Loading…
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Tender Value
₹10.6 L
EMD Value
₹10,641
Closing Date
5 Nov 2025, 5:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Executive Officer
NAC Office Hindol
Installation of 11 KV line and 63 KVA transformer with necessary fittings for newly created MCC and MRF at Kandarasuni Ward No 12 Hindol NAC
2025_ORULB_120060_1
02/2025-26
Open Tender
Electrical Works
Percentage
Ward No.12 Kandarasuni
Please refer Tender documents.
1 document required · 1 mandatory
₹6,000
₹10,641
Yes
25 Oct 2025
25 Oct 2025
6 Nov 2025
25 Oct 2025
5 Nov 2025
25 Oct 2025
PSC POLE 10 METER LONG 330 KG.
PSC Pole Clamp (GI)
Straight Cross Arm 100X50X6MM, 9.56 KG/Mtr, each Channel (GI) length 1.2 mtr, 2 no's channel (GI) required = 2x9.56x1.2)
Fish Plate (GI) 50x6 mm, 2.36 kg/Mtr, each 0.280 mtr. Length, 8 no's required= (8X2.36X0.280)
Straight Cross Arm 100X50X6MM, 9.56 KG/Mtr, each Channel (GI) length 0.306 mtr, 2 no's channel (GI) required = 2x9.56x1.2)
Danger Plate, 1 no's
Black Clamp for danger plate 25X3 mm, Flat (GI), 0.59KG/Mtr, Flat (GI) of 0.510 mtr length 1 no's = (1X0.59X0.510)
GI barbed wire anticlimbing device 3 Kg. Per support
Black Clamp for anticlimbing device 25X3 mm Flat (GI), 0.59 Kg/Mtr. Flat (GI) of 0.51 mtr. Length 4 no's = (4X0.59X0.510)
11 KV pin insulator polymer
H W fitting (B&S) 70KN, 3 Bolt
Disc insulator (B&S) 70 KN polymer
Earthing of Support (Coil Type)
NB-8 GI wire (Dia 4.6 mm) 0.131 KG/ Mtr- 2 Mtr for connecting pole with Coil earthing
NON METALLIC TILES-11 KV 55SQMM CVRD AAAC
IPC for 55 sq. mm AAA conuctor (For covered conductor)-11 kv
Spike (GI) (using 5x6 mm Flat (GI) welded with 8 mm square bar) (2 nos. of spike per set in each pole)
GI Nut, Bolt & Washer of different sizes (3.55 Kg each Cut Pole)
Black Paint (GIS Numbering & Zebra stripping)
Yelow Color Plaint (GIS Numbering & Zebra Stripping) for Background)
Concreting ratio 1:1.5:3 (M-20 Grade) (500mmX500mmX1667 mm) = 0.42 Cu. Mtr (Per Pole)
PSC POLE 10 METER LONG 330 KG.
PSC Pole Clamp (GI)
Straight Cross Arm 100X50X6MM, 9.56 KG/Mtr, each Channel (GI) length 1.2 mtr, 4 no's channel (GI) required = 4x9.56x1.2)
Fish Plate (GI) 50x6 mm, 2.36 kg/Mtr, each 0.280 mtr. Length, 16 no's required= (16X2.36X0.280)
Straight Cross Arm 100X50X6MM, 9.56 KG/Mtr, each Channel (GI) length 0.306 mtr, 4 no's channel (GI) required = 4x9.56x1.2)
Danger Plate, 1 no's
Black Clamp for danger plate 25X3 mm, Flat (GI), 0.59KG/Mtr, Flat (GI) of 0.510 mtr length 1 no's = (1X0.59X0.510)
GI barbed wire anticlimbing device 3 Kg. Per support
Black Clamp for anticlimbing device 25X3 mm Flat (GI), 0.59 Kg/Mtr. Flat (GI) of 0.51 mtr. Length 4 no's = (4X0.59X0.510)
11 KV pin insulator polymer
H W fitting (B&S) 70KN, 3 Bolt
Disc insulator (B&S) 70 KN polymer
Earthing of Support (Coil Type)
NB-8 GI wire (Dia 4.6 mm) 0.131 KG/ Mtr- 2 Mtr for connecting pole with Coil earthing
NON METALLIC TILES-11 KV 55SQMM CVRD AAAC
IPC for 55 sq. mm AAA conuctor (For covered conductor)-11 kv
Spike (GI) (using 5x6 mm Flat (GI) welded with 8 mm square bar) (2 nos. of spike per set in each pole)
H,T. stay Clamp, 50x8 mm Flat (GI), 3.14 Kg/Mtr, 0.551 Mtr. Length 2 no's qty required (1 pair)
H.T. Stay set (Complete)
7/10 SWG stay wire 15kg/stay
GI Nut, Bolt & Washer of different sizes (7.433 Kg each Cut Pole)
Black Paint (GIS Numbering & Zebra stripping)
Yelow Color Plaint (GIS Numbering & Zebra Stripping) for Background)
Fixing of complete 11 KV line complete stay set includes 1) Turn Buckle Assembly 2)Stay Rod & Stay plate 3) Stay Insulator 4) Stay Wire 5) Stay clamps with Nuts & bolts will do the excvation including excvation, supply of 0.5 cum cement concrete foundation 1:2:4 size (500mmX500mmX800mm) using 20mm BHG metal with all labour and materials as per TPCODL Drawing & Standard
Concreting ration 1:15:3 (M-20 Grade) (500mmX500mmX1667 mm)-0.42 Cu. Mtr(Per pole)
PSC POLE 10 METER LONG 330 KG.
PSC Pole Clamp (GI)
11 KV V cross Arm (GI) (10.2 Kg. each)
Top barcket 100X50X6 mm GI Channel (GI) (2 kg each)
Danger Plate, 1 no's for each
Black Clamp for danger plate 25X3 mm, Flat (GI), 0.59KG/Mtr, Flat (GI) of 0.510 mtr length 1 no's = (1X0.59X0.510)
GI barbed wire anticlimbing device 3 Kg. Per support
Black Clamp for anticlimbing device 25X3 mm Flat (GI), 0.59 Kg/Mtr. Flat (GI) of 0.51 mtr. Length 4 no's = (4X0.59X0.510)
11 KV pin insulator polymer, 03 nos. required for each support
Earthing of Support (Coil Type)
NB-8 GI wire (Dia 4.6 mm) 0.131 KG/ Mtr- 2 Mtr for connecting pole with Coil earthing
GI Nut, Bolt & Washer of different sizes (1.45 Kg/ Pin Point)
55 sq. mm. XLPE Insulated AAA conductor
Black Paint (GIS Numbering & Zebra stripping)
Yelow Color Plaint (GIS Numbering & Zebra Stripping) for Background)
NON Metallic tiles- 11 KV 55 SQMM CVRD AAAC
Spike (GI) (using 5x6 mm Flat (GI) welded with 8 mm square bar) (2 nos. of spike per set in each pole)
Concretion ratio 1:1.5:3 (M-20 Grade) (500mmX500mmX1667mm) = 0.42 Cu. Mtr (Per Pole)
WPB (GI) Pole 160X152 (11 Mtr. Long, 30.44 KG/Mtr.)-DP (Total Pole Weight with Base plate & Stiffner= 334.84 KG+10.74 KG=345.58KG)
Top channel (GI) GI 100X50X6 MM (3000 mm long) (9.56 Kg./Mtr. 2 Nos.) (Each 2X3.000X9.56= 57.36 Kg.)
Fish Plate (GI) 50X6 mm, 2.36 kg/Mtr., each 0.280 mtr. Length, 6 nos. required = (6x2.36x0.280)
AB Switch mounting channel (GI) 750X40X4.8 mm GI Channel (GI) (3000 mm long) (7.14 Kg./Mtr. 2 Nos.) (Each 2X3.000X7.14= 42.84 Kg.)
AB Switch Side Support channel (GI) 100x50x6 mm, 9.56 Kg/Mtr. Each channel (GI) length 0.35 mtr. 2 nos. channel (GI) requird = (9.56x2x0.35)
Channel (GI) Support for down pipe 75x40x4.8 mm, 7.14 Kg/ Mtr., each channel (GI) length 0.8 Mtr., 1 nos. channel (GI) requird =7.14x0.8x1)
HG/DO Fuse Mounting Channel (GI) 75X40X4.8 mm GI Channel (GI) (810 mm long 2 nos.) (7.14 Kg/Mtr., 2 nos.) (Each 2X3.00X7.14= 42.84 Kg.)
Cantilever support channel (GI) 75X40X4.8 mm. GI Channel (GI) (810 mm. long 2 nos.) (7.14 Kg./Mtr., 2 nos.) (Each 2X0.810X7.14 = 11.57 Kg.)
Cantilever support Angle (GI) 50X50X6 mm. GI (1282 mm. long 2 nos.) (4.5 Kg./Mtr., 2 nos.) (Each 2X1.282X4.5 = 11.54 Kg.)
Transformer Base GI Channel (GI) 100x50x6 MM GI (300 mm long) (9.56 Kg./Mtr., 2 nos.) (Each 2X3.000X9.56=57.36 Kg.)
Transformer Base Support GI Channel (GI) 100x50x6 MM GI (515 mm long) (9.56 Kg./Mtr., 2 nos.) (Each 2X0.515X9.56=9.85 Kg.)
Transformer Belting Angel (GI) 50x50x6 MM GI (3000 mm long) (4.5 Kg./Mtr., 2 nos.) (Each 2X3.0X4.5 Kg.)
Transformer Belting Angel (GI) 60x60x6 MM GI (580 mm long) (4.5 Kg./Mtr., 2 nos.) (Each 2X0.580X4.5 = Kg.)
LTDB Mounting Angel (GI) 50X50X6 MM GI (1000 mm long) (4.5 Kg./Mtr., 2 nos.) (Each 2X1X4.5 Kg.)
5X6 mm Fkat (GI) for earting, 2.36 kg/mtr., (2.5X7 mtr. For mesh formation, 12 Mtr. For LA and 2.5 mtr. For raising 11 mtr for AB switch, 2.8 mtr. For HG Fuse, 6X2 mtr. For DTR Nutral, (1.3+4.5) mtr. For DTR body, 0.500 mtr. For LTDB & AB Switch operating handle, 3 mtr. for fencing) (Each 65.6X2.36 = 154.81 Kg.)
63 KVA, 11/0.4 KV (AL) Transformer, BIS Energy Loss 11, Ammendment-4
LT Distribution Box with MCCB, Aluminium Busbar of single Bay with kit kat fuse for 63 KVA S/S
55 SQ MM. AAACXLPE Covered Conductor
4 Cx65mm2 LT XLPE Cable (Arroured)- For 63 KVA Trf.
AB Switch (11KV, 200A 3pole, 60Hz)
H.G. Fuse (11KV. 200A,3Pole)
WEDGE CONNECTOR FOR 55 SQMM CONDUCTOR
POLYCARBONATE BIRD GUARD
Disc insulator (B&S) 70 KN polymer
H W fitting (B&S) 70 KN(3bolted)
Lightning Arrester (12KV, 10KA) Station Class 2
11 KV pin insulator polymer
HT stay set complete
HT stay Clamp (1.9 Kg/pair)
7/10 SWG GI stay wire, Grade-2 (15Kg./Set)
40 mm Nominal bore GI pipe (medium gauge) earthing device with 3 mtr. Long
GI Nuts & Bolts of Assorted size (25 Kg/DSS DP)
GI Barbed wire/Anticlimbing device (3 Kg./Pole)
Black Clamp for anticlimbing device 25X3 mm. Flat (GI), 0.59 Kg./Mtr. Flat(GI) of 0.510 mtr. Length 8 nos. = (8X0.59X0.510)
Danger plate 11 kv
Black Clamp for danger plate 25X3 mm. Flat (GI), 0.59 Kg./Mtr. Flat(GI) of 0.510 mtr. Length 2 nos. = (2X0.59X0.510)
Name plate
(i) Yellow color paint (GIS numbering & zebra stripping) for Background
(ii) Black Color paint (GIS Numbering & Zebra stripping) for numbering
Connecting ratio 1:1.5:3 (M-20 Grade) (500mmX500mmX1800mm)=0.450 Cu. Mtr(Per Pole) (For WPB Pole)
Coupin ration 1:1.5:3(M-20 Grade) (500mmX500mmX450mm)=0.113 Cu. Mtr(Per Pole)
PCC ration 1:3:6 (M-10 Grade) for DSS Area (5x3x0)=1.5 Cu. Mtr
Fixing of stay set with 0.5 Cum cement concrete foundation 1:3:6 (M-10 Grade) size (900mmX600mmX900mm) using 40mm BHG metal with all labor and material expect stay set, stay wire, stay insulator
Construction Earthing chamber including installation of earthing pipe Making earthing chamber including excavation, soil treatment with bentonide powder, calculation of earth resistance, including installation of 3 Mtr GI Pipe 40mm/50mm including welding of Flat (GI) around pipe.
Laying of 4 Cx 95mm2LT XLPE Cable
SITC and Erection of GI Fenching with gate
Supply of AL Lugs suitable for 95 sq. mm cable/ conductor, Crimping with cable and Fixing/ connecting include supply and erection of PVC Tape as per voltage requirement
Supply and erection of double Compression Flame proof Type Glanding for armored cable 3.5/4C 50- 95 sqmm including making hole in Base plate and dressing of cable along with vermin proofing property supply to be done as per TPCODL Spec and approved make dowells.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 3.87 MB
BOQ_558247.xls
BOQ • 0.33 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .