Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹49.9 LAccepted-AOC 1ST COMPLEX RADHANPUR ROAD NEAR BYPASS CIRCLE OPP 1SQUARE MARKET MAHESANA GUJARAT 384002 | MAHESANA | GUJARAT | 384002 | L1 | Accepted-AOC L1 | |
| 2 | L2₹49.9 L+₹2,864 (0.06%)Rejected-Finance 121 MADHAV SQUAR OPP AVANTIKA COMPLEX LIMDA LANE JAMNAGAR 361001 | JAMNAGAR | GUJARAT | 361001 | L2 | Rejected-Finance L2 | |
| 3 | L3₹50.1 L+₹26,964 (0.54%)Rejected-Finance INS VALSURA JAMNAGAR | JAMNAGAR | GUJARAT | 360520 | L3 | Rejected-Finance L3 | |
| 4 | L4₹50.5 L+₹63,024 (1.26%)Rejected-Finance C O BHAGYODAY STORES BAZAR CHOWK NALIYA KUTCH 370 655 | KACHCHH | GUJARAT | 370655 | L4 | Rejected-Finance L4 | |
| 5 | L5₹50.6 L+₹72,064 (1.44%)Rejected-Finance | L5 | Rejected-Finance L5 |
Tender Value
₹50.0 L
EMD Value
₹99,960
Closing Date
26 Dec 2020, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Lt Col Bhamre Kiran S
Military Engineer Service Garrison Engineer (AF) No.1 Air Force Station No.1 Jamnagar 361 003
HIRING OF RESOURCES FOR MANAGEMENT OF 66/11 KV POWER SUPPLY AND OTHER TECHNICAL INSTALLATION OF AF STATION JAMNAGAR
2020_MES_393593_2
8766/E8
Open Tender
Miscellaneous Works
Works
335 days
Jamnagar
Please refer tender documents
6 documents required · 6 mandatory
₹500
GE (AF) Jamnagar No. 1
₹99,960
Yes
5 Jan 2021
19 Dec 2020
28 Dec 2020
19 Dec 2020
26 Dec 2020
19 Dec 2020
60 days
Amount
Note:- (i) Contractor’s special attention is invited that the Estimated cost for M&O Part of this BOQ is Rs.48,75,371.00 based on prevailing rate of Schedule of Minimum fair wages. If the total quoted amount of M&O Part of the BOQ is less than the estimated cost of the same, then the lowest bidder will have to deposit FDR/BGB in favour of Accepting Officer within 07 days of opening of Financial Bid for the difference in estimated cost of M&O part & quoted amount of M&O part. (ii) In case the said FDR/BGB is not submitted within stipulated period as mentioned above, the contractor shall be banned for 06 months & their bid will be rejected and finance bid will not be opened. FDR/BGB submitted shall be released only after satisfactory completion of work on submission of proof of payment that all the person deployed under this contract has been paid not less than Schedule of Minimum fair wages as mentioned under Note No.5.02 to 5.03 here in after.
MANNING AND OPERATION
Hiring resources for management of 66 KV switchyard for continuous operation with one operator per shift of 08 hours for three Shift in a day (including Sunday & holiday) all as specified and directed by Engg -in-charge with following instruction :-
Note:- Minimum qualification of operator shall be ITI (Electrician) with 2 years experience for operating 66 KV EHTV switch yard.
66/11 KV Main incoming PGVCL 66 KV Supply line with switch yard and
(a) 5 MVA Power Transformer – 02 No
(b) 66 KV Line No 1 & Line No. 2
(c) HV 66/11 KV Panel with IDMT & Differential & other relays - 01 NO.
(d) RMU with Bus Coupler -01 No.
(e) Line Panle -01 Nos
(f) Current Transformer
(g) Circuit Breaker
(h) Potential Transformer
(i) Isolator
(j) Surge Arrestors
(k) Protection system
(l) Earthings
Hiring resources for management of Electrical Installation MAFI PS-I of 11 KV installation consisting of VCBs,Power Transformer , Isolation transformer with LT Panels for continuous operation with one operator per shift of 08 hours for three Shift in a day (including Sunday & holiday) all as specified and directed by Engg -in-charge.
Hiring resources for management of Electrical Installation MAFI PS-II of 11 KV installation consisting of VCBs,Power Transformer , Isolation transformer, with LT Panels for continuous operation with one operator per shift of 08 hours for three Shift in a day (including Sunday & holiday) all as specified and directed by Engg -in-charge
Hiring resources for management of Main Receving station of 11 KV installation consisting of VCBs-19 No., LT Panels for continuous operation with one operator per shift of 08 hours for three Shift in a day (including Sunday & holiday) all as specified and directed by Engg -in-charge Note:- For Item No. 2 to 4 Minimum qualification of operator shall be ITI (Electrician) with 2 years experience for operating 11 KV switch yard.
Notes for all items of this BOQ :- Contractors special attention is invited that The Accepting Officer reserves the right to terminate the contract or part thereof due to administrative reason without any prior notice. No compensation shall be made to the contractor for termination of contract / part thereof. The rates quoted by the contractor should be inclusive of all statutory taxes & duties including GST.
(i) Contractor / his operator will be responsible to operate all the above plants / machinery when ever required and as asked / directed by AGE / JE during shift
(ii) The contractor shall not pay wages lower than minimum wages for labour as fixed by Govt of India / State Govt. / Union Territory (Whichever is higher) under Minimum Wages Act or Contract Labour (Abolition and Regulation Act). Minimum Wage for Highly Skilled category will be considered for item Nos 1 to 4 of the BOQ
(iii) Contractor special attention is invited that payment of operator / labour shall be made only through Account payee cheque and same shall be deposited in bank account of operator / labour. Documentary evidence for the same shall be submitted to Engineer -in-Charge before payment of RAR/Final bill.
(iv) Contractor and his person detailed for manning of various installations shall also be responsible for serviceability of all equipment installed in various installations. In case of any major fault occurs in the installation he will report directly to concerned JE E/M / AGE E/M. Person deputed for operation will be responsible for minor maintenance such as checking of oil, checking of Diesel, checking of battery terminal and cleaning of all equipments and cleaning of installation room and surrounding areas complete.
(v) In case absence of any operator / workmen from any shift will be penalized with a penalty of double the rate quoted by the contractor in addition to the shift not taken in to consideration for payment.
(vi) Safety equipment's will be provided to all tradesman without any extra cost to government.
(vii) Log book (Sheet), daily breakdown register and other requisite registers will be maintained by operator and get it signed by on duty tradesman & JE i/c on daily basis & monthly signed by Engineer-In-Charge and contractor and other details as specified in PS.
(viii) Communication eqpt (cell phone) at each installation hired for resource management should be provided (strictly camera less & internet less) intimation of cell phone number shall be provided immediately on takes over of site by the contractor. The same shall be effective during period of running of contract. (Necessary permission for cell phone to be obtained from Airforce authorities by the contractor)
(ix) Quoted rate by the contractor shall be deemed to include cost of reliever and general cleaning of the DG Sets / Transformer / LT Panel / RMU / VCB / CSS and surround area of the installation including necessary T&Ps shall be provided by contractor.
(x) The Contractor shall maintain the attendance register for the operator employed by him and same shall be signed by JE & Engineer - in - Charge and will be produce at RAR / FB / or as and when required / demanded.
MAINTENANCE
Preventive / comprehensive yearly maintenance of 66 / 11 KV EHTV switch yard (details as under) by performing following activities:-
Details of equipments installed in switch yard:-
(a) 5 MVA Power Transformer – 02 No
(b) 66 KV Line No 1 & Line No. 2
(c) HV 66/11 KV Panel with IDMT & Differential & other relays - 01 NO.
(d) RMU with Bus Coupler -01 No.
(e) Line Panle -01 Nos
(f) Current Transformer
(g) Circuit Breaker
(h) Potential Transformer
(i) Isolator
(j) Surge Arrestors
(k) Protection system
Details of Activity to be carried out for yearly maintenance
(A) Transformer
(i) IR & PI Value
(ii) BDV, PPM and oil routine test of transformer as per IS : 1866
(iii) Testing of oil for DGA
(iv) Tan delta and capacitance measurement of bushing and main windings
(v) Measure of winding resistance at all tap positions
(vi) All low voltage routine tests
(B) Current Transformer
(i) Insulation resistance measurement – Primary to earth (By 5 KV Megger)
(ii) Capacitance and tan delta measurement
(iii) Checking of star point earthing
(C) Circuit Breaker
(i) Measurement of static contact resistance
(ii) Checking of close / trip Coil current
(iii) Measurement of Breaker timings
(iv) High voltage test in Case VCB (VI testing)
(v) Insulation resistance test
(D) Potential Transformer
(i) Measurement of secondary voltage
(ii) Checking of star point earthing
(iii) Insulation resistance measurement – Primary to earth
(iv) Capacitance and tan delta measurement
(E) Isolator
(i) Main contact resistance measurement
(ii) Earth Switch contact resistance measurement
(F) Surge Arrestors
(i) Insulation resistance measurement
(ii) Measurement of leakage current
(iii) Checking of structure earthing
(G) Batteries / Battery Charger
(i) Measurement of specific gravity and voltage of pilot cell and solution level check
(ii) Battery impedance testing
(iii) Discharge test of battery sets (run down test)
(iv) Discharge Cycle check
(H) Protection system
(i) Testing of all relay with logic checks
(I) Thermal Imaging of sub-station.
(J) DC Leakage monitoring daily & if any to be attended immediately
(A) minor consumable items, ie Nuts bolts, Control wires , PVC tapes, Welding Job, cotton waste & cleaning clothes, petroleum jelly, grease , lubricating oil, emery paper , T & P items etc.
(B) Following testing kit for carrying out different tests (as per PGVCL / GETCO norms)
(a) Tan-delta testing kit.
(b) Contact resistance kit.
(c) DCRM (Dynamic contact Resistance) kit.
(d) Breaker time testing Kit.
(e) Oil (BDV & PPM, DGA) test at Approved Lab.
(f) Earth resistance tester.
(g) Relay testing kit.
(h) Vacuum Interrupter Tester.
(i) Turn Ratio Kit.
(j) Winding resistance Kit.
(k) Transformer testing kit.
Yearly maintenance shall be carried out through Approved Agency by GETCO / PGVCL and contractor shall submit documentry evidence to Engineer-in-Charge for their approval.
Yearly maintenance shall be carried out as per GETCO / PGVCL norms.
Necessary Shutdown from GETCO shall be obtain by the contractor under his own arrangement after approval of Engineer-in-Charge in writing.
Contractor shall submit test result of all equipments after completion of maintenance dully signed by the GETCO / PGVCL approved agency.
Contractor shall submit health certificate of complete 66 / 11 KV switchyard after completion of maintenance dully signed by the GETCO / PGVCL approved agency before claiming payment of testing.
Note: For Item no 6, Work shall be executed by the authorised service mechanic/Electrician of manufacturer,After satisfactorily completion of servicing of HT Transformer/VCB If any fault occurs upto completion of contract peried should be attended by concerned rep within stripulated time frame without any failure , quoted rates is deemed to be included all such charges.(ii) If any above HT Equipment and connected itms become breakdown, the contractor shall loacate the problem/fault at site within 12 hours on intimation by JE/Engineer-In-Charge and ensure that the fault and rectified within 24 Hours , failing which an amount of Rs 300 /- per hour will be recovered as penal recovery from any payment due to contractor after expiry of 24 hours.)
SURESH ELECTRICALS
Hirachand Sunderji and co
KRISHNA ENGINEERING
Sukhi Electricals
EVEREST BUILDERS
Vijay Construction Co
jagdish machinery stores
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .