Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹89.9 LAccepted-AOC CHANDAN NAGAR OPP IOCL PERTROL PUMP RAMPUR ROAD BAREILLY UP 243001 | BAREILLY | BAREILLY | UTTAR PRADESH | 243001 | L1 | Accepted-AOC Competent committee approved the tender in favour of Ist Lowest Bidder | |
| 2 | L2₹96.9 L+₹7.1 L (7.85%)Rejected-AOC | L2 | Rejected-AOC Competent committee rejected the file due to higher rates |
Tender Value
₹1.6 Cr
EMD Value
₹1.6 L
Closing Date
4 Jan 2022, 5:00 pmClosed
SUPERINTENDING ENGINEER
ELECTRICITY DISTRIBUTION CIRCLE, KATJU MARG, BAREILLY
For Shifting of LT, 11 KV and 33 KV line From Lal Phatak (SBI Bank) to Buduan Road under 33/11 KV S/s Kandharpur under EDD-II, Bareilly (Full deposite Scheme)
2021_MVVNL_651390_1
64/EDCB/2021-22
Open Tender
Electrical Works
Item Rate
180 days
WORK
AS PER TENDER FORM
3 documents required · 3 mandatory
₹5,900
SE,EDC
₹1.6 L
23 Jun 2022
5 Dec 2021
5 Jan 2022
5 Dec 2021
4 Jan 2022
5 Dec 2021
Amount
The work of safe carriage of the following material from CB Ganj store center to work site under the jurisdiction of EDD-II, Bareilly. Approx. distance upto 30 Km. Including safe loading and unloading.
ST Pole 11 Mtr
ST Pole 09 Mtr
PCC Pole 8.5 Mtr
11 KV XLPE Cable 3x185 Sq mm
11 KV XLPE Cable 3x70 Sq mm
33 KV XLPE Cable 3x300 Sq mm
Cable Box for 11 KV XLPE Cable 3x185 Sq mm
Cable Box for 11 KV XLPE Cable 3x70 Sq mm
Cable Box for 33 KV XLPE Cable 3x300 Sq mm
Straight Through Cable Jointing Kits for 11 KV XLPE Cable 3x185 sqmm
Straight Through Cable Jointing Kits for 33 KV XLPE Cable 3x300 sqmm
ACSR Dog Conductor
ACSR Weasel Conductor
LT AB Cable 3x120 sqmm
LT AB Cable 3x95 sqmm
LT AB Cable 3x50 sqmm
LT AB Cable 3x16 sqmm
11/0.4 KV 3 Phase 25 KVA T/F
11/0.4 KV 3 Phase 250 KVA T/F
Other Line material i.e., 33 KV & 11 KV pin insulater/stay/earthing complete/Disc Fitting/Disc Insulators/Dropper Channel/Crossing Bracing/ Top Channel/Binding Wire/Danger Board/Barbed Wire/numberplate/stone pad/Control Cable etc
Construction of T/F plinth 1.5x1.5x2 m3 for mounting 250 KVA T/F including foundation work (below ground 0.5 M), Brick work, RCC slab of 4” thickness and plastering in 1:6 ratio with 02 Nos channel pieces of 1.5 mtr long of size 100x50x6 mm compete in all respect
Cage fencing of 250 KVA Plinth mounted transformer in Town areas to avoid electrical human/cattle accidents by fabrication of cage (1 Inch Sq wiremesh) made of 10 No gauge in suitable size angle iron frame of size 7.5'(L)x5'(W)x8’(H) by strenghtening of wire mesh 20x3 mm M.S. flat haorizentally as well as vertically, Grouting the panel with 1:2:4 cement/coorse send/brick ballast. The Frame should be bolted on angles at the four corners so that frame may be un-bolted/bolted at the time of replacement of the transformer. Provision of 1 gate should be there for maintenance of the transformer. Painting (1 coat of red oxide + 2 coat of Bus green enamel paint). The wire mesh should be earthed with 50x6 mm MS earthing strip with existing earthing of Transformer Body. All men, material and T&P provided by the contractor to complete the fabrication, transportation and installation.
Mounting of Following Capacity Transformers as per norms complete in all respect -
25 KVA T/F
250 KVA T/F
Erection of Single/Double pole in H.T/L.T lines including fitting of all accessories as per RESSPO Norms
PCC Pole 8.5 Mtr long (Single)
ST Pole 11 Mtr long (Single)
ST Pole 11 Mtr long (Double)
ST Pole 9 Mtr long (Single)
Four Pole Structure as per norms
Grouting of following Pole with 1:4:8 mixture in size(450x450x1500mm.) including cost of cement/BB & sand Required as per RESSPO Norms
PCC Pole 8.5 Mtr long (Single)
ST Pole 11 Mtr long (Single)
ST Pole 11 Mtr long (Double)
ST Pole 9 Mtr long (Single)
Four Pole Structure as per norms
The work of Driving the earthing electrode and making connections with 6 S.W.G. GI wire as per RESSPO Norms
Laying, Stringing & Sagging of Following Conductor complete in all respect
ACSR Weasal Conductor
ACSR DOG Conductor
Arial Bunched Conductor (3x120 sqmm)
Arial Bunched Conductor (3x95 sqmm)
Arial Bunched Conductor (3x50 sqmm)
Arial Bunched Conductor (3x16 sqmm)
Under ground laying of 11 KV XLPE 3x185 sq mm cable in Double circuit by drill method to Double pole situated at both sides in all respect.
Under ground laying of 11 KV XLPE 3x70 sq mm cable in Double circuit by drill method to Double pole situated at both sides in all respect.
Under ground laying of 33 KV XLPE 3x300sq mm cable in Double circuit by drill method to Double pole situated at both sides complete in all respect.
Hoisting of 33 KV XLPE Cable (3x300 sqmm) on double pole bote with GI pipe of size 6 " dia 4 Mtr long including the jumpering complete with clamps , nut and bolts.
Hoisting of 11 KV XLPE Cable (3x185 Sqmm) on double pole bote with GI pipe of size 6" dia 4 Mtr long including the jumpering complete with clamps , nut and bolts
Hoisting of 11 KV XLPE Cable (3x70 Sqmm) on double pole bote with GI pipe of size 6" dia 4 Mtr long including the jumpering complete with clamps , nut and bolts
Supply & Laying of 6" dia G Pipe at various places i.e road crossing & Hoisting etc. complete in all respect ((ISO certified GI pipe 150 NB 3 mm thick dia 6" would be Provided by contractor at his own cost)
Fixing of 11 KV Cable Boxes for 3x185 sqmm XLPE Cable complete in all respect
Fixing of 11 KV Cable Boxes for 3x70 sqmm XLPE Cable complete in all respect
Fixing of 33 KV Cable Boxes for 3x300 sqmm XLPE Cable complete in all respect
Fixing of 11 KV Straigh through Jointing Kits for 3x185 sqmm XLPE Cable complete in all respect
Fixing of 33 KV Straigh through Jointing Kits complete in all respect
The work of digging of pits, erection of Stay Clamp, Insulator etc.
Grouting of stays, 1:4:8 cc ratio (600x600x300mm.) as per RESPO norms.
Fixing of 3 Phase Distribution Box complete in all respect
Fixing of 1 Phase Distribution Box complete in all respect
Guarding at road crossing complete in all respect
Safe back carriage of Scrap (if any) from work site to C.B. Ganj store Bareilly approx distance upto 30 Km including safe loading & unloading.
Cutting of Tree Branches
Anil Kumar Yadav
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .