Loading…
Loading…
Tender Value
₹80 L
EMD Value
₹80,000
Closing Date
22 Jul 2026, 6:00 pmClosed
executive engineer kadodara division
Tender for ARC work of aying, testing and commissioning of 11/22 KV XLPE Cable (XLPE Cable to be Supplied by DGVCL) with Cable End Termination & straight through joint kits (to be supplied by contractor) amounting Rs 80,00,000 undervarious scheme under jurisdiction of Kadodara Ind s/dn of Kadodara Division.
323586
DGVCLDKDD/0216/07/2026 Approved Date: 10-07-2026 SR.NO.08
Open
Electrical
Works
Surat
3 documents required · 3 mandatory
₹5,900
DAKSHIN GUJARAT VIJ COMPANY LTD.
₹80,000
13 Jul 2026
13 Jul 2026
13 Jul 2026
22 Jul 2026
13 Jul 2026
CAPITAL WORK LABOUR RATES FOR FY 2025-26 (WITHOUT GST)
Sr. Item Code Item Unit Rate
Labour charge for excavation of cable trench of 400mm
width x 1200mm depth, in any type of soil for laying of
1 9925000001 cable of size up to 240 mm2 (For additional cable 200 Meter
mm additional width shall be considered i.e. half trench
length is to be considered)
Labour charge for excavation of cable trench of 600mm
width x 1200mm depth, in any type of soil for laying of
2 9925000002 cable of size up to 240 mm2 (For additional cable 200 Meter
mm additional width shall be considered i.e. half trench
length is to be considered)
Labour charge for excavation of cable trench of 400mm
width x 1500mm depth, in any type of soil for laying of
3 9925000003 cable of size up to 240 mm2 (For additional cable 200 Meter
mm additional width shall be considered i.e. half trench
length is to be considered)
Labour charge for laying of 11kV / 22 kV XLPE Cable of
size up to 240 mm2 & preparation of sand layer 100mm
thick, in the cable trench & covering the cable with
mm dia (Inner), thickness 25 mm, 1.0 meter long RCC
half round muffs and providing and fixing of 4inch width
4 9925000004 yellow colour polyethylene tape with printing "CAUTION Meter
ELECTRIC CABLE BELOW" at 0.75 m depth from ground
surface after laying cable in trench. This will provide
indication that electric cable is passing underground so
as to protect cable from mechnical injuries, refilling the
same, as per Instruction of Engineer in Charge (EIC).
Labour charge for horizontal drilling using Auger
machine without damage to surface road at max
mtrs depth & putting of 6.11 kg/cm2 , class-4,Green
color, 110mm O.D. , 8.5mm thickness H.D.P.E. pipe
confirms to IS 4984- 1987(3rd revision) and BIS
certification and laying of 11KV/22KV XLPE cable of size
up to 240 mm2 in HDPE pipe, as per Site Condition
(excluding cost of pipe). The detail map obtained from
HDD machine and excell sheet(hard and soft copy)
indicating the respective depth and distance from
adjacent landmark for each segment for HDD is must
required to be submitted. HDD to be carried out at depth
1.5 mtrs to 2.0 mtrs as per site conditions and as per
instruction of EIC.
Labour charge for horizontal drilling manually without
damage to surface road at max 2.0 mtrs depth & putting
of 6.11 kg/cm2 , class-4,Green color, 110mm
O.D. , 8.5mm thickness H.D.P.E. pipe confirms to IS 4984-
1987(3rd revision) and BIS certification and laying of
11KV/22KV XLPE cable of size up to 240 mm2 size, as
per Site Condition (excluding cost of pipe). The detail
map and excell sheet(hard and soft copy) indicating the
respective depth and distance from adjacent landmark
for each segment of cable to be submitted. Drilling to be
carried out at depth Minimum 1.2 mtrs to 2.0 mtrs as per
site conditions as per instruction of EIC.
Supply of 6.11kg/cm2 , class-4,Green color, 110mm O.D.
8.5 mm thickness
7 9925000007 H.D.P.E. pipe confirms to IS 4984 and BIS certification Meter
for laying of underground 11KV / 22KV XLPE cable up to
Labour work for RCC concreting on disputed location
and repairing of damage portion of road crossing for the
work carried out for roads crossing as well as concreting
& muffing of ploes including all materials (1:2:4)
Providing & fixing concrete stone route marker of
mm width x 150 mm thick x 650 mm height embedded in
earth at least 300 mm below & 350 mm above ground
level respectively at distance approx 50 meters along
the length of cable. The RCC concreting (1:2:4)(all
necessary maeterials will be in bidder's scope) of route
marker is to be carried out 300 mm width x 150 mm
9 9925000009 thick x 300 mm below ground level as per instruction No.
of EIC. The route marker should be with name of
company with approved yellow colour-DGVCL. The
distance from marker to cable and cable depth with
feeder name etc., marked with arrow sign is to be
painted on it.The route marker is to be fixed at location
near to any fixed permanent location (not necessary to
fix exact on top of cable) as per instruction of EIC.
Erection of D.P. (double pole) structure using 9 / 11 Mtr.
RSJ pole with cable connection arrangement along with
10 9925000010 fitting of necessary fabrication for 11KV cable including No.
excavation of pit & refilling of earth as per instruction of
EIC. (Exclusive of concreting & muffing of poles)
Erection of Single pole structure using 9 / 11 Mtr RSJ
pole with cable connection arrangement along with
fitting ofnecessary fabrication for 11KV/22 KV cable
including excavation of pit & refilling of earth as per
instruction of EIC. (Exclusive of concreting & muffing of
Erection of D.P. (double pole) structure using 8.0 Mtr.
PSC pole with cable connection arrangement along with
12 9925000012 fitting of necessary fabrication for 11KV cable including No.
excavation of pit & refilling of earth as per instruction of
EIC. (Exclusive of concreting & muffing of poles)
Erection of Single pole structure using 8.0 Mtr PSC pole
with cable connection arrangement along with fitting
13 9925000013 ofnecessary fabrication for 11KV/22 KV cable including No.
excavation of pit & refilling of earth as per instruction of
EIC. (Exclusive of concreting & muffing of poles)
Labour charge for erecting of 11kV / 22 kV XLPE cable of
size up to 240 mm2 on DP Structure with fixing of 02 Nos
14 9925000014 polymer cleats on top and middle part.Polymer cleats,
nut bolts etc. fixing material to be provided by
Providing & fixing of 6.11kg/cm2 , class-4,Green color,
110mm O.D. , 8.5mm thickness H.D.P.E. pipe confirms to
IS 4984 and BIS certification on the erected DP structure
for the mechanical protection of cable by inserting the
cable inside HDPE pipe. The HDPE pipe shall be erected Per
in such a way that 300mm shall be below the ground Job
level and the rest 2700 mm shall be supported on the
DP Structure with 01 No Polymer cleat.All materials
including polymer cleat and Nut bolt to be provided by
Providing and fixing of pipe type earthing from 80 mm dia
class-B GI pipe with pit to be filled with salt & coke and
construction of chamber as per DGVCL Drg. No. dg /100
16 9925000016 for DP and cable. The earthing pit should be joined with No.
cable by G.I. strip of size 1” width & 2 mm thick. All
material GI pipe, Coke, Salt etc will be supplied by
Supply & fixing of heat shrink type end terminations
17 9925000017 (outdoor) for upto 11kV 3C x 185 mm2 size XLPE cable as No.
per DGVCL technical specification
Supply & fixing of heat & shrinkable end terminations
(outdoor) for upto 22 kV
3C x 185 mm2 size XLPE cable as per DGVCL technical
Supply & fixing of heat shrink type end terminations
19 9925000019 (indoor) for upto 11kV 3C x 185 mm2 size XLPE cable as No.
per DGVCL technical specification)
Supply & fixing of heat & shrinkable end terminations
(indoor) for upto 22 kV
3C x 185 mm2 size XLPE cable as per DGVCL technical
Supply & fixing of heat shrinkable straight through joint
for upto 11kV 3C x
185 mm2 size XLPE cableas per DGVCL technical
Supply & fixing of heat shrinkable straight through joint
22 9925000022 type for upto 22kV 3C x 185 mm2 size XLPE cable as per No.
DGVCL technical specification
Labour charge for excavation of 2100mm long x
1200mm wide x 1200 mm deep joint pits for installation
of 11kV / 22kV Straight through joints as per instruction
of engineer-in-charge & covering the cable with 150 mm
dia (Outer), thickness 25 mm, 1.0 meter long RCC half
round muffs & refilling same as per instruction of EIC .
Providing and fixing of insulating bus bar, made from
11KV/22KV XLPE cable after removal of semi conducting
layer and applying of PVC heat shrinkable anti- tracking
core insulating tubing (1.1KV), on both end terminal
using Aluminium long barrel heavy duty up to 240 sq mm
24 9925000024 lugs, Aluminium bus connector. Taping with PG- clamp No.
for bus conductor as per drawing and as per instruction
of EIC. The Alluminium lugs and PG clamp shall be
covered with 11KV/22KV HT insulating
tapes.(11KV/22KV XLPE cable will be in scope of DGVCL
while all other materials will be in bidder's scope)
Testing of cable at various points and commissioning the
25 9925000025 feeder as per instruction of engineer-in-charge.Test No.
result shall be submitted by contractor with bill.
Preparation and submission of 6 (six) copies, of
complete layout drawings with GIS mapping as per
actual cable routing showing road crossing, HDPE pipe
sleeving, jointing locations, markers etc.
Providing and fixing of Sign Board at junction point Made
out of 2 mm aluminium sheet size 750x300 mm (2.5 x
ft) rectangle, as per design, pretreated with phosphate
process and acid etching coated with one coat of epoxy
primer and two coats of best quality paints, reflectorized
with Hi Intensity retro — reflective sheeting as per the
latest and frame fabricated from suitable size iron angle.
The Sign Board is to be fixed on the base prepared from
channel and bracing angles which is grouted by means
of cement concreting of 1:2:4 for size of 300 mm dia x
800 mm height (500 mm to be grouted in ground). The
details to be displayed on sign board will be given by
InchargeEngineer. (a) Hi intensity Micro prismatic
Providing and fixing of Sign Board (Danger Board) on
Distribution Transformer Centers Made out of 2mm
aluminium sheet size 300x300mm (1X1 ft) as per design,
pre treated with phosphate process and acid etching
coated with one coat of epoxy primer and two coats of
28 9925000028 best quality paints, reflectorized with Hi-Intensity No
retroreflective sheeting as per the latest and frame
fabricated from suitable size iron angle. The Sign Board
(Danger Board is to be fixed at the location as per
instruction of In-charge Engineer. (a) Hi intensity Micro
prismatic Grade
Providing & fixing of aluminium tag of size 250 mm (L) x
75 mm (W) from 3 mm aluminium sheet along with
mm dia aluminium binding wire for fixing of aluminium
tag near end termination joint at DP structure for
identifyng the cable. The details of feeder i.e. 11 / 22 KV
with feeder name shound be punched on the tag by letter
punch of size 16 mm as per instruction of In-charge
Supply & fixing of heat shrink type end terminations
30 9925000030 (outdoor) for 11kV 3C x 240 mm2 size XLPE cable as per No.
DGVCL technical specification
Supply & fixing of heat & shrinkable end terminations
31 9925000031 (outdoor) for 22 kV 3C x 240 mm2 size XLPE cable as No.
per DGVCL technical specification)
Supply & fixing of heat shrink type end terminations
32 9925000032 (indoor) for 11kV 3C x 240 mm2 size XLPE cable as per No.
DGVCL technical specification)
Supply & fixing of heat & shrinkable end terminations
33 9925000033 (indoor) for 22 kV 3C x 240 mm2 size XLPE cable as per No.
DGVCL technical specification
Supply & fixing of heat shrinkable straight through joint
34 9925000034 for 11kV 3C x 240 mm2 size XLPE cableas per DGVCL No.
technical specification.
Supply & fixing of heat shrinkable straight through joint
35 9925000035 type for 22kV 3C x 240 mm2 size XLPE cable as per No.
DGVCL technical specification
Installation, Testing and commissioning of 11 KV,630 A
SCADA Compatible, RRL type3 Way RMU including Two
36 9925000038 numbers of earthings as per Drawing (material is in Nos
bidder's scope) and as per DGVCL Technical
Installation, Testing and commissioning of 11 KV,630 A
SCADA Compatible, RRLL type4 Way RMU including Two
37 9925000039 numbers of earthings as per Drawing (material is in Nos
bidder's scope) and as per DGVCL Technical
Installation, Testing and commissioning of 22KV,630 A
SCADA Compatible, RRL type-3 Way, RMU including Two
38 9925000040 numbers of earthings as per Drawing (material is in Nos
bidder's scope) and as per DGVCL Technical
Installation, Testing and commissioning of 22KV,630 A
SCADA Compatible, RRLL type-4 Way, RMU including
39 9925000041 Two numbers of earthings as per Drawing (material is in Nos
bidder's scope) and as per DGVCL Technical
Construction of plinth for 11KV, RRL type- 3 Way( i.e Two
numbers of Isolator & One number of Breaker) Ring Main
40 9925000042 Unit as per DGVCL's technical specification mentioned Nos
in drawing no: Drg. 11kv-01. All required material will be
supplied by contractor.
Construction of plinth for 11KV, RRLL type4 Way (i.e Two
numbers of Isolator & Two number of Breaker)Ring Main
41 9925000043 Unit as per DGVCL's technical specification mentioned Nos
in drawing no:Drg. 11kv-02.AlI required material will be
supplied by contractor.
Construction of plinth for 22KV, RRL type- 3 Way (i.e Two
numbers of Isolator & One number of Breaker) Ring Main
42 9925000044 Unit as per DGVCL's technical specification mentioned Nos
in drawing no: Drg. 22kv-01. All required material will be
supplied by contractor.
Construction of plinth for 22KV, RRLL type4 Way (i.e Two
numbers of Isolator & Two number of Breaker)Ring Main
43 9925000045 Unit as per DGVCL's technical specification mentioned Nos
in drawing no:Drg. 22kv-02.All required material will be
supplied by contractor.
Modifications e.g. Providing and fixing ofTerminal
protectors i.e. Re-use able boot (HT Side 11/22KV, LT
Side 1.1KV) including 11/22 KV insulating taps and
L.T.(I.I KV) insulating taps ,Busbar, Tapping from Bus Bar
(11/22 KV XLPE cable) through P.G. Clamp for H.T.
Jumper to D.O. Fuse to bushings of Transformer Center,
providing & Fixing of jumper and providing & fixing of
Heat Shrinkable Anti Tracking CoreInsulating Tubing
44 9925000046 (Insulation Level 11/22 KV) in H.T. jumper , Clamping Nos.
arrangement of cable support frame on both side of
existing Over Head type Distribution Transformer to
utilize in Under Ground cable network as per drawing &
as per instruction of Engineer incharge. All live parts i.e.
PGClamp, connections of D.O.fuses, HT bushings etc .
shall be covered with fixing of 11/22 KV HT insulating
tapes. ( 11/22 KV XLPE cable will be in scope of DGVCL
while all other materials will be in bidder's scope )
Laying of any size of 11/ 22 KV XLPE /PILC Cable in Cable
redaymade trench or in open space Per
46 9925000060 Labour charges for Lying of O/H XLPE cable pole to pole KM
Supply of 150 mm dia (Inner), thickness 25 mm,
meter long RCC half round pipe
Total Estimated Amount (Exl. Gst )
Eighty lac only
Executive Engineer (O&M),
D.G.V.C.L., Kadodara Division
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
Notice.pdf
Integrity Part.pdf
Detail Technical Specification.pdf
Order condition.pdf
Schedule B Kadodara Ind Sdn.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .