| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹7.6 LAccepted-AOC | L1 | Accepted-AOC L1 being lowest | |
| 2 | L2₹8.0 L+₹39,900 (5.26%)Rejected-AOC 31 SARASWATI SONI MARG DEHRADUN | DEHRADUN | L2 | Rejected-AOC being not lowest | |
| 3 | L3₹8.6 L+₹1.0 L (13.2%)Rejected-AOC PREM NAGAR GALI NO 3 RAJPUTANA SALEMPUR ROORKEE DISTT HARIDWAR UK | ROORKEE | HARIDWAR | UTTARAKHAND | L3 | Rejected-AOC being not lowest | |
| 4 | L4₹9.7 L+₹2.1 L (27.8%)Rejected-AOC 362 SUBHASH NAGAR PO CLEMENT TOWN DEHRADUN UTTARAKHAND | L4 | Rejected-AOC being not lowest | |
| 5 | L5₹11.9 L+₹4.3 L (56.5%)Rejected-AOC 0 AJAY KUMAR 85 HASTAM HASTAM BANDA UTTAR PRADESH 210001 HASTAM BANDA UTTAR PRADESH 210001 UDYAM UP 13 0007628 | BANDA | UTTAR PRADESH | 210001 | L5 | Rejected-AOC being not lowest |
Tender Value
₹14 L
EMD Value
₹28,000
Closing Date
13 Feb 2021, 6:00 pmClosed
CWE HILLS DEHRADUN
HQ Commander Works Engineers Hills Mall Road Dehradun Cantt Dehradun 248003
REPAIR AND REPLACEMENT TO ELECTRIC PANEL AT LOWER PUMP HOUSE IN RAIWALA MILITARY STATION
2021_MES_414836_1
86315/RWL/E8
Open Tender
Civil Works
Item Rate
120 days
Raiwala
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
AGE I Raiwala
₹28,000
Yes
5 Mar 2021
21 Jan 2021
15 Feb 2021
21 Jan 2021
13 Feb 2021
30 Jan 2021
22 Jan 2021 - 28 Jan 2021
Amount
M&L for Design, supply, Fabrication, Installation, testing and Commissioning factory made, LT panel board, Indoor type, totally enclosed, dust and vermin proofm suitably ventilated, floor mounted, 415 volts, 3 phase and neutral, 50 hz, AC supply system, fully compartmentalised, made out of 2.00mm thick CRCA sheet steel, protection of enclosure IP-54 as per IS : 2147 of 1962 with pre-treatment and powder coated of approved colour including suitable frame work / support made out of suitable size of angle iron / flat iron, front opening type with provision for cable entry, with proper ferrule and cable glands, internal wiring with PVC insulated multi stranded copper conductor FRLS cable of adequate size (minimum 1.5 sqmm), including required civil works/anchoring bolts for fixing, PCC foundation etc with and including following all as specified and directed : - (a) Busbarchamber : Electrically grade shrouded aluminium bus bar of capacity 600 Amps for each phase and 300 Amps for neutral and current density 0.8A/Sqmm , including interconnection of all switch gears, fixed on DMC insulators and provision of extension.
OUTGOING:- with two compartment each comparment witll consist the following : (i ) MCCB 200 amps, 415Volts, 3 pole 50 Hz, 25/30 KA with adjustable thermal magnetic release, in built instantaneous protection, Ics = 100%Icu(1 sec) complete all as specified and directed - 01 Nos .(II ) Contactor 95 Amps cat part No LC1E95M7 of schneider or equivalent ABB / Siemens - 03 Nos (iii) Motor protection relay type D2MPR of minilec or equivalent in Schnider / ABB - 01 No (iv) Phase failure relay with under and over voltage settings (type/ model ALV D2 of minilec or equivalent in ABB /Schneider - 01 No , (v) Star delta timer of make secure /selec - 01 Nos , (vi) Green push button with NO -01 No make AIRON or equivalent in Legrand /seimens , (vii )Red Push button with NC - 01 No make AIRON or equivalent in Legrand /seimens (Viii ) ON Red indicaiton lamp - 01 No make AIRON or equivalent in Legrand /seimens , (ix)OFF Green Indication Lamp - 01 No make AIRON or equivalent in Legrand /seimens , (x )Terminals 125 Amps bus bar type -06 Nos , (xi )MCB DP 6 amps 10 KA - 01 No (xii ) CT of ratio 250 /5 amps 5VA Class 1.0 .-03 Nos Make Safetek or equvalent in L&T / AE ,Incuding necessary conneciton with pvc insulated stranded copper conductor cable of suitable size Make:- (a) LED indicator / Push button -ASS / VAA/L&T/siemens (b) LT Panels : ABB / Schneider / Universl switchgear control / Tenco systems and switch gears Pvt Ltd Indore. (c) ACB/MCCB/MCB : L&T/ABB/SCHNEIDER / SIEMENS / LEGRAND.
Notes for Item No 1 :- 1. Panel manufacturers should have in house powder coating plant with minimum 8 tank pretreatment of MS sheet facilities, dust free spray paint booth.(8 tanks pretreatment process includes: degreasing/water rinsing/de-dusting/water rinsing/activation/phosphating water rinsing/passivation). 2. Thickness of powder coating shall not be less than 80 microns and test certificate for powder coating shall be furnished along with LT panel 3. The panel manufacturer should have following certification: (i) CPRI certification degree of protection IP-54 ( should have IEC:61439-1-2 & IEC:60529 tests) (ii) CPRI certification short circuit with stand strength should be 50 KA RMS for 1 sec with initial peak of 105 KA (iii) CPRI certification rated current for short circuit not less than 5000A 4. All the electricals switch gear like MCCBs, MCB should be of same make 5. Drawing of panel board should be got approved from GE before fabrication. 6. Panel board should be fully compartmentalized in accordance to form 4 b of IEC 61439-1-2.
Material and Labor for Design, supply, Fabrication, Installation, testing and Commissioning factory made, LT panel board, Outdoor type, totally enclosed, dust and vermin proof suitably ventilated, floor mounted, 415 volts, 3 phase and neutral, 50 hz, AC supply system, fully compartmentalised, both side open able, made out of 3.00mm thick CRCA sheet steel, protection of enclosure IP-54 as per IS : 2147 of 1962 with pre-treatment and powder coated of approved colour including suitable frame work / support made out of suitable size of angle iron / flat iron, front opening type with provision for cable entry, with proper ferrule and cable glands, internal wiring with PVC insulated multi stranded copper conductor FRLS cable of adequate size (minimum 1.5 sqmm), including required civil works/anchoring bolts for fixing, PCC foundation etc with and including following all as specified and directed : - (a) Busbarchamber : Electrically grade copper shrouded bus bar of capacity 600 Amps for each phase and 300 amps for Neutral and current density 1.6A/Sqmm including interconnection of all switch gears, fixed on DMC insulators and provision of extension.
OUTGOING:- Consist the following : (i ) MCCB 200 amps, 415Volts, 3 pole 50 Hz, 25/30 KA with adjustable thermal magnetic release, in built instantaneous protection, Ics = 100%Icu(1 sec) complete all as specified and directed - 02 Nos (ii) MCB SP 10 - 20 Amps 10 KA - 02 Nos. Make:- (a) LED indicator / Push button -ASS / VAA /L&T/Siemens (b) LT Panels:- ABB / Schneider / Universl switchgear control / Tenco systems and switch gears Pvt Ltd Indore. (c) ACB/MCCB/MCB:- L&T/ABB/SCHNEIDER / SIEMENS / LEGRAND.
Notes for Item No1 :- 1. Panel manufacturers should have in house powder coating plant with minimum 8 tank pretreatment of MS sheet facilities, dust free spray paint booth.(8 tanks pretreatment process includes: degreasing/water rinsing/de-dusting/water rinsing/activation/phosphating water rinsing/passivation). 2. Thickness of powder coating shall not be less than 80 microns and test certificate for powder coating shall be furnished along with LT panel 3. The panel manufacturer should have following certification: (i) CPRI certification degree of protection IP-54 ( should have IEC:61439-1-2 & IEC:60529 tests) (ii) CPRI certification short circuit with stand strength should be 50 KA RMS for 1 sec with initial peak of 105 KA (iii) CPRI certification rated current for short circuit not less than 5000A 4. All the electricals switch gear like MCCBs, MCB should be of same make 5. Drawing of panel board should be got approved from GE before fabrication. 6. Panel board should be fully compartmentalized in accordance to form 4 b of IEC 61439-1-2.Make of Panel Board Universal switchgear control / Techno Switchgear control
Material and Labour for Design, supply, Fabrication, Installation, testing and Commissioning factory made, LT panel board, Indoor type, totally enclosed, dust and vermin proofm suitably ventilated, floor mounted, 415 volts, 3 phase and neutral, 50 hz, AC supply system, fully compartmentalised, made out of 2.00mm thick CRCA sheet steel, protection of enclosure IP-54 as per IS : 2147 of 1962 with pre-treatment and powder coated of approved colour including suitable frame work / support made out of suitable size of angle iron / flat iron, front opening type with provision for cable entry, with proper ferrule and cable glands, internal wiring with PVC insulated multi stranded copper conductor FRLS cable of adequate size (minimum 1.5 sqmm), including required civil works/anchoring bolts for fixing, PCC foundation etc with and including following all as specified and directed : - (a) Busbarchamber : Electrically grade shrouded aluminium bus bar of capacity 600 Amps for each phase and 300 Amps for neutral and current density 0.8A/Sqmm , including interconnection of all switch gears, fixed on DMC insulators and provision of extension.
OUTGOING with two compartment each comparment witll consist the following : (i ) MCCB 100 amps, 415Volts, 3 pole 50 Hz, 25/30 KA with adjustable thermal magnetic release, in built instantaneous protection, Ics = 100%Icu(1 sec) complete all as specified and directed - 02 Nos .(II ) Contactor 80 Amps cat part No LC1E80M7 of schneider or equivalent ABB / Siemens - 03 Nos (iii) Motor protection relay type D2MPR of minilec or equivalent in Schnider / ABB - 01 No (iv) Phase failure relay with under and over voltage settings (type/ model ALV D2 of minilec or equivalent in ABB /Schneider - 01 No , (v) Star delta timer of make secure /selec - 01 Nos , (vi) Green push button with NO -01 No make AIRON or equivalent in Legrand /seimens , (vii )Red Push button with NC - 01 No make AIRON or equivalent in Legrand /seimens (iii ) ON Red indicaiton lamp - 01 No make AIRON or equivalent in Legrand /seimens , (ix)OFF Green Indication Lamp - 01 No make AIRON or equivalent in Legrand /seimens , (x )Terminals 125 Amps bus bar type -06 Nos , (xi )MCB DP 6 amps 10 KA - 01 No (xii ) CT of ratio 160 /5 amps 5VA Class 1.0 .-03 Nos Make Safetek or equvalent in L&T / AE ,Incuding necessary conneciton with pvc insulated stranded copper conductor cable of suitable size Make:- (a) LED indicator / Push button - ASS / VAA/L&T/Siemens etc . (b) LT Panels:- ABB / Schneider / Universl switchgear control / Tenco systems and switch gears Pvt Ltd Indore. (c) ACB/MCCB/MCB:- L&T/ABB/SCHNEIDER / SIEMENS / LEGRAND.
Notes for Item No1 :- 1. Panel manufacturers should have in house powder coating plant with minimum 8 tank pretreatment of MS sheet facilities, dust free spray paint booth.(8 tanks pretreatment process includes: degreasing/water rinsing/de-dusting/water rinsing/activation/phosphating water rinsing/passivation). 2. Thickness of powder coating shall not be less than 80 microns and test certificate for powder coating shall be furnished along with LT panel 3. The panel manufacturer should have following certification: (i) CPRI certification degree of protection IP-54 ( should have IEC:61439-1-2 & IEC:60529 tests) (ii) CPRI certification short circuit with stand strength should be 50 KA RMS for 1 sec with initial peak of 105 KA (iii) CPRI certification rated current for short circuit not less than 5000A 4. All the electricals switch gear like MCCBs, MCB should be of same make 5. Drawing of panel board should be got approved from GE before fabrication. 6. Panel board should be fully compartmentalized in accordance to form 4 b of IEC 61439-1-2.
Dismantling and taking out MS angle iron / flat / channels / plate of any size and thickness and shape for cable supports/ pipe support /structure to feeder pillars/cope boxes/ ladder from existing trench/duct including cutting, bending, drilling, unscrewing & making good existing wall structure and handing over to user and removing off cutts of scrap from site complete all as specified & as directed by Engg-in-Charge
Dismantling old unserviceable out door /indoor type switch gear panel alongwith associated bus bar, metering , fuses , MCCBs (U/S) switches, starters etc indication lamps including disconnecting power cables and removing unserviceable panel from site complete all as specified and as directed by Engg-in-Charge. Note for item No-4&5:- The complete dismantled items shall be deposited in stores of MES department. The rate quoted by the contractor shall include the cost of transportation.
S&F PVC heavy duty pipe of 80mm bore including dismentling/ cutting chasing in floor/wall nexc 15 cm width or girth and making good floor/wall in CM 1:3 & finishing the surface as per existing complete all as specified & directed by Engg-in-Charge. Note:- The pipe shall be properly grouted on walls/floor as per direction of Engg-in-Charge.
Disconnecting the exising cable connections from Panels & moters etc and relaying the cable through pipe and recnnecting cable to panels & moter's as per direction of Engg-in-Charge
M/s RP AGRAWAL
M/S Konark Electric Sales Corporation
KAPOOR ELECTRICALS
AJAY KUMAR CONTRACTOR
Fortuna Technologies
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .