EXECUTIVE ENGINEER
OFFICE OF THE EXECUTIVE ENGINEER , LSGD DIVISION, PALAKKAD
LAC ADS 2017-18 Chittur Constituency - Construction of Pulinirakkode Community Hall - Stage III Electrification.
2020_LSGD_357296_3
24/E/20-21
Open Tender
Electrical Works
Item Rate
180 days
LSGD DIVISION
PLEASE REFER TENDER DOCUMENTS
4 documents required · 4 mandatory
₹2,500
Yes
online
₹30,000
Yes
13 Nov 2020
15 Sept 2020
28 Sept 2020
15 Sept 2020
24 Sept 2020
15 Sept 2020
Amount
Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties,tie mounts etc.as required(RoHS compliant modular accessories)
Single Control light point with 6A, plate ceiling rose - Short point (90.2.1.1 )
Twin Control light point with 6A, plate ceiling rose - Short point (90.2.1.2)
Single Control light point without ceiling rose - Short point (90.2.1.3 )
Single control ceiling fan point with 6 A, 3 plate ceiling rose & with socket size stepped electronic regulator. - Short point (90.2.1.4)
Combined plug point with 6 A, 5 pin plug socket controlled by 6A switch in the same switch board as that of light points. (90.2.1.6)
Independent Plug - Short Point ( 90.2.1.7 )
Supply, conveyance installation testing and commissioning the light fittings of following types complete with all accessories and lamps etc. directly on wall or ceiling with PVC round block neatly painted and giving connection with required length of 16/0.20mm 3 core copper conductor flex wire etc.as required.
1200 mm 1X20W LED Lamp with box type fixture. (90.3.20.3)
Do - directly on wall using 2 nos. flat iron brackets made from 25x6mm flat iron, painting the flat iron bracket and giving connections with required length of 16/0.20mm 3core copper conductor flex wire etc.as required.
1200 mm 1X20W LED Lamp with box type fixture. (90.3.22.3)
Supply and fixing cast aluminium stove enamelled bulk head fitting with deep drawn anodised aluminium body,epoxy powder coated,heat resistant prismatic glass cover suitable with 7w LED bulb to wall/ceiling including giving connections with required length of 16/0.20mm PVC insulated 3 core round copper conductor flex wire conforming to to relevant ISS or extending the original wiring and making good the surface as required. (od70979/2018_2019)
Supply Conveyance, installation, testing and commissioning of 70W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD Less than 10%, power factor greater than 0.98,RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer) (90.15.4.3)
Do - 36/40W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection -Do - (90.15.4.2)
Supply, fabrication, conveyance and fixing the following sizes of B class GI pipe bent to shape / cut and welded to shape and fixing the same to wall / parapet using clamps as noted along with each size, painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required. 25 mm dia with HG company fabricated clamps.(90.3.18.1)
Supply Conveyance, installation, testing and commission -ing of 40W LED Flood light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing, acrylic cover complete with THD less than10%, power factor greater than 0.98,RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certifica -tes from NABL accredited Third party lab to be produced compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer. (90.15.4.5)
Supply, conveyance, installation, testing and commissioning of the following sizes of exhaust fans in the existing opening,fixing necessary bolt and nuts, making good the damages etc. as required including giving connections with required length of 24/0.20mm PVC insulated and PVC sheathed 3 core round copper conductor flex wire conforming to relevant ISS. 200 mm sweep Light Duty Exhaust fan in plastic body with self opening lowers working on 230V single phase A/C.
Charges for cutting holes/providing metal frame suitable for accommodating exhaust fans up to 305mm sweep including plastering colour washing etc. as required.
Supply, Conveyance and providing suitable size Cat No.ZBS565 frame or equivalent make for fixing (2x 2 Full glow-30/36W) Fittings or equivalent make. (od23844/2019_ 2020)
Supply Conveyance, installation, testing and commissioning of pre-wired light fitting of all types complete with 2 x2 Full Glow LED etc. suspended from ceiling using 4 nos steel chain (16 SWG or nearest available size) of length not exceeding 30 cm properly hooked to steel hooks anchored to the ceiling and giving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required.for 2x2 LED surface/recess mounting LED fitting out put not less than 4000lumen efficiency not less than 105lu/watt make: Philips or equivalent. (od74031/ 2019_ 2020)
Supplying and providing extra steel chain (16 SWG) 4 x 1.00 m long with 16/0.20 mm 3 core copper conductor flex wire conforming to relevant ISS or with the extended original wiring and giving connection etc.as required. (90.3.8)
Supply,conveyance installation testing and commissioning of pre-wired square type 18w LED fitting (1 x 1) complete with all accessories and drives etc. Lumen out put not less than 1800 efficiency not less than 100lumen/watt suspended from ceiling using 4 nos steel chain (16 SWG or nearest) of length not exceeding 30 cm properly hooked to steel hooks anchored to the ceiling and giving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required. (for fitting in false ceiling) make philips or equivalent. (od23842/2019_ 2020)
Do - LED round down light fittings with aluminium housing and polycarbonate diffuser, 12w, efficacy of 105lm/w directly in the existing opening on the false - ceiling including giving connections with required length of 16/0.20 mm 3 core round copper conductor flex wire conforming to relevant ISS or with the extended original wiring etc as required.Osram, Luxpower DL 12w / Equilent.
Supply and fixing angle / straight brass lined skirt type, bakelite batten holder with 200mm Plastic shade and 7 W LED lamp and giving connection etc as required. (od15215/2019_2020)
Supply,conveyance,installation,testing and commissioning of ceiling fans of the following sizes using standard accessories excluding resistance type regulator,wiring the down rod with 16/0.20mm PVC insulated and PVC sheathed 650/1100V grade 3 core round copper conductor flex wire or with extended original wiring etc.as required.
1200mm sweep - 5star rated ceiling fan complete with 300mm down rod,canopies, shackeles etc. working on 230V/240V single phase A/C (90.4.5.2)
Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required.(90.4.1)
Supply and installation of suitable size MS belt type fan clamp fabricated from flat iron 40 x 6 mm,150mm long x 2 Nos with M.S. rod bent to shape, neatly painted with 2 coats of enamel paint over a coat of red oxide primer as per IS 732 as required.(90.4.2)
Supply and providing every additional length of down rod of 15mm heavy gauge GI / WI pipe with 16/0.20mm PVC insulated and PVC sheathed 3 core round copper conductor flex wire conforming in relevant ISS or with original wiring extended including painting as required. (od20558/ 2019_2020)
Supply,conveyance,installation,testing and commissioning of 400 mm sweep (16") Almonard supreme high speed wall mounting fan of all types using mounting brackets supplied along with the fan and giving connection including all charges.
Supply,conveyance,installation,testing and commissioning of 450mm sweep (18") Almonard heavy duty wall mounting Air circulator of all types using mounting brackets supplied along with the fan and giving connection etc. complete.
Supply and fixing of following sizes of light gauge PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 20 mm. (90.6.10.1)
Do - 25 mm- Do - (90.6.10.2)
Supply and drawing 650/1100 V grade FRLS PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.
1.50 sq.mm 2 Run (1.17.2)
1.50 sq.mm 4 Run (1.17.4)
2.50 sq.mm 2 Run (1.17.11)
2.50 sq.mm 4 Run (1.17.13)
2.50 sq.mm 6 Run (1.17.15)
Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required. 1 or 2 Module (75mmX75mm) (1.27.1)
Do - 3 Module (100mmX75mm) (1.27.2)
Do - 8 Module (125mmX125mm) (1.27.5)
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 6 pin 15/16 amp socket outlet.(1.24.5)
Do - Do - 15/16 amp switch. (1.24.3)
Do - Do - 3 pin 5/6 amp socket outlet. (1.24.4)
Do - Do - 5/6 amp switch. (1.24.1)
Do - 25A SP switch with indicator.90.10.3.14
Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. (1.26)
Supply and installation of sheet steel, phosphatised and painted,dust and vermin proof enclosure of MCB DB including copper /brass bus bar,neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall, making good the damages, colour washing etc.as required. 4way (8+12) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43) (90.11.1.14)
Do - 4way (8+12) - three phase double cover. (IP42/43) (90.11.1.10 )
Do - single pole MCB DB,240v,on surface/ recess - Do - 12 way, Double door. (2.3.3)
Do - 8 way, Double door. (2.3.2)
Do - 6 way, Double door. (2.3.1)
Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.
63 amps 4 pole isolator (2.13.2 )
40 amps 4 pole isolator (2.13.1 )
40 amps double pole, 240volts, isolator. (2.12.1 )
Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 30/100 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.
63 A rating, 4 pole RCCB, 100 rnA (2.15.3)
40 A rating, 4 pole RCCB, 30 rnA (2.15.2)
25/32 A rating, 4 pole RCCB, 30 rnA (2.15.1)
25A rating, 2 pole RCCB, 30 rnA (2.14.1)
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
6 A. to 32 A. ratings , SP MCB, "C" curve,10 kA breaking capacity. (2.10.1 )
Do - 6 A. to 32 A. ratingsTP MCB, "C" curve,10 kA breaking capacity. (2.10.4 )
Do - 40 A TP MCB, "C" curve,10 kA breaking capacity.
Supply and providing and fixing 63A TPN disconnector fuse switch unit in sheet steel enclosure with ISI marked HRC fuses on wall/angle iron frame including drilling holes in frame, making connections etc.as required.
Supply and installation of switch gear units in sheet steel enclosure arrangement of the following ratings on existing angle iron frame work or directly to wall using necessary bolts & nuts, fixing the unitto wall, making good the damages, colour washing etc. including giving necessary connections as required. 63 A, 415 V, 50 Hz, AC 23 A duty, 4 pole on-load change over switch.
Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable,1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages,colour washing etc.as required.
4 core 16 sq mm with factory made clamp - Do - - Do - (90.12.7.41)
4 core 10 sq mm with factory made clamp - Do - (90.12.7.40 )
4 core 25 sq mm with factory made clamp - Do - (90.12.7.42 )
Do - 2 core 6 sq mm with factory made clamp - Do - - Do - (90.12.7.2)
Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.4 core 10 sq mm. (90.12.5.40)
Do - 2 core 6 sq. mm. ( 90.12.5.2)
Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation 63/50 mm or nearest size (90.12.10.3)
Do - DWC pipe in ordinary soil 0.75m below ground level including excavation 50/38 mm or nearest size (90.12.10.2)
Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.50x50mm Cable Management System with base and lid. (90.9.1.1)
Do - 50 x 50 mm PVC Cable Management System - Do -External angle 90 degree. (90.9.1.2)
Do - 50 x 50 mm PVC Cable Management System - Do -Internal angle 90 degree.(90.9.1.4)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
4 core 16 sq. mm (28mm) (9.1.33)
4 core 10 sq mm (25mm) (9.1.32)
4 core 25 sq. mm (28mm) (9.1.34)
2 core 6 sq. mm (19mm) (9.1.1)
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2 metre long etc. with charcoal/coke and salt as required.(od14959/2019_2020)
Providing and fixing 25mmx3mm G.I strip earth lead from the test joint to the earth plate. (od14961/2019_2020)
Do - 2x25mmx3mm G.I strip test joint for earthing system. (od68978/2018_2019)
Supply and drawing bare earthing conductors of the following sizes along with wiring / cables and giving connection as required. 2.00mm copper conductor (14SWG) (od14862/2019_2020)
Do - 2.65mm copper conductor (12 SWG) (od21802/2019 _2020)
Do - 3.15 mm copper conductor (10 SWG) (od14864/ 2019_2020)
Supply and laying bare earthing conductors of the following sizes laid 0.6 m below ground level including excavating trench of suitable size and refilling etc. as required (in ordinary soil) 3.15mm copper conductor.(10SWG) (od21872/2019_ 2020)
Suplying,threading,laying and jointing of 15mm B class GI pipe with all required accessories in ground in the existing trench as protective covering to earth leads.(od21874/ 2019_2020)
Supply of superior quality 2.00mm copper earth socket and including crimping etc.as required. (od14945/2019_ 2020)
Do - 2.65mm copper conductor (12 SWG) (od21880/ 2019_2020)
Do - 3.15mm copper earth socket and including crimping etc. as required. (od21884/2019_2020)
Supply and providing12x3mm brass nut and bolt etc.as required.(od21888/2019_2020)
Do - 25 x 6 mm brass bolt & nut. (od14951/2019_2020)
Supply & installation of dust and vermin proof, 3 Phase Sintex Meter Board( GS-MB- 5628 (515 x 240 x 145) including p/f 3Nos. 63 A HRC Fuse Base with HRC Fuse link ,63 A neutal link and to fix KSEB meters, etc as required including fixing it on wall, making good the damages colour washing etc. as required. (od15345/ 2019_ 2020)
Supply, fabrication, conveyance and fixing the following sizes of B class GI pipe bent to shape / cut and welded to shape and fixing the same to wall / parapet using clamps as noted along with each size, painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.32 mm dia with HG company fabricated clamps. (90.3.18.2) For Srevice Pipe.
Supply and providing M8 anchor bolt hook in wall / parapet for binding support for service main.
Supply, conveyance, installation, testing and giving connections of two zone PA Amplifier 120W (60+60) RMS operating on AC 220‐ 240V, 50Hz/DC, and having 65‐ 15,000 Hz ±3dB frequency response, Bass, Treble and Master Control, 6 mic input channel, 2 Auxiliary inputs & preout 4, 8 Ohms, 70V & 100V speaker outputs in each zone. Recommended: TZA 1200 AHUJA or Equivalent
Supply, conveyance, installation, testing and giving connection of wall mounting Speaker Box of 20 Watts rms, 3" Woofer & 1" Tweeter speakers,Power taps of 20W / 10W/ 5W, 8 Ω on 100V, frequency response 90Hz ‐20KHz. including wall mount bracket (in pair) Recommended: ARC 20 or Equivalent.
Supply, conveyance, installation, testing and giving connection of wall mounting Speaker Box of 10 Watts rms, Power taps of 10W/5W on 100V,frequency response 60 - 15000Hz..Recommended: 3727 MX or Equivalent.
Supply, conveyance, installation, testing of Handheld UHF Wireless Microphone with dual channel non diversity wireless receiver having following minimum specifications. Frequency response 50-16kHz, Single channel non diversity Receiver, Operating frequency Range 720 - 865MHz. (Recommended: XR 40HH series-Studiomaster)
Supply, conveyance, installation, testing of dynamic microphone having 50‐15 KHz frequency response, ‐50dB±3dB @ 1KHz sensitivity with XLR connectors & 6.5M low noise cable.It should be ideal for speech, vocal and dynamic instrument miking.(Recommended: ASM‐780 XLR Ahuja or Equivalent)
Supply, conveyance, installation, testing of PA Microphone Stands with following minimum specifications. Floor Stand, Height - 920-1500 mm, Base Dia - 230mm, Weight - 5.6 Kg. Recommended: DGT/DGN-AHUJA
Supply,conveyance,installation,testing and commissioning of 13 W LED Gate light fitting IP 65 of Prince Orna Midi of K-lite/equivalent make on existing pipe and giving connection etc as required.
Supply and fixing junction box of size 140x140x95 of Syntex type suitable for terination of Street light cable (GSJB1414). od48500/ 2019_ 2020
RAMAN.V
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_546782.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .