Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹11.9 LAccepted-AOC PARUVAYAD W VIILITAITHUNAD ALUVA SRM 600017 | ERNAKULAM | KERALA | 680667 | L1 | Accepted-AOC L1 | |
| 2 | L2₹12.1 L+₹17,953.90 (1.51%)Rejected-Finance RKP 6 8 B C KADOOR CHAMBER KADOOR SALES CORPORATION KADOOR CHAMBER RAMANATUKARA RAMANATTUKARA KOZHIKODE KERALA 673633 | KOZHIKODE | KERALA | 673633 | L2 | Rejected-Finance L2 | |
| 3 | Rejected-Technical | - | Rejected-Technical L3 | |
| 4 | Rejected-Technical | - | Rejected-Technical L4 |
Tender Value
₹14.3 L
EMD Value
₹35,625
Closing Date
22 Jul 2020, 5:00 pmClosed
Assistant Executive Engineer
municipal office Manjeri
Manjeri Municipality Supply installation testing commissioning of 82.50 KVA diesel Generator set for Newly constructed Municipal office
2020_LSGD_371274_2
E1-ETN/87/20-21
Open Tender
Electrical Works
Item Rate
60 days
Manjeri Municipality
Please refer Tender documents.
8 documents required · 8 mandatory
₹3,230
Yes
online
₹35,625
Yes
3 Nov 2020
13 Jul 2020
24 Jul 2020
13 Jul 2020
22 Jul 2020
13 Jul 2020
Amount
Supply, conveyance, Installation, testing & commissioning of 82.5 KVA Diesel Generator set with AMF integral acoustic enclosure as per CPCB norms with standared acessories as per echnical details given below. 1. Engine : a)Make of Engine-KOEL/Cummins/Volvo/Cooper/Greaves b) Type of Engine -Three Phase Diesel Engine c) No. of Cylinders - As per manufactures standards. d) Method of Cooling - Water cooled with radiator. e) Aspiration Turbo charged after cooled. f) Design - Suitable for generating set operation 2.Standard accessories with Diesel Engine a) Fly wheel to suit flexible coupling b) Close Coupling c) Air cleaner d) Radiator with fan provided with fan guard. e) Fuel Pump f) Mechnical governor g) Fuel filter h) Lubricating oil filter i) Exhaust silencer j) Exhaust Muffler k) Battery Charger/Generator 3. Engine Instrument Panel with the following items a) Starting switch with key or button b) Lubricating oil pressure gauge. c) Water temperature gauge. d) RPM Indicator with hour meter e) Battery charging Ammeter 4 Safety Controls for Engine a) Trip for low lubricating oil pressure b) Trip for high water temperature. 6.Brushless Alternator a) Make - KOEL GREEN Crompton/Greaves/Stamford b) Type - Self exited and self regulated. c) Capacity - 82.5 KVA/66 K W @ 0.8PF d) System of Voltage - 3 phase, 415 V, e) Frequency - 50 Hz f) Insulation - Class F/H The Alternator should confirm to IS 4722. Operation and service manual, spares and tools shall be provided. 7. Fuel Tank Suitable size built in type integrated with the acoustic enclosure Fuel connection shall be done as per standards 8. Battery Suitable size built in type integrated battery with leads and terminals of appropriate AH capacity as per Manufactures requirement. Automatic Battery charger Solid state phase indication lamp for supply ON/OFF with HRC protection. standard AMFconrol panel as per kerala Electrical Inspectorate requirements, floor mounting type, CTs of suitable ratings, indicatiing Lamps, Contractors,
Excavation for foundation in soft soil including dressing of sides and ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 metres.
Providing and laying in position cement concrete 1 :3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required.
Providing and laying in position cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc including form work etc as required.
Providing, laying and fixing 80mm dia G.I. pipe (medium class) complete with G.I. fittings for extending DG set exhaust etc as required.
Supply and providing following size B class GI pipe with specials and flanged coupling in each full length of pipe, as additional exhaust piping, fixing the same firmly to the building/structure using necessary supports, such angle iron, MS clamp etc. Painting the pipe and accessories with synthetic enamel paint over a coat of zychromate primer etc as required 80 mm dia
Supply and providing following size B class GI pipe with specials and flanged coupling in each full length of pipe, as additional exhaust piping, fixing the same firmly to the building/structure using necessary supports, such angle iron, MS clamp etc. Painting the pipe and accessories with synthetic enamel paint over a coat of zychromate primer etc as required 100 mm dia
Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.3.5 core 120 sq mm
Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required. 2 core 10 sq mm
Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required. 3.5 core 120 sq mm
Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.2 core 10 sq mm with factory made clamp
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 2 X 10 sq. mm (19mm)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3 1/2 X 120 sq. mm (45mm)
Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation 50/38 mm or nearest size
Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation 120/102.5 mm or nearest size
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Supply and providing test joint for the earthing system using 2 Nos of the following sizes of strips including cutting and bending to shape ,drilling necessary holes and fixed to the watering pipe etc as required 2x25x3 mm tinned copper strip
Supply and providing and fixing 25 mm X 3 mm Copper. strip earth lead from the test joint to the earth plate
Supply and clamping the following size of strips on surface of wall/ parapet/ existing cable tray using clamps fabricated from 20 X 3 mm GI flat duly ainted or heavy duty GI spacer saddles spacing of clamps not exceeding 1 m, aking good the damages, colour washing etc. as required ( for horizontal run) 25 x 3 mm copper strip
Supplying and laying 25 mm X 3 mm copper strip at 0.50 metre below ground as strip earth br electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)
Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required 2.00 mm copper conductor ( 14 SWG)
Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.00 mm (14 SWG)
Supply and providing 25x6mm brass nut and bolt etc. as required
Supply and providing 25x3mm brass nut and bolt etc. as required
Fabrication, supply, conveyance, installation testing and omissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623.Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 1.6mm CRCA sheet, powder coated (excluding base frame)
Supply and providing 3mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc
Supply and providing heavy duty 'A' section neoprene gasket in the panel board U' section rubber beeding suitable for 1.60/ 2.00 mm sheet
Supply and fabrication conveyance and installation of base frame of panel board using 75 x 40 mm rolled steel channel (ISMC)
Supply and providing copper bus bars including finger type SMC bus bar supports in the bus chamber, suitable size nut & bolt, providng heat shrink sleeves etc. as required.
Supply and providing copper earth bus in the panel board
Suply & fixing the following multi-function meters in the panel assembly.Multifunction meter to read: V, A, F, 3 phase accuracy class 1
Suply & fixing the following multi-function meters in the panel assembly.Multifunction meter to read: V, A, F, 3 phase accuracy class 1
Supply, conveyance installation testing and commissioning the LED type indicator for 230/415 V- Blue color in existing panel board
Supply, conveyance installation testing and commissioning the LED type indicator for 230/415 V- red, Green, Yellow or Orange color in existing panel board
Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.125A, 35/36 kA (Ics=100%Icu), 3 pole, current limiting type MCCB with microprocessor based release with overload setting of 50 - 100% having adjustable OL & SC
Providing and fixing following capacity On-Load Change Over Switchesinside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.100A, 4 pole
Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.100 Amp TP&N
Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.63 Amp TP & N
MCCB Accessories Supply and fixing one number earth fault Relay up to 125A to 200A with CBCT.
MCCB Accessories Supply and fixing shunt release for all voltage range up to 630A.
MCCB Accessories Supply and fixing rotary handle, External type (including BUC handle with door interlock ) in the existing MCCB of rating up to 250 A 1
Painting letters or figures with enamel paint as identification mark to SB, DB, panel board etc as required
Supply and providing First Aid Chart duly framed and placed in a conspicuous location for clear vision
Supply and providing 9 Litre capacity GI Fire Bucket painted in post office red with primer coat of red oxide and written with white paint 'FIRE' mounted on MS angle frame work/ wall bracket filled with fine sand, painting the bracket/ floor stand including making good the damages, colour washing etc. as required.
Supply and providing 5 Kg. Dry Chemical Powder type Fire Extinguisher with hose and clamps including fixing it to wall as required
Supply and fixing Danger notice board of size, 125 x 75 mm
supply and providing 2.00 mm thick, 3.3 kV, Synthetic elastromeric fire etardant insulating sheet
Charges towards the preparation of necessary plan, scheme and other related papers for submission to KSELB & KSEB - First A3 Sheet
Charges towards the preparation of necessary plan, scheme and other related papers for submission to KSELB & KSEB - Each Additional A3 Sheet
Fee to be paid to KSELB towards scrutiny & inspection , meter testing etc (actual amount will be reimbursed on production of original documents
KADOOR SALES CORPORATION
Generic Power Pvt Ltd
Percept Technologies
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_525595.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .