CE Jodhpur Zone
HQ Chief Engineer Jodhpur Zone Jodhpur Opp Military Hospital Rasala Road Jodhpur
PROVISION OF MODERN LPG BLDG ALONWITH CONNECTED SERVICES AT JODHPUR MIL STN
2025_MES_727705_1
800630/E8
Open Tender
Civil Works
365 days
GE (A) No. 2 Jodhpur
As Per NIT
10 documents required · 10 mandatory
₹2,000
GE (A) No. 2 Jodhpur
₹4.5 L
3 Mar 2026
3 Mar 2026
16 Jun 2026
10 Mar 2026
9 Jun 2026
26 May 2026
Lump sum price worked out by the contractor for "BUILDING WORKS" as listed in Schedule ‘A’ Part-I representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES B/F from Sl page No. 28
Lump sum price worked out by the contractor for "SITE CLEARANCE, EXCAVATION & EARTHWORK" as listed in Schedule ‘A’ Part-II representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES B/F from Sl page No. 30
Lump sum price worked out by the contractor for "INTERNAL WATER SUPPLY" as listed in Schedule ‘A’ Part-III representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES B/F from Sl page No. 31
Lump sum price worked out by the contractor for "INTERNAL ELECTRIFICATIONS" as listed in Schedule ‘A’ Part-IV representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES B/F from Sl page No.34
Lump sum price worked out by the contractor for "ROAD & PATH" as listed in Schedule ‘A’ Part-V representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES B/F from Sl page No. 37
Lump sum price worked out by the contractor for "SEWAGE DISPOSAL" as listed in Schedule ‘A’ Part-VI representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES B/F from Sl page No. 39
Lump sum price worked out by the contractor for "AREA DRAINAGE" as listed in Schedule ‘A’ Part-VII representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price of prepriced by the MES B/F from Sl page No. 40
Lump sum price worked out by the contractor for "FENCING, COMPOUND WALL & GATE" as listed in Schedule ‘A’ Part-VIII representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES Rs. B/F from Sl page No. 43
Lump sum price worked out by the contractor for "LIGHTENING PROTECTION" as listed in Schedule ‘A’ Part-IX representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES B/F from Sl page No. 44
Lump sum price worked out by the contractor for "EXTERNAL WATER SUPPLY" as listed in Schedule ‘A’ Part-X representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES B/F from Sl page No. 45
Lump sum price worked out by the contractor for "EXTERNAL ELECTRIC SUPPLY" as listed in Schedule ‘A’ Part-XI representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES B/F from Sl page No. 47
Lump sum price worked out by the contractor for "FIRE DETECTION, FIRE ALARM AND FIRE FIGHTING SYSTEM" as listed in Schedule ‘A’ Part-XII representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES B/F from Sl page No.49
Lump sum price worked out by the contractor for "DEMOLITION OF FENCING" as listed in Schedule ‘A’ Part-XIII representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES B/F from Sl page No.50
Sch 'A' PART-XIV (MISCELLANEOUS ITEMS) Notes: (i) This schedule is not pre-priced by MES and the pre-priced rate indicated as "Rs 0.00" under column 5 signifies this fact only. (ii) Excavation and earth work except for the items which categorically includes for same shall be measured and paid under Sch "A" Part-II "SITE CLEARANCE, EXCAVATION & EARTHWORK"
INTERNAL WATER SUPPLY Supply & fixing 15mm bore fancy type chromium plated pillar cock with wall flange, screwed for iron pipe or CPVC pipes or for brass ferrule and fixed complete all as specified and directed. Make -JaguaR Cat Part No. ORP-10001PM-7037 or equivalent complete all as specfified.
INTERNAL WATER SUPPLY Supply & fixing overhead shower 150mm x 150mm of square shape single flow with rubit cleaning system ABS body crome plated with gray face plate with arm having swivel joint chromium plated complete all as specified and directed all as specified and directed. Make -Jaguar Queen series Cat Part No. OHS-35495 or equivalent
INTERNAL WATER SUPPLY Supply & fixing 15mm bore fancy type chromium plated bib taps wall flange, screwed for iron pipe or CPVC pipes or for brass ferrule and fixed complete all as specified and directed. Make -Jaguar Essco Series or equivalent
INTERNAL ELECTRIFICATIONS: - S & F LED batten suitable for indoor application 20 W, 4' length, wall mounted with aluminium housing, end cap made of ABS plastic of white colour finish and high efficiency translucence (HET) diffuser and integral electronic driver including two point surface mounting on wall/ ceiling and connecting up with twin core twisted flexible copper conductor cable of suitable size complete all as specified and as directed by Engr-in-Charge. Make : Havells Cat part No. LH EXACP7IN1W 020 or equivalent
INTERNAL ELECTRIFICATION: S&F sheet metal enclosure flame proof, weatherprof. (for DB's when MCBs to be used), flushed in wall single pole and neutral Double door, 8 way, 240 volts with PVC MCB blanking plates, stove enamelled, dust and vernim proof suitable for incorporation of MCB's and isolators etc complete all as specified and as directed.
SEWAG DISPOSAL Supply, install, jointing and commisioning On site LLDPE conventional septic tank for 10 users, designed to carry sewage and sullage water, including excavation in any type of soil, PCC 1:4:8 below foundation, Vent shaft, connection etc., complete for., complete with effective depth of 1.5 m and overall depth of 3m complete all as shown on drawing and as specified.
FENCING, STEEL GATE & COMPOUND WALL: -M&L for Mild steel gate 5.5 metre wide and 1.25m high from top of foot path, in double leaf including RCC pillars, excavation and earth work in any type of soil, plastering 10 mm in CM 1: 4 on RCC pillars,applying two coats of weather proof paint over primer, painting to steel surfaces with two coats of synthetic enamel paint over a coat of red oxide primer complete all as specifed & directed as shown on Drg No CEJZ/TD/06 Sht 1/2 and 2/2.
FENCING, STEEL GATE & COMPOUND WALL: -M&L for steel gate 1.2 metre wide and 1.25m high from top of foot path, in Single leaf including RCC pillars, excavation and earth work in any type of soil, plastering 10 mm in CM 1: 4 on RCC pillars,applying two coats of wweather proof paint over primer, painting to steel surfaces with two coats of synthetic enamel paint over a coat of red oxide primer complete all as specifed & directed as shown on Drg No CEJZ/TD/06 Sht 1/2 and 2/2
External water supply : -M&L for valve pit chamber of size 600x600x600mm internal dimension including necessary earth work excavation with earth work on any type of soil, PCC M-10 type C-2 as in foundation, PCC Solid Block Masonry in CM 1:4, 15 mm thick plaster in CM 1:4 internally and externally, flush pointed in same mortar as work proceeds, 75 mm thick PCC coping all round (M-15 with 20 mm aggregate), flooring shall be 40 mm thick PCC M-15 (Nominal mix) laid over 75 mm thick hard core. Top cover shall be made out of MS sheet 3.00 mm thick fixed in angle iron frame made out of angle iron size 40x40x6 mm with two number of hinges on one side and locking arrangement at other side complete including painting with two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer complete all as specified.
External water supply: -Cutting the existing water supply DI/GI pipe line 150 mm dia and taking branch connection of 80 mm dia pipe, including S & F 150 mm x 150 mm x 80 mm DI Tee complete.
External water supply : -M&L for laying of pipe of size 80 mm bore under road crossing by trenchless technology by auguring or mechanical means in any type of soil, including supply and laying of 80 mm bore GI pipe medium grade, complete all as specified and as directed.
External Electric supply : -M&L for 2.5 sqmm twin core copper conductor PVC insulated PVC sheathed cable 1100 volt grde for drawing through poles for making connection to street light fitting provided on poles and upto junction box including thimble etc.
External Electric supply : -Supply and fix press moulded SMC junction box of inner demensions 250x200x105mm, suitable 3 phase/4 core cable including 8 way connector, 10 Amp-01 No MCB SP 230 volt AC 50 Hz 10 KA-01 No weather cable connecction 2z2.5 conductor from MCB to street light fitting and suitable fittings and fixture complete all as specified and directed.
External Electric supply : -Supply, install and commissioning of factory made vermin proof LT panel Outdoor, self supported, CPRI Approved make, front and rear openable, double door hinged type with locking arrangement and slopping top canopy, suitable protection with dust and vermin proof etc, fabricated out of 3.15 mm thick CRCA sheet duly powder coated with 7 tank chemical process, mounted fixed on and included MS angle section 50 x 50 x 6 mm on PCC 1:2:4 type B-1, plateform 60 CM above the ground level and 45 CM below the ground level, factory fabricated with front and back openable double door system with and lock openable by keys, having chromium plated 19 mm dia fancy lock, louvers and air vent, gasket including following (a) Cu bus bar 250 Amps cap 4 wire fixed on insulator not less than 1.0 mtr long bus bar -1 set (b) Incoming MCCB160 Amps, 4 pole, 415 Volts AC adjustble having rupturing capacity 35 KA - 01No ( For Incomming). (c) Outgoing MCCB 4 pole, 125 Amps, 415 Volt, AC, 25 KA with adjustble thermal magnetic release -01 Nos (Outgoing for Pump panel). (d) Outgoing MCCB 4 pole, 32 Amps, 415 Volt, AC, 25 KA with thermal magnetic release -02 Nos ( Lighting -01 & street light & Spare) (e) Outgoing MCB SP 40 Amps,10 KA with thermal magnetic release -02 Nos ( Lighting -01 & street light & Spare) (f) Street light timer with accessories-01 Nos
External Electric supply : -M&L for bore under road crossing by trenchless technology by aguring or mechanical means in any type of soil for laying of Cable of size 16 to 150 mm as specified and directed
FIRE FIGHTING: -Supply, installing & testing of ISI marked ABC stored pressure type Fire Extinguisher dry chemical poweder (ABC) type of capacity 9 Kg, IS 15683 portable type consisting of mild steel body as per IS : 513, mild steel neck ring as per IS : 2052, brass valve, body test pressure upto 30 kg/cm2, anti-corrosive treatment by epoxy polyester coating of 50 micron, jet range minimum 2.5 to 3 metre, working pressure 60-65 kg/cm2 confirming to IS : 2878 suitable for B and C class fire complete and all as specified and directed.
FIRE FIGHTING: -Supply, installing & testing of ISI marked ABC stored pressure type Fire Extinguisher dry chemical poweder (ABC) type of capacity 6 Kg, IS 15683 portable type consisting of mild steel body as per IS 15683, mild steel neck ring as per IS : 2052, brass valve, body test pressure upto 30 kg/cm2, anti-corrosive treatment by epoxy polyester coating of 50 micron, jet range minimum 2.5 to 3 metre, working pressure 60-65 kg/cm2 confirming to IS : 2878 suitable for B and C class fire complete and all as specified and directed.
FIRE FIGHTING: -Supply, installing & testing of ISI marked Carbon dioxide type (CO2) Fire Extinguisher of capacity 4.5 Kg, portable type consisting of mild steel body as per IS : 15683, mild steel neck ring as per IS : 2052, body test pressure upto 250 kg/cm2, anti-corrosive treatment by epoxy polyester coating of 50 micron, jet range minimum 2.5 to 3 metre, working pressure 60-65 kg/cm2 confirming to IS : 2878 suitable for B and C class fire complete and all as specified and directed.
FIRE FIGHTING: -Supply, installing & testing of ISI marked Fire Extingusher Dry Chemical Powder (ABC) Type Trolly mounted 25 Kg confirming to IS : 160018 complete and all as specified and directed.
FIRE FIGHTING: -Supply and fix MS Fire Bucket (dry sand) Capcity 10 ltr confirming to IS : 2546 complete and all as specified and directed.
FIRE FIGHTING: -Supply and fix Fire fighting HooK with wooden stick fire HooK15'' made from forged seel and wooden stic of length 80'' complete and all as specified and directed.
FIRE FIGHTING: -Supply and fix fire hydrant stand post with provision of single outlet comfiring to IS 908
FIRE FIGHTING: -Supply, installation, testing & commissioning of flame proof LPG Gas Detector . Made of aluminium die cast material with self purging semiconductor sensor, BIS/CE/EN/UL approved.
FIRE FIGHTING: -Supply, installation, testing & commissioning of LPG Gas Detector alarm panel suitable for 4 nos LPG gas detectors, complete all as specified and directed by Engr-in-charge.
FIRE FIGHTING: -Supply and fix Deluge Valve systemsuitable for 80mm bore deluge valve with contro panel suitable size piping , pressure gauge complete and all as specified and directed.
FIRE FIGHTING: -Supply, install and commissioning of factory made vermin proof LT panel (for Pump House) Indoor, self supported, CPRI Approved make, front and rear openable, double door hinged type with locking arrangement and slopping top canopy, suitable protection with dust and vermin proof etc, fabricated out of 2.0 mm thick CRCA sheet duly powder coated with 7 tank chemical process, mounted fixed on and included MS angle section 50 x 50 x 6 mm on PCC 1:2:4 type B-1, plateform 60 CM above the ground level and 45 CM below the ground level, factory fabricated with front and back openable double door system with and lock openable by keys, having chromium plated 19 mm dia fancy lock, louvers and air vent, gasket including following (a) Al bus bar 200 Amps, 4 Nos strip fixed on insulator not less than 1.0 mtr long bus bar -1 set . (b) Incoming MCCB 160 Amps, 4 pole, 415 Volts AC having adjustable rupturing capacity 36 KA - 01No ( For Incomming ). (c) Incoming MCCB 125 Amps, 4 pole, 415 Volts AC having rupturing capacity 16KA - 01No ( For Outgoing for pump ). (d) Outgoing MCCB 4 pole, 63 Amps, 415 Volt, AC, 16 KA with thermal magnetic release -02 Nos (for Pump-01 & Spare). Contd......
FIRE FIGHTING: -Supply, laying & testing Wiring for circuit/submain wiring, using FRLSH, PVC insulated copper conductor, single core cable in & including Steel conduit of size 20 mm with tees, bends, elbows fixed on walls surface type as required size of cable 1.5 sqmm, 2 core, 1100 volts grade complete all as specified.
E/M DEMOLITION: - Dismantling of existing obstruction as marked on site plan, comprising of PCC poles = 4 No.s, FI Brackets with Light fittings=4 Nos. , street light cable 6 Sqmm, 2 core and stacking near site for measurments to be handed over to contractor under sch of credit. The material shall be removed only after credit is recovered from the RAR.
CHEMICAL EARTHING: -Supply only chemical for earthing for the item at ser No. 42 above. (The specific chemical to be used shall be as approved by GE)
M&L for Earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground (earth pit not less than 2.25 metre deep below ground level) with top edge of plate not less than 1.5 metre below normal ground level connected to galvanized earth lead wire 4 mm dia by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical Plate No 3 of MES SSR Part-I connected to main switch board or main control board all as specified and testing on completion including provision of earth wire protected by galvanized iron 15 mm dia light grade pipe and watering pipe shall be 20 mm bore light grade including all excavation and earth work in any type of strata, PCC pit with pre-cast RCC cover, charcoal/salt, funnel etc complete all as directed. NOTES : (a) The concrete pit shall be PCC 1:3:6 type C-1, 40 mm thick pre cast cover slab of RCC M25 design mix using 20mm graded stone aggregate reinforced with 8mm TMT bars @ 10 cm C/C on both sides with suitable cast iron handle shall be provided in lieu of cast iron cover shown in electrical plate No 3 of MES SSR Part-I. (b) Item includes the cost of 7.5 M GI pipe for protection of earth wire. Any variation in length shall be adjusted through deviation order. (c) Item includes cost of 7.5 M earth lead wire. Any variation in length shall be adjusted through deviation order. (d) PCC pit shall be provided at least 500 mm away from the pit and not on the earth pit itself and the extra cost of additional length of watering pipe, bends, elbow etc shall be deemed included in the unit rate.
M&L for Earthing complete with Copper earth plate electrode 60 cm x 60 cm x 3.15 mm thick buried directly in ground (earth pit not less than 2.25 metre deep below ground level) with top edge of plate not less than 1.5 metre below normal ground level connected to copper strip 20 x 3.15 mm by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical Plate No 3 of MES SSR Part-I connected to main switch board or main control board all as specified and testing on completion including provision of earth wire protected by galvanized iron 40 mm dia light grade pipe and watering pipe shall be 20 mm bore light grade including all excavation and earth work in any type of strata, PCC pit with pre-cast RCC cover, charcoal/salt, funnel etc complete all as directed. NOTES : (a) The concrete pit shall be PCC 1:3:6 type C-1, 40 mm thick pre cast cover slab of RCC M25 design mix using 20mm graded stone aggregate reinforced with 8mm TMT bars @ 10 cm C/C on both sides with suitable cast iron handle shall be provided in lieu of cast iron cover shown in electrical plate No 3 of MES SSR Part-I. (b) Item includes the cost of 7.5 M GI pipe for protection of earth wire. Any variation in length shall be adjusted through deviation order. (c) Item includes cost of 7.5 M copper earth strip. Any variation in length shall be adjusted through deviation order. (d) PCC pit shall be provided at least 500 mm away from the pit and not on the earth pit itself and the extra cost of additional length of watering pipe, bends, elbow etc shall be deemed included in the unit rate.
M&L for Earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground (earth pit not less than 2.25 metre deep below ground level) with top edge of plate not less than 1.5 metre below normal ground level connected to galvanized earth lead wire 32 x 6 mm by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical Plate No 3 of MES SSR Part-I connected to main switch board or main control board all as specified and testing on completion including provision of earth wire protected by galvanized iron 40 mm dia light grade pipe and watering pipe shall be 20 mm bore light grade including all excavation and earth work in any type of strata, PCC pit with pre-cast RCC cover, charcoal/salt, funnel etc complete all as directed. NOTES : (a) The concrete pit shall be PCC 1:3:6 type C-1, 40 mm thick pre cast cover slab of RCC M25 design mix using 20mm graded stone aggregate reinforced with 8mm TMT bars @ 10 cm C/C on both sides with suitable cast iron handle shall be provided in lieu of cast iron cover shown in electrical plate No 3 of MES SSR Part-I. (b) Item includes the cost of 7.5 M GI pipe for protection of earth wire. Any variation in length shall be adjusted through deviation order. (c) Item includes cost of 7.5 M earth strip. Any variation in length shall be adjusted through deviation order. (d) PCC pit shall be provided at least 500 mm away from the pit and not on the earth pit itself and the extra cost of additional length of watering pipe, bends, elbow etc shall be deemed included in the unit rate.
Please Enable Macros to View BoQ information
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.40 MB
800630Tender03032026.pdf
Tender Documents • 5.34 MB
BOQ_845775.xls
BOQ • 0.31 MB
Drg8006302.pdf
Additional Documents • 10.85 MB
Download all tender documents and submit your bid