Loading…
Loading…
Tender Value
₹16 L
EMD Value
₹20,000
Closing Date
18 Jun 2026, 6:00 pm
Executive Engineer DGVCL,SURAT RURAL DIVISION
Tender for Installation, Testing and commissioning of 11/22KV, SCADA Compatible, RRLL/RRL type including Construction of plinth for RMU as per approved drawing by DGVCL at division & any other sub division under Surat Rural Division.
309194
DGVCL/ SRD/E-TENDER/2026-27/ No:16
Open
Electrical Works
Surat
3 documents required · 3 mandatory
₹1,180
DAKSHIN GUJARAT VIJ COMPANY LTD.
₹20,000
27 May 2026
27 May 2026
27 May 2026
18 Jun 2026
27 May 2026
Name of Work:Tender for Installation, Testing and commissioning of 11/22KV, SCADA Compatible, RRLL/RRL type-3/4 Way,
RMU including Construction of plinth for RMU as per approved drawing by DGVCL at Puna sub division & any other sub
division under Surat Rural Division.
Description Unit Rate ty
Labour charge for excavation of cable trench of 400mm width x 1200mm
depth, in any type of soil for laying of cable of size up to 240 mm2 (For
additional cable 200 mm additional width shall be considered i.e. half trench
length is to be considered
Labour charge for excavation of cable trench of 600mm width x 1200mm
depth, in any type of soil for laying of cable of size up to 240 mm2 (For
additional cable 200 mm additional width shall be considered i.e. half trench
length is to be considered
Labour charge for excavation of cable trench of 400mm width x 1500mm
depth, in any type of soil for laying of cable of size up to 240 mm2 (For
additional cable 200 mm additional width shall be considered i.e. half trench
leng th is to be considered
Labour charge for laying of 11kV / 22 kV XLPE Cable of size up to 240 mm2
& preparation of sand layer 100mm thick, in the cable trench & covering the
cable with 150 mm dia (Inner), thickness 25 mm, 1.0 meter long RCC half
round muffs and providing and fixing of 4inch width yellow colour
4 9925000004 polyethylene tape with printing"CAUTION ELECTRIC CABLE BELOW' at 0.75 Meter
m depth from ground surface after laying cable in trench. This will provide
indication that electric cable is passing underground so as to protect cable
from mechanical injuries, refilling the same, as per Instruction of E gineer in
Labour charge for horizontal drilling using Auger machine without damage to
surface road at max 2.0 mtrs depth & putting of 6.11 kg/cm2 , class-4,Green
color, 110mm 0.D. 8.5mm thickness H.D.P.E. pipe confirms to IS 4984-
1987(3rd revision) and BIS certification and laying of 11KV/22KV XLPE cable
of size up to 240 mm2 in HDPE pipe, as per Site Condition (excluding cost of
5 9925000005 pipe). The detail map obtained from HDD machine and excel sheet hard and Meter
soft copy) indicating the respective depth and distance from adjacent
landmark for each segment for HDD is must require to be submitted. HDD to
be carried out at depth 1.5 mtrs to 2.0 mtrs as per site conditions and as er
instruction of EIC.
Labour charge for horizontal drilling manually without damage to surface
road at max 2.0 mtrs depth & putting of 6.11 kg/cm2 , class-4,Green color,
110mm O.D. , 8.5mm thickness H.D.P.E. pipe confirms to IS 4984-1987(3rd
revision) and BIS certification and laying of 11KV/22KV XLPE cable of size up
6 9925000006 to 240 mm2 size, as per Site Condition (excluding cost of pipe). The detail Meter
map and excel sheet (hard and soft copy) indicating the respective depth and
distance from adjacent landmark for each segment of cable to be submitted.
Drilling to be carried out at depth Minimum 1.2 mtrs to 2.0 mtrs as per site
conditions as per instruction of EIC.
Supply of 6.11kg/cm2 , class-4,Green color, 110mm O.D. , 8.5 mm thickness
7 9925000007 H.D.P.E. pipe confirms to IS 4984 and BIS certification for laying of Meter
underground 11KV/ 22KV XLPE cable up to 240 mm 2 size.
Labour work for RCC concreting on disputed location and repairing of
damage portion of road crossing for the work carried out for roads crossing
as well as concreting & muffing of poles including all materials
Providing & fixing concrete stone route marker of 300 mm width x 150 mm
thick x 650 mm height embedded in earth at least 300 mm below & 350 mm
above ground level respectively at distance approx. 50 meters along the
length of cable. The RCC concreting (1:2:4)(all necessary materials will be in
bidder's scope) of route marker is to be carried out 300 mm width x 150 mm
9 9925000009 thick x 300 mm below ground level as per instruction of EIC. The route No
marker should be with name of company with approved yellow colour-
DGVCL. The distance from marker to cable and cable depth with feeder name
etc., marked with arrow sign is to be painted on it. The route marker is to be
fixed at location near to any fixed permanent location (not necessary to fix
exact on top of cable) as per instruction of EIC.
Erection of D.P. (double pole) structure using 9 / 11 Mtr. RSJ pole with cable
connection arrangement along with fitting of necessary fabrication for 11KV
10 9925000010 cable including excavation of pit & refilling of earth as per instruction of EIC. No
(Exclusive of concreting & muffing of poles)
Erection of Single pole structure using 9 / 11 Mtr RSJ pole with cable
connection arrangement along with fitting of necessary fabrication for
11KV/22 KV cable including excavation of pit & refilling of earth as per
instruction of EIC. (Exclusive of concreting & muffing of poles
Erection of D.P. (double pole) structure using 8.0 Mtr. PSC pole with cable
connection arrangement along with fitting of necessary fabrication for 11KV
12 9925000012 cable including excavation of pit & refilling of earth as per instruction of EIC. No
(Exclusive of concreting & muffing of poles
Erection of Single pole structure using 8.0 Mtr PSC pole with cable connection
arrangement along with fitting of necessary fabrication for 11KV/22 KV cable
including excavation of pit & refilling of earth as per instruction of EIC.
(Exclusive of concreting& muffing of poles
Labour charge for erecting of 11kV / 22 kV XLPE cable of size up to 240 mm
2 on DP Structure with fixing of 02 Nos polymer cleats on top and middle
part. Polymer cleats, nut bolts etc. fixing material to be provided by
Providing & fixing of 6.11kg/cm2 , class4,Green color, 110mm O.D. 8.5mm
thickness H.D.P.E. pipe confirms to IS 4984 and BIS certification on the
erected DP structure for the mechanical protection of cable by inserting the
cable inside HDPE pipe. The HDPE pipe shall be erected in such a way that
15 9925000015 perJob
300mm shall be below the ground level and the rest 2700 mm shall be
supported on the DP Structure with 01 No Polymer cleat. All materials
including polymer cleat and Nut bolt to be provided by contractor.
Providing and fixing of pipe type earthing from 80 mm dia class-B GI pipe
with pit to be filled with salt & coke and construction of chamber as per
DGVCL Drg. No. dg /100 for DP and cable. The earthing pit should be joined
with cable by G.I. strip of size 1" width & 2 mm thick. All material GI pipe,
Coke Salt etc will be supplied by bidder.
Supply & fixing of heat shrink type end terminations (outdoor) for up to 11kV
17 9925000017 3C x 185 mm2 size XLPE cable as per DGVCL technical s ecification No
Supply & fixing of heat & shrinkable end terminations (outdoor) for up to
18 9925000018 kV 3C x 185 mm 2 size XLPE cable ( as per DGVCL technical specification) No
Supply & fixing of heat shrinkable type end terminations (indoor) for up to
19 9925000019 11kV 3C x 185 mm 2 size XLPE cable as per DGVCL technical specification No
Supply & fixing of heat & shrinkable end terminations (indoor) for up to
20 9925000020 kV 3C x 185 mm 2 size XLPE cable as per DGVCL technical specification No
Supply & fixing of heat shrinkable straight through joint for up to 11kV 3C x
21 9925000021 185 mm 2 size XLPE cables as per DGVCL technical specification. No
Supply & fixing of heat shrinkable straight through joint type for up to 22kV
22 9925000022 3C x 185 mm 2 size XLPE cable as per DGVCL technical specification No
Labour charge for excavation of 2100mm long x 1200mm wide x 1200 mm
deep joint pits for installation of 11kV / 22kV Straight through joints as per
23 9925000023 instruction of engineer-in-charge & covering the cable with 150 mm dia No
(Outer), thickness 25 mm, 1.0 meter long RCC half round muffs & refilling
same as per instruction of EIC .
Providing and fixing of insulating bus bar, made from 11KV/22KV XLPE cable
after removal of semi conducting layer and applying of PVC heat shrinkable
antitracking core insulating tubing (1.1KV), on both end terminal using
Aluminium long barrel heavy duty up to 240 sq mm lugs, Aluminium bus
24 9925000024 connector. Taping with PGclamp for bus conductor as per drawing and as per No
instruction of EIC. The Allurninium lugs and PG clamp shall be covered with
11KV/22KV HT insulating tapes.(11KV/22KV XLPE cable will be in scope of
DGVCL while all other materials will be in bidder's scope.
Testing of cable at various points and commissioning the feeder as per
25 9925000025 instruction of engineer-in-charge.Test result shall be submitted by contractor No
Preparation and submission of 6 (six) copies, of complete layout drawings
26 9925000026 with GIS mapping as per actual cable routing showing road crossing, HDPE Set
pipe sleeving, jointing locations, markers etc.
Providing and fixing of Sign Board at junction point Made out of 2 mm
aluminium sheet size 750x300 mm (2.5 x 1 ft) rectangle, as per design,
pretreated with phosphate process and acid etching coated with one coat of
epoxy primer and two coats of best quality paints, reflectorized with Hi
Intensity retro — reflective sheeting as per the latest and frame fabricated
27 9925000027 from suitable size iron angle. The Sign Board is to be fixed on the base No
prepared from channel and bracing angles which is grouted by means of
cement concreting of 1:2:4 for size of 300 mm dia x 800 mm height (500 mm
to be grouted in ground). The details to be displayed on sign board will be
given by InchargeEngineer. (a) Hi intensity Micro prismatic Grade
Providing and fixing of Sign Board (Danger Board) on Distribution
Transformer Centers Made out of 2mm aluminium sheet size 300x300mm
(1X1 ft) as per design, pre treated with phosphate process and acid etching
coated with one coat of epoxy primer and two coats of best quality paints,
28 9925000028 reflectorized with Hi-Intensity retroreflective sheeting as per the latest and No
frame fabricated from suitable size iron angle. The Sign Board (Danger Board
is to be fixed at the location as per instruction of In-charge Engineer. (a) Hi
intensity Micro prismatic Grade
Providing & fixing of aluminium tag of size 250 mm (L) x 75 mm (W) from
mm aluminium sheet along with 1.0 mm dia aluminium binding wire for fixing
of aluminium tag near end termination joint at DP structure for identifying
the cable. The details of feeder i.e. 11 / 22 KV with feeder name should be
punched on the tag by letter punch of size 16 mm as per instruction of In-
charge Engineer.
Supply & fixing of heat shrink type end terminations (outdoor) for 11kV 3C x
30 9925000030 240 mm2 size XLPE cable as per DGVCL technical specification. Nos
Supply & fixing of heat & shrinkable end terminations (outdoor) for 22 kV 3C
31 9925000031 x 240 mm2 size XLPE cable as per DGVCL technical specification Nos
Supply & fixing of heat shrink type end terminations (indoor) for 11kV 3C x
32 9925000032 240 mm2 size XLPE cable as per DGVCL technical specification Nos
Supply & fixing of heat & shrinkable end terminations (indoor) for 22 kV 3C x
33 9925000033 240 mm2 size XLPE cable as per DGVCL technical specification Nos
Supply & fixing of heat shrinkable straight through joint for 11kV 3C x
mm2 size XLPE cables as per DGVCL technical s ecification.
Supply & fixing of heat shrinkable straight through joint type for 22kV 3C x
35 9925000035 240 mm2 size XLPE cable as per DGVCL technical s ecification Nos
Installation, Testing and commissioning of 11 KV,630 A SCADA Compatible,
RRL type3 Way RMU including Two numbers of earthings as per Drawing
(material is in bidder's scope) and as per DGVCL Technical specification.
Installation, Testing and commissioning of 11 KV,630 A SCADA Compatible,
RRLL type4 Way RMU including Two numbers of earthings as per Drawing
(material is in bidder's scope) and as per DGVCL Technical specification.
Installation, Testing and commissioning of 22KV,630 A SCADA Compatible,
RRL type-3 Way, RMU including Two numbers of earthings as per Drawing
(material is in bidder's scope) and as per DGVCL Technical specification.
Installation, Testing and commissioning of 22KV,630 A SCADA Compatible,
RRLL type-4 Way, RMU including Two numbers of earthings as per Drawing
(material is in bidder's scope) and as per DGVCL Technical specification.
Construction of plinth for 11KV, RRL type- 3 Way( i.e Two numbers of
Isolator & One number of Breaker) Ring Main Unit as per DGVCL's technical
specification mentioned in drawing no: Drg. 11kv-01. All required material
will be supplied by contractor.
Construction of plinth for 11KV, RRLL type4 Way (i.e Two numbers of
Isolator & Two number of Breaker)Ring Main Unit as per DGVCL's technical
specification mentioned in drawing no:Drg. 11kv-02.AlI required material will
be supplied by contractor.
Construction of plinth for 22KV, RRL type- 3 Way (i.e Two numbers of
Isolator & One number of Breaker) Ring Main Unit as per DGVCL's technical
specification mentioned in drawing no: Drg. 22kv-01. All required material
will be supplied by contractor.
Construction of plinth for 22KV, RRLL type4 Way (i.e Two numbers of
Isolator & Two number of Breaker)Ring Main Unit as per DGVCL's technical
specification mentioned in drawing no:Drg. 22kv-02.All required material will
be supplied by contractor.
Modifications e.g. Providing and fixing ofTerminal protectors i.e. Re-use able
boot (HT Side 11/22KV, LT Side 1.1KV) including 11/22 KV insulating taps
and L.T.(I.I KV) insulating taps ,Busbar, Tapping from Bus Bar (11/22 KV
XLPE cable) through P.G. Clamp for H.T. Jumper to D.O. Fuse to bushings of
Transformer Center, providing & Fixing of jumper and providing & fixing of
Heat Shrinkable Anti Tracking CoreInsulating Tubing (Insulation Level 11/22
44 9925000046 KV) in H.T. jumper , Clamping arrangement of cable support frame on both no
side of existing Over Head type Distribution Transformer to utilize in Under
Ground cable network as per drawing & as per instruction of Engineer
incharge. All live parts i.e. PGClamp, connections of D.O.fuses, HT bushings
etc . shall be covered with fixing of 11/22 KV HT insulating tapes. ( 11/22 KV
XLPE cable will be in scope of DGVCL while all other materials will be in
bidder's scope )
Laying of any size of 11/ 22 KV XLPE /PILCCable in readymade trench or in
45 9925000047 open space
Labour charges for Lying of O/H XLPE cable pole to pole (Including all
47 Dismental OF 100MM2 AAAC CONDUCTOR KM
Binding of messanger Conductorat with a distance not more than 0.75 mtr
48 9926000064 with 6 turns minimum on XLPE Cable with single strand binding wire NO
(including cost of binding wire)
49 Supply and fixing of Suspenssion clamp to Hold the cable (J-Hook) no
(EXcluding all taxes for the underground cable as per company’s rules and %above/
regulations.) below
Note:- Bidder will have to construct RMU Plinth as per GPRD Cell approved
drawing as per letter no-CEI/INS/186 dated -23.01.2025.
Exe. Engineer (O&M)
DGVCL, Surat Rural Division
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
SCHEDULE A.pdf
BID DOCUMENT.pdf
(3) Integrity Pact.pdf
SCHEDULE B.pdf
(5) Signed OH HT XLPE Cable Drawing 1.pdf
(6) Signed OH HT XLPE Cable Drawing 2.pdf
(7) Signed OH HT XLPE Cable Drawing 3.pdf
(8) Signed OH HT XLPE Cable Drawing 4.pdf
(9) Signed Overhead RE standard drawings.pdf
(10) Route Marker with concreting drawing_0001.pdf
(11) Technical Specification of Termination Kit of XLPE cable.pdf
(12) GPRD_CEI Drawing Approval RMU PLINTH.pdf
Download all tender documents and submit your bid