| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.4 LAccepted-AOC MUKALATH VALAYANCHIRANGARA PO PERUMBAVOOR ERNAKULAM KOCHI 683556 | PERUMBAVOOR | ERNAKULAM | KERALA | 683556 | ₹9.4 L Quoted ₹9.5 L | L1 | Accepted-AOC lowest tender |
| 2 | L2₹14.2 L+₹4.7 L (49.3%)Rejected-Finance | ₹14.2 L+₹4.7 L (49.3%) | L2 | Rejected-Finance Other than lowest tender |
| 3 | L3₹16.6 L+₹7.1 L (74.0%)Rejected-Finance JOY VILA MRA 230 MOOLAVILKOM JUNCTION VANCHIYOOR TRIVANDRUM 695 035 | TRIVANDRUM | THIRUVANANTHAPURAM | KERALA | 695035 | ₹16.6 L+₹7.1 L (74.0%) | L3 | Rejected-Finance Other than lowest tender |
Tender Value
Refer Docs
EMD Value
₹30,000
Closing Date
15 Dec 2020, 6:00 pmClosed
GE NS KOCHI
Military Engineer Services Garrison Engineer (Naval Services) Kataribagh, Naval Base Post Kochi, 682 004
OUTSOURCING OF MAIN REC. STA INC PUMP HOUSE AND DG SET AT NAE , REP/MAINT OF CEILING FAN, EXH FAN, ELE SUPLY, SWITCH, TUBE LIGHT, GEYSER AND REP TO SPLIT AC AND REP TO BOUNDARY WALL LGT FTG ,STREET LIGHT, LT LINE, EARTHING, TRANS AND MISC REP AT NAE
2020_MES_399432_1
8729/E8
Open Tender
Electrical and Maintenance Works
Item Rate
210 days
ALUVA
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GE NS KOCHI
₹30,000
Yes
20 Jan 2021
30 Nov 2020
17 Dec 2020
30 Nov 2020
15 Dec 2020
1 Dec 2020
Amount
Manning, operation and routine maintenance of substation at Naval Air Enclave Nedumbassery by keeping the substation functional round the clock including all Sundays and holidays, so that electric supply can be given to the user without any interruption and maintaining all HT/LT switchgears and transformer and any fault occurs in the system like disconnection/ tripping of RMU, HT/LT switchgears, AMF, APFC panel, starters, adjusting the tap of transformers, monitoring and maintaining the power factor above the specified limit round the clock and attending any type of fault or breakdown in the station and operation & routine maintenance of DG set of Capacity 62.5 KVA, operation and maintenance of water supply pump sets, fire fighting pump sets etc, at Naval Enclave Nedumbassery and also cleaning of substation and surroundings, including maintaining complaint, shut down and any other register as per the direction of Engineer-in-Charge at any time.
Notes: (i) The electrician should have good knowledge to work with HT/LT line and the fault/ breakdown if occurs shall be attended immediately. (ii) Contractor has to ensure minimum One highly skilled Electrician (ITI/Diploma holder) per shift @ 8hours (Three shifts per day). If not, Penalty / Recovery as per relevant PS clause shall be imposed. Any other man power of helper shall be provided by the contractor as per site requirement. Rate quoted by the contractor shall be deemed to be included in the unit rate.The person deployed in the shift will not leave the duty station until the reliever takeover the complete installation for operation. (iii) It is the responsibility of the contractor to collect and carry fuel from the store yard of AGE B/R Alwaye of GE (NS) Kochi, to Naval Air Enclave, Nedumbassery for running the DG set and the cost for which is deemed to be included in the rate quoted. (iv) The fuel in the DG set has to be checked periodically and top up whenever necessary to ensure the readiness of DG set at any time. (v) All petty items such as insulation tape, cotton waste, grease, distilled water, coolant, etc. required for routine/ periodical maintenance and repairs and the rate for which is deemed to be included in the quoted rate. (vi) All required tools such as cutting pliers, spanner set, screw drivers, line tester, hand gloves, multi meter, HT/LT insulation tester, earth tester, crimping tools, first aid kit, etc., has to be provided b y the contractor and the expenditure for these items is deemed to be included in the quoted rate.
GST LIABILITY It is considered prudent to specify that the GST is included in the rates quoted against items of outsourcing as well as items of repairs/comprehensive maintenance to be paid separately under material and labour’ parts. MONTHLY WAGES Monthly wages shall be paid by the contractor to the workers/labour only online. Proof of statutory deductions in favour of workers/labour shall be submitted by the contractor to the Engineer in Charge along with RAR/Final Bill for verification. The contractor will be required to submit copy of valid labour licence from the Labour Commissioner within 15 days of commencement of the work BASIC RATE, EPF, ESIC, BONUS, OVER HEAD PROFIT, TAXES & LWC The bidder to quote basic rate, employer's contribution towards Employees Provident Fund (EPF) liability, contribution towards Employees State Insurance Corporation (ESIC), contribution towards bonus, overhead and profit and labour welfare cess (LWC) separately, as applicable depending upon the manpower requirement. This will create onus on the contractor to ascertain the relevant rates and quote accordingly. The rates quoted shall be inclusive of all taxes, cess, and levies as applicable including GST as prevailing applicable law. Contractor shall be note liable for the same.
Taking down carefully copper/aluminum point wiring (light, fan, socket or power) complete and making good disturbed surfaces of walls, floors, ceiling and match with existing surface complete all as specified and directed.
Material and labour for point wiring in repair with 1.5 sqmm PVC insulated unsheathed single core multistranded copper conductor cable, FRLS, ISI marked drawn through and including PVC conduit of suitable size and all accessories, not less than 2mm thick, fire resistant, ISI marked including 2 mm thick and 4cm depth GI sheet pressed terminal box ( recessed) with 3 mm thick laminated hylam sheet top cover including 1.50 Sqmm PVC insulated unsheathed multistranded single core copper conductor FRLS, ISI marked cable as earth continuity conductor and making good the disturbed surfaces of walls, floors, ceiling etc all as specified and directed for One light point controlled by one switch.
Ditto All as per Item No 3, But for One ceiling fan point controlled by one switch.
Ditto All as per Item No 3, But for One 3 pin 5 Amps socket outlet controlled by one switch on independent board.
Ditto All as per Item No 3, But for One 3 pin 5 Amps socket outlet controlled by one switch in the same board with other switches.
Ditto All as per Item No 3, But with 2.5 Sq mm cable for wiring and 2.50 Sqmm cable as earth continuity conductor for one 16 Amps switch socket outlet on independent board.
Supply and fix switch piano, Modular type, 6 Amps, SP, one way, one module complete all as specified and directed.
Supply and fix switch piano, modular type, 16 Amps, SP, one way, one module complete all as specified and directed.
Supply and fix socket outlet, modular type, 6 Amps, 2/3 pin combined , 2 module complete all as specified and directed.
Supply and fix switch socket combination, 2/3 pin, 2 module 06/16Amps, modular type, complete all as specified and directed.
Supply and fix modular white cover plate with frame for one module complete all as specified and directed.
Supply and fix modular white cover plate with frame for two module complete all as specified and directed.
Supply and fix modular white cover plate with frame for three module complete all as specified and directed.
Supply and fix modular white cover plate with frame for six module complete all as specified and directed.
Material and labour for sub main wiring with two runs of 4 Sqmm PVC insulated unsheathed single core multistraded copper conductor cable, FRLS, ISI marked and one run of 4 Sqmm multistranded insulated copper conductor cable, FRLS, ISI marked as earth continuity conductor drawn through and including PVC conduit of suitable size and all accessories, not less than 20mm thick, fire resistant, ISI marked and making good the disturbed surfaces of walls / floors / ceiling etc and including removing the existing aluminium sub main wiring cable, complete all as specified and directed.
Supply and fix in repairs sheet metal enclosure for MCB DB SPN 8 ways, 240V, with 200 Amps bus bar, double door, complete all as specified and directed.
Supply and fix in repairs MCB SP 6 to 32 Amps, 'C' series complete all as specified and directed.
Supply and fix in repairs MCB SPN 32 Amps 'C' series complete all as specified and directed.
Supply and fix in repairs MCB TPN 63 Amps 'C' series complete all as specified and directed.
Dismantling and taking down any type of light fittings (single/double) of any wattage or size, complete all as specified and directed.
Supply and fix LED Tube light suitable for 4 feet, 18/20Watt Florescent T/light fittings complete all as specified and directed. Make : Luker (LT5M20) or Equivalent in Bajaj, CG
Taking down unserviceable 1200mm/1400mm sweep ceiling fan, overhauling the existing burnt out fan motor winding, cleaning the motor slots, rewinding the motor with insulated copper winding wire of existing gauge baking/ heating up the motor to achieve the proper insulation resistance, replacing of body screws testing and commissioning on full load for 8 hours continuous running and re-hanging/ re-fixing after repair, complete all as specified & directed.
Supply & fix fan regulator electronic, socket type,hum proof, AC Volts,5 step, complete all as specified and directed.
Supply & fix in repair 2.5 MFD condensor/capacitor, 240 volts, AC,complete all as specified and directed.
Supply & fix in repair satinless steel ball bearing suitable for fan of any size and make, complete all as specified and directed.
Material & Labour for disconnecting water cooler 60/120 Ltrs capacity from position, transporting to local workshop for servicing including cleaning of interior parts and body with solvent materials, replacement of unserviceable spares/parts if required, necessary repairs, transporting back, Installing at its original location, Connecting, Testing and commissioning complete all as specified & directed.
Material & Labour for disconnecting Refrigerator of 165 to 310 Ltrs capacity from position, transporting to local workshop for servicing including cleaning of interior parts and body with solvent materials, replacement of unserviceable spares/parts if required, necessary repairs, transporting back, installing at its original location, connecting, testing and commissioning complete all as specified & directed.
Material & Labour for General servicing of Indoor & outdoor unit of split type AC upto 1.5 TR to 2 TR after taking down from the existing position, clean internal parts, clean external cover with suitable liquid/solvent, clean filter/washing with water, replace the unserviceable parts if any including re fixing the AC in same/other location and connecting, commissioning complete all as specified & directed. Note: - The quote rate shall be inclusive of the cost of spare parts.
Supply & Fix hermetically sealed compressor unit suitable for 1.5TR /2 TR capacities split ACs including taking down old unserviceable sealed compressor unit, connecting up complete all as specified & directed.
Supply & Fix Prime control Remote Board and temperature digital display sensor suitable for split type AC of any capacity including taking down old unserviceable board & display sensor complete all as specified & directed. Make: Voltas.
Supply & Fix in repair Running capacitor 60 MFD suitable for window/ split AC complete all as specified & directed. Make : Keltron/Havells/Epcos
Supply & Fix in repair Fan Motor suitable for Split AC upto 2 TR capacity each complete all as specified & directed. Make: Voltas/LG/ Blue star.
Supply & Fix in repair Swing Motor for indoor unit suitable for Split AC upto 2 TR capacity each complete all as specified & directed. Make: Voltas/LG/ Blue star.
Supply and fix Thermostat unit all as specified complete all as specified & directed.
Taking down High bay luminaries from Hanger and supply and fix high bay industrial indoor luminaries 50W of Make :Luker (LHBY50), complete all as specified
Material & Labour for repairing electric operated hanger sliding door including repair to electric motor and gear box, cutoff switch, sliding wheels, control panel etc, complete all as directed.
Material & Labour for servicing of HT VCBs, 11 KV, 400/630 Amp capacity, indoor type by drawing out breaker assay from panel, cleaning/decarbonizing the contact points by suitable means, applying petroleum jelly, lubrication, adjust the trolley in and out mechanism and moving parts, testing of all tripping system and device, internal wiring circuit etc, tightening of all connections, replacement of HRC fuse (if any found unserviceable ) engage the VCB with the supply system and testing for smooth function complete all as directed.
Material & Labour for calibration of protective relays both 02 Nos over current and 01 No earth fault relay of IDMT or any other type by using relay injection kit and re-set timing and tripping current according to the connected load complete all as directed.
Supply and filling of new transformers oil having di-electric strength not less than 45 KV complete all as directed.
Material & Labour for servicing of transformer, 11 KV/415V step down or step up 415/11KV indoor/outdoor, type of capacity 200 KVA, disconnecting HT/LT side, drain out the transformer oil, checking IR value of oil, opening the transformer and taking out the winding assembly, clean thoroughly the bottom for sludge, replacement of complete gasket set, arresting minor leakage from drain valve and other places, heating /drying the winding assembly checking of HT/LT insulators for desired IR Value, replacement of corroded nuts/bolts, washer etc., re-fitting of transformer oil and topping up with new oil, re-fix and re-installation of transformer and testing all as directed Note:- De-hydration/ filtration/new oil/LT/HT bushing will be measured and paid separately.
Material & Labour for Filtrations of transformer oil of distribution transformer of different capacities through stream line filter unit to increase di -electric strength (BDV) of transformer oil not less than 40 KV for 1 minute at 4 mm gap including topping up transformer oil to the required level as indicated to each transformer and testing, transformer oil before and after filtration complete as directed. Note: Transformer oil will be measured and paid separately. Contractor shall submit record of tests in duplicate to Engineer in Charge.
Supply and replacement of silica gel of superior quality for air breather of transformer installed at NAD Alwaye.
Supply only power capacitor (MPP) in existing capacitor bank of capacity 5 KVAR complete as directed. Make : L&T/ Havells
Material & Labour for removing complete covers of the LT panel board, cleaning the bus bars with CTC solution, removing the carbon deposits, rust particles etc. tightening the bus bars, bolts, nuts including replacing with required new bolts nuts, insulating the exposed portion with insulating tapes and replacing the damaged insulators/ hylam sheets etc, and re-fixing the covers and testing complete as specified and directed.
Supply and fix MCCB 3 pole 415V fixed type breaking capacity 36 KA 250 Amps complete as specified and directed.
Material and labour for earthing completely with galvanised iron earth plate electrode 60 cm x 60 cm x 6.3 mm buried directly in ground to a depth not less than 2.25m below ground level with top edge of the earth plate at a depth not less than 1.5m below normal ground level surrounded from all side by 15 cm of thick and packed layers of charcoal dust and common salt ,filling alternate layers and electrode connected by using GI wire 4 mm dia (maximum length of 7.5 meters ) by means of bolt, nut and washer of GI and providing GI light grade pipe 15 mm dia as protection pipe for GI wire, connected main control board / test point and provided with GI pipe of light grade 20 mm bore for watering and including funnel, wire mesh PCC chamber of 1:3:6 type C1 ,and RCC cover of 1:2:4 type B1 including necessary earth work in any type of soil /strata, disposal of soil all as directed and shown in electrical plate No. 3 of SSR part -1 including testing on entire completion.
Supply and laying in replacement of XLPE insulated, armoured heavy duty LT electric cable with aluminium conductor, 1100 volts grade, cross section area of cable 70 sqmm 3.5 core, laid in trenches or fixed on walls, poles etc, complete all as specified and as directed.
Dismantling & taking down of any wattage or any size of flood light fitting from the poles complete all as directed.
Supply and fixing of LED Flood light 50 Watt of Luker Product code LFL -50 and taking down the old complete all as directed.
Material & Labour for servicing of 6 cylinder engine of DG set by using proper tools and service facilities and carry out the following 'B' check maintenance of Make :- cater pillar of capacity 62.5 KVA at NAE Nedumbassery, complete all as directed.
Material & Labour for dismantling of self starter 12/24V from engine and transporting to workshop for repair, opening cleaning and replacing defective bushes, bentex pinion ball bearing and including varnishing of coils heating, drying etc for DG set upto 75 KVA complete all as directed.
Filling only Engine oil multi grade OMD-110/20W 40/SAE 40 in replacement of old engine oil complete all as directed.
Supply and replace fan belt suitable for 62.5 KVA capacity Generator set of Make Crompton Greaves complete all as directed.
Supply and fill coolent for radiator complete all as directed. Make : Servo/BP/HP or Equivalent.
Servicing of DG panel, cleaning, checking of electric connections, replacing defective components, meter, relays, indicating lamps, and all other control systems for the proper functioning of the panel of DG set 62.5 KVA all as directed.
Comprehensive maintenance of addressable fire alarm system installed at NAE Nedumbassery for functionality of all components, cleaning all device, replacement of defective spares / components, comprising of following all as specified and directed. Make : Notifier. (a) Microprocessor based control Panel 2 Loop - 01 No. (b) Electronic siren - 01 No (c) Fire alarm hooters - 02 Nos. (d) Manual call points - 09 Nos. (e) Repeater Panels - 01 Nos. (f) 36 AH Battery - 01 Nos Note:- (a) Contractor shall maintain all the documents and produce to the concerned Engineer in charge as and when required /preparation of RAR. (b) Contractor shall give the Demo and training for all duty staffs about the fire alarm System. The unit rate quoted shall be inclusive of the same. (c) Spares required for replacement, shall be measured separately as 'Supply only' under respective items.
Supply only addressable Manual call point resettable type all as specified and directed. Make : Edward/GST/Honey well/ Morley/Siemens.
Supply and laying 2 core1.5 sq mm PVC insulated unsheathed FRLS multi stranded copper conductor cable all as specified and as directed. Make : Polycab/Havells/Finolex/Indoasian/National
Supply and install in repair of addressable multi sensor detection with heat and smoke combination including testing and commissioning on completion complete all as specified and directed. (Model:-MOFHMPTSEI B501AP/IV)
Amount Credit shall be deducted to arrive the Contract Sum.
RASNA ENTERPRISES
S L ELECTRICAL WORKS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .