Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹8.2 LAccepted-AOC | L1 | Accepted-AOC Agrement Executed |
Tender Value
₹8.2 L
EMD Value
₹20,500
Closing Date
16 Sept 2020, 6:00 pmClosed
Assistant Executive Engineer
Pwd Electrical Subdivision, Kasaragod, 671121
Generator Set Installation
2020_PWD_380964_2
ESD/TN/10/2020-21
Open Tender
Electrical Works
Item Rate
90 days
Narkilakkad
Please refer Tender documents.
7 documents required · 7 mandatory
₹1,850
Yes
online
₹20,500
Yes
12 Feb 2021
9 Sept 2020
22 Sept 2020
9 Sept 2020
16 Sept 2020
9 Sept 2020
Amount
Wiring
od110179/2019_2020 : Supply, conveyance, Installation, testing & commissioning of 62.5 KVA Diesel Generator set with integral acoustic enclosure as per CPCB norms with srandared acessories as per technical details given below. 1. Engine : a) Make of Engine - Kirloskar/Escorts/Mahendra/Cummins/Greeves Cotton b) Type of Engine - Diesel Engine c) No. of Cylinders - As per manufactures standards. d) Method of Cooling - Water cooled with radiator. e) Design - Suitable for generating set operation 2.Standard accessories with Diesel Engine a) Fly wheel to suit flexible coupling b) Close Coupling c) Air cleaner d) Radiator with fan provided with fan guard. e) Fuel Pump f) Fuel filter g) Lubricating oil filter h) Exhaust silencer i) Exhaust Muffler j) Battery Charger/Generator 3. Engine Instrument Panel with the following items a) Starting switch with key or button b) Lubricating oil pressure gauge. c) Water temperature gauge. d) RPM Indicator with hour meter e) Battery charging Ammeter 4. Safety Controls for Engine a) Trip for low lubricating oil pressure b) Trip for high water temperature. 6. Brushless Alternator a) Make - Kirloskar/KEL/Crompton/Greaves/Stamford b) Type - Self exited and self regulated. c) Capacity - 62.5 KVA/50 K W @ 0.8PF d) System of Voltage - 3 phase, 415 V, e) Frequency - 50 Hz f) Insulation - Class F/H The Alternator should confirm to IS 4722. Operation and service manual, spares and tools shall be provided. 7. Fuel Tank Suitable size built in type integrated with the acoustic enclosure Fuel connection shall be done as per standards 8. Battery Suitable size built in type integrated battery with leads and terminals of appropriate AH capacity as per Manufactures requirement. Automatic Battery charger Solid state phase indication lamp for supply ON/OFF with HRC protection. standard control panel as per Kerala Electrical Inspectorate requirements, with suitably rated 4 pole MCB and accessories such as Multi function meter and separate Energy meter etc.Complete.
14.1 : Excavation for foundation in soft soil including dressing of sides and ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 metres.
14.10 : Providing and laying in position reinforced cement concrete 1 :2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required (excluding reinforcement).
90.12.1.29 : Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in ground including excavation of trench of size 35 x 75 cm, refilling the trench etc. as required but excluding sand cushioning and protective covering (in ordinary soil).3.5 core 50 sq mm
90.12.7.29 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 50 sq mm with factory made clamp
90.12.1.40 : Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in ground including excavation of trench of size 35 x 75 cm, refilling the trench etc. as required but excluding sand cushioning and protective covering (in ordinary soil).4 core 10 sq mm
90.12.1.3 : Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in ground including excavation of trench of size 35 x 75 cm, refilling the trench etc. as required but excluding sand cushioning and protective covering (in ordinary soil).2 core 10 sq mm
90.12.7.3 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.2 core 10 sq mm with factory made clamp
90.12.7.40 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 10 sq mm with factory made clamp
90.12.10.2 : Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation50/38 mm or nearest size
9.1.22 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 50 sq. mm (35mm)
9.1.2 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 X 10 sq. mm (19mm)
9.1.32 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm)
od50844/2020_2021 : Supply and fixing 100 A , 415V , AC 23A , COS in SS Enclosure with front handle making connections, etc. as required.
90.11.1.19 : Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required6 way (8+12) - double cover TPN vertical DB with provision for fixing MCCB as incomer and SP/ TP MCB as outgoing (IP 42/43)
90.14.10.2 : Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16 A-100A, 25/35 kA (Ics=100%Icu), 3 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL
2.10.4 : Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole
od50846/2020_2021 : Supplying and fixing 40 amps to 63 amps TP MCB, "C" curve, 10kA suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
2.10.1 : Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
2.11 : Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
od110506/2019_2020 : Supply and providing 100mm/ dia B class MS Pipe size M. S. pipe -4.85mm thickness complete with suitable size 12mm flange coupling with minimum 5/6mtr using allied packing with MS bolt with washer and rising the same on the wall/ parapet using chain pullies, scaffoldings, supports with M.S angles/channels etc. including painting the pipe with one coat of zinchromate primer over a coat of high temperature resistance alu. paint etc. for extending the exhaust pipe of the newly errected 160KVA D. G. sets.
90.6.10.1 : Supply and fixing of following sizes of light gauge PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required20 mm
1.17.20 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.2 x 4 sq. mm
1.27.3 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.4 Module (125mmX75mm)
90.10.3.15 : Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )32A DP switch with indicator
90.10.3.33 : Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A 3pin Shuttered socket
od110504/2019_2020 : Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required.
od97524/2019_2020 : Providing and fixing 25 mm X 3 mm G.I. strip earth lead from the test joint to the earth plate
od97525/2019_2020 : Providing and fixing 2 X 25 mm X 3 mm G.I. strip test joint for earthing system
od97526/2019_2020 : Supply and providing 25x6mm brass nut and bolt etc. as required.
od98250/2019_2020 : Supplying and laying 25 mm X 3mm copper strip on surface or in recess for connections etc. as required.
90.16.1.6 : Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required6.00 mm copper conductor (4 SWG)
90.16.2.1 : Supply and laying of the following sizes of B class GI pipe laid 0.6 m below ground level including excavating trench of suitable size and refilling etc, as required.15.mm dia. G.I pipe ( medium class)
90.16.1.2 : Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.65 mm copper conductor (12 SWG)
90.16.1.1 : Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.00 mm copper conductor ( 14 SWG)
90.16.5.1 : Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.00 mm (14 SWG)
90.16.5.2 : Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.65 mm (12 SWG)
90.16.5.6 : Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.6. mm ( 4 SWG)
od97533/2019_2020 : Supply and providing 9 Litre capacity GI Fire Bucket painted in post office red with primer coat of red oxide and written with white paint 'FIRE' mounted on MS angle frame work/ wall bracket filled with fine sand, painting the bracket/ floor stand including making good the damages, colour washing etc. as required
od35993/2020_2021 : Providing and fixing Fire Extinguisher-ABC 5 Kg Type at suitable location, etc. as required.
od97535/2019_2020 : Supply and providing 2.00 mm thick, 3.3 kV, Synthetic elastromeric fire retardant insulating sheet
od97538/2019_2020 : Charges towards the preparation of necessary plan, scheme and other related papers for submission to KSELB & KSEB - First A3 Sheet
od110502/2019_2020 : Charges for additional copies of Electrical/fire Drawing per A3 sheet
od97540/2019_2020 : Fees for getting sanction from Electrical inspectrate including all laison work etc.(actuals will be paid on production of relevant documents.)
Bidder Name
HARIS T A
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_544816.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .