole upto 4 mtr height for mounting of Solar Lights suitable for easy and quick instllation including PCC 1:3:6 type C-1 (using 20 mm graded crushed stone aggregate) complete all as specified and directed.
Sypply, Install, Test and Commissioning of LT feeder piller box outdoor type fabricated of size 0.6x0.6x0.5M,out of 3.00 mm thick CRCA sheet, CPRI approved complete with powder coating with seven tank process mounted on MS angle frame of size 40x40x5mm, duly grounted with PCC 1:2:4 type B-1 with the following:- (a) Aluminium bus bar 200 Amp with coloured heat shrinkable insulated sleeve 415 volts as per IS of suitable size mounted on DMC/epoxy insulator (not than 50mmx50mm conicle type at a maximum interval of 500 mm - 01 Set. (b) MCCB FP 63 Amps 16 KA - 01 No For Main incoming (c) Digital ammeter 0-250 Amp (d) Digital Volt meter 0-500 V (e) RYB indication lamp LED type -3 Nos
Supply and installing, testing & commissioning in replacement of factory fabricated outdoor type feeder pillar board of size 700X600X500 mm , outer shell made out of 3.15 mm thick CRCA sheet and inner shell made out of 2 mm thick CRCA sheet and MS angle section 50x50x6 mm mounted on PCC 1:2:4 type B-1 platform 60 cm above and 45 cm below the ground level, frame factory fabricated with front openable double door system and cable alley (Each door hinged with body at 3 places with body and hinges should be welded with body and door) lockable/open able with arrangement of pad locking on door 01 no of pad lock of three keys shall be used to make the outer shell completely vermin proof suitable for 3 phase 4 wire 415 Volt, 50 Hz, tested at factory approved from CPRI factory fabricated having modern fabrication and testing process followed by powder coated painting after 7-tank pre treatement control & power wiring with suitable size of copper conductor along with suitable gasket to make it dust/vermin proof and general construction confirming to IS:61439/2011 Part-1 and part -2 type test certificate with not less than IP-56 and breaking capacity 65 KA comprising of the following :- (a) MCCB 160 Amps TPN, 25 KA -01 No (b) MCB 40Amp TPN 4 pole - 04 Nos (c) Aluminium busbar of capacity 250 Amps with colour coated heat shrinkable sleeve and suitable hole for out going connection - Set of four. (d) Digital ammeter 0-250 Amp (e) Digital Volt meter 0-500 V (f) RYB indication lamp LED type-3 Nos (g) Misc items like screws, cable tie, copper cable 1.5/2.5 Sqmm, cabe lugs, sleeves, glands etc complete are included in quoted rates
Notes for item Sr No. 71 to 72 (i) The quoted rate shall include minor items such as lugs, nuts & bolts, washers, top insulators, sleeves, provision of extra holes in bus bar etc. (ii) All internal wiring shall be done with suitable size of PVC insulated solid copper conductor FRLS cable conforming to IS-694. (iii) Panel drawing shall be got approved before placing of order from Engr-in-Charge/GE. (iv) The bus connection for cable from main bus bar to outgoing MCCB will be connected through suitable rating bus bar strip type duly insulated. (v) Cable will be entered in panles through gland. (vi) Cost of marking description and matter on the front door as specified and directed by Engr-in-Charge is incl in quoted rate.
Material and labour in replacement of broken earth pit of size 300x300x300 mm made of PCC 1:2:4 type B1 using 20 mm graded crushed stone aggregate, and earth pit cover made out of RCC 1:2:4 type B1, cover reinforced with 8 mm dia TMT bars @ 100 mm centre to centre both ways with handle made out of 8 mm dia bar, watering arrangement with funnel and wire mesh and including reconnecting of earth lead of any type with new nuts, bolts and washers as required at site with testing result all as specified and directed.
Material and labour in repairs of stay by tightening of stay wire after untying the conductor spans from the poles to make correct tensions and maintain verticality of poles, including re-jointing the conductors in position with new binding wire all as specified and directed.
Repairing of existing unserviceable PCC coping of LT/HT pole by breaking completely and material and labour for PCC 1:2:4 type B1, (using 20mm graded crushed stone aggregate) of size 600X600X300mm including form work and applying two coats of white wash all as specified and directed.
Taking down old unserviceable Indicator lamp any type any colour and supply and fixing new Indicator red/yellow/green including making electrical connection with suitable size of copper lugs duly crimped complete all as specified and directed.
Supply and fixing in replacement sensor of nature switch operation should be based on natural light lux level, required illuminance level for switching on is <30 Lux and for switching off >10 lux , the sensor should also have part night operation facility of min 4 hrs to max 12 hrs complete all as specified and directed Make:- Swadeep , Model nature switch -02(sensor) or equivalent as approved by GE.
Supply and fixing in replacement of contactor 3 pole 18 Amp in street light timer box coil operating voltage 230 volt complete all as specified and directed Make- BCH/L&T or equivalent as approved by GE
Supply and fixing in replacement of contactor two pole 25/40 Amp in street light timer box coil operating voltage 230 volt complete all as specified and directed Make- L&T/BCH or equivalent as approved by GE
Supply and fixing in replacement of contactor coil (230V) for MU series 25/40 Amps 2 pole contactors complete all as specified and directed Make- L&T (Cat No CS90793) or equivalent as approved by GE
Supply and fixing in replacement of contactor coil (240V) for freedom series 18 Amps 3 pole contactors complete all as specified and directed Make- BCH, Cat No CE15D1N-K or equivalent as approved by GE
Supply and fix in replacement of danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled red, with letters, figures and conventional skull and bones in signal white colour and fixed with M.S. clamps, bolts and nuts of approved size, for LT, 20x15cm size complete all as specified and directed
Dismantling and taking down old unserviceable ACSR conductor incl cutting, welding complete all as per direction of Engr-in-charge.
Material and labour for aluminium conductor steel reinforced (ACSR) conductor of size ISI marked for LT over head lines on poles including stretching, tightining of poles insulator with winding wire of suitable size with insulator/streching of ACSR conductor all as specified and directed by Engineer-in-Charge.
Material and labour for vibratory compactive, precast cement concrete rubber moulded, coloured (except grey colour), interlocking designer paver blocks in Milano shape, comfirming to IS-15658-2006 of 60 mm thickness, M-35 grade, as in path, harding standing, etc laid over and including 25 mm compacted sand cushioning, including 75 mm thick PCC 1:4:8 type D-2 using 40mm graded crushed stone aggregate including surface excavation over area n. exc. 30 cm deep and averaging 15 cm deep and getting out in soft/loose soil and removing excavated soil exc. 50 mtr but n. exc. 250 mtr, complete all as specified and directed by Engineer-in-charge.
Material & Labour for surface cleaning of steel tubular poles LT 9 mtrs long including removing rusted particles painting with two coats of synthetic enamel aluminium paint over a coat of red oxide primer including cross arms, bracings, supports clamps eye hooks, security light bracket clamps etc providing black & white strips alternatively 30cm each from coping upto 1.5 mtr height starting with black strip using synthetic enamel paints incl reparing and painting on coping with cement base white paint complete all as directed. Note: (i) The quoted rate shall includes marking of numbers on each LT pole as per direction of Engr-in-Charge. (ii) The quoted rates shall include the repair work of coping with cement/PCC
Material & Labour for cement base paint on PCC pole 9 mtr including black & white strips alternatively 30cm each from coping upto 1.5 mtr height starting with black strip using synthetic enamel paint and painting with two coats of synthetic enamel aluminium paint over a coat of red oxide primer including cross arm bracing supports, clamps, eye hooks, security light bracket, clamp etc incl incl reparing and painting on coping with cement base white paint complete all as directed. Note: (i) The quoted rate shall includes making of numbers on each LT pole as per direction of Engr-in-Charge. (ii) The quoted rates shall including the reparing of coping with cement / PCC.
Material and labour for Air circuit breaker, fixed type, spring operated, manually TPN, 4 pole, 800 Amp, 415 Volts with thermal magnetic release, (O/L, S/C, E/F protection & confirming to IEC-60947-2& 3 rated breaking capacity and making capacity 50 KA short time current all as specified and directed by Engr-in-Charge.
Supply and fixing indoor/outdoor end termination joint heat shrinkable 1100 Volts for XLPE cable of size 3.5/4.0 x 10-50 Sqmm complete all as directed by Engr-in-Charge.
Supply and fixing indoor/outdoor end termination joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 70-120 Sqmm complete all as directed by Engr-in-Charge.
Note:- Amount of credit of Rs 132549.00 for retrieved materials is mentioned in Schedule of Credit attached in tender documents in pdf form which will be deducted offline while acceptance of tender.
Gopal Enterprises
M/S Sonu Traders
KULWANT SINGH
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .