Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹8.7 CrAccepted-AOC | ₹8.7 Cr | L1 | Accepted-AOC Being L1 Bidder |
| 2 | L2₹10.5 Cr+₹1.8 Cr (20.0%)Rejected-Finance | ₹10.5 Cr+₹1.8 Cr (20.0%) | L2 | Rejected-Finance Not being L1 Bidder |
| 3 | L3₹10.6 Cr+₹1.9 Cr (21.2%)Rejected-Finance 3A RAM MOHAN MULICK GARDEN LANE UNIT NO 6A 3RD FLOOR KOLKATA 700010 | KOLKATA | WEST BENGAL | 700010 | ₹10.6 Cr+₹1.9 Cr (21.2%) | L3 | Rejected-Finance Not being L1 Bidder |
| 4 | Rejected-Technical NA BCL 5 HIDE ROAD HIDE ROAD KOLKATA WEST BENGAL 700043 | KOLKATA | WEST BENGAL | 700043 | - | - | Rejected-Technical Being not fulfilling criteria as per NIT |
| 5 | Rejected-Technical WZ 250 B 2 GALI NO 08 SADH NAGAR I PALAM COLONY NEW DELHI 110045 | NEW DELHI | SOUTH WEST DELHI | DELHI | 110045 | - | - | Rejected-Technical Being not fulfilling criteria as per NIT |
Tender Value
₹10.8 Cr
EMD Value
₹8.7 L
Closing Date
11 Jul 2024, 6:00 pmClosed
CHIEF ENGINEER AF SHILLONG ZONE
HQ CHIEF ENGINEER AF SHILLONG ZONE MILITARY ENGINEER SERVICES ELEPHANT FALLS CAMP PO NONGLYER SHILLONG 793009
PROVN OF MD ACCN FOR DSC PERSONNEL (PHASE-I) AT AF STN BARRACKPORE
2024_MES_649763_2
88880/BKP/E8
Open Tender
Civil Works
Lump-sum
700 days
GE (AF) BARRACKPORE
As per NIT Conditions
8 documents required · 8 mandatory
₹3,000
GE (AF) BARRACKPORE
₹8.7 L
Yes
23 Oct 2024
8 Jun 2024
13 Jul 2024
8 Jun 2024
11 Jul 2024
22 Jun 2024
Amount
NOTE (Applicable for all Parts/ Items):- The bidders/contractors are advised to read tender document, all drawings & all corrigendum/ amendments and General conditions of contracts before entry/quoting the rates.
SCHEDULE "A" Part - I (BUILDINGS/STRUCTURES) (Note: This schedule is not pre-priced by MES and the pre-priced rate indicated as "Rs 0.00" under Col.5 signifies this fact only.)
Construction of Block of 16 ORs Quarter in G+4 configuration, RCC framed structure complete all as specified and as shown on drawings.
Construction of Pump House Building, RCC framed structure, single storey, complete all as specified and as shown on drawings.
Construction of UG Sump of 5000 Gallons capacity, RCC framed structure, complete all as specified and as shown on drawings.
Construction of Garbage Bin complete all as specified and as shown on drawings.
SCHEDULE 'A' PART- II SITE CLEARANCE, SITE DEVELOPMENT AND EARTH WORK Details of prepriced Schedule is given in tender documents.
SCHEDULE 'A' PART- III (INTERNAL ELECTRIC SUPPLY) Details of prepriced Schedule is given in tender documents.
SCHEDULE 'A' PART- IV (INTERNAL WATER SUPPLY) Details of prepriced Schedule is given in tender documents.
SCHEDULE 'A' PART- V (ROAD / PATH / CULVERT) Details of prepriced Schedule is given in tender documents.
SCHEDULE 'A' PART- VI ( SEWAGE DISPOSAL) Details of prepriced Schedule is given in tender documents.
SCHEDULE 'A' PART- VII (AREA DRAINAGE) Details of prepriced Schedule is given in tender documents.
SCHEDULE 'A' PART- VIII (EXTERNAL WATER SUPPLY) Details of prepriced Schedule is given in tender documents.
SCHEDULE 'A' PART- IX (EXTERNAL ELECTRIC SUPPLY) Details of prepriced Schedule is given in tender documents.
SCHEDULE 'A' PART- X (LIFT) Details of prepriced Schedule is given in tender documents.
SCHEDULE 'A' PART- XI (DEMOLITION/DISMANTLING) Details of prepriced Schedule is given in tender documents.
SCHEDULE 'A' PART- XII (HOT WATER SUPPLY) Details of prepriced Schedule is given in tender documents.
SCHEDULE 'A' PART- XIII (LIGHTENING PROTECTION) Details of prepriced Schedule is given in tender documents.
SCHEDULE 'A' PART- XIV (FIRE FIGHTING AND FIRE ALARM SYSTEM) Details of prepriced Schedule is given in tender documents.
SCHEDULE "A" PART -XV (MISCELLANEOUS ITEMS) Note:- This schedule is not pre-priced by MES and the pre-priced rate indicated as "Rs 0.00" under Col 5 signifies this fact only.
S&F TV socket including connection complete all as specified and directed.
S&F LED light fittings 4 feet, 1 x 20 W, 220 V AC decorative box type with driver including LED tube light, connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and directed.
S&F LED light fittings with high output diffuser 2 feet, 1 x 10 W, 220 V AC decorative type with driver including LED lamp, connecting up with three core flexible copper conductor cable of suitable size complete all as specified and directed.
S&F LED security light fittings, 1 x 30 watt with integral reflector made of aluminium alloy LM6 with LED driver including LED lamp, surge protector and all accessories, pre-wired, including bracket made of 40mm bore GI tubing, medium grade of 1.5m long, bent to shape with MS clamp, including connecting up with three core PVC insulated sheathed copper conductor cable of suitable size complete all as specified and directed.
S&F Energy efficient five star rated ceiling fan, 1200 mm sweep, 230 volts, single phase AC with service value 6.00 BEE, Brushless Direct Current (BLDC) wothout remote type with accessories like holding down rod, hanging clamps, blades, fan hook including writing MES number (as per standard practice) and connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete in all respect all as specified and directed.
S&F Exhaust fan, heavy duty, of size 300 mm sweep, metallic steel body, single phase, 900/950RPM, including suitable metallic louver, blades, frame and connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete in all respect all as specified and directed.
S&F electric water heater storage type steel body with stainless steel inner tank and heating element upto 1.5/2 KW capacity 25 litre, BEE 5 Star rated complete with all accessories such as safety valve, thermostat, NRV, including PVC connection pipe for hot/ cold water to existing water lines,necessary fixing arrangement by using 50 X 5 mm MS plate and writing MES No and paste the instruction sheet of Do’s and DO NOT complete all as specified and as directed.
S&F MCB single pole of capacity 6 to 32 amps, C-curve, 10 KA, 230 volts, 50 Hz and making connection complete all as specified and directed.
S&F MCB single pole and neutral of capacity 6 to 32 amps, C-curve, 10 KA, 230 volts, 50 Hz and making connection complete all as specified and directed.
Supply, fixing, connecting, testing and commissioning MCCB, TP with thermal magnetic release 160 Amps, 25kA breaking capacity, 415Volts AC, 50Hz complete all as specified and directed.
M&L for earthing complete with galvanized steel earth plate electrode 600 mm X 600 mm X 6 mm thick buried directly in ground (earth pit not less than 2.25 Mtr deep below normal ground level with top edge of plate not less than 1.5 Mtr below normal ground level connected to galvanised earth lead wire 4.0 mm dia by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical plate No-3 SSR Part -1 2009 connected to earthing test point including earth wire protection pipe of dia 15 mm (medium grage), excavation and earth work, disposal of surplus spoil, provn of RCC cover 50 mm thick, reinforced with 8mm dia TMT bars @150 mm /C/C both ways with one handle for lifting made out of 10 mm dia TMT bar embedded in precast RCC (1:2:4) type B1, cover slab of size 54 cm x 54 cm x 5 cm and PCC (1:3:6) type C-1 concrete pit, funnel with watering pipe 20 mm bore (light grade) testing on completion complete all as specified and directed. [Note : (a) Proper earthing pit should be provided with pit cover. (b) Excavation/earthwork is deemed to be included in the quoted rate.]
S&F 15 mm bore angle cock, cast copper alloy, chromium plated with long shank and cup, fency type, screwed down, high pressure with crutch or butterfly handle, screwed both ends for iron pipe complete all as specified and directed.
S&F 15 mm bore shower rose, cast copper alloy, chromoum plate with long shank and cup, fency type of length 300mm (minimum) complete all as specified and directed.
Construction of RCC septic tank conventional type designed to carry sewage and sullage water, excavation in ordinary soil, foundation PCC (1:4:8) type D2 (using 40mm graded stone aggregate), RCC M-30 (design mix) using 20mm graded stone aggregate for RCC wall,base slab,baffle wall and roof slab incl beam etc vent shaft,manhole openings with cover connection etc complete with effective depth of 1.50m and overall depth of 3.0m for 100 users complete all as specified and as shown on drawings.
Construction of Soakage well exc. In ordinary soil , foundation in PCC (1:3:6) type C2 (using 40mm graded stone aggregate), wells of honey combed masonry with top ring of RCC M-30 (design mix) using 20mm graded stone aggregate, including intercepting chamber, screen chamber made of brick work in CM 1:4, RCC cover slab in M-30 /SFRC cover, interconnecting pipes of RCC/DWC complete, filled with brick bats, size 1.8m dia x 3.0m deep (effective depth) complete all as specified and as shown on drawings.
M & L for boring of holes under road, pavement, hard standing by trenchless technology using ultra sound technique and necessary machine & including provision of HDPE pipe of 150 mm bore, PN 10, suitable for 0.4 mpa working pressure, for protection of UG cable complete all as specified and directed. (Note: Cost of HDPE pipe shall deemed to be included in the unit rate.)
M&L for construction of brick masonry valve pit chamber of internal dimension 900 x 900 x 900 mm depth with sub class 'B', old size, in CM (1:6) and 10mm thick plastering in CM (1:4) ,PCC (1:4:8) type D2 (using 40mm graded broken stone aggregate ) as in foundation lean concrete ,PCC (1:3:6) type C1 (using 20mm graded broken stone aggregate) as in bedding and copping MS frame with 50x50x6mm angle iron 5mm thick MS sheet cover plate with locking system ,hinges and two coats of synthetic enamel paint over one coat of red oxide primer including preperation of surface ,three coats of white wash on plastered suface (exposed to view ) including necessary excavation in soft loose ,soil ,returning filling in and removal of surplus soil to a distance not excedding 50 m complete all as specified and directed.
Supply, installation, testing and commissioning for Submersible pump horizontal type suitable for open well/UG sump, 10.5 - 30 meter head, discharge 315 - 110 LPM, having capacity 3 HP, including securing cable made up of SWR (Steel Wire Rope) multi stranded, including all kind of connecting accessories, suitable size brass/bronze NRV heavy duty of equal size of delivery pipe, GI fittings such as union, reducers, Tee, Bend etc to connect with delivery line laid in trenches, CPVC column pipe of size 50mm (not less than 6 RM long) or as per OEM design suitable for suction end inserted into UG sump , foot valve heavy duty suitable for column pipe, 3 core copper conductor, flat, submersible cable of size 2.5 sqmm (not less than 30 RM) from starter to pumpset all as specified and as directed by Engineer-in-Charge. Note: Contractor shall provide copper cable connection for pumpsets from panel board to starter , starter to star delta pump sets up, complete all as specified and directed.
S&F DOL Submersible starter suitable for 3HP capacity pumpsets with enclosure panel, fixed inside the LT panel board of separate segments, RYB indicator, Ammeter, Volt meter, On/Off Button, Reverse current/Single Phase preventer, timer relay, overload relay and 3 phase contactors for star delta operation of suitable capcity, connecting of cables, termination, copper lugs and cable glands etc complete all as specified and as directed.
M&L for Earthing complete with GI earth plate elecrode of size 600 mm × 600 mm × 6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to GI earth strip 32 mm x 6 mm by means of bolts, nuts, check nuts and washers of brass or HS steel all as shown in electrical plate No. 3 connected to earthing test point and and necessary excavation and earth work pre-cast RCC(1:1.5:3) type A-1 pit cover 50mm thick, reinforced with 8mm dia TMT bars @150 mm C/C both ways with one handle for lifting made out of 10 mm dia TMT bar embedded in precast RCC (1:1.5:3) type A-1, cover slab of size 54 cm x 54 cm x 5 cm and PCC (1:2:4) type B-1 concrete pit and angle iron frame and opening arrangement ) incl providing charcoal or coke and common salt in alternate layer of 15 cm compacted thickness all around the earth electrode with funnel and 20 mm bore galvanized iron watering pipe (medium grade) wire mesh, copper lugs, complete in all respect, protected by 40 mm bore (light grade) galvanized iron pipe up to earthing test point as directed, incl disposal of spoil to a distance not exc 50 mtr and necessary testing on completion complete all as specified and as directed. [Note : (a) Proper earthing pit should be provided with pit cover. (b) The unit rate includes for protection pipe and earth strip upto 7.5 m. Any variation in length of earth lead and protection pipe beyond 7.5 m shall be measured and paid seperately. (c) Excavation/earthwork is deemed to be included in the quoted rate.]
Supply and installation, testing and commissioning of copper wound transformer step down, outdoor type, complete with standard fittings, HT 6.6 KV 3 Phase, LT 433 volts, 3 Phase + 1 Neutral, 4 wire with off load tappings on HT side to vary secondary voltage within limit, all as per IS:1180 (Part I), level 2 (as per latest edision/amendment), 3 Phase, & 50Hz, Type of cooling ONAN, off circuit Tap switch changer, including all connected accessories as per standadrd schedule of capacity 100 KVA, top up/first filling of oil and testing as per standard practice all as specified and directed. Specification of Transformer :- (Item No. 13.24 contd..) (a) Cooling type - ONAN oil cooled as per IS 335, BS 148, D 1473, IEC Pub 296. (b) Winding - Copper wound as per ASTM B-49. (c) Air clearance - Minimum air clearance for HV-HV and LV-LV as per IS 1180 or latest. (d) Vector group - DYN-11. (e) Flux density - Should not be more than 1.55 Tesla (f) Star rate - 5 star rated and labelled on the body with colour code, logo etc as per BEE standard. (g) Transformer tank shall be constructed robust rectangular shape with wall thickness not less than MS plate supported with adequate Angle iron at all corners, joints etc with healthy fabrication method, painted inside with weather proof oil resistance paint, external body painted with weather proof paint after applying healthy zinc chromite primer. Colour shall be get approved by GE. (h) Radiators - Press fin type (j) Pressure Release Device shall be provided with operating pressure before 0.25 Kg/Sqcm (k) HT/LT bushings shall confirm IS 3347 with standard make
Serial Item No. 15.22 (Contd....) (l) HT/LT spindles shall be made up of brass and fitted properly on their respective terminals. (m) Silica gel with breather shall be placed at the place where moisture ingress can be avoided to maximum and it must be mentioned in the drawing during approval stage. (n) Oil level guage, Temp guage and pressure guage shall be provided where indicated as per approved drawing. NOTE :- (Item No. 13.24 contd..) (a) All the arrangements for loading unloading and placement on platform shall be made by the contractor. (b) The contractor/manufacturer shall furnish original certificate (paid voucher and test certificate) of the CRGO manufacturer. (c) The manufacturer /contractor shall furnish the diameter of LV and HV copper winding and its total resistance. The stray losses shall be specified in percentage terms. (d) The contractor shall get the approval of GE for the make of the transformer they plan to procure. (e) Prior to manufacturing the general arrangement drawing design details of the transformer shall be got approved by GE. (f) Transformer shall be dispatch only after inspection clearance by inspecting officer detailed bu Accepting Officer. (g) Testing of transformer at various load factors shall be done at site with the help of OEM technician till achieving satisfactory result at site in front of Engineer-in-Charge. (h) All the HT/LT UG cables shall be properly connected it at their respective terminals without any any contact before testing.
Serial Item No. 15.22 (Contd....) (j) Transformer shall be provided with robust lifting hook so that it can be easily lifted for transportation and shifting. (k) Transformer shall be mounted on channel and wheel with stopper pin so it can be moved easily. (l) Necessary foundation with plinth shall be provided as per manufacturer's recommendation, quoted rate shall be deemed to be included accordingly.
M&L for pole painting complete with two coats of aluminium paint over a coat of red oxide primer (including over the nut bolts, clamp and channels) including preparation of serfaces complete all as specified and directed.
M&L for numbering LT/HT pole after making circle in black colour paint and writing clearly by using soft brush or with the help of stencil sponge in white colour width of letter shall be maximum 1cm and height shall be max 4cm complete all as specified and as directed by Engineer-in-Charge.
M&L for Earthing complete with copper earth plate electrode of size 600 x 600 x 3.15 mm thick buried directly in ground with earth pit not less than 2.25 meter deep below ground level with top edge of plate not less than 1.5 meter below normal ground level connected to 20×3mm copper strip as earth lead by means of nuts, bolts, check nuts, washers of galvanised iron as steel, protected by galvanized iron pipe 40mm bore (Medium grade) all as directed including cement concrete (1:3:6) type C-1 earth pit with precast RCC (1:1.5:3) type A-1 cover slab of size 42 x 42 x10cm thick reinforced with 8mm dia TMT bars @ 15 cm c/c both ways with 10mm dia mild steel round bar of 30 cm long, bent to shape as lifting handle, funnel, wire mesh, 20 mm bore galvanized iron pipe (medium grade) for watering, earth testing point, charcoal or coke and salt in alternate layers with necessary earth work in soft/loose soil complete all as shown in electrical plate No 3 of SSR Part I including testing on completion all complete as specified and directed.( Copper strip upto 7.5m including testing consider in this item). [Note : (a) Proper earthing pit should be provided with pit cover. (b) The unit rate includes for protection pipe and earth strip upto 7.5 m. Any variation in length of earth lead and protection pipe beyond 7.5 m shall be measured and paid seperately. (c) Excavation/earthwork is deemed to be included in the quoted rate.]
S&F LED street light fitting 70 Watt 230 V AC outdoor type, IP65/66 protection, with high pressure die cast aluminum hosing and heat resistantcomplete with driver, with impact and corrosion resistant including thermal management in multiple optics, including LED lamp, surge protector and all accessories, pre-wired, including bracket made of 40mm bore GI tubing, light grade of 1.5m long, bent to shape (threaded and drilling holes for wire entry) with MS clamp, including connecting up with three core PVC insulated sheathed copper conductor cable of suitable size complete all as specified and directed.
Cutting of road/ hardstanding of size 30 cm width x 45 cm depth for laying of cable protection pipes not more than 80mm bore including making good the road surfaces with necessary returning filling and 15 cm thick PCC (1:2:4) type B1 (using 20mm graded stone aggregate) on top, complete all as specified and directed. (Note: Cable protection pipe shall be measured and paid seperately.)
M&L for Cable Junction Box of size 130 x 180 x 77 mm, outdoor type, thermal protection, mounted on pole by MS clamp of suitable sizes, with metric knockout for cable entry of size 10 Sqmm, complete all as specified and directed.
S&F Time Switch, astronomical type, digital time 24 Hrs, 230 V, single phase of 20 Amp rating with contactor fitted inside steel enclosure double door outdoor type of thickness 3mm complete all as specified and directed.
Note for Item No 15.32 & 15.33 : (i) The contractor shall submit the test certificate from manufacturer (ii) The contractor shall submit QAP (Quality assurance programme) within 15 days after placement of order for LT Panel testing at factory. LT Panel shall be dispatch only after inspection at manufacture premises to be done by OEM Auth & MES Auth at manufacture permisses. (iii) The contractor shall furnish origional bill certificate (Purchase voucher and test certificate) of the LT panel manufacturer. (iv) The contractor shall get the approval of GE for make of the LT panel board before placing the order. (v) Prior to manufacturing the general arrangement drawing design details of the LT panel shall be get approved from GE. (vi) Connection of LT panel/starters/MCCBs through multi core copper conductor control cable of suitable size (irrespective of length) is deemed to be included in the unit rate.
LIFT Annual Maintenance Contract through authorized OEM for one year including minor repair of technical faults and routine preventive maintenance, weekly & monthly compulsory checking and preventive maintenance by suitable technician from manufacturer and repair/replacement of the following:- (a) Repairing service of defective parts (b) Parts repalcement for Motor bearing, solonoid valve, solonoid coil, rubber pad, main rope, speed governor/governor rope, DBR, Limit switches, proximity switch, Junction box, Hydraulic oil, Break liner, counter weight shoe liner, Car door, landing door lock contact, contactors and relays, transformer, hydraulic tubes/pipes and hydraulic fluid etc. (c) Motor winding, replacement of controller PCB, Hall buttons/Indicators, COP button/Indicators, Cabin fan, car door motor. (d) Main switch, ELCB/MCB, earthing, cabin fan and light etc. (Note: AMC shall be carried out after Defect Liability period.)
Supplying, installation of silent Diesel Engine Driven generating set 415 volt, 3 phase 4 wire 0.8 PF,engine as per IS 10001/10002 and alternator as per IS 13364 complete with relay panel and switch gears for Automatic starting on main failure, control panel having meter and sound proof canopy as per CPCB norms and foundation of capacity 25 KVA Comprising and including of following:- (A) DIESEL ENGINE: Liquid cooled turbo charged with after cooler to deliver suitable BHP at 1500RPM under NTP conditions of BS 5514 and conforming to IS 10002, DIN 6271 & ISO 3046 with an overload capacity of 10% for one hour in any 12 hours continuous operation. Diesel engine of rated speed at full load electric start developing with system with radiator and including electronic governor control of class A1, engine control panel, lub oil pump, water pump, fuel tank, exhaust pipe with silencer and suitable for electric start with batteries of adequate capacity and suitable for alternator of specified capacity complete with fly wheel direct/flexible coupling and coupling guard complete with following:- (a) Radiator with blower fan or heat exchangar with guard. (b) Pipe coupling for engine cooling system piping. (c ) Corrosion inhibitor coolant (d) Paper element filters (i) Fuel filter (ii) Lube oil filter complete with first filling of lub oil (iii) Bypass filter (e) Fly wheel housing and fly wheel to suit alternator. (f) Engine bearing mechanism in fly wheel housing. (g) Shut off coil with safeties for LLOP/HWT/over speed. (h) Dry type replaceable air cleaners and vacuum indicators. (j) Residential silencers.
Serial Item No. 15.36 (Contd....) (k) Stainless steel exhaust flexible bellows. (l) Motor driven priming pump. (m) Battery charging alternator. (n) Exhaust piping made out of STIC 'C' class, MS pipe inclusive of all accessories and hardware, necessary supports scaffolding as per manufacturer's recommendations to sustain back pressure with rain cap. (o) Mineral wool insulation 2 inch thick suitable for 400 degree Celsius temperature cladded with aluminium sheet 30 gauge for the entire length of exhaust pipe. (p) First fill of oil, coolant and diesel during commissioning and 12 hours testing. (q) Interconnecting copper cabling of adequate capacity batteries control. (r ) Fuel pipe class (s) Self starter (t) Electric operated electronic governor. (u) Fuel injection pump. (v) Electronic instrument panel, complete with all accessories as per manufacturer's specifications displaying the following:- (i) Battery as per manufacturer recommendation. (ii) Water temperature. (iii) lubricating oil pressure. (iv) Engine speed -1500 RPM (v) Engine hours (vi) Frequency. (vii) Voltage. (viii) Safety control (Trip and indication). (ix) High water temperature (x) Low lube oil temperature & (xi) Overspeed stop
Serial Item No. 15.36 (Contd....) (c) Suitable battery charger connected to load side to charger battery including connecting leads. (Note: AMF Panel shall be installed out side the acoustic enclosure). (E) BASE PLATE: Common fabricated base frame for engine & alternator made from structural Steel channel, jerk proof on PCC 1:2:4 type B1 foundation including adequate number of anti-vibration pads in adequate quantity all as per the recommendation of the manufacturer. (Note:- Cost of suitable size of PCC foundation is deemed to be included in the unit rate quoted by the contractor). (F) DIESEL STORAGE TANK: Fuel tank of MS sheet of capacity not less than 12 Hrs continuous operation on full load with fuel level guage, drain plug, locking arrengements, etc including connection to Engine through fuel filter/ manual feed pump as per manufacturer recommendation. (G) ACOUSTIC ENCLOSURE: Sheet metal fabricatedcope type silent enclosure manufactured on CNC machines as per CPCB norms and power coated after seven tank process, the enclosure shall be designed for reducing the sound level to 75 DB (A) at a distance of 1 M at 75 % load under field condition and 70DB at 3 M from Gen set when DG set is working at full load along with testing conformance, laveling certification etc as laid down in GSR No.371(E) dt 17 May 2002 or latest. (H) MISC: Tool kit operation, maint cat, spare part list, overhauling manuals, guarantee card etc shall be provided as per manufacturers standard practice. (j) PCC foundation of size 60 cm projection on both sides from the actual size of DG set and height of 1.20 mtr above ground level and 0.75mm below ground shall deemed to be included on the quoted rate. (k) Adequate diesel and load bank for 12 Hrs fall load testing shall be provided by the contractor during testing and commissioning of DG Set.
Supply & stacking of sweet earth (only approved earth) from out side of MD land complete all as directed. (Note: Earth measured in stacks will be reduced by 20% for payment.)
Supply and land scaping/ plantation of Barmudas/American grass/carpet grass / Italian grass, small size by dibbing root method including preparation of ground to required depth and filling of sweet earth, cow dung and watering etc complete all as specified and directed by Enge-in-Charge.
Supply and planting of sapling of plants of shurbs of different spices with height 2 to 3 feet including preparation of ground to required depth and filling of sweet earth, cow dung and watering etc complete all as specified and directed by Enge-in-Charge.
Supply and planting of sapling of plants of palms and mounds plants of different spices with height 3 to 4 feet including preparation of ground to required depth and filling of sweet earth, cow dung and watering etc complete all as specified and directed by Enge-in-Charge.
Supply and planting of sapling of decorative and ornamental plants of different spices with height 5 to 6 feet including preparation of ground to required depth and filling of sweet earth, cow dung and watering etc complete all as specified and directed by Enge-in-Charge.
Supply and planting of hedges and ground covers of different spices including preparation of ground to required depth and filling of sweet earth, cow dung and watering etc complete all as specified and directed by Enge-in-Charge.
Supply and installation of Jet Pump with air pipe ad elivery pipe of 25mm bore GI pipe (medium grade) and 32mm bore GI pipe (medium grade) and GM jet assy capacity 2HP single phase 230V AC complete all as specified and as directed by Enge-in-Charge. .
S & F 25mm bore GI tubing, medium grade, with all fittings such as bend, unions, tee, elbow, reducer including testing laid in trenches, complete all as specified and directed.
Taking out unservicable sheet metal DB Box/ main switch complete all as specified and as directed.
Taking out unservicable light fittings af any size and type complete all as specified and as directed.
Supply ,fixing, testing and commissioning repeater fire alarm control panel/annunciator working as programmalble active or passive repeater as per ground requirement, addressable fire system type, touch screen user interface panel for menu options, having facilties to updates automatically through the network, capacity to control all the detectors installed in the building through main control panel board intelligent functionality, transparent, battery backup and power supply included, plug/play and go features, capacble for remote readout/control, designed to provide full indication of events and controls of the main control panel installed in various locations and shall be updated through the network, primary supply 230V AC, operating voltage 30V DC including all connecting cables internally from one panel to another for better backfeed networking and communicating system for all panels complete all as specified and as directed.
S&F fire alarm cable plain annealed solid copper conductor wire to BS EN 60228, class 2, primary insulation of glass mica FR tape, secondary insulation of high performance PVC type - C, earth wire of annealed tinned copper to BS EN 60228 electrostatic screen of aluminium fire barrier with 100% overlap, FRLS PVC ST-2 sheathed 2 core wire of size 1.5sqmm drawn on ceiling/floor/conduit or casing capping including all kind of PVC conduit pipe and accessories complete all as specified and as directed. Note: Cable connection to all the fire alarm units, sensors, indicators, panels and modules shall be deemed to be included in quoted price.
S&F portable type fire extinguisher cylindrical in shape, foam type fixed inside the lift and exit way staircase wall and entrance door of each quarter including complete mounting accessories complete all as specified and as directed. Note: Lift x 02 Nos each, Stair case landing x 02 Nos each, Entrance of every quarter x 02 Nos each
S&F hose box with glass door suitable for indoor/outdoor type for keeping 02 Nos hose pipe of length 15 meter each, branch pipe nozzle, coupling etc of MS sheet of thickness 2.0 mm complete all as specified and as directed. (Note : Nozzle head should be made up of brass metal heavy grade as per IS grad. Hose box needs to be provided with lock and key facilities
S&F Automatic star delta starter of capacity 15HP with suitable capacitor mounted contactors of 40Amp, 3 Phase, 415V, 50Hz including overload relay of 63Amps, single phase preventor, volt meter, ammeter and R-Y-B LED indicators enclosed in MS sheet panel with all kind of inernal wiring, connector blocks complete all as specified and as directed.
S&F copper flat 3 core cable, PVC insulated suitable for pump operation, 3 phase, 4 sqmm size, PVC insulated heavy grade including connection from starter to motor for star/delta connection complete all as specified and as directed. Note: PVC cable trunk with cover from ground floor to top of the building upto pumpset and all kind of fixing accessories shall deemed to be included in quoted rate.
Supply and fixing Poyethylene circular tank, vertical mounted with closed top cover, 3 layer quoted , heavy grade of capacity 5000 ltr over the G+4 top of the building including tank adapter, internal connection of nearby water tanks with GI pipes, all kind of GI pipe fittings vary from 100mm to 25mm, connecting upto fire pump suction end complete all as specified and as directed. Note: (i) GI pipes and connected control valves shall be measured and paid separately. (ii) Feasibility for fixing/installation of 5 x 5000 Ltr tanks shall be obtained from B/R scope.
S&F emergency exit display board of size 30cm x 10cm, at exit point of each floor made up of acrlylic cover with pre-wired LED lights for illumination at night complete all as specified and as directed. Note: (i) Writing letters shall be displayed in red colour. (ii) Concealed type Point wiring shall be provided with switch control by taping from nearest junction box or nearest point by the contractor.
Supplying and installation of Smart RF/ Single Phase AC Meter Tamper Proof, Static Meter of Class 1.0, 315 V, 50 Hz, 10 A-60 A bearing IS No IS-16444 and relevant IEC standards with inbuilt Radio Frequency communication facility with self healing mesh network with default and on demand display, billing data generation facility, anti-tamper features, Microprocessor and LED/LCD based circuitry including SMC Meter Box of minimum size 250 X 250 X 160 mm or as suitable for 1 Phase meter with viewing glass, concealed hinge and earth bolt plugged complete all as specified and directed. Meter Should support sending the following data : 15/30 min instantaneous data for voltage, current, power factor, power, cumulative energy and frequency, monthly billing survey for Cumulative Energy and Max Demand to software Meter shall have connect / disconnect functionality operable from mdm/billing software and prepaid features shall be MDM / Billing end as per prevalent IS . The communication system shall support: (a) On demand energy transfer (b) Two way communication with DCU/HES (c) Clock Synchronisation facility with HES (Head End System) (d) Communication including different makes of meter shall be such that it shall communicate with same DCU directly or via Mesh Network. (e) Meter Protocol shall be open interface system in accordance of transmission control protocol/internet protocol. (f) The cost of the meter shall include 2 years recurring sim charges during the defect liability period. Notes: (a) It shall be possible to run the meter in both prepaid and postpaid mode (b) The meters shall carry 5 year warranty. (c) The OEM shall need to share the Authentication / Encryption keys of the meters along with relevant protocol details with the department. The department shall need complete support of the OEM to be able to integrate the meter with any software of the department choice.
Supply / Planning / Setup/Tuning of RF/ Communication infrastructure including the Network Management and Headend for the project the IP-67 protection Data Concentrator Units (DCU) compatible for remote Automatic Metering Infrastructure (AMI) solution and capable of communicating with the smart energy Meter in the corresponding frequency band and with the data server through GPRS/Ethernet. It shall have internal memory to store data of at least 200 modules. It shall have inbuilt battery back-up. It shall have IP-67 protection. It shall support auto discovery of the meters and self healing mechanism for the breaks in the RF network. It shall have the following minimum features: (1) It shall be able to configure the communication with underlying nodes / meters (2) It shall be able to pull data at conifigurable frequency from the nodes / meters. It shall be able to prioritise control commands. (3) DCU shall support on demand data from nodes. (4) DCU shall support data transfer via cellular / optical fibre communication. In case of cellular communication, it shall support dynamic IP sim from any telecom service provider (minimum 4G and fallback to 2G) working in the location. (5) DCU shall be able to communicate to the nearest meters directly. For farther meters, it shall allow communication through exisiting meters via mesh or other formation (repeater meters etc). (6) DCU shall allow more than one make of meters for the communication. (7) Quoted rates deemed to be included for hosting and GPRS charges/communication charges/broadband charges for minimum 2 years of defect liability period after completion.
Supply and Setup of Meter Data Management (MDM) system including supply and configuration of the Web based Software with following modules: (i) Meter Data Management Module The meter data management module shall be deemed for collecting the data from the meter to DCU and server and vice versa, make the data available in bidirectional mode ton the currency recharge, online payment gateway, post paid billing modules, scheduling maintenance, low balance warning, quarter wise KVA allocation/tripping, tariff regulations, software customisations etc all as directed. (ii) Secure Mobile App/PC Based/Swipe Machine/Online Payment Gateway for all users assigned by the BSO/GE. (a) 30 min instantenous data from all the meters for minimum seven parameters- Cumulative Energy, Power, Current, Voltage, Power Factor and Frequency. (b) Abstract Download for Monthly and quarterly billing survey data for cumulative energy and max demand and tampering features. (iii) Billing Module: The billing module capable to create data sheet for currency recharges, recharge history, maximum demand individually, user complaint registers, cheque/payment reconcillations, fixed charges, energy bill details etc. (iv) Occupation and Vacation Module: Provision to enter admin controls for transfers/vacations. The system shall support occupation/ vacation based on the unit categories. The system shall support automatic data capture on occupation and vacation events. (v) Customer Module: The system shall include a customer portal for the resident /occupant to log in and view their own energy / billing data. There shall be android and iOS mobile apps for the user to monitor its own data and balance on regular basis.
Item No 15.61 Contd ....... (vi) Energy Accounting Module The system shall include features of energy accounting. The system shall be able to account for total energy block wise, facility wise and shall also allow calculations of unaccounted energy in case tally with incomer EB energy meter. (vii) Communication Module The system shall provide communication of energy data and bills via print, email and sms methods. (viii) Meter Master Data: The system shall support meter master data repository. The system shall support meter replacement process. (ix) Excel Export:The system shall support export of metering and billing data in excel format. (x) Customer Care Module - the software shall include a customer care module where the user shall be log in any complaints. The service provider shall monitor the complaints and carry out the necessary activities for the complaints resolution. (xi) Meter Installation Module - The software shall include an app based meter installation module where the meter installation or changes can be captured on the app itself and the readings shall be demonstrated to the user if required on the app itself. (xii) Activities Communication - The software support communication of the various activities such as occupation, vacation, meter change. personal detail change etc. with the user as well as the department on email.
NOTE: Schedule of cedit (Sch 'A' Part- XVI) amount of Rs 1,06,615.00 shall be deducted from the total quoted amount of BOQ.
DNS CONSTRUCTION COMPANY (BID ID -3049848)
NARSINGH DEVELOPERS LLP (BID ID -3049923)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
145828331.pdf
Tender Document • 0.65 MB
145828334.html
Tender Document • 0.07 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .