Staff Officer(EnM), Argada Area
GM Unit, Sirka, Argada Area, Ramgarh-829101
Supply, Installation and commissioning of 3.3 KV Grade Neutral Grounding Registor(NGR) with safety features at Gidi-A OCP under Argada Area.
2026_CCL_364713_1
SO(EnM)/AA/e-NIT/26-27/28
Open Tender
Electrical and Maintenance Works
Item Rate
15 days
Gidi A OCP
2 documents required · 2 mandatory
₹17,100
2 Sept 2026
2 Sept 2026
15 Sept 2026
3 Sept 2026
14 Sept 2026
3 Sept 2026
3 Sept 2026 - 10 Sept 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Design, manufacturing, supply and commissioning of 3.3 KV KV, 10 Amps, Restricted Neutral Grounding system (NGR) resistance 190 ohms consisting of Neutral grounding resistor, stainless steel non-magnetic punched grid type AISI 304 grade, Max temperature rise 375 deg C, Indoor Epoxy Resin cast neural current transformer, 11KV 50/5A, IOT and Solid state NGR monitoring fail safe relay, Fuse enclosure, HRC fuses, connectors, glands, control wires and bushing studs, Buzzer (electronic), floor mounted, powder coated control panel and resistance box with all accessories, Outdoor type,
Safety Features:,
1. Resistance temperature sensor: Trips the breaker if resistance temperature exceeds a set value
2. Trip logs: Log of last 25 trips
3. Temperature logs: Hourly resistance temperature log for the last 24 hours.
4. Current Logs: Hourly Neutral current log for the last 24 hours. | 2 | Set | - | - |
| 2 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. | 2 | Set | - | - |
| 3 | Supplying and drawing of 7 x 2.5 sq. mm of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. | 100 | Mtrs. | - | - |
| 4 | Supplying and drawing of 4 x 4 sq. mm of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. | 125 | Mtrs. | - | - |
| 5 | Total impact of GST for the purpose of CTC | - | Nos | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 3.27 MB
BOQ_377633.xls
BOQ • 0.29 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .