Loading…
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Tender Value
₹36.0 L
EMD Value
₹72,000
Closing Date
18 Dec 2025, 3:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Electrical General work in connection with Engg. Work "Divisional Hospital, Katihar:- Renovation of Leakage of Roofs, Isolation Ward, Physiotherapist Unit and Up-gradation".
51_2025~NFR
51_2025
Open
Works - General
6 Months
Katihar, Bihar
₹0
₹72,000
18 Dec 2025
26 Nov 2025
4 Dec 2025
1-Electrical General work in connection with Engg. Work "Divisional
Renovation of Leakage of Roofs, Isolation Ward, Physiotherapist Unit and Up-gradation".
Item- 1 Please see item breakup for details.
S No. Item Description of Item Unit Qty Rate Amount
1 1 Supply, wiring, testing & commissioning of Numbers 272.00 734.00 199648.00
concealed point wiring by FR PVC insulated and
unsheathed 1.5 sq mm, single core multi strand
copper wire with earth continuity wire by PVC
insulated and unsheathed 1 sq mm , single core
multi strand copper wire concealed on wall
through PVC rigid conduit pipe of dia not less
than 20 mm dia heavy duty including all types
of joints and bends as required, complete with 6
amps flush type controlling modular switch to be
mounted on modular GI inner plate and modular
mounting frame of suitable module as per
requirement complete to be concealed in wall as
per instruction of Engineer Incharge at site.
Existing wall should be cut and re-mended to
original finish by contractor's own material. (a)
FL Point/LED Tube Point/Recess Light Point/Wall
Mounted Bracket Fan Point with c/rose
KATIHAR DIVISION-ELECTRICAL/N F RLY
2 2 (b) Lamp Point with angle holder Numbers 60.00 648.00 38880.00
3 3 (c) Fan point with c/rose and 5 step fan Numbers 40.00 1335.00 53400.00
4 4 (d) Exhaust fan point with c/rose Numbers 18.00 742.00 13356.00
6 6 Supply, wiring, testing & commissioning of Numbers 40.00 787.00 31480.00
concealed 6/16 amps power plug point on
separate board complete with modular 16 amps
switch (with indicator) and 6/16 amps 3 pin
combined shuttered socket to be mounted on
modular GI inner plate 4M or suitable size with
modular mounting frame to be concealed in wall
as per instruction of Engineer Incharge at Site.
7 7 Supply, installation, testing & commissioning of Numbers 82.00 2113.00 173266.00
Surface/Recessed LED luminaire with slim line
CRCA sheet metal body, square type, (System
wattage-18 Watt, Nominal system efficacy >=
100 lm/watt) suitable for 600 x 600 mm
modular ceiling as per instruction of Engineer
incharge at site.
8 8 Supply, testing & fixing of wall mounted bracket Numbers 130.00 1840.00 239200.00
fan 400 mm sweep complete with all
accessories to be fixed on wall by suitable fixing
arrangement including connection by 2 core, 1.5
sqmm PVC insulated and FR PVC Round
Sheathed, Copper Conductor (flexible) industrial
cable as per instruction of Engineer Incharge at
9 9 Fixing, testing & commissioning of ceiling fan Numbers 40.00 42.00 1680.00
with supply & fixing of MS clamp with hook, nut,
bolt, washer etc. as per instruction of Engineer
incharge at site. (Fan will be supplied by
10 10 Supply, wiring & testing of main wire by 2.5 sq Metre 4000.00 68.00 272000.00
mm, Single Core FR-LSH PVC Insulated Industrial
Grade Copper Conductor (Unsheathed) Flexible
Cables, 1100 Volts and earth continuity wire by
1.0 sq mm FR-LSH PVC Insulated Industrial
Grade Copper Conductor Conforming to IS: 694
concealed in wall through PVC rigid conduit pipe
not less than 20 mm dia as per instruction of
Engineer incharge at site.
11 11 Supply, wiring & testing of sub-main wire by 4 Metre 2500.00 80.00 200000.00
sq mm, Single Core FR-LSH PVC Insulated
Industrial Grade Copper Conductor
(Unsheathed) Flexible Cables, 1100 Volts and
earth continuity wire by 1.0 sq mm FR-LSH PVC
Insulated Industrial Grade Copper Conductor
Conforming to IS: 694 through PVC rigid conduit
pipe not less than 20 mm dia as per instruction
of Engineer incharge at site.
12 12 Supply, wiring & testing of main wire by 6 sq Metre 1200.00 86.00 103200.00
mm, Single Core FR-LSH PVC Insulated Industrial
Grade Copper Conductor (Unsheathed) Flexible
Cables, 1100 Volts and earth continuity wire by
1.0 sq mm FR-LSH PVC Insulated Industrial
Grade Copper Conductor Conforming to IS: 694
through PVC rigid conduit pipe/polythene pipe
not less than 20 mm dia as per instruction of
Engineer incharge at site.
KATIHAR DIVISION-ELECTRICAL/N F RLY
13 13 Supply, installation, testing & commissioning of Numbers 33.00 1099.00 36267.00
modular power unit complete with 32 Amp mini
MCB DP "C" series 3kA , 25 amps starter, 25
Amp Socket and 25 Amp plug to be mounted on
6 module GI box, 6 module combined plate
concealed on wall and wiring by 6 sq mm, Single
Core FR-LSH PVC Insulated Industrial Grade
Copper Conductor (Unsheathed) Flexible Cables,
1100 Volts with earth coninuity wire by 1 sq mm
copper cable Conforming to IS: 694 to be drawn
through Rigid PVC conduit pipe not less than 20
mm dia as per instruction of Engineer incharge
at site. (For Geyser Point)
14 14 Supply, installation, testing & commissioning of Numbers 5.00 8192.00 40960.00
Stationary storage type electric water heater
(Geyser), Digital display, Type:-Vertical,
Capacity (Ltrs):25, Power input: 2000 watt,
Class:-I, Star Rating: 5 Star suitable for
operation on 230 Volts, single phase AC, 50 Hz.
Storage electric water heater shall be complete
in all respect with fittings as per general
technical requirements and as per instruction of
Engineer incharge at site.
15 15 Supply, installation, testing & commissioning of Numbers 16.00 7151.00 114416.00
Stationary storage type electric water heater
(Geyser), Digital display, Type:-Vertical,
Capacity (Ltrs):15, Power input: 2000 watt,
Class:-I, Star Rating: 5 Star suitable for 230
Volts, single phase AC, 50 Hz supply. Storage
electric water heater shall be complete in all
respect with fittings as per general technical
requirements as per instruction of Engineer
Incharge at site.
16 16 Supply, installation, commissioning & testing of Square 288.00 1632.00 470016.00
LED indication name board (Length of board will Foot
be as per proportion of letter so that all the 4
side of the board will have extra space) with
channel letters with 3.75 ft. in lenght with
suitable widen and 4 mm projection size which
inside ACP board (Brand- ALUDECOR, category-
AL 33 series exterior & thikness-3 mm) with
acrylic face on front and having Sumsung 5630
LED's (Shape- Lens type, operating voltage- 12
V DC, carring current-80 mA, power Dissipation-
0.96 watt, working hours-50000, case material-
ABS ,protection-IP68) inside for illumination
letters in English, Hindi, Bengali or regional
language complete with all materials including
provision of erection structure made of MS
angle/channel/flat duly painted with aluminium
paint over a coat of red oxide primer with CC
foundation (1:3:6) of cement, sand and stone
chips as required at site and as per instruction
of Egnineer incharge at site.
17 17 Supply, inatalation, testing & commissioning of Numbers 10.00 11651.00 116510.00
LED Signage Utility Board Dual Face Printing
with high power LEDs Driver including suitable
fixing arrangements as per instruction of
Engineer incharge at site. (Size - 24" x 24")
KATIHAR DIVISION-ELECTRICAL/N F RLY
18 18 Supply ,erection & fixing of glow sign board Square 72.00 397.00 28584.00
(utility board) of size 12 ft x 3 ft complete made Foot
of acrylic sheet 3 mm, vinyl pasting/flex print, GI
sheet etc having computerised priniting in Hindi
and English with structure made of MS angle/flat
of suitable size with corrosion resistant painting
including internal wiring with PVC insulated and
sheathed multi stranded 2.5 sq mm single core
aluminium wire with minimum 04 nos energy
efficient LED T8 fitting with LED tube and
complete with all accessories with hanging
fixture steel chain, flat, angle etc. as per
instruction of Engineer incharge at site.
19 19 Supply, erection, testing & commissioning of 12 Set 2.00 348301.00 696602.00
mt long High Mast Tower with 8 nos. x 150 watt
LED luminaries in symmetrical arrangement
complete with all accessories (Double drum
winch, SS wire rope, integral power tool motor,
head frame, junction box, foundation bolt, LED
aviation light, Fedder pillar with single dial timer
& raising lowering mechanism etc.) including
shallow foundation with M20 grade concrete etc.
as per instruction of Engineer Incharge at Site.
20 20 Supply,installation, testing & commissioning of Numbers 10.00 3005.00 30050.00
insect killer of dimension (L - 26 inch X W - 4.5
inch x H - 11 inch) having coverage area 550 ft
with 02 nos tube of power consumption 60 watt
as per instruction of Engineer incharge at site. It
should be fixed with necessary clamping.
21 21 Supply, installation, testing & commissioning of Set 2.00 67350.00 134700.00
Inverter of 2 kVA / 72V DC digitally controlled
IGBT based double conversion PWM technology
True On-Line UPS System, 1 Phase input & 1
Phase output with 6 x 100 AH SMF battery and
trolley as per instruction of Engineer Incharge at
22 22 Supply, installation, testing & commissioning of Numbers 1.00 79059.00 79059.00
Submersible pump motor set of 25 HP / 18.7 kW,
stage-10, 75 mm outlet, Head- 92-46 mtr,
Discharge- 660-1200 LPM, Full load current-26.0
amp, Rated voltage-415 volt as per instruction
of Engineer Incharge at Site.
23 23 Supply, installation, testing and commissioning Numbers 1.00 22458.00 22458.00
of Automatic Star-Delta starter in SS housing for
25 HP / 18.5 kW motor rating at 415 volt, 3 Ph,
50 Hz as per instruction of Engineer Incharge at
24 24 Supply, installation, testing & commissioning of Set 1.00 52500.00 52500.00
10 HP, 7.5 kW submersible pump motor set
complete, 5 star rated, suitable for 400 Volt, 50
Hz, 3 phase supply with stage-12, 50 mm outlet,
Head- 140-46 mtr, Discharge- 60-420 LPM, Full
load current-18.0 amp, Rated voltage-415 volt.
Borewell dia- 150 mm as per instruction of
Engineer incharge at site.
25 25 Supply, installation, testing and commissioning Set 1.00 13821.00 13821.00
of Fulley Automatic Star-Delta starter in SS
housing for 10 HP / 7.5 kW motor rating at 415
volt, 3 Ph, 50 Hz with Volt meter, Ammeter, Dry
running preventer, Single phase preventer and
over load protection as per instruction of
Engineer incharge at site.
26 26 Supply, laying, commissioning & testing of HDPE Metre 200.00 351.00 70200.00
pipe 110 mm dia PN-6 grade to be laid partly
along the pole /underground with suitable fixing
arrangement by MS clamp made of MS flat of
size 50x6 mm and suitable size nut , bolt,
washer and required bend, joints as per
instruction of Engineer Incharge at site.
KATIHAR DIVISION-ELECTRICAL/N F RLY
27 27 (a) Supply, installation, testing & commissioning Set 5.00 10721.00 53605.00
of 4 way VTPN MCCB DB (MCCB+12 modules)
with IP 43 grade protection, metal door with
wire sets, busbar, earth bar, blanking plates,
cable ties etc with supply and fixing of following
MCCB/MCB as per instruction of Engineer
incharge at site.
conforms to IS/IEC 60898:2002
Conforms to IS/IEC 60898 - 1:2002
31 31 (a) Supply, fabrication, erection, testing, Set 1.00 30310.00 30310.00
commissioning & painting of floor mounted
powder coated cubicle panel board (Modular
look) of suitable size (neither big nor small) ),
outdoor type with double door made of suitable
size MS/GI angle 50 x 50 x 6 mm, MS/GI flat 50 x
6 mm, 14 SWG MS sheet/Powder coated CRCA
sheet with provision of weather proof,rust
proof,dust proof,water proof having internal
rubber gasket with supply and fixing of following
ACB/MCCB/Bus bar/Meter etc. (Connections to
be made by copper strips, glands should be
provided at cable entry and exit, components
should be compartmentalized, Each
compartment will be provided with the door and
pad locking arrangement. The compartment
illumination lamp with door operated switch
shall be provided for each compartment. Panel
board drawing approval must be obtained with
clear indication of make of items of
32 32 (b) Supply & fixing of onload changeover switch Numbers 1.00 24733.00 24733.00
630 amps Four Pole, 415 V 50 Hz, with Sheet
Steel Enclosure (with front handle) as per IS/IEC
electrolytic grade copper consisting of 4 bars ( 3
Ph and Neutral ) ( Bus bar should have
insulation cover)
38 38 (h) Digital voltmeter (0-500) amps and Digital Set 1.00 5139.00 5139.00
ammeter (0-500) amps with s/switch and CTs
40 40 Laying, commissioning & testing of HT/LT Metre 400.00 50.00 20000.00
XLPE/PVC cable of different sizes partly along
the pole and partly through ground in cable
trench by excavation of ground below 1.5 mt
from ground level with suitable fixing
arrangement by MS clamp of size 50x6 mm and
suitable size nut, bolt. Loading, Unloading &
Carrying of cable to actual work site by
contractor's own arrangement. (Aluminium
Crimping Socket should be provided for each
Cable Termination). (Cable will be supplied by
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .