Executive Engineer, Elect. Divn. PWD B and R Br. Ambala Cantt.
construction of Mukund Lal Civil Hospital Yamuna Nagar (Pdg Balance HVAC Work).
2023_HRY_268833_1
202339AB8E29 5699 4950 A770 17ABDBE17B6C663BAR
Open Tender
Civil Works
Works
30 days
Ambala Cantt.
Please refer Tender documents.
2 documents required · 2 mandatory
₹15,000
₹3.3 L
Yes
20 Jun 2023
27 Mar 2023
18 Apr 2023
27 Mar 2023
17 Apr 2023
27 Mar 2023
Amount
[13.32]Providing and fixing bolts including nuts and washers complete. HSR
[23.22.4.2]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 4.2. Supply and erection of double door sheet steel enclosure distribution board suitable for MCBS and ELCBS etc. recessed in wall including bonding to earth with all labour and material required to complete the job in all respect up to the entire satisfaction of the Engineer-in-Charge of the work. SPN DB Double Door 8 way ( 2 incoming and 6 outgoing) HSR
[23.22.4.3]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 4.3. Supply and erection of double door sheet steel enclosure distribution board suitable for MCBS and ELCBS etc. recessed in wall including bonding to earth with all labour and material required to complete the job in all respect up to the entire satisfaction of the Engineer-in-Charge of the work. SPN DB Double Door 12 way ( 2 incoming and 10 outgoing) HSR
[23.22.4.4]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 4.4. Supply and erection of double door sheet steel enclosure distribution board suitable for MCBS and ELCBS etc. recessed in wall including bonding to earth with all labour and material required to complete the job in all respect up to the entire satisfaction of the Engineer-in-Charge of the work. SPN DB Double Door 16 way ( 2 incoming and 14 outgoing) HSR
[23.22.5.1]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 5.1. Supply and erection of miniature circuit Breaker 240/415 V in the existing distribution board including making necessary connections:- 6 amp. to 32 amp Single Pole HSR
[23.22.5.5]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 5.5. Supply and erection of miniature circuit Breaker 240/415 V in the existing distribution board including making necessary connections:- 6 amp. to 32 amp MCBs TRIPLE POLE HSR
[23.22.5.7]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 5.7. Supply and erection of miniature circuit Breaker 240/415 V in the existing distribution board including making necessary connections:- 6 amp. to 32 amp MCBs FOUR POLE HSR
[23.22.5.8]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 5.8. Supply and erection of miniature circuit Breaker 240/415 V in the existing distribution board including making necessary connections:- 40 amp to 63 amp. MCBs FOUR POLE HSR
[23.3.6.1]COPPER WIRING IN PVC CONDUIT (SURFACE/RECESS) 6.1. Wiring main and sub mains in two single core for phase and neutral wire and one single core for earth wire PVC insulated Copper conductor cable 1100 Volts grade in PVC Conduit etc as required. 1 run of Size 1.50 Sqmm(1/1.40mm) HSR
[25.1.1]Supplying, fixing, testing and commissioning of condenser water pipes / non insulated chilled water pipes of following sizes of MS C class along with necessary clamps, vibration isolators and fittings such as bends, tees etc. but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect. 1. 300mm dia. HSR
[25.1.10]Supplying, fixing, testing and commissioning of condenser water pipes / non insulated chilled water pipes of following sizes of MS C class along with necessary clamps, vibration isolators and fittings such as bends, tees etc. but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect. 10. 40mm dia. HSR
[25.1.2]Supplying, fixing, testing and commissioning of condenser water pipes / non insulated chilled water pipes of following sizes of MS C class along with necessary clamps, vibration isolators and fittings such as bends, tees etc. but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect. 2. 250 mm dia HSR
[25.1.3]Supplying, fixing, testing and commissioning of condenser water pipes / non insulated chilled water pipes of following sizes of MS C class along with necessary clamps, vibration isolators and fittings such as bends, tees etc. but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect. 3. 200mm dia. HSR
[25.1.4]Supplying, fixing, testing and commissioning of condenser water pipes / non insulated chilled water pipes of following sizes of MS C class along with necessary clamps, vibration isolators and fittings such as bends, tees etc. but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect. 4. 150mm dia. HSR
[25.1.5]Supplying, fixing, testing and commissioning of condenser water pipes / non insulated chilled water pipes of following sizes of MS C class along with necessary clamps, vibration isolators and fittings such as bends, tees etc. but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect. 5. 125mm dia. HSR
[25.1.6]Supplying, fixing, testing and commissioning of condenser water pipes / non insulated chilled water pipes of following sizes of MS C class along with necessary clamps, vibration isolators and fittings such as bends, tees etc. but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect. 6. 100mm dia. HSR
[25.1.7]Supplying, fixing, testing and commissioning of condenser water pipes / non insulated chilled water pipes of following sizes of MS C class along with necessary clamps, vibration isolators and fittings such as bends, tees etc. but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect. 7. 80mm dia. HSR
[25.1.8]Supplying, fixing, testing and commissioning of condenser water pipes / non insulated chilled water pipes of following sizes of MS C class along with necessary clamps, vibration isolators and fittings such as bends, tees etc. but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect. 8. 65mm dia. HSR
[25.1.9]Supplying, fixing, testing and commissioning of condenser water pipes / non insulated chilled water pipes of following sizes of MS C class along with necessary clamps, vibration isolators and fittings such as bends, tees etc. but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect. 9. 50mm dia. HSR
[25.7.1]Supply, installation, and commissioning of factory/site fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required. 1. Thickness 0.63 mm sheet HSR
[4.12.1]Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead up to 50 m and lift up to 1.5 m, as directed by Engineer-in-charge. 1. All kinds of soil HSR
[4.32]Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m. HSR
[6.1.4]Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work below plinth level and up to Floor IV level: 4. 1:3:6 (1 Cement : 3 coarse sand (zone-III) : 6 graded stone aggregate 20 mm nominal size) HSR
[6.15.1]Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. above plinth level up to floor four level, excluding cost of centering, shuttering, finishing and reinforcement : 1. 1:1.5:3 (1 cement : 1.5 coarse sand(zone-III) : 3 graded stone aggregate 20 mm nominal size) HSR
[6.29.1]Centering and shuttering including strutting, propping etc. and removal of form work for : 1. Foundations, footings, bases for columns HSR
[6.29.3]Centering and shuttering including strutting, propping etc. and removal of form work for : 3. Columns, piers, abutments, pillars, posts and struts HSR
[6.30.5]Centering and shuttering including strutting, propping etc. and removal of form for 5. Lintels, beams, plinth beams, girders, bressumers and cantilevers HSR
[6.33.6]Steel reinforcement for R.C.C. work, where not included in the complete rate of RCC, including straightening, cutting, bending, placing in position, binding, wastage, overlaps, welded joints, spacer bars, chairs, stays, hangers and annealed steel wire etc. complete in all respect below plinth level 6. Thermo-Mechanically Treated bars of grade Fe-500D or more. HSR
[7.92.1]`Stone block masonry (including quoin-blocks, jamb blocks, closer etc.) with precast solid concrete blocks of approved size laid in cement sand mortar 1:6 (1 cement : 6 fine sand ) in foundation and plinth ` 1. precast cement concrete block made from medium size stone 15 to 20 cm, 35% in volume at the face and cement, concrete 1:4:8 (with stone aggregate of 20 mm and down gauge) 65% in volume. HSR
Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled / hot water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg / cu m density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class `O` insulation applied by suitable adhesive or Chemically cross linked polyethlyne foam of class`O`(XLPE) with Aluminium PE foil for as per given below pipe size. The joints shall be sealed with 50 mm x 1 mm thick self adhesive tape at the joints etc. and complete as per specifications including repairing of damage to building etc. and as required complete in all respect. Note:- The Pipes of sizes 150mm and below shall be M.S. `C` class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above. 25 mm dia(19 mm thick insulation) NS
Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled / hot water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg / cu m density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class `O` insulation applied by suitable adhesive or Chemically cross linked polyethlyne foam of class`O`(XLPE) with Aluminium PE foil for as per given below pipe size. The joints shall be sealed with 50 mm x 1 mm thick self adhesive tape at the joints etc. and complete as per specifications including repairing of damage to building etc. and as required complete in all respect. Note:- The Pipes of sizes 150mm and below shall be M.S. `C` class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above. 32 mm dia(19 mm thick insulation) NS
Supply, installation, testing and commissioning of GI volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc, as per specifications. NS
Supplying, fixing testing commissioning of supply air diffusers of powder coated aluminium with aluminium volume control dampers with anti smudge ring and removable core. NS
Supplying, fixing testing commissioning of Return air diffusers of powder coated aluminium without volume control dampers with anti smudge ring and removable core NS
Supplying, Fixing,testing and commissioning of fire dampers in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring,the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications. Fire damper NS
Supply and fixing of acoustic lining of supply air duct and plenum with 25 mm thick resin bonded glass wool having density of 32 kg/m³, with 25 mm X 25 mm GI section of 1.25 mm thick, at 600 mm centre to centre covered with Reinforced Plastic tissue paper and 0.5 mm thick perforated aluminum sheet fixed to inside surface of ducts with cadmium plated nuts, bolts, stick pins, CPRX compound etc. or anti-microbial Chemically cross linked polyethlyne foam of class`O`(XLPE)complete as required and as per specifications. NS
Supplying and fixing of following thickness duly laminated aluminum foil of mat finish closed cell Nitrile rubber (Class `O`) insulation on existing duct after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation or anti-microbial Chemically cross linked polyethlyne foam of class`O`(XLPE) with Aluminium PE foil complete as per specifications and as required. 25 mm for external duct NS
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. (3½) X 400 sq. mm NS
Providing and fixing earth bus of 50 mm X 5 mm copper strip on surface for connections etc. as required NS
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. NS
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. NS
Supplying and installing following size of perforated pre-painted M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts and nuts, painting suspenders etc as required. 100 mm width x 50 mm depth x 1.6 mm thickness NS
Supplying and installing following size of perforated pre-painted M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts and nuts, painting suspenders etc as required. 150 mm width x 50 mm depth x 1.6 mm thickness NS
Supplying and installing following size of perforated pre-painted M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts and nuts, painting suspenders etc as required. 300 mm width x 50 mm depth x 1.6 mm thickness NS
Supplying and installing following size of perforated pre-painted M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts and nuts, painting suspenders etc as required. 600 mm width x 62.5 mm depth x 2.0 mm thickness NS
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated NS
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.9.1.24 - 3½ X 95 sq. mm (45mm) NS
Supply,installation,testing and commissining of direct driven Tube axial flow fans suitable for installing in any position in Horizontal or vertical with adjustable pitch blade, MS with powder double coated / High duty GSS long Casing, cast aluminium alloy impeller complete with TEFC Sq. Cage Induction type IE-2 motor suitable for 415 volts ± 10%, 50Hz ± 3 %, 4 Pole, three phase A.C supply of class `H` insulation motor`s winding with support, mountings, vibration isolators, fire retardant flexible canvass connector 150 mm deep with 25 mm slack at Outlet etc..Motor shall be suitable for 250 °C temperature rated for 2 hours and shall be completely be accommodated inside the fan casing.The fans shall be as per specifications and tender drawing of following capacity:- Thickness of the casing shall not be less than: For Dia (300 to 650) mm – 2mm, Dia (700 to 1140) mm – 3 mm, Dia (1200 to 1400) mm – 4mm and Dia 1600 – 5 mm.Multi piece casing is not accepted. Manufacturer shall furnish AMCA Test Certificate for air performance along with fire test certificate (Latest) for each fan sourced from that particular factory. 2000 CFM / 15 mm Wg - For Basement Store NS
Supply, installation, testing and commissioning of Bipolar Air Ionizer combination of Needle point , Tube Type and Carbon Brush Type which produces a natural Bio Climate rich in equal amount of positive and negative ions. The ionizer shall be kill microorganism and pathogens, remove Odour, VOC and reduce dust particle. The Ionizer should be UL 2998 and UL 867 listed.The housing material is 18G steel powder coated. Models accept 24V AC input, 120V AC to 12V DC wall pack, 120V/240V AC to 12V DC power supply and 241V/277V AC to 12V DC power supply. AHU`s 1200 CFM NS
Supply, installation, testing and commissioning of Bipolar Air Ionizer combination of Needle point , Tube Type and Carbon Brush Type which produces a natural Bio Climate rich in equal amount of positive and negative ions. The ionizer shall be kill microorganism and pathogens, remove Odour, VOC and reduce dust particle. The Ionizer should be UL 2998 and UL 867 listed.The housing material is 18G steel powder coated. Models accept 24V AC input, 120V AC to 12V DC wall pack, 120V/240V AC to 12V DC power supply and 241V/277V AC to 12V DC power supply. AHU`s 1500 CFM NS
upply, installation, testing and commissioning of Bipolar Air Ionizer combination of Needle point , Tube Type and Carbon Brush Type which produces a natural Bio Climate rich in equal amount of positive and negative ions. The ionizer shall be kill microorganism and pathogens, remove Odour, VOC and reduce dust particle. The Ionizer should be UL 2998 and UL 867 listed.The housing material is 18G steel powder coated. Models accept 24V AC input, 120V AC to 12V DC wall pack, 120V/240V AC to 12V DC power supply and 241V/277V AC to 12V DC power supply. AHU`s 4000 CFM NS
Supply, installation, testing and commissioning of Bipolar Air Ionizer combination of Needle point , Tube Type and Carbon Brush Type which produces a natural Bio Climate rich in equal amount of positive and negative ions. The ionizer shall be kill microorganism and pathogens, remove Odour, VOC and reduce dust particle. The Ionizer should be UL 2998 and UL 867 listed.The housing material is 18G steel powder coated. Models accept 24V AC input, 120V AC to 12V DC wall pack, 120V/240V AC to 12V DC power supply and 241V/277V AC to 12V DC power supply. AHU`s 8000 CFM NS
Supply, installation, testing and commissioning of Bipolar Air Ionizer combination of Needle point , Tube Type and Carbon Brush Type which produces a natural Bio Climate rich in equal amount of positive and negative ions. The ionizer shall be kill microorganism and pathogens, remove Odour, VOC and reduce dust particle. The Ionizer should be UL 2998 and UL 867 listed.The housing material is 18G steel powder coated. Models accept 24V AC input, 120V AC to 12V DC wall pack, 120V/240V AC to 12V DC power supply and 241V/277V AC to 12V DC power supply. AHU`s 14000 CFM NS
Supply, installation, testing and commissioning of Bipolar Air Ionizer combination of Needle point , Tube Type and Carbon Brush Type which produces a natural Bio Climate rich in equal amount of positive and negative ions. The ionizer shall be kill microorganism and pathogens, remove Odour, VOC and reduce dust particle. The Ionizer should be UL 2998 and UL 867 listed.The housing material is 18G steel powder coated. Models accept 24V AC input, 120V AC to 12V DC wall pack, 120V/240V AC to 12V DC power supply and 241V/277V AC to 12V DC power supply. FCU: 2.5 TR / 1000 CFM NS
Supply, installation, testing and commissioning of Centrifugal Air Separator with matching flanges, bolts, nuts and gasket, with supervent, strainer, insulation, valves and fittings, 300 mm dia, PN16 etc NS
Tank shall be complete with Pressurization kit including Pumps required in the configuration of N plus 1 (1working plus 1 Stand By). The cost shall include necessary valve package and control logic panel (Head-25mtrs ) NS
Supply,installation,testing and commissioning of M.S. expansion tank of size 450 mm x 450 mm x 450 mm height made of 3 mm thick mild steel sheet complete with 19 mm thick nitrile rubber insulation covered with 24G Aluminium foil and complete with air vent and drain connection with valve, and control valves etc. as required. NS
Supply, fabrication, installation and testing of Aluminium sheet metal ducting duly silicon sealed and as per tender drawings.The price shall include with supports such as full threaded rod and GI slotted channel / Wire Rope hanger including nut bolt fastner for ceiling hung and rigid Supports if laid on floor complete with end fixing in accordance with the approved shop drawings and as required by the specifications. , access door etc. 22 Gauge NS
Supply, Errection and testing of under noted sizes of Copper conductor 1100 volts bflexinle ABC conductor, PVC type D insulated, cross laid up , overshielded cable on existing cable trays. 3C X 2.5 Sq.mm NS
Supply, Errection and testing of under noted sizes of Copper conductor 1100 volts bflexinle ABC conductor, PVC type D insulated, cross laid up , overshielded cable on existing cable trays. 4C X 4.0 Sq.mm NS
Supplying and making end termination with brass/Pg compression gland and copper lugs for following size of PVC unsheathed copper conductor cable single core 1100 Volts grade as required. 4C X 1.5 sq. mm NS
Supplying and making end termination with brass/Pg compression gland and copper lugs for following size of PVC unsheathed copper conductor cable single core 1100 Volts grade as required. 3C X 2.5 sq. mm NS
Supplying and making end termination with brass/Pg compression gland and copper lugs for following size of PVC unsheathed copper conductor cable single core 1100 Volts grade as required. 4C X 4 sq. mm NS
Supply, Errection and testing of under noted sizes of Copper conductor 1100 volts bflexinle ABC conductor, PVC type D insulated, cross laid up , overshielded cable on existing cable trays. 4C X 1.5 Sq.mm NS
Supply testing of under noted sizes of Aluminium conductor insulated PVC sheathed and sleeved armoured and overall PVC sleeved 1.1 KV grade power distribution cables conforming to relevant IS code and as per specification on existing cable trays. 95 Sq. mm 3.5 Core Cable . NS
Supply testing of under noted sizes of Aluminium conductor insulated PVC sheathed and sleeved armoured and overall PVC sleeved 1.1 KV grade power distribution cables conforming to relevant IS code and as per specification on existing cable trays.50 Sq. mm 3.5 Core Cable . NS
Supply testing of under noted sizes of Aluminium conductor insulated PVC sheathed and sleeved armoured and overall PVC sleeved 1.1 KV grade power distribution cables conforming to relevant IS code and as per specification on existing cable trays.35 Sq. mm 3.5 Core Cable . NS
Supply testing of under noted sizes of Aluminium conductor insulated PVC sheathed and sleeved armoured and overall PVC sleeved 1.1 KV grade power distribution cables conforming to relevant IS code and as per specification on existing cable trays. 25 Sq. mm 3.5 Core Cable . NS
Extra for Supplying and fixing of insulation on following nominal dia pipes with FR quality expanded polystyrene moulded pipe section of density 20 kg/cum after a thick of coat of cold setting adhesive (CPRX compound) wrapping with 500 g polythene faced hessian and then applying 0.6 mm aluminium sheet cladding complete with felt strip at joints repairing etc. as per specifications and as required complete in all respect. each Add 25% cost of pipe (40 mm Dia) NS
Extra for Supplying and fixing of insulation on following nominal dia pipes with FR quality expanded polystyrene moulded pipe section of density 20 kg/cum after a thick of coat of cold setting adhesive (CPRX compound) wrapping with 500 g polythene faced hessian and then applying 0.6 mm aluminium sheet cladding complete with felt strip at joints repairing etc. as per specifications and as required complete in all respect. each Add 25% cost of pipe (50 mm Dia) NS
Extra for Supplying and fixing of insulation on following nominal dia pipes with FR quality expanded polystyrene moulded pipe section of density 20 kg/cum after a thick of coat of cold setting adhesive (CPRX compound) wrapping with 500 g polythene faced hessian and then applying 0.6 mm aluminium sheet cladding complete with felt strip at joints repairing etc. as per specifications and as required complete in all respect. each Add 25% cost of pipe (65 mm Dia) NS
Extra for Supplying and fixing of insulation on following nominal dia pipes with FR quality expanded polystyrene moulded pipe section of density 20 kg/cum after a thick of coat of cold setting adhesive (CPRX compound) wrapping with 500 g polythene faced hessian and then applying 0.6 mm aluminium sheet cladding complete with felt strip at joints repairing etc. as per specifications and as required complete in all respect. each Add 25% cost of pipe (80 mm Dia) NS
Extra for Supplying and fixing of insulation on following nominal dia pipes with FR quality expanded polystyrene moulded pipe section of density 20 kg/cum after a thick of coat of cold setting adhesive (CPRX compound) wrapping with 500 g polythene faced hessian and then applying 0.6 mm aluminium sheet cladding complete with felt strip at joints repairing etc. as per specifications and as required complete in all respect. each Add 25% cost of pipe (100 mm Dia) NS
Extra for Supplying and fixing of insulation on following nominal dia pipes with FR quality expanded polystyrene moulded pipe section of density 20 kg/cum after a thick of coat of cold setting adhesive (CPRX compound) wrapping with 500 g polythene faced hessian and then applying 0.6 mm aluminium sheet cladding complete with felt strip at joints repairing etc. as per specifications and as required complete in all respect. each Add 25% cost of pipe (125 mm Dia) NS
Extra for Supplying and fixing of insulation on following nominal dia pipes with FR quality expanded polystyrene moulded pipe section of density 20 kg/cum after a thick of coat of cold setting adhesive (CPRX compound) wrapping with 500 g polythene faced hessian and then applying 0.6 mm aluminium sheet cladding complete with felt strip at joints repairing etc. as per specifications and as required complete in all respect. each Add 25% cost of pipe (150 mm Dia) NS
Extra for Supplying and fixing of insulation on following nominal dia pipes with FR quality expanded polystyrene moulded pipe section of density 20 kg/cum after a thick of coat of cold setting adhesive (CPRX compound) wrapping with 500 g polythene faced hessian and then applying 0.6 mm aluminium sheet cladding complete with felt strip at joints repairing etc. as per specifications and as required complete in all respect. each Add 25% cost of pipe (200 mm Dia) NS
Extra for Supplying and fixing of insulation on following nominal dia pipes with FR quality expanded polystyrene moulded pipe section of density 20 kg/cum after a thick of coat of cold setting adhesive (CPRX compound) wrapping with 500 g polythene faced hessian and then applying 0.6 mm aluminium sheet cladding complete with felt strip at joints repairing etc. as per specifications and as required complete in all respect. each Add 25% cost of pipe (250 mm Dia) NS
Extra for Supplying and fixing of insulation on following nominal dia pipes with FR quality expanded polystyrene moulded pipe section of density 20 kg/cum after a thick of coat of cold setting adhesive (CPRX compound) wrapping with 500 g polythene faced hessian and then applying 0.6 mm aluminium sheet cladding complete with felt strip at joints repairing etc. as per specifications and as required complete in all respect. each Add 25% cost of pipe (300 mm Dia) NS
Supply and erection of under ground cable ,loose in existing pipe or trenches complete with necessary connections . 400 Sq. mm 3.5 Core Cable NS
M/s Sharma Electrical Engineer
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .