Loading…
Loading…
| # | Company | Amount |
|---|---|---|
| 1 | ₹1.5 Cr 6TH FLOOR PLOT NO 33 34 FLAT NO 602 UDAYA ELITE JAYABHERI PINE VALLEY GACHIBOWLI HYDERABAD 500032 TELANGANA MOB 9989103668 |
Tender Value
₹1.6 Cr
EMD Value
₹1.6 L
Closing Date
23 Sept 2026, 3:00 pmClosed
NBCC Bhawan
NBCC Bhawan
Repair Rectification of Existing Services works at ICMAI COE At Hyderabad (2nd Call)
NBCC/RBG/South/ICMAI/HYD/2026/39~EW8489fe3b44d89b59d856dfa6
NBCC/RBG/South/ICMAI/HYD/2026/39
Open Tender-Domestic
Miscellaneous Services
NBCC Bhawan
₹11,800
₹1.6 L
13 Oct 2026
18 Sept 2026
23 Sept 2026
18 Sept 2026
23 Sept 2026
S.no Description DSR Amount NDSR Amount Remarks
1 DSR 2025/NDSR Electrical work 65,93,044.50 25,79,998.55
2 DSR 2025/NDSR Air Conditioning work 65,115.75 11,93,610.43
3 DSR 2025/NDSR Fire Fighting works 6,79,102.20 10,62,427.25
4 NDSR Plumbing works 2860969.60
6 DSR 2023/NDSR SS Railing work 6,08,977.08 35,000.00
8 Total DSR + NDSR 1,56,78,245.36
Digitally signed by DEEPAK
ELECTRICAL WORKS - BOQ
SNO DSR -25 DESCRIPTION Unit QTY. DSR Rate DSR Rate incl. CI NDSR Rate DSR Amount NDSR Amount
Supplying and fixing 5 amps to 32 amps rating, 240 volts, 'C' series, miniature circuit breaker suitable for inductive
load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as
1 2.1 required.
Single pole and neutral
Supplying and fixing following rating, four pole, (three phase and
neutral), 415 volts, residual current circuit breaker (RCCB), having a
sensitivity current 30 mA in the existing MCB DB complete with
2 2.15 connections, testing and commissioning etc, as required,
Earthing with G.I. earth pipe 4.5 Meter long, 40 mm
dia including accessories, and providing masonry
enclosure with cover plate having locking Each 14 7,658.00 8,040.90 1,12,572.60
arrangement and watering pipe etc. with charcoal/
3 5.2 coke and salt as required.
4 5.9 Providing & fixing of 25mm x 5mm GI strip on surface or recess for earth connection as required. Meter 66 160.00 168.00 11,088.00
Earthing with copper earth plate 600 mm X 600 mm X
3 mm thick including accessories, and providing
masonry enclosure with cover plate having locking Set 6 15,004.00 15,754.20 94,525.20
arrangement and watering pipe of 2.7 Meter long etc.
5 5.6 with charcoal/ coke and salt as required.
6 5.8 Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. Meter 50 1,950.00 2,047.50 1,02,375.00
Wiring for light point/ fan point/ exhaust fan point/ call bell point/normal switch with 1.5 sq.mm FRLS PVC insulated
copper conductor single core cable in surface / recessed FRLS PVC conduit, with modular switch, modular plate,
suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as
7 1.3 required.
Digitally signed by DEEPAK
Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/
recessed PVC conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop meter 2400 480.00 504.00 12,09,600.00
8 1.5 earthing as required.
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper
9 1.7 conductor, single core cable in surface/ recessed PVC FRLS conduit as required.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface
or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A Each 300 545.00 572.25 1,71,675.00
10 1.31 modular switch, connections etc. as required.
Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as
11 11.26 required.
LED Down lighter (SMD Type) (System lumen Unit Rate efficacy ≥ 105 < 120 lm/Watt )Supplying, Installation, Testing & Commissioning of
LED Recessed/ surface Down lighter (Round/ square/ Rectangular) SMD type of following bodymaterial with PMMA and prismatic diffuser
and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt,
frequency 50/60 hz, Operating temp range -50C to 400C, internal surge protection of 2.5 KV with Short & Open circuit protection
,THD < 10% , P. F.≥0.95, IP20, CRI >80,UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5%), life time (LED, Driver &
electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K /4000°K /
5700°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Colour Matching) <3, Maximum power consumption should not more Nos 432 920.00 966.00 - 4,17,312.00
than the specified rating and Fixture shall be confirming to relevant BIS standards. Manufactures Word Mark/ Name Engraved/ Embossing/
Screen printing on housing Complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper
conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 and <120
lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT
shall be as approved. by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED
junction temperature shall not rise above 90°C) Powder coated die cast /Extruded aluminium. Body including trim : 18 Watt
LED Down lighter (SMD Type) (System lumen efficacy ≥120<135lm/Watt) Supplying, installation, Testing & Commissioning of
LED Recessed/surface Down lighter (Round/ square/ Rectangular) SMD type of following body material with PMMA and prismatic diffuser
and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt,
frequency 50/60 hz, Operating temp range -5 0C to 40 0C centigrade, internal surge protection of 2.5 KV with Short & Open
circuit protection ,THD < 10%, P. F.≥0.95, IP20, CRI >80, UGR (Unified GlareRating) <19, Flicker free (flicker should be below 5%), life time
(LED, Driver & electrical circuitry), lifetime of minimum 50000 Burning Hours with 70%of initial Lumen maintained till life ends,
CCT3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption Nos 125 942.00 989.10 1,23,637.50
should not more than the specified rating and Fixture shall be of relevant BIS standard. Ma nufactures Word Mark/ Name Engraved/
Embossing/ Screen printing on housing Complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated
copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135
lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT
shall be as approved by Engineer-in Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED
junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body including trim .: 18 WATT
LED Panel light 2x2 ft. (System lumen efficacy ≥105 <120 lm/Watt) Supplying, installation, Testing & Commissioning of Panel light 2x2 ft., of
following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating
voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short
& Open circuit protection, THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %),
life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with, 70% of initial Lumen maintained till life ends as per
LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour
Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard.
Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections
with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM
warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per
BIS shall be submitted.
Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium
housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness >
LT CABLES 0.00
Supply and laying of XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts
grade, cross-sectional area as follows 0.00
TRANSFORMER 0.00
Digitally signed by DEEPAK
Servicing of 500 kVA, 11kV/433V off circuit STEP DOWN TRANSFORMER,(Copper double wound, oil immersed
17 NDSR naturally cooled, core type trf) and neutral brought out for earthing. 1302041.50
18 NDSR Servicing of 630A 11kV load break swtich job 1 89,087.05 - 89087.05
19 NDSR Servicing of 200KVA DG SET B CHECK job 1 3,90,612.45 - 390612.45
20 NDSR Removal of old wiring, light fixtures etc., job 1 1,16,498.45 - 116498.45
21 NDSR Obtaining statutory approval NOC from Local Bodies. Job 1 3,25,000.00 325000.00
AIR CONDITIONING WORKS- BOQ
S.no DSR 2025/NDSR Item Decsription Qty Unit DSR Rate DSR Rate incl. CI NDSR Rate DSR Amount NDSR Amount
1 NDSR Supply of 11 TR Air cooled condesing unit for 22 TR Air cooled package unit 2 Nos 225262 450524.00
Towards installation, pressure testing, vaccumising, Gas charging and Commissioning of 22TR Air Cooled
3 NDSR Towards Supply & Installation of Outdoor Stand for 22TR Air Cooled Packaged Unit 1 Nos 1424.85 1424.85
4 NDSR Towards Supply of R22 Gas 60 Kg 12.89 773.49
Supplying, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following
sizes of soft/hard drawn copper refrigerant piping for VRV/VRF system, complete with fittings, with suitable
adjustable ring type hanger supports, jointing/brazing
5 31.14.8 including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile 25 RMT 1157 1214.85 30,371.25 0.00
rubber tubular sleeves sections of 19 mm thick insulation
as given below for Suction and Liquid lines, all accessories as per specifications etc. as required : 28.58 mm dia
(OD) (Hard drawn) with tube thickness 1.2
6 NDSR Towards Supply and installation of 5/8 hard drawn copper pipeline with support for package unit. 25 RMT 162.84 0 4071.00
15.86 mm dia (OD) (Soft drawn) with tube thickness 1.2
8 31.14.3 12.7 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm 30 RMT 488 512.4 15,372.00 0.00
Towards Supply & Installation of 2TR Split Air conditioner Outdoor Unit copper Coil including servicing of the
untis,gas charging and commissioning
10 NDSR Towards Supply & Installation of Outdoor Stand for 2TR Split Air Conditioning Unit- 8 Nos 33.93 271.40
Towards Supply & Installation of 1.5TR Split Air conditioner Outdoor Unit copper Coil including servicing of the
untis,gas charging and commissioning
12 NDSR Towards Supply & Installation of Outdoor Stand for 1.5TR Split Air Conditioning Unit 8 Nos 27140.00 217120.00
13 NDSR Towards Dismantling-erection & Commissioning of Split Air Conditioning-Outdoor Units 16 Nos 23069.00 369104.00
14 NDSR Towards Dismantling-erection & Commissioning of 11TR Packaged Outdoor Unit 3 Nos 20355.00 61065.00
15 Towards Servicing of the Indoor /Out door units rectification of elec. Works including Gas top-up for 8.5TR Air
Cooled Ductable AC Unit
16 owards Servicing of the Indoor /Out door units rectification of elec. Works including Gas top-up for 5TR Air Cooled
17 NDSR Towards Supply & Installation of Indoor Power Controller with remote (Double Controller) 2 Nos 7463.50 14927.00
18 NDSR Towards Supply & Installation of Indoor Power Controller with remote (Single Controller) 2 Nos 13705.70 27411.40
Sub total B 60250.80
19 Towards Servicing of the Indoor /Out door units rectification of elec. Works including Gas top-up for 8.5TR Air
Cooled Ductable AC Unit
20 Towards Servicing of the Indoor /Out door units rectification of elec. Works including Gas top-up for 5TR Air
Cooled Ductable AC Unit
Sub total C 23984.99
Digitally signed by DEEPAK
FIRE FIGHTING WORKS- BOQ
S.no DSR/NDSR ItemDecsription Qty Unit DSR Rate DSR Rate incl. CI NDSR Rate DSR Amount NDSR Amount
SERVICING AND REPAIRS
Servicing of Hydrant valves 63mm dia oblique type, single outlet, gunmetal,conforming to IS:5290 with ISI marking
and required fititngs and accessories
Servicing of 16 SWG MS single hoseboxes of with frontglass and key suitable to accomdate two hoses of 15m long
and one branch pipes with required supports
Supply and installation of 63 mm dia 15.00 Mtrs long Controlled Percolating type Hose with gunmetal coupling
binded on both sides with GI wire conforming to IS:8423 respectively
4 NDSR Supply and installation of Gunmetal branchpipe with nozzle conforming to IS:903 with ISI marking No's 9 3,357.90 30221.10
Servicing of Hosereel with 19mm BORE,30MTR LONG rubber hose, 6mm bore PVC shut-off nozzle and 25mm dia
5 NDSR globe valve conforming to IS:884 and with required fittings No's 9 3,426.43 30837.87
6 NDSR Painting and testing of entire hydrant system No's 1 95,939.90 95939.90
7 NDSR Servicing and repaire of pump house 2280 lpm electrical pump No's 1 61,675.65 61675.65
8 NDSR Servicing and repaire of pump house 180 lpm Jockey pump No's 1 41,117.10 41117.10
9 NDSR Servicing and repaire of pump house 900 lpm Booster pump lp 1 27,411.40 27411.40
10 NDSR Booster pump connectivity and getting into running condition lp 1 34,264.25 34264.25
Providing and fixing in position industrial type pressure gauges with gun metal / brass valves complete etc. as
12 NDSR Cable connectivity for 2280 electrical and jockey pumps lp 1 41,117.10 41117.10
FIRE PUMPS AND ACCESSORIES
Supplying, installation, testing
and commissioning of diesel engine driven main fire pump conforming to IS 12469: 2019 suitable for automatic
operation and consisting of following, complete in all respects, as required : (Diesel Driven
(b) Horizontal type, multistage, centrifugal pump of cast of iron body and bronze impeller with stainless steel shaft,
13 27.2.5 mechanical seal as required. Each 1 642112 674217.6 6,74,218 0.00
(c) Suitable HP, 1500 RPM water cooled with radiator, diesel engine conforming to relevant IS standard complete
with auto starting mechanism, 12 /24 volts electric starting equipment, diesel tank,
exhaust pipe extended upto 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm
thick aluminium sheet cladding, residential silencer, instruments and protection as
per standard specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post
office red colour etc. as required.
14 NDSR Supplying, laying, testing & commissioning of XLPE insulated, aluminium / copper conductor, - 0.00
14 a NDSR 3.5C x 16 Sqmm. Jockey pumps ( Aluminium armoured cable ) Rmt 12 712.70 - 8552.40
14b NDSR 12 C x 1.5 Sqmm.Diesel engines( Copper armoured cable ) Rmt 15 931.99 - 13979.85
14c NDSR 2 C x 1.5 Sqmm.for Instrumentation ( Copper armoured cable ) Rmt 30 383.76 - 11512.80
14d NDSR 3.5C x 50 Sqmm. XLPE al.cable aluminium ( Aluminium armoured cable ) Rmt 25 1,178.69 - 29467.25
15 NDSR Supplying, Installing, testing and commissioning CI butterfly valves as per BS 5155 ( PN 16) - 0.00
16 NDSR Supplying, installing, testing and commissioning of C.I. Non-return valves as per IS:5312( PN 16) - 0.00
17 NDSR Supplying and fixing approved make 25 mm dia. Automatic Air Release Valve with unions etc. complete. No's 1 1,713.21 - 1713.21
18 NDSR Supply and installation of Pressure gauges of suitable range for pumpsets No's 1 1491 1565.55 1,565.55 0.00
19 NDSR Supply and Installation of Pressure switches No's 1 1670 1753.5 1,753.50 0.00
Supply,fabrication,testing and commissioning of M.S. Black ERW Medium grade piping as per IS : 1239 complete
with necessary fittings for aboveground piping. Make: jindal/tata
Obtaining Statutory approval from Local Bodies Job 1
Plumbing Works- BOQ
Digitally signed by DEEPAK
S.no NDSR Item Decsription Qty Unit DSR Rate DSR Rate incl. CI NDSR Rate DSR Amount NDSR Amount
NDSR Ground Floor, 1st Floor, 2nd Floor Wash Room & Toilet Old Plumbing
Work rechecking & rework.
1a NDSR i) 20mm CPVC conciled pipe & fittings damage & blockage rework 400 RMT 85.66 34264.00
1b NDSR ii) Urinal (Sensor) Electric Operating Automatic Flusher Change without urinal.(Hindware) 12 NOS 8223.42 98681.04
NDSR iii) 6 Urinal Sensor urinal total change fitting (Hindware).
1d NDSR iv) Bottle trap old (Urinal) long body total change. 18 NOS 3426.43 61675.74
NDSR v) Washbasin total rechecking rework No change.
1f NDSR vi) Washbasin pillarcock (Hindware) work total change 34 NOS 2741.14 93198.76
1g NDSR vii) Angle cock, cp extension, Connection pipe, Flooring drain jali, Total change & rework. 1 JOB 55919.26 55919.26
1h NDSR viii) White wall mounted P Trape toilet with tank, rechecking & rework & parts replace. 6 NOS 3426.43 20558.58
1i NDSR ix) Health Faucet & Single taps replace. (Hindware). 12 NOS 2398.50 28782.00
2 3rd Floor & 4th Floor bathroom old plumbing work total dismental 20 bathroom old item remove Labor Charge.
NDSR i)Total bathroom conciled 20mm CPVC Pipe, 110, 75mm PVC & fittings rework bathroom point = western W/C,
2a Washbasin, Wallmixture, Head Shower, Health Faucet, Geyser Point, Bottle Trap point total new work, Labor
NDSR ii) (Hindware) Sanitary fitting PS – WC, Washbasin, Mixer, Head Shower, Pillar Cock, Angel Cock, Health Faucet,
2b Waste coupling, Waste Pipe, Floor Drain Jali, White cement, Silicon, Teflon Tape. CP Extension Nipple, 2” inlet Pipe
NDSR Outside vertical line old work W/C Line, Drain Line, RainWater Line, WaterLine dismental Labor Charge.
NDSR i)New Vertical line (Aashirvad) 110mm PVC (SWR) Pipe & Fittings, Tee, Door Bend, Door Y, Socket, Bracket Clamp,
W/C toilet line work Labor with material & sky folding. 500 RFT 301.53 150762.70
NDSR ii) 75mm PVC /(SWR) Pipe & Fittings, Tee, Door Bend, Door Y, Socket, Bracket Clamp, drainline bathroom work
outside vertical line material with Labor Charges. 450 RFT 152.29 68528.50
NDSR iii) Rain water line terrace to ground floor outside.110mm SWR Pipe & Fittings, Bracket Clamp, Material & Labor
NDSR iv) Water line terrace to bathroom 4th & 3rd Floor bathroom outside (Aashirvad) 25mm, 40mm, 50mm
CPVC Pipe & fitting work, Material & Labor Charges. 1 JOB 52081.66 52081.66
NDSR v) Terrace to 2nd Floor, 1st Floor, Ground Floor CPVC Water Line40mm, 32mm, 25mm Pipe & fitting
works, Material with Labor Charge.
1) 20mm CPVC Pipe 300 RFT
3e 2) 32mm CPVC Pipe 100 RFT
3) 40mm CPVC Pipe 100 RFT
4) CPVC Fitting, Tee, Elbow Union Valve.
5)Bracket & Clump, Nilsh , Fitting 530.68 RFT 289.34 153548.31
NDSR vi) Motor Line old total remove, new line work same 50 mm CPVC line 360 RFT work fittings Bracket Clamp
3f solution, 150 digging soil line work.
NDSR vii) Terrace old water tank (Sintex 10,000 Ltr.) change.
1) Old Pipe line & fitting 88.9mm
work rechecking & rework 260 RFT.
2) New water tank fitting 10,000 Ltr
tank, Heavy ball valve, Union Tee,
3g Long Bend, Elbow, Socket, Brass
Male , Female fittings New Change
Work. Total work material with
Labor Charges and Transport
Concrete & Chamber Cover. 260 RFT 1107.00 287819.70
NDSR 3) Water Tank shifting (Crane & Labor Rent, Terrace Shifting.
3i NDSR viii) Building drainage line Chamber gallytrap old work total dismentaling & digging Soil removal Labor Charges. 1 Job 20558.55 20558.55
Digitally signed by DEEPAK
New drainage, Chamber, gallytrap work, Material.
1) 8” Aashirvad Red Colour Pipe
(UGD) work pcc & concreate
2) Round Chamber bricks work &
cover fitting 2/2.
3) Gallytrap work 10”/10”.
3j NDSR 4) Dust, Cement, Bricks,5) Material with Labor Charges 1 jOB 330307.37 330307.37
Digitally signed by DEEPAK
SS Railing Works- BOQ
Correctio Rate incl
S.no DSR/NDSR Item Decsription Qty Unit DSR Rate NDSR Rate DSR Amount NDSR Amount
1 10.28 Providing and fixing stainless steel ( Grade 304) railing made of
Hollow tubes, channels, plates etc., including welding,
grinding, buffing, polishing and making curvature (wherever
required) and fitting the same with necessary stainless steel
nuts and bolts complete, i/c fixing the railing with necessary
accessories & stainless steel dash fasteners , stainless steel
bolts etc., of required size, on the top of the floor or the side of
waist slab with suitable arrangement as per approval of
Engineer-in-charge, (for payment purpose only weight of
stainless steel members shall be considered excluding fixing
accessories such as nuts, bolts, fasteners etc.).
2 NDSR Repair works and reconditioning/cleaning/buffing of exisiting
Digitally signed by DEEPAK
stage.html
html • 0.05 MB
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.06 MB
NIT ICMAI 2nd Call.pdf
Tender Document
GCC for Construction Work 2026.pdf
Tender Document
SCC ICMAI.pdf
Tender Document
Tender drawings.pdf
Tender Document
Technical Specifications.pdf
Tender Document
LIST OF APPROVED MAKES-ICMAI.pdf
Tender Document
BOQ ICMAI Services works.pdf
Tender Document
corrigendum-5591-Corrigendum 01.pdf
pdf • 0.37 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .