Assistant Commandant (Electrical)
SHQ BSF BHOPAL, FATEHPUR DOBRA, BHOPAL (MP)
Dehydration of 02 Nos 400 KVA and 02 Nos 200 KVA Transformers installed at KLP Nagpur
2026_BSF_929369_1
06/SHQ-BPL/MW/BSF/2026-27
Open Tender
Electrical Works
Percentage
30 days
116 BN BSF, MANDAWA
As per NIT
10 documents required · 10 mandatory
₹0
₹2,580
8 Oct 2026
8 Oct 2026
19 Oct 2026
8 Oct 2026
17 Oct 2026
8 Oct 2026
8 Oct 2026 - 17 Oct 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | To and fro transportation, loading, unloading and shifting of vacuum type transformer oil filtration machine with all accessories and T&P to the work site and back, including all incidental charges, complete as required. | 1 | Job | 7,690 | ₹7,690 |
| 2 | Dehydration and filtration of existing transformer 11 KV/0.433 KV of 400 KVA through oil filter machine with two or more circulation to clear oil free from moisture, sludge, acidic & other chemical reactor to achieve the required dieletric strength of oil in the existing installed transformer including testing the oil before and after filteration in BDV testing kit at site complete etc. as required. [Capacity 505 Ltr x 02 Nos] | 1,010 | ltr | 14 | ₹14,140 |
| 3 | Dehydration and filtration of existing transformer 11 KV/0.433 KV of 200 KVA through oil filter machine with two or more circulation to clear oil free from moisture, sludge, acidic & other chemical reactor to achieve the required dieletric strength of oil in the existing installed transformer including testing the oil before and after filteration in BDV testing kit at site complete etc. as required. [Capacity 380 Ltr x 02 Nos] | 760 | ltr | 14 | ₹10,640 |
| 4 | Supplying and topping up of transformer with fresh transformer insulation oil during filtration, dehydration process in existing transformer confirming to IS:335/1993 of EHV grade with up-to-date amendment, up to required level. | 209 | Ltr | 227 | ₹47,443 |
| 5 | Supplying & Replacement of silica gel by removing from existing breather unit complete etc. as reqd. | 3 | Kg | 593 | ₹1,779 |
| 6 | Repair & Maintenance of 400 KVA (11/0.433 kV) outdoor oil-filled transformer by arresting oil leakage through replacement of all worn-out/damaged gaskets with new gaskets, cleaning of gasket seating surfaces, tightening of all nuts, bolts and fasteners, checking and tightening of HV/LV bushings and terminal connections, cleaning of transformer and carrying out all allied works complete as directed by the Engineer-in-Charge. | 2 | Job | 12,849 | ₹25,698 |
| 7 | Repair and Maintenance of 200KVA (11/0.433 kV) outdoor oil-filled transformer by arresting oil leakage through replacement of all worn-out/damaged gaskets with new gaskets, cleaning of gasket seating surfaces, tightening of all nuts, bolts and fasteners, checking and tightening of HV/LV bushings and terminal connections, cleaning of transformer and carrying out all allied works complete as directed by the Engineer-in-Charge. | 2 | Job | 10,793 | ₹21,586 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.66 MB
BOQ_976644.xls
BOQ • 0.30 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .